POLYMERIC ARMOR DESIGN OF AN IMPROVED PROTECTION TO MECHANICAL STRESSES AND FLUIDS FOR OIL GAS AND PETROCHEM (OGP) APPLICATIONS

Similar documents
Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR

SECTION MEDIUM-VOLTAGE CABLES PART 1 GENERAL

STANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV. Approved by AMERICAN NATIONAL STANDARDS INSTITUTE.

PILC Replacement: Getting the Lead Out

SECTION WIRE, CABLE AND BUSWAYS. A. This section specifies providing wire, cable and busways.

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

NORMAS DE REFERENCIA AEIC CS 1: ASTM B

IEEE 1580 Type P MOR Polyrad XT-125 Multi Conductor

Conductor Shield A combination of semi-conducting tape and extruded thermosetting semi-conducting material meeting UL 1309, IEEE 1580 and UL1072.

PV Solar Wiring Solutions

15 kv EPR Insulated, Jacketed, URD Cable

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

WESTERN UNDERGROUND COMMITTEE GUIDE 2.14 (2.14/01/0990)

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD. ANSI/SCTE (Formerly IPS SP 100)

DEVELOPMENT OF HIGH VOLTAGE EXTRUDED CABLES: THE ITALIAN EXPERIENCE

SECTION A. ASTM B3 - Standard Specification for Soft or Annealed Copper Wire; 2013.

New designed XLPE-insulated cables substituting paper-insulated pipe type cables

Glossary Of Terms M-1

INSTRUMENTATION, CONTROL AND THERMOCOUPLE CABLES

Selection of the Correct Optical Cable Outer Jacket for the Application

SPECIFICATION FOR FRLS POWER CABLES

STANDARD SPECIFICATION FOR SIGNAL CABLE. A. This Specification provides for single and multi-conductor insulated and jacketed cable for

SECTION INSULATED WIRE AND CABLE

MATERIAL STANDARD FOR CABLES AND WIRES

NEMA Standards Publication No. WC ICEA Publication No. S

26/35kV Copper XLPE Insulation Electric Cable

QUALIFICATION UPDATE. Eric Rasmussen. Quality Cables Since 1854

OFFSHORE CABLES NEK 606 : with FIREBAR the TOTAL SAFETY fire and water resistant cable

ES2000 TUBING Environmental Sealing, Polyolefin, Semirigid, Adhesive-Lined

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING

3 MODIFICATIONS TO EXISTING STANDARDS

New Conduit Specification

DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +105 C, 1000 VOLTS, TYPE LSFSGU

SOUTH CAROLINA ELECTRIC COOPERATIVES' PRIMARY UNDERGROUND POWER CABLE SPECIFICATION

SERV-RITE Wire and Cable

*** Supercedes: BECO E and COM , , & ***

Construction guideline

ANSI/NEMA WC ICEA S Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy

CONSULTATIONS TECHNICAL GUIDELINE. HVDC extruded cable

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

MATERIAL STANDARD FOR ELECTRICAL HEAT TRACING ORIGINAL EDITION JAN. 1996

SECTION WIRES AND CABLES

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

This section applies to the design and installation relating to wire and cable systems and terminations. 16G Figure 1 16G Figure 2

Engineering Data for Copper and Aluminum Conductor Electrical Cables

--> Buy True-PDF --> Auto-delivered in 0~10 minutes. TB/T Translated English of Chinese Standard: TB/T1484.

YF /8" YF /2" YF /4"

System No. C-AJ-8096

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

UNIFIED FACILITIES GUIDE SPECIFICATIONS

catalog Copper Wires

Standard of Practice - Campus Electrical Distribution System

WIRING METHODS CHAPTER 38

Pair Count Minimum Bend Radius Design Type Maximum Pulling Tension

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

Una e mpre sa Vi akab l e GLOSSARY.

ANSI/NEMA WC 71 ICEA S Nonshielded Cables Rated V for Use in the Distribution of Electric Energy

PVC Insulating Tape. Electrical Tapes

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

Kaf-Tech Product Specification

12-SDMS-01 Rev.02 SPECIFICATIONS FOR

Specification FOR. 12.7/22KV AL-CV/WS 12.7/22KV Aluminum Conductor XLPE Insulated Copper Wire Screened PVC Sheathed Power Cable.

Cables ELE E L CT E C R T R IC I C A A L L

1.2 REFERENCES.1 CSA C22.2 No.0.3, Test Methods for Electrical Wires and Cables.

SECTION HEAT TRACING FOR PLUMBING PIPING

Clark Public Utilities

SECTION HEAT TRACING FOR PLUMBING PIPING

H. Underground Transmission System Design

Mining Products. Jacketing and Insulating Tapes Trailing Cable Splice Kits High Voltage Splice and Termination Kits Cable Repair Tape Special Items

Mining Products Jacketing and Insulating Tapes Trailing Cable Splice Kits High Voltage Splice and Termination Kits Cable Repair Tape Special Items Fon

SPECIAL SPECIFICATION 6623 Multi-Duct Conduit System

SECTION ELECTRICAL SITE UTILITIES

History of Cable Systems HISTORICAL OVERVIEW OF MEDIUM & HIGH VOLTAGE CABLES. Nigel Hampton

INTERNATIONAL STANDARD

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

UNIVERSITY OF MISSOURI Hydronic Energy Distribution 2016 Q1

CHAPTER LOCAL AMENDMENTS TO THE NATIONAL ELECTRICAL CODE 2011 EDITION

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section PIPE AND EQUIPMENT INSULATION

SECTION PARK NON-SEGREGATED BUS SPECIFICATION

Rail Wire Guide. Harnessing and Electro-Mechanical Solutions for Demanding, Harsh Environment Applications... LFH FREE

WHAT MAKES ENCORE S XHHW-2 UNIQUE? Our SuperSlick Elite technology may be installed without additonal lubricant

DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +90 C, TYPE LS3SWU (INCLUDING VARIATION LS3SWUS)

Building Wire CARRYING YOUR ELECTRICITY

System No. C-AJ-8133

3.0) TRANSMISSION LINES MINIMUM REQUIRED STANDARDS LINES

ANSI/NEMA WC ICEA S Standard for Control, Thermocouple Extension, and Instrumentation Cables

CAJ. Combos. C-AJ of 5. Through Penetrations Series. Concrete. 3Fire Protection Products

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

IMPORTANT CODE UPDATE ENFORCEMENT DATE FOR NEW NATIONAL ELECTRIC CODE IS SET FOR MAY 1, 2013

SECTION WALL AND DOOR PROTECTION

FEDERAL STANDARD TEST METHODS FOR CABLES AND WIRE, INSULATED

Heavy Wall Heat Shrinkable Tubing 5-7. Flame Retardant Heavy Wall Heat Shrinkable Tubing 8. Heat Shrinkable Ends Caps 9

INTERNATIONAL STANDARD

FEDERAL STANDARD TEST METHODS FOR CABLES AND WIRE, INSULATED

U.V resistance UL Sunlight Resistance. Flame retardant IEC

CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION

1. Division 23 Section "Hangers and Supports for HVAC Piping and Equipment" for pipe insulation shields and protection saddles.

SPECIFICATIONS FOR THE CONSTRUCTION OF NEW PASSENGER EQUIPMENT CARS PREFACE

A. Section Fire Procection, HVAC & Plumbing Penetration Firestopping. B. Section Interior Painting: Painting insulation jacket.

Transcription:

POLYMERIC ARMOR DESIGN OF AN IMPROVED PROTECTION TO MECHANICAL STRESSES AND FLUIDS FOR OIL GAS AND PETROCHEM (OGP) APPLICATIONS Paul CINQUEMANI, Prysmian Cables & Systems USA, LLC, paul.cinquemani@prysmian.com Luca DE RAI, Prysmian Cables & Systems SpA, (Italy), luca.derai@prysmian.com Marco FRIGERIO, Prysmian Cables & Systems SpA, (Italy), marco.frigerio@prysmian.com Paolo VEGGETTI, Prysmian Cables & Systems Oy, (Finland), paolo.veggetti@prysmian.com ABSTRACT Electric power cables for OGP application can be subjected to very high tension during installation, so they can get damaged by high Sidewall Bearing Pressure and by other accidental impacts. Typically, manufacturers and cable installers have used various ways to protect cables from mechanical stresses. Cable manufacturers use metal clad armor of either aluminum interlocked armor (AIA) or continuously corrugated metal armor. This paper will detail the development and evaluation of a new design of power cable that provides increased mechanical protection without the use of metallic armor while also improving overall flexibility, by a composite polymeric protection. The new design incorporates a polymer layer that has been shown to improve both the mechanical toughness of electrical power cables while providing improved flexibility compared to cables using metallic armor. In addition, the cable design must be suitable to protect the insulated cores from the attack of hydrocarbons, oils and various fluids which are typical of the OGP industry applications. The design proposed is providing the necessary protection to fluids by a special polymeric layer, combined with a metal thin foil, without all the disadvantages of the metal clad armored cables (weight, stiffness, difficult termination etc.). The data presented supports that polymeric armor provides 5 times better impact performance than metallic armored products, and provides a fluids protection equivalent to the metal clad armor design. This allows installers and customers to install cables for longer distances without the need for expensive splices which also affects cable reliability; the experience on the installation field by a few customers is already confirming the great benefits of such new cable. mechanical abuse resistance is beneficial to the end user. However, one major drawback to installation of conventional metal clad cables is the limitation of maximum lengths that can be pulled due to sidewall bearing pressure contraints. Conventional Type MC encompasses basically two types 1) continuous corrugated aluminum sheath and 2) aluminum interlocked strip armor (AIA) that is also provided to a lesser extent with galvanized steel strips (GSIA). The continuous corrugated aluminum sheath is typically produced by forming a flat aluminum sheath circumferentially and longitudinally around a cabled core whereas it is then slit to proper width, edge welded and lastly corrugated. The profiles of the corrugations are specifically designed to provide optimum bending characteristics. This design results in a very rigid armor with limited sidewall bearing pressure (SWBP) capabilities during installation. Industry recommendations vary between 1000 to 1500 pounds per foot of bend-radius. The interlocked aluminum strip armor is typically produced with two (2) predetermined flat strips that are edge formed, shaped and helically applied in a single pass resulting in tape armor where each strip is interlocked with each adjacent strip. This armor results is a somewhat more flexible armor compared to the continuously corrugated aluminum. Due to the strip interlocking this armor lacks an impervious barrier and cannot protect the cable core against aggressive chemicals or moisture. This design is also further limited in SWBP to industry recommended values of 800 pounds per foot of bend-radius. INTRODUCTION The NFPA National Electrical Code (NEC) clearly defines the applications where Metal Clad Cables (Type MC) are required to be installed or may optionally be used in the occupancies covered therein [1]. In many other locations and applications metal clad cable may be used as a beneficial option such as conduit replacement or as an alternate design when greater mechanical abuse resistant cable is desired by the end user. In fact it has become quite common for multi-conductor Type MC power cables to be installed as the cable of choice in many industry applications, even where metal clad is not required by the NEC. The popularity arises from the diverse installations and locations where additional

PVC/LS0H OUTER JACKET CCW ALUMINUM 1.2 mm Corrugation depth = 6 mm PP YARN FILLERS EPR INSULATION deformation and damage to the underlying core. Metallic Shield: Copolymer coated aluminum tape longitudinally applied with sealed overlap. Polymeric Layer: Extruded layer bonded to the underlying metallic shield barrier. This combination is resistant to aggressive chemicals such as hydrocarbons, solvents, acids, bases and moisture. Sheath: Extruded overall low temperature, flame and sunlight resistant polyvinyl chloride or low smoke halogen free jacket. COPPER CONDUCTOR Figure 1. Conventional Type MC - Continuous Corrugated Aluminum Sheath Design In both conventional Type MC designs, exceeding the maximum recommended values of SWBP during an installation may distort or tend to flatten the metal clad armor. This permanent change of shape can distort the underlying core resulting in excessive electrical stress within the insulated conductor as well other mechanical damages to the core. Extreme damage may result in immediate detection or cable failure during field testing prior to energizing the circuit. Lesser damage may go undetected, ultimately leading premature electrical failure in service. POLYMERIC SHIELD FOR MECHANICAL AND CHEMICAL PROTECTION New concepts to mechanical protection have led to the development of advanced polymeric armor designs that provide the essential mechanical armor characteristics as well as protection against moisture and chemicals. Polymeric armor designs consist of multiple layers as shown in Figure 2.. Figure 2. Polymeric shield design PVC/LSOH Outer Jacket Extruded oil and hydrocarbon resistant polymeric layer Al Laminate tape Polymeric Armor Extruded Filler/Bedding EPR Insulation Copper Conductor The components consist of the following: Filler/Bedding: Extruded halogen free non-hydroscopic polymeric bedding or optional non-hydroscopic filler yarns. Polymeric Protection: Impact resistant, shock absorbing extruded polymer capable of reducing risk of permanent PERFORMANCE OF POLYMERIC SHIELD Impact Performance Comparative impact testing was conducted in apparatus designed in accordance with EDF Specification HN 33-S- 52 [5]. The test was conducted at different energy impact levels and employed an impact tool of a 90 V shaped wedge with 80 mils (2 mm) radius tip. After a single impact at the specified energy level, the thicknesses of various layers and local damage on the extruded insulation shield, by means of an optical laser system, was measured with an electronic digital caliber. Mass Height of Weight Energy of Impact Damage on Insulation (N) inches (mm) (Joules) mils (mm) 14.3 (363.6) 200 26 (0.65) 550 17.9 (454.4) 250 28 (0.7) 21.5 (545.4) 300 28 (0.7) Table 1. Impact Test Results on 3/C #2/0 AWG 15 kv Rated Cable with Polymeric Armor Mass Height Energy of Impact Damage on Insulation (N) (mm) (Joules) mils (mm) 550 14.3 (363.6) 200 95 (2.4) 17.9 (454.5) 250 98 (2.5) 21.5 (545.4) 300 110 (2.8) Table 2. Impact Test Results on 3/C #2/0 AWG 15 kv Rated Cable with Continuous Corrugated Armor Testing continued on the three conductor 2/0 AWG 15kV rated cables employing polymeric armour and continuous corrugated aluminium armor to determine the magnitude of impact on each design that resulted in the same level of damage on the ethylene propylene rubber (EPR) insulated conductor. This was determined to be an impact level of 200 joules for the polymeric armour design as compared to 140 joules for the continuous & corrugated aluminium metal clad cable design. Further testing on three conductor 350 kcm 15 kv rated cables found the impact magnitude that resulted in the equivalent level damage on the insulation shield of the EPR insulated conductor was 250 joules for the polymeric armour and 200 joules for the continuous & corrugated aluminium metal clad cable design.

Polymeric Armor Continuous Corrugated Aluminum Armor Figure 3. Polymeric Armor and Continuous Corrugated Al Armor - 3/C 350 kcm 15 kv - Before Impact Testing Figure 5. Polymeric Armor and Continuous Corrugated Al Armor 9/C #12 AWG 600 V Cables - After 80 Joules of Impact and Overall Jacket Removed Polymeric Armor Continuous Corrugated Aluminum Armor Figure 4. Polymeric Armor and Continuous Corrugated Al Armor - 3/C 350 kcm 15 KV- After 250 Joules of Impact Figure 6. 9/C #12 AWG Insulated Core Removed From Polymeric Armor Design After 80 Joules Impact Impact testing was also conducted on typical 600 volt rated control cables. The typical cable configuration of nine (9) conductors #12 AWG conductor cables was employed The testing apparatus and impact tool design were identical as employed for impact testing of the 15 kv power cable sizes. Figure 7. 9/C #12 AWG Insulated Core Removed From Continuous Corrugated Al Armor - 80 Joules Impact Mass Height of Weight Energy of Impact Damage on Insulated (N) inches (mm) (Joule) delta diameter, mils (mm) 250 4.7 (120.0) 30 8 (0.2) 250 6.3 (160.0) 40 8 (0.2) 250 7.9 (200.0) 50 11.8 (0.3) 250 9.5 (240.0) 60 21.7 (0.55) 250 11.0 (280.0) 70 25.6 (0.65) 250 12.6 (320.0) 80 27.6 (0.7) Table 3. Impact Test Results on 9/C #12 AWG 600 V Rated Power Control with Polymeric Armor Mass Height of Weight Energy of Impact Damage on Insulated (N) (mm) (Joule) delta diameter, mils (mm) 250 4.7 (120.0) 30 31.5 (0.8) 250 6.3 (160.0) 40 31.5 (0.8) 250 7.9 (200.0) 50 31.5 (0.8) 250 9.5 (240.0) 60 35.4 (0.9) 250 11.0 (280.0) 70 43.3 (1.1) 250 12.6 (320.0) 80 57.1 (1.45) Table 4. Impact Test Results on 9/C #12 AWG 600 V Rated Control with Continuous Corrugated Armor This technology has also been adopted in communications and optical fiber cable designs for terrestrial and aerial applications replacing metallic armor/sheaths as successfully demonstrated in power and control cables. The severity of an 80 joules impact can easily be seen in Figure 5. At this impact level the measured damage on the insulated core is two times greater on the continuous corrugated aluminum armor than the polymeric armor. This can be seen in Figure 7 where exposure of the #12 AWG conductors through the insulation was observed. The criticality of such exposure is the potential to lose circuit integrity via phase to phase or phase to armor and potentially short circuiting and losing power to critical equipment and instrumentation in an industrial or commercial facility. The insulation within the core of the polymeric armor cable, while exhibiting some damage is not in jeopardy of a phase to phase short circuit. Sidewall Bearing Pressure Performance Sidewall Bearing Pressure (SWBP) develops when a cable is pulled around a bend under pulling tension. It is the vector sum of the sidewall pressure due to tension in the conductor acting horizontally, and the weight of the conductor acting vertically. SWBP should always be calculated for that conductor that presses hardest on the inside bend of the curvature, i.e., pipe, conduct, wheel, etc. In most cases sidewall bearing pressure limits for power

cable have been demonstrated to be quite satisfactory via 30 to 50 years of historical data. These were initially based upon theoretical methods and consequently, safety factors were incorporated in the equations. Currently, North American standards do not define a test protocol for determination of sidewall bearing pressure. Recent work has been conducted to prove the electrical and mechanical suitability in reducing insulation thickness for medium voltage cables. Specifically SWBP test apparatus was developed and implemented to demonstrate that such cables can withstand the SWBP rigors of standard full wall cables for the same voltage classes. However, the apparatus for this work was limited to single conductor cables and was intended to demonstrate the suitability at currently accepted SWBP limits. In earlier work under the Electric Power Research Institute (EPRI) testing methodologies were developed for this program but were greatly focused on single core electrical utility type cables. Both of these methods were independently developed due to no recognized standardization for such as test. For this project in consideration that multi-conductor power cables were quite large, the SWBP testing was conducted in accordance IEC Draft 901TR ED.1 Clause 5.2, intended for larger core cable.. Installation Performance In a recent actual installation, three conductor 350 kcm and three conductor 750 kcm copper 15 kv rated cables with polymeric armor were installed in a very tortuous cable route. Typically when power cables are installed pulling tensions, bending radius and sidewall bearing pressures are monitored. Once the sidewall bearing pressure has reached the maximum limit the installer can utilize a midassist/tugger device to reduce the tension seen at the pulling eye or grip. This lowers the SWBP so the cables can continue to be pulled without damage to the cable core. In severe cases where mid-assisting may not be sufficient and the installation profile cannot be changed to reduce tension, the cable must be cut and spliced. This is undesirable as splices in such pulling profiles can be difficult to accomplish in tight quarters, will result in lost time and increased installation costs, and provide an opportunity to reduce integrity of the electrical system over the life of the cable. With a maximum allowable SWPB limit of 3000 pound/ft both polymeric armored cables were successfully installed in this demanding pull. Even the 750 kcm 15 kv rated cable did not show any signs of damage with SWBP measured and exceeding 2000 pounds/ft. Several times during the installation the SWPB exceeded 1500 pounds/ft which is the maximum limit for continuous corrugated armor. If 3/C 750 kcm cables with continuous corrugated armor were employed for this installation, two splice points would have been required to avoid damage to the cable. Chemical protection performance Figure 8. Apparatus for Sidewall Bearing Pressure Testing Here a 50 foot (15 m) length of cable is passed forwards and backwards around a fixed wheel under a SWBP calculated by T/R using the tension of the steel wire (T) from the pulling wench and the wheel radius (R). The cable remains in contact with the fixed wheel for at least 90 during the test. Lubricant may be applied as necessary at the contact point of the wheel. Repeated testing of medium voltage designs of polymeric armor cables has resulted in a maximum recommended sidewall bearing pressure of 3000 pounds per foot of bend-radius. This is twice the industry maximum value of 1500 pounds for corrugated and welded armor. In order to evaluate the chemical performance of the polymeric shield design, the cable has been submitted to different kind of tests. The specifications UL1072 for MV cables and UL44 for LV cables require the Fuel C and Oil IRM902 test compliancy of the complete cable. The purpose of the tests is to measure the performance of the cable versus aggressive fluids at high temperature, which are present in OGP and chemical industry applications. After the cable has been exposed to such fluids for a long period, the insulation characteristics have been measured, in order to assess indirectly the permeability of the polymeric shield and the effects on the electrical performances of the insulated cores. Fuel C test Material: aromatic fuel Characteristics: o Low vapour pressure o Low viscosity/molecular weight => high permeation rate o Highly aggressive against rubber (as by ASTM D471) o Widely used in chemical industry Measurements: o Density o Mechanical properties (insulation)

Figure 9. Toluene 50 C immersion insulation mechanical properties In addition, a numerical calculation has been done to estimate the long term permeation values of toluene at 25 C and 50 C; such calculation is based on the permeability measurement on the complete cable. The results in figure 10 show the hydrocarbon concentration on the unprotected conventional design versus the polymeric shield design, extended to 10 years period. The safe level line is the limit within the cable operational is not affected. Figure 11. Oil immersion of cable in oven Figure 12. IRM902 100 C immersion insulation mechanical properties Figure 10. Hydrocarbon concentration inside cable Oil IRM902 test Material: highly parafinic oil Characteristics: o Most commonly used reference oil in chemical industry o Higher viscosity/molecular weight o Aggressive against plastics Measurements: o Density o Mechanical properties (insulation)

CONCLUSIONS Direct comparison testing between new advanced polymeric shield designs and continuous corrugated aluminum armor designs have been conducted. Polymer armor designs have shown to be significantly more resistant to crush and impact type damage and able to withstand much higher lateral forces during installation. In addition, cable testing versus aggressive fluids has been assessed: the polymeric shield design is providing long term high resistance to oil and hydrocarbons at high temperature. Such polymeric shield designs have also been subjected to and passed an extreme battery of flame propagation testing, smoke testing, cold bend/impact at testing -40 C and are approved under the auspices of Underwriters Laboratories, Canadian Standards Association, American Bureau of Shipping, Coast Guard, etc. REFERENCES [1] NFPA 70: National Fire Protection Association, National Electrical Code, 2005 [2] HN 33-S-52 EDF Specification for Single Core Cables with Polymeric Insulation for Rated Voltages of 36/63 (72.5) kv and 52/90 (100) kv and up to 87/150 (170) kv. [3] Y. Wen and P. Cinquemani, Performance of Reduced Wall EPR Insulated Medium Voltage Power Cables: Part II Mechanical Characteristics, IEEE-PES Transmission & Distribution Conference, 1996. [4] EPRI-EL-3333, Maximum Safe Pulling Lengths for Solid Dielectric Insulated Cables, Volumes 1 and 2, February 1984 [5] IEC Draft 61901TR ED.1-20/682/CD Clause 5.2, Development Tests Recommended on Cables with a Longitudinally Applied Metal Tape, April 2004 Figure 13. Cutback of 3/C Medium Voltage Polymeric Armor Design