Comparison of Measured Indoor Environment for Social Housing in West Yorkshire, UK

Similar documents
The BIG Energy Upgrade Energy Innovation for Retrofitting Deprived Community Housing in the UK

USING DYNAMIC SIMULATION FOR DEMONSTRATING THE IMPACT OF ENERGY CONSUMPTION BY RETROFIT AND BEHAVIOURAL CHANGE. Young Ki Kim 1 and Hasim Altan 1

VARIATION OF INDOOR TEMPERATURES AND HEATING PRACTICES IN UK DWELLINGS

The feasibility of natural ventilation in plus energy houses in Germany

Field Study of Auckland Housing Winter Indoor Health Conditions Associated with Insulation, Heating and Energy

THE REDUCTION IN AIR INFILTRATION IN DWELLINGS DUE TO WINDOW REPLACEMENT

Indoor Air Quality. Basic Management for Healthy Office Environments. Peter A Shelling CSP CIEC

Understanding occupant heating practices in UK dwellings

Why you should not need to call in the priest. Topics I can cover. Why moisture can be a problem. The regulations, codes and standards should

COMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING

Doctoral Seminar Natural Ventilation Effectiveness in Single and Multi-Storey Buildings

Passive Strategies and Low-Carbon Technologies: Evaluating the Energy Performance and Thermal Comfort of a Passive House Design

Performance monitoring of energy efficient retrofits 4 case study properties in Northern Ireland

(92-100) (81-91) (69-80) (55-68) (39-54) (21-38) (1-20)

Window use in single person offices: do occupants control personal ventilation to provide adequate IAQ? Adorkor Bruce-Konuah 1 University Of Sheffield

RELATION BETWEEN INDOOR THERMAL ENVIRONMENT AND RENOVATION IN LIEGE RESIDENTIAL BUILDINGS

INDOOR AIR QUALITY AND ENERGY EFFICIENCY IN THE DESIGN OF BUILDING SERVICES SYSTEMS FOR SCHOOL CLASSROOMS

Development of the adaptive model for thermal comfort in Japanese houses

According to our research and study most occupant complaints relating to IAQ are attributable to the following factors:

Passivhaus Introduction

Extra 6. Sustainability. The Sigma Home. December 2009

Radon Levels and Indoor Air Quality in Northern Ireland Certified Passive House Buildings

Theory versus practice of energy and comfort in 4 low energy houses in Belgium

WEATHERPROOFING SOCIAL HOUSING IN AN URBAN ENVIRONMENT THROUGH RETROFITTING: A HOLISTIC APPROACH

Project Description. Projected build start date 12 Apr 2010 Projected date of occupation 28 Feb

BPE Case study of Pippin Close and Barnlea Close

Energy in the Home Trying to save my 20% Julian Paren

ECO-RETROFITTING VERY OLD DWELLINGS: CURRENT AND FUTURE ENERGY AND CARBON PERFORMANCE FOR TWO UK CITIES

MONITORING OF INDOOR AIR QUALITY FOR IMPROVEMENT OF SAFETY AND HEALTH FACTOR TOWARDS SUSTAINABLE WORK ENVIRONMENT IN INDUSTRY

Simulation investigation of heating load for solid wall house retrofitted with Vacuum Insulation Panels

Building Better Buildings (BPE) 15 February 2016, UCL. Paul Ciniglio Sustainability & Asset Strategist. First Wessex

Design and Evaluation of a Low Carbon Emitting Naturally Ventilated Student Health Centre

Relation between indoor thermal environment and renovation in Liege residential buildings

Breathability of building elements

Indoor Air Quality Assessments during Renovations at Waverly Elementary School Project #J (January 4, 12, 15, 25 and 29, 2018)

Coggins, Marie; Broderick, Aine; Byrne, Miriam. /s8f92c

Measurements of CO2 levels in a classroom and its effect on the performance of the students

Energy Performance Certificate

Evaluation of indoor air quality in classrooms equipped with different methods of ventilation

INVESTIGATING THE EFFECT OF CO 2 CONCENTRATION ON REPORTED THERMAL COMFORT

University of Rochester Environmental Health & Safety Indoor Air Quality Program March 23, 2005

(81-91) (69-80) (55-68) (39-54) (21-38) (1-20)

Field Investigation of Comfort Temperature and Adaptive Model in Japanese Houses

Energy Performance Certificate

Increased ventilation

From Drawing Board to Occupied Space: Assessing the design process of a transformational learning space

Energy Use in Homes. A series of reports on domestic energy use in England. Thermal Insulation

Energy Performance Certificate

ENERGY CONSERVATION VS HEALTH. THE AIR QUALITY PICTURE. Aizaz Samuel Energy Systems Research Unit University of Strathclyde, Glasgow, Scotland

WHAT IS IEQ? INDOOR ENVIRONMENT QUALITY KEY TO HEALTH & COMFORT A QUESTION WHAT IS SO IMPORTANT ABOUT IAQ? WHAT ELSE IS SO IMPORTANT ABOUT IEQ?

Environmentally Responsive School Buildings in the UK

Sumit Sharma, Ved Prakash Sharma, R Suresh TERI GRIHA SUMMIT 2016

COMFORT AND INDOOR AIR QUALITY IN PASSIVE HOUSES IN THE U.S

BPE Case Study - Lyndhurst Crescent, Swindon

Energy Performance Certificate

Energy Performance Certificate

Whole Life Cycle Costing Julian Dickens

Productivity, investment and energy in a naturally ventilated lean office development

Passivhaus Executive Summary

Energy Performance Certificate

Analysis of indoor air quality in a store with additional gas heater

Minimum Energy Consumption 84% energy heating savings*

VARIABILITY OF THERMAL STRATIFICATION IN NATURALLY VENTILATED RESIDENTIAL BUILDINGS. Stephanie Gauthier 1, David Shipworth 1

Princedale Road Post Occupancy Evaluation

Energy Performance Certificate

Energy Performance Certificate

Energy Performance Certificate

Incorporating health benefits into ex-ante project appraisal

performance. In order to make clear the effects of thermal performance and lifestyle on thermal environment and energy consumption for well-insulated

The Energy Efficiency Partnership for Homes (EEPH) Costs and Benefits of Energy Efficiency Measures

Energy Performance Certificate

INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY IN BUILDINGS

Effect of Different Ventilation Conditions on Indoor CO2 Levels

Energy Performance Certificate

Energy Performance Certificate

Energy Performance Certificate

Energy Performance Certificate

Energy Performance of Buildings Directive: Achieving both high indoor air quality and low energy consumption in European buildings

Energy Performance Certificate

(92 plus) (81-91) (69-80) (55-68) (39-54) (21-38) (1-20) Estimated energy use, carbon dioxide (CO 2) emissions and fuel costs of this home

Energy Performance Certificate

In 2011, Auckland Council commissioned a report to identify how the City could reduce its Carbon emissions. The top 6 recommendations for the built

Design and retrofitting of a hybrid building in Athens

6 th Annual North American Passive House Conference. Evaluation of Potential for Moisture in High R- value Walls in Cold Climates

Good (4 points each) > mg/m Bq m Bq m Bq m -3 < ,000 1,000-10,000 10, ,000

Assessing the Indoor Comfort and Carbon Dioxide Concentration in High-Rise Residential Buildings in Kuala Lumpur: The People s Housing Programme (PPR)

Overview. Background Methodology Field testing and occupant surveys Computer modelling Summary Conclusions

Building Performance Evaluation in Domestic Buildings

Developing Robust Solutions for Roof Upgrades

Energy Performance Certificate

Energy Performance Certificate

New Generation Office Building

Welsh Future Homes. Developer: United Welsh Housing Association. Project Description. Architect: bere:architects. Location: Ebbw Vale, Wales

Characteristics and performance of MVHR systems A meta study of heat recovery ventilation systems in new dwellings

Evaluation of retrofit approaches for two social housing tower blocks in Portsmouth, UK

Chapter 14 Indoor Air Quality

10 tips from your Architect

Energy Performance Certificate

Thermal comfort in a 21st century climate

Transcription:

PLEA2013-29th Conference, Sustainable Architecture for a Renewable Future, Munich, Germany 10-12 September 2013 Comparison of Measured Indoor Environment for Social Housing in West Yorkshire, UK HASIM ALTAN 1, MOHAMED REFAEE 1 1 Building Environments Analysis Unit (BEAU), School of Architecture, University of Sheffield, Sheffield, UK ABSTRACT: The study is part of a project aiming to investigate the energy efficiency within the most deprived communities across six local authorities in Yorkshire and the Humber region in the UK. A post occupancy evaluation is performed on four dwellings before refurbishments are undertaken to investigate the indoor environmental conditions and to compare the measured levels with the accepted standards. The results have shown that one home in Kirklees almost complied with the range of winter internal temperatures in living room, and similarly all bedrooms in Kirklees and Leeds complied with the guidelines in winter season. In addition, relative humidity levels were almost in the acceptable range under both summer and winter conditions. The average indoor CO 2 levels were also measured in four homes, indicating inadequate ventilation during the monitoring period. A random day was chosen to visualise CO 2 concentration behaviour in the same homes and it was found that the CO 2 level followed a pattern that rising during the morning, evening times in response to human indoor activities. Moreover, there was a direct correlation between CO 2 and air temperature levels showing that there is a dilemma of keeping windows closed with stale indoor air in the four dwellings. Keywords: energy innovation; deprived communities; indoor environments; social housing; post occupancy evaluation INTRODUCTION The BIG Energy Upgrade (BEU), also known as the Energy Innovation for Deprived Communities (EIDC), is a project aims to investigate the energy efficiency within the most deprived communities across six Local Authorities (LAs) in Yorkshire and the Humber region in the UK. A post occupancy evaluation has been carried out by the Building Environments Analysis Unit (BEAU) at the University of Sheffield on a sample of dwellings (i.e. two in Kirklees and two in Leeds areas) in the region (West Yorkshire in England, UK) before their refurbishments have been undertaken as part of the BEU partnership, with 14.9 million funding that is part financed by the European Regional Development Fund (ERDF) programme 2007 to 2013. Currently, the existing buildings contribute around 45% of the UK s overall annual carbon dioxide (CO 2 ) emissions with more than a quarter coming from domestic buildings. For the country to meet its 80% CO 2 reduction target by 2050, there needs to be an extensive refurbishment throughout the existing building stock to improve their energy efficiency [1]. Refurbishment option could be seen as more modest and simple at the first glance referring to demolition/dismantling and new development, but the results of improving energy performance of housing in Belgrade showed efficiency in energy savings and CO 2 emission reductions, as well as improved housing quality and standards. By improvement of thermal insulation and replacement of windows, contribution to energy savings and upgrading of the building appearance have been achieved [2]. The indoor environment is an influential factor to environmental quality. People spend a majority of their time in buildings and therefore the indoor environment is the main setting for many; consequently certain conditions of this environment can have a profound effect on the quality of the environment and the occupants health [3]. Studies have highlighted that at present many people live in conditions that are considered unhealthy because of the high levels of mould growth, damp and dust mite concentrations. Approximately 20% of all dwellings in England suffer from mould growth and dampness to some degree [4]. Oreszczyn and Pretlove indicate that a key parameter in house dust mite survival and mould growth is Relative Humidity (RH). Relative humidity is a function of both moisture and temperature, which are dependent on many other interrelated factors of the indoor environment, including fabric insulation, occupants activities within the home (i.e. number of occupants, hours of occupation, ability to pay fuel bills and amount of moisture generating activities), the heating system (i.e. efficiency, control and distribution), ventilation and external climate. Using these factors they have developed a model to identify the risk of mould growth in dwellings [2, 6]. Ucci et al investigated the links between asthma and low ventilation rates in housing because of the fact that the trend towards the reduction of domestic ventilation rates for energy efficiency had resulted in poor indoor air quality which may represent a causal factor for the high asthma prevalence in the UK [5]. Sick Building Syndrome (SBS) is a type of illnesses related to poor

Indoor Air Quality (IAQ) in buildings and it has contributed to the awareness of poor health associated with a poor indoor environment. SBS can be defined as the discomfort or sickness associated with poor indoor environments with no clear identification of the source substance [7, 8]. This study has been undertaken as part of the BEU programme with an aim to deliver a new approach to energy efficiency and renewable energy projects within a minimum of ten of the most deprived communities in the UK. The properties will be assessed by energy efficiency experts and then brought up to modern standards with a range of measures including so-called smart electricity meters and heating systems upgrades to boilers, wall and loft insulation, double glazing, insulated cladding and even solar panels where appropriate. It is therefore important for the success of the EIDC project that both detailed monitoring and post occupancy evaluation are performed on a sample of dwellings before rolling out a wider refurbishment. The aim of this study is to investigate the indoor environmental conditions of four selected homes in Kirklees and Leeds areas at Yorkshire and the Humber region in the UK, before refurbishment, and to compare the measured levels with the widely accepted standards. METHODOLOGY Indoor air temperatures and relative humidity levels were measured at four selected homes using HOBO U12-012 and U10-003 data loggers. Indoor carbon dioxide levels were also recorded in four deprived community homes using Telaire 7001 CO 2 meters. Although CO 2 is not toxic, it is commonly used as an indicator of air quality, and high levels of CO 2 indicates inadequate ventilation in a space. All HOBO U12-012 data loggers and CO 2 meters were placed in the living room in each home, specifically in the breathing zone of a person sitting on a sofa (approximately 1.5 metre above the floor level) and away from open windows. In addition, participants were requested to behave as normal within their homes during the monitoring period in order to obtain realistic data. HOBO U10-003 data loggers were placed in the bedroom in each home. The aim of the post occupancy evaluation carried out was to monitor indoor air quality and to gain an insight into indoor conditions within deprived community homes to be able to compare their indoor environmental conditions i.e. air temperature ( C), relative humidity (RH%) and carbon dioxide (CO 2 ), with the recommended standards (i.e. CIBSE and ASHRAE). Average levels of each variable were collected in 15- minute intervals over a 24-hour period for periods of two weeks. RESULTS AND DISCUSSION The monitoring process has been undertaken before any refurbishment to be completed in the four selected dwellings. Results have been compared to the published standard guidelines by the Chartered Institution of Building Services Engineers (CIBSE) and the American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE). Below, Table 1 describes the home type, home age, tenure, ventilation condition, window type, cooker type, number of occupants and their ages. Table 1: General description of sampling location in Kirklees and Leeds (West Yorkshire). Description Dwelling K*1 Dwelling K2 Dwelling L**1 Dwelling L2 Type of building Home age (yr) Dwelling Tenure Window Type Cooker Type No. of Occupants and Ages Type of Ventilation Semi-detached 65 4 (67, 65, 38 and 37 years) Semi-detached 65 Owned 3 (60, 57 and 33 years) K*= Kirklees L**= Leeds Terraced 40 2 (69 and 68 years) Terraced 40 2 (58 and 61 years) Figure 1 shows the average indoor air temperature for each of the monitored dwellings in Kirklees and Leeds areas. The dashed line in Figure 1 is the internal air temperature of 22 C recommended in living room. In comparison with the standard guidelines, it is clear that one home (K2) did not comply with the CIBSE s recommendation for the range of internal temperatures

(22-23 C) in living room, and both L1 and L2 also do not comply with this standard guideline. Figure 2 on the other hand, shows the average relative humidity (RH%) levels for the living rooms, and in this case, both rooms do comply with the standard guidelines for the four selected homes in Kirklees and Leeds. The recommended level of indoor relative humidity should be between 40-70% [9]. seen that the levels are fluctuating around the recommended value for indoor space. Figure 3: Level of CO 2 in the living rooms of four homes during one week in Kirklees and Leeds. Figure 1: Daily indoor temperature for the living rooms in four homes in Kirklees and Leeds. 19th November 2011 was chosen as a random date to plot the CO 2 concentration against time to investigate the behaviour of carbon dioxide during the selected day over a 24-hour period. Figure 4 indicates that the indoor CO 2 levels followed a pattern in the four deprived community homes. Levels were seen to be under 1000 ppm during early morning and day time, later rising at evening time due to the increase of human activity and the lack of ventilation. Figure 2: Daily indoor RH% for the living rooms of four homes in Kirklees and Leeds. Carbon dioxide (CO 2 ) is present in the natural environment, being produced by combustion of biological processes, and it is present at typical levels of about 360 ppm in the ambient urban environment though this can rise substantially inside occupied buildings. Currently, there are no UK CO 2 standards for indoor air, while the ASHRAE recommends that carbon dioxide levels should not exceed 1000 ppm inside a space [10]. Figure 3 shows the indoor CO 2 levels of the living room of four deprived community homes for one week in Kirklees and Leeds areas. As a result, it can be Figure 4: CO 2 concentration of four homes in Kirklees and Leeds for one day (19/11/2011). The indoor temperature and relative humidity of four bedrooms were plotted against the standard guidelines (shown dashed lines). Figure 5 shows that participant K2 does not comply with the standard guideline for indoor air temperature for the bedroom which is 17 C to 19 C [9]. In Leeds, participant L1 does not comply with the same guideline either. Figure 6 shows that relative humidity levels comply with the standard guidelines in

the bedrooms as well as in the living rooms for both location homes. Figure 7: Correlation of daily carbon dioxide and daily temperature for four homes. Figure 5: Daily indoor temperature for the bedrooms of four homes in Kirklees and Leeds. Figure 8 shows the average indoor air temperature of the living room for Kirklees home which was 2.6 C higher than the average indoor temperature of the living room for Leeds home. In addition, it also shows the mean of indoor temperature of the bedroom for Kirklees home was 0.6 C higher than the mean of indoor temperature of the bedroom for Leeds home. Moreover, a t-test analysis showed that the mean air temperatures were statistically significant and that their t-test results are as follows: t = 2.43, p =< 0.05 and t = 0.80, p= < 0.05 Figure 6: Daily indoor RH% for the bedrooms for four homes in Kirklees and Leeds. Daily indoor air temperatures and daily CO 2 levels of the four selected homes were correlated with statistically significant results (r =0.676, p =<0.05), (r =0.498, p =<0.05), (r =0.390, p =<0.05), and (r =0.599, p =<0.05). Figure 7 shows this direct (positive) relation between indoor temperatures and CO 2 levels for four deprived community homes. These results may indicate that the warmer spaces have lack of air ventilation rates and therefore the CO 2 levels are higher, and it also reflects the dilemma of achieving proper ventilation and indoor thermal comfort. Figure 8: Difference of mean temperatures for the living rooms and the bedrooms of four homes in Kirklees and Leeds. Figure 9 shows the carbon dioxide levels were compared with mean of the two living rooms for Kirklees and Leeds homes. The t-test analysis showed that the mean CO 2 levels were statistically different (25 ppm) which was significant and their t-test result is as follows: t 0.040, p < 0.05

Figure 9: Difference of CO 2 levels between the living rooms for Kirklees and Leeds. CONCLUSION The study aimed to investigate the indoor environmental conditions, i.e. air temperature, relative humidity and CO 2 levels, of four deprived community homes in Kirklees and Leeds areas at West Yorkshire in the UK before refurbishment to compare with the widely accepted standards. The conclusions from this study are based on a limited number of samples (in this case, four homes from deprived communities). To further generalise the results, it would be necessary to do more sampling on a larger population which will be the future work. From this limited data, the measured values of indoor temperature levels have been found not to comply with the standard guidelines in both locations whereas the measured values of relative humidity levels have been found to comply with the recommended standards in four selected homes. It was found that there is a direct and a positive relation between indoor air temperatures and CO 2 levels which reflected the dilemma of achieving proper ventilation and indoor thermal comfort in these deprived community homes. Moreover, the results have indicated that the warmer spaces have lack of air ventilation rates and therefore the CO 2 levels are higher, which confirms the same dilemma of achieving proper ventilation and indoor thermal comfort conditions. 2. Stein, B., (2008). Refurbishment as Challenge for Future Architects, In The Oxford Conference 2008, Oxford, UK, July 22-23. 3. Saunders, T., (2002). The Boiled Frog Syndrome: Your Health and the Built Environment. Thomas Wiley Academy: West Sussex. 4. Oreszczyn, T. and S. Pretlove, (2000). Mould Index, In Rudge, J. and F. Nicol, (editors) Cutting the Cost of Cold, E & FN Spoon, London, p. 122-133. 5. M. Ucci, M., Ridley, I., Pretlove, S., Davies, M., Mumovic, D., Oreszczyn, T., McCarthy, M. and Singh, J. (2004). Ventilation Rates and Moisture-related Allergens in UK Dwellings, In Proceedings of the 2nd WHO International Housing and Health Symposium 2004, Vilnius, Lithuania, September 29 - October 1, p. 328-334. 6. Carrer, P., Maroni, M., Alcini, D. and D. Cavallo, (2001). Allegens in Indoor Air: Environmental Assessment and Health Effects. The Science of the Total Environment, 270, p. 33-42. 7. Molhave, L., (1987). The Sick Buildings: A Subpopulation among the Problem Buildings, In Proceedings of the IV International Conference on Indoor Air Quality and Climate, West Berlin, Institute for Water, Soil, and Air Hygiene, Indoor Air 1987 Vol. 2, August 17-21, p. 469-473. 8. Burge, S., Hedge, A., Wilson, S., Bass, J.H. and A. Robertson, (1987). Sick Building Syndrome: A Study of 4373 Office Workers, The Annals of Occupational Hygiene, 31(4A), p. 493-504. 9. CIBSE, (2006). Environmental Design CIBSE Guide A, Chartered Institution of Building Service Engineers London. 10. American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE), (2013). [Online], Available: http://www.ashrae.org/, [10 May 2013]. ACKNOWLEDGEMENTS This paper is the result of the work undertaken as part of the BIG Energy Upgrade (BEU) programme. The project has attracted 7.0 million from the European Regional Development Fund (ERDF) through the Yorkshire and Humber ERDF Programme 2007-13. REFERENCES 1. National Refurbishment Centre, (2013). [Online], Available: http://www.rethinkingrefurbishment.com/, [10 May 2013].