LARGE SCALE DYNAMIC FAILURE TESTS OF LOW DAMPING RUBBER BASE ISOLATORS

Similar documents
COMPARISON OF SEISMIC PERFORMANCE OF BASE-ISOLATED HOUSE WITH VARIOUS DEVICES

Dynamic Stability of Elastomeric Bearings at Large Displacement

THE APPLICATION OF RESPONSE CONTROL DESIGN USING MIDDLE-STORY ISOLATION SYSTEM TO HIGH-RISE BUILDING

A SHAKING TABLE TEST OF REINFORCED CONCRETE FRAMES DESIGNED UNDER OLD SEISMIC REGULATIONS IN JAPAN

MID-STORY SEISMIC ISOLATION FOR STRENGTHENING OF A MULTI-STORY BUILDING

Development and Application of Seismic Isolation and Response Control of Buildings in Japan

Floating Type Isolation System Using Earthquake Early Warning

EARTHQUAKE RESPONSE ANALYSIS OF A MID-STORY SEISMIC ISOLATED BUILDING

PSEUDO DYNAMIC TESTS AND IMPLEMENTATION OF SLIDING BRIDGE ISOLATORS WITH VERTICAL MOTION

Kiran K. Shetty & Krishnamoorthy Department of Civil Engineering, Manipal Institute of Technology, Manipal , Karnataka, India

Full-scale dynamic testing of an 11-story RC building and interpretation of the results from the seismic-resistance viewpoint

Vibration control of a building model with base isolation

INELASTIC SEISMIC PERFORMANCE OF RC TALL PIERS WITH HOLLOW SECTION

EXPERIMENTAL STUDY ON THE EFFECT OF TENSION FOR RUBBER BEARINGS

INELASTIC SEISMIC RESPONSE ANALYSES OF REINFORCED CONCRETE BRIDGE PIERS WITH THREE-DIMENSIONAL FE ANALYSIS METHOD. Guangfeng Zhang 1, Shigeki Unjoh 2

COMPARISON OF SEISMIC PERFORMANCE OF BASE-ISOLATED HOUSE WITH VARIOUS DEVICES

WIRE-ROPE BRACING SYSTEM WITH ELASTO-PLASTIC DAMPERS FOR SEISMIC RESPONSE REDUCTION OF STEEL FRAMES

ON THE SEISMIC UPGRADING OF EXISTING BUILDING BY SEISMIC ISOLATION SYSTEM

Fukushima Daiichi Nuclear Power Station Unit No.1

Effect of Base Isolation in Multi-Storeyed RC Building

A NOVEL ELASTOMERIC BASE ISOLATION SYSTEM FOR SEISMIC MITIGATION OF LOW-RISE BUILDINGS

ULTIMATE EARTHQUAKE RESISTANT CAPACITY OF CFT-FRAME

SHAKING TABLE TEST USING MULTIPURPOSE TEST BED

Effect of Seismic Reinforcement of Sheet Pile Quay Wall Using Ground Anchor

Seismic Performance and Modeling of Post-Tensioned, Precast Concrete Shear Walls

EXPRIMENTAL AND ANALYTICAL STUDY ON SEISMIC BEHAVIOR OF TRADITIONAL WOODEN FRAMES CONSIDERING HORIZONTAL DIAPHRAGM DEFORMATION AND COLUMN SLIPPAGE

STRESS CHARACTERISTICS OF PILE GROUP DURING EARTHQUAKE BASED ON CENTRIFUGE LARGE SHEAR BOX SHAKING TABLE TESTS

Application of Isolation Technology in High-voltage Electrical Equipments

Seismic Evaluation of a 1930 Steel Bridge with Lightly Reinforced Concrete Piers

E-DEFENSE EXPERIMENTS ON FULL-SCALE WOODEN HOUSES

Osamu Takahashi, Hiromasa Aida 1 Junji Suhara, Ryoichiro Matsumoto 2 Yasuo Tsuyuki 3 Takafumi Fujita 4. Kozo Keikaku Engineering 2

Soil-Structure Interaction Effects on Building Response in Recent Earthquakes

NONLINEAR DYNAMIC BEHAVIOR AND SEISMIC ISOLATION OF STEEL TOWERS OF CABLE-STAYED BRIDGES UNDER GREAT EARTHQUAKE GROUND MOTION

Shaking Table Test of Controlled Rocking Reinforced Concrete Frames

Load Bearing Mechanism of Piled Raft Foundation during Earthquake

BI-DIRECTIONAL PSEUDO-DYNAMIC TEST OF CIRCULAR SECTIONAL CFST BRIDGE PIERS

Study on the seismic isolation of high-elevated rigid frame bridge with double deck

VIBRATION RESPONSE CHARACTERISTICS OF ROCKING PILLAR BASE ISOLATION SYSTEM SUITABLE FOR MASONRY HOUSES

Base isolation. Philippe Bisch IOSIS, EGIS group. EUROCODE 8 Background and Applications

Development of Cylindrical Passive Damper using High Damping Rubber

Real-Time Hybrid Testing of Laminated Rubber Dampers for Seismic Retrofit of Bridges

STUDY ON THE DAMAGES OF STEEL GIRDERS BY HYOGO-KEN NANBU EARTHQUAKE USING NONLINEAR SEISMIC RESPONSE ANALYSIS

This point intends to acquaint the reader with some of the basic concepts of the earthquake engineer:

Effective Length of RC Column with Spandrel Wall

Wire-rope Bracing System with Central Cylinder,

Framework for Design of Next-Generation Base-Isolated Nuclear Facility Structures

Comparison of Chevron and Suspended Zipper Braced Steel Frames

SEISMIC ANALYSIS OF SYMMETRIC BUILDING WITH BASE ISOLATION TECHNIQUE

Load Bearing Mechanism of Piled Raft Foundation during Earthquake

Seismic Collapsing Process Analysis of One-story Thatched Roof Wooden Structure under Strong Earthquake Ground Motion

Bi-Directional Experimental Hybrid Simulations of Elastomeric Isolation Bearings for Validation of Hysteretic Modeling

SEISMIC COLLAPSING BEHAVIOUR OF ONE-STORY WOODEN STRUCTURE WITH THATCHED ROOF UNDER STRONG EARTHQUAKE GROUND MOTION

STUDY ON SHAKING TABLE TESTS OF ISOLATED BRIDGE MODEL WITH LRB

Effect of plastic hinge, soil nonlinearity and uplift on earthquake energy in structures

Question Paper Code : 11410

A Method of Dynamic Nonlinear Analysis for RC Frames under Seismic Loadings

Title. Author(s)KANATA, T.; MATSUMURA, M.; NAKANISHI, Y.; YAMAGUCHI, Issue Date Doc URL. Type. Note. File Information STRUCTURES

EVALUATION OF LAMINATED HOLLOW CIRCULAR ELASTOMERIC RUBBER BEARING

Shaking table test on seismic response of reduced-scale models of multi-story buildings allowed to uplift

Vibration Control of a Tower Complex Connected by Sky Gardens

FINITE ELEMENT ANALYSIS FOCUSED ON THE FLANGE PLATES AND CONNECTING BOLTS OF RUBER BEARINGS

SEISMIC CONCEPTUAL DESIGN OF LONG-SPAN CABLE-STAYED BRIDGE

Bi-axial Bending Behavior of RHS-columns Including Post-buckling and Deterioration Range

Abstract. 1 Introduction

GRAVITY LOAD COLLAPSE OF REINFORCED CONCRETE COLUMNS WITH DECREASED AXIAL LOAD

Dynamic Behavior of RC Framed Irregular Building Using Lead Rubber Bearing

Dual earthquake resistant frames

Collapsing Simulation of Wooden House Retrofitted by ACM Braces During Seismic Ground Motion

Nonlinear Dynamic Analysis of Base Isolated Reinforced Concrete Building

Research on seismic behavior of Wood-Concrete Hybrid Structure

Development and Realization of Base Isolation System for High-Rise Buildings

Controlled Rocking Approach for the Seismic Resistance of Structures

SHAKE TABLE TESTING OF BRIDGE REINFORCED CONCRETE COLUMNS UNDER COMBINED ACTIONS

SEISMIC RESPONSE OF A REINFORCED CONCRETE ARCH BRIDGE

SEISMIC DESIGN OF STRUCTURE

Belleville Spring. The relation between the load F and the axial deflection y of each disc. Maximum stress induced at the inner edge

VERTICAL COMPONENT EFFECT OF EARTHQUAKE IN SEISMIC PERFORMANCE OF REINFORCED CONCRETE BRIDGE PIERS

WISE DYNAMIC TESTING FOR KNOWING STRUCTURES MORE ABSTRACT

Rocking Seismic Isolation of Bridges Supported by Direct Foundations

INFLUENCE OF BNWF SOIL MODELLING ON DYNAMIC BEHAVIOUR OF PILE FOUNDATION FOR RC FRAME WITH STRUCTURAL WALL

Assistant Professor, Applied Mechanics Department, Government College of Engineering, Amravati, India 2

FULL-SCALE VERIFICATION TEST OF DYNAMIC RESPONSE CONTOROL TECHNIQUES FOR STRONG EARTHQUAKES

Gravity Load Collapse of Reinforced Concrete Columns with Brittle Failure Modes

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume X, No X, 2010

Axial Load Behaviors of PSRC Composite Columns with Anchor-Type Transverse Reinforcements

Behavior of Steel Beam to Concrete Filled Tubular Steel Joints after Exposure to Fire

CONSTRUCTION OF A 3-D FULL-SCALE EARTHQUAKE TESTING FACILITY

PLASTIC DEFORMATION CAPACITY AND HYSTERETIC BEHAVIOR OF U-SHAPED STEEL DAMPERS FOR SEISMIC ISOLATED-BUILDINGS UNDER DYNAMIC CYCLIC LOADINGS

Development of 3D Seismic Isolation Technology for Advanced Nuclear Power Plant Application

Vibration test in a Building named "Chisuikan" using Three-dimensional Seismic Isolation System

Responses of Base-Isolated Buildings in Tokyo during the 2011 Great East Japan Earthquake

Seismic Collapsing Analysis of Two-Story Wooden House, Kyo-machiya, against Strong Earthquake Ground Motion

Seismic Response Analysis of a Concrete Filled Steel Tubular (CFST) Arch Bridge

ANALYTICAL AND EXPERIMENTAL STUDIES ON THE SEISMIC RESPONSE OF BASE ISOLATION SYSTEMS FOR ELECTRIC POWER EQUIPMENT

Low modulus-high damping rubber for vibration control devices - development and outlook

Wataru Goto. NTT FACILITIES, INC. in Japan. 15th World Conference on Earthquake Engineering 24 to 28 September 2012 LISBON PORTUGAL

Structural Design of Super High Rise Buildings in High Seismic Intensity Area

RETROFITTING METHOD OF EXISTING REINFORCED CONCRETE BUILDINGS USING ELASTO-PLASTIC STEEL DAMPERS

Earthquake Design of Flexible Soil Retaining Structures

DYNAMIC TESTING OF FULL-SCALE 11-STORY RC BUILDING AND ITS 3-STORY STRUCTURAL PART: COMPARISON OF THE RESULTS AND SEISMIC RESISTANCE ESTIMATION

Transcription:

LARGE SCALE DYNAMIC FAILURE TESTS OF LOW DAMPING RUBBER BASE ISOLATORS Chikahiro MINOWA 1, Nobuo MASAKI And Masanori IIBA 3 SUMMARY Two large scale dynamic tests were performed for different sized rubber base isolators that were both made of same low damping rubber with actual response velocity of seismic excitations. In each test a 0 ton mass was placed on four isolators located at the corners of the mass. The entire mass system was then placed on the large scale seismic simulator, which has dimensions of 15m by 14.5m, with a maximum velocity of 100cm/s, and a maximum displacement of 0.m. The seismic simulator was used to drive the mass until the isolators reached failure. In the first the isolators of small second shape factor simply dropped down, but did not break. In the second test of large second shape factor however, all four isolators were completely sheared off. INTRODUCTION After Hyougoken Nanbu earthquake, many base isolated buildings have been constructed. For these building, the laminated rubber isolators have been used. The laminated rubber isolators are expected to have large horizontal displacement absorption and small horizontal stiffness. And moreover these basic characteristics, they also are expected to have a life of over 60 years. So many experimental studies have been curried out to ensure the dynamic ultimate strength for the load during great earthquake excitations. But almost all of these tests were conducted with small laminated rubber isolators because of the capacity limit of the shaking tables [],[4]. Or the ultimate strength is pursued by a static experiment [1],[3]. Therefore the objective of our study is to observe the failure mode of the laminated rubber with actual velocity and to make a comparison between dynamic tests results and static tests results. (SLENDER SHAPE) (FLAT SHAPE) Figure 1 Base isolated structure model on a table Figure Two laminated rubber isolators for tests DYNAMIC TEST MODEL Figure 1 shows the base isolated structure model which was installed on the large scale earthquake simulator of National Institute of Earth Science and Disaster Prevention, which is the one horizontal direction shaking table. 1 3 National Research Institute for Earth Science and Disaster Prevention Research and Development Division, BRIDGESTONE Corporation Building Research Institute, Ministory of Construction

The structure was consisted of the mass of 00 ton which made of steel strips and the stage which made of H- shape steel frames. The stage has a mass of 0 ton, therefore the total mass on the four laminated rubber isolators is 0 ton. Each steel strips were combined by tension rods and stacked on the stage. Therefore, the mass could move as a rigid body. The dimensions of the mass were 7.0m by 4.9m and 5.5m high. Four laminated rubber isolators were used to support the mass with the natural period of seconds. In these dynamic failure tests two different types of laminated rubber isolators which made of same natural rubber material were provided. For the safety two restraints were installed at both side of the mass with a gap between the mass and the restraint of 0.6m in the shaking direction. So the mass could not move over 0.6m in the shaking direction. The restraints were designed for absorbing the horizontal inertia force of the mass of 0 ton during seismic excitations. The restraints also have a gap in the vertical direction to support the mass after the buckling of the laminated rubber isolators. In this test, the gap in vertical direction was 0.045m. LAMINATED RUBBER ISOLATORS Figure shows the laminated rubber isolators which were used in the dynamic failure tests. The both of laminated rubber isolators were made of mainly natural rubber of low damping (ζ= -3%). Two parameters, S1 and S for the shape of laminated rubber isolator, are defined as follows, S d = r 1, S 4 t r = d r n t r dr: a diameter of laminated rubber isolator, tr : a thickness of single rubber layer, n: number of rubber layers. The slender shape isolators have a diameter of 0.4m, a single rubber layer thickness of 0.004m, a primary shape factor (S1) of 6.5, a second shape factor (S) of.76. The flat shape isolators have a diameter of 0.m, a single rubber layer thickness of 0.0015m, a primary shape factor (S1) of 33.3, a second shape factor (S) of 5.0. The nominal pressure (vertical stress) are 3.58MPa for the slender shape isolators and 15.58MPa for flat shape isolators respectively. Both of the isolators have a same horizontal stiffness of 490kN/m. The predicted maximum horizontal displacements are also 0.4m for the slender shape isolator and 0.64m for the flat shape isolator respectively. Mechanical properties of natural rubber were as follows: Shear Modules G=0.6MPa, Hardness IRHD=40, Elongation ε=650% Figure 3 Outline of dynamic test model Figure 4 Time record of response of Figure 5 Time record of response of and Sensor distribution 45cm/s input 5cm/s input MEASUREMENT AND DYNAMIC TEST PROCEDURE

Figure 3 shows the position of the sensors. In this figure, AX, AY, AZ show the accelerators for X, Y, Z directions. And D shows the displacement transducers. Four vertical transducers at the each corners of the moving mass are used to measure the height reduction of the laminated rubber isolators. Five displacement transducers in X direction (shaking direction) are provided at the center and the each corners of the moving mass. Therefore the rotational, torsional and sway displacement could be measured. Acceleration, velocity and displacement of the shaking table were also measured. All data from the sensors were converted to digital data by the 1 bit analog-digital transducer with sampling time of 0.001sec. The restoring force FH of the four rubber isolators is derived from the mass and the acceleration of the center of the gravity of the mass, or also given by using the dynamic pressure pd of shaking table actuators, as follows: FH=m a, FH=pd Ac mt at Where m is 0 ton of the moving mass, a is the response acceleration, Ac is actuator section area 000 square cm, mt is table mass 195ton, at is table acceleration. In the dynamic failure test of the slender shape laminated rubber isolators, the artificial seismic wave which using Taft EW phase characteristics wave was used as the input ground motion. On the other hand, for the test of flat shape isolators, JMA Kobe waveform was used. In the shaking table tests, a suite of the wave forms with the different input velocity level were provided, because of the observations of basic characteristic of the laminated rubber isolator. Therefore, the laminated rubber isolators of slender shape were experienced 15 input earthquake motions of the different velocity level before the rubber isolator drop-down. The isolators of flat shape also experienced four input earthquake motions before the isolator shear-off. DYNAMIC FAILURE TEST RESULTS Slender shape laminated rubber isolator (S=.76) Figure 4 shows the time record of response of the mass as input 45 cm/s of the artificial seismic wave which using Taft EW phase characteristics. In this figure, from the top to the bottom in turn, input velocity, input acceleration, response acceleration, horizontal displacement (relative displacement between the shaking table and the mass), and vertical displacement of the isolators are shown. The maximum acceleration of the mass was 50 gal, maximum total horizontal restoring force and horizontal displacement were 50kN and 0.45m. Horizontal displacement of 0.45m was 108% of the diameter of the laminated rubber isolator. Although there was no superposition areas of the laminated rubber isolator, the vertical bearing capability was not loosed. Maximum vertical displacement was 0.035m.At this input level, the mass did not dropped down. But as shown in Figure 6, the restoring force characteristic shows the negative slope over the horizontal displacement of 0.4m Figure 5 also shows the time record of the response in case of the mass dropped down. In Figure 5, from the top to the bottom in turn, input velocity, input acceleration, response acceleration, horizontal displacement, and vertical displacement of the isolators and vertical acceleration of the mass are shown. The minimum input velocity was 5cm/s and the maximum displacement of the mass relative to the shaking table before failure was 0.534m. The isolators had displacement of 17% of their diameter and 351% of the rubber shear strain before they reached failure by buckling. In this case, when the mass dropped down, there were some shocks on the mass. At the moment of the drop-down, the response acceleration of 1308.9gal in the vertical direction was observed. On the other hand, the maximum horizontal acceleration was -1009.6gal. Both of. Figure 6 Restoring force curves Figure 7 Relation between vertical stress Figure 8 Restoring force curve of of dynamic(45m/s) and static and horizontal shear strain (5cm/s) using actuator pressure(5cm/s) 3

the acceleration wave form of vertical and horizontal direction looks like an impulse wave. In Figure 7, the relation of the vertical stress and horizontal shear strain is shown. Figure 8 shows the restoring force characteristics of using the dynamic pressures of shaking table actuators, which was not disturbed by the shock noise of the drop- down. Figure9,10 shows the vertical displacement characteristics of an isolator and the averaged one of four isolators. Figure 9 shows the unbalanced vertical deformations. The unbalanced vertical displacements of isolators [5] was explained in the model of Figure 11. The vertical displacements v of isolators would vary with the changes of superposition area Si of rubber bearings, the overturning moments, and the horizontal shift u of gravity center of the mass which would be included in the overturning moment. S i = ( d rca ( u)) 1 u u cos ( d rca ( u)) u 4 d rca ( u), v = n tr E S a i mg( L / ± u L ) mah where Ea is apparent elastic modulus of laminated rubber. In order to express the vertical displacements at large horizontal displacements u over dr, Ca(u) (=1+0.1 u in the calculation ) was adopted. The calculated vertical displacements using the above equations are shown in Figure 11-15, neglecting static vertical displacement. Figure 11 shows the vertical displacements due to the overturning moments, Figure 1 is due to the gravity center shift. Figure 14 agrees with Figure 10. The agreement shows that the averaged vertical displacements of Figure 10 is given by the change of superposition area. Figure 15 shows fairly good agreement with Figure 9. The deformation mode of the laminated rubber isolator at the drop-down is shown in Figure 16. After the dropdown, the mass was jumping up, so the mass continued to vibrate and was back to the original position. Although the isolators were experienced the buckling, there was no reduction of the restoring force characteristics and no damage in the laminated rubber isolators. Figure 9 Relation of vertical and horizontal displacement one rubber bearing Figure 10 Averaged relation of vertical and horizontal displacement of four rubber bearings Figure 10 Model of vertical displacement Figure 11 Vertical displacement Figure 1 Vertical displacement analysis due to overturning moment due to gravity center shift 4

Input Modified Taft 45cm/s Rubber Bearing 40mm (3ch) Neglecting Overturning Morment and Gravity Center Movements Input Modified Taft 45cm/s Rubber Bearing 40mm (3ch) Calculated Vertical Deformation in mm 50 40 30 0 10 0-10 -500-400 -300-00 -100 0 100 00 300 400 500 Measured Horizontal Deformtion in mm Figure 14 Vertical displacement without moment and gravity center movement Calculated Vertical Deformation in mm 50 40 30 0 10 0-10 -500-400 -300-00 -100 0 100 00 300 400 500 Measured Horizontal Deformtion in mm Figure 15 Vertical displacement including moment and gravity center movement Figure 16 Deformation shape of slender rubber bearing Figure 17 Sheared off flat rubber bearing Flat shape laminated rubber isolators (S=5) Figure 18 shows the time records of response of the mass as input 35 cm/s of JAM Kobe wave with the same order of 319.1 gal. The maximum response acceleration of the mass in Figure 4. The maximum acceleration of the shaking table was horizontal direction was 06.7 gal and the maximum total horizontal restoring force and horizontal displacement were 00kN and 0.147m respectively. Horizontal displacement of 0.147m was equivalent to 363% of the total rubber height of the laminated rubber isolator. The sheared off isolators are shown in Figure 17, and the time records of the response of the mass of the input velocity of 45cm/s of JAM Kobe wave with the same order of Figure 4 are shown in Figure 19. In this case, at the horizontal displacement of 0.175m, all of the four isolators were sheared off simultaneously. After the isolators shear-off, the mass landed on the restraints of the both side of the mass. So some shocks occurred in the mass as indicated in the time records of the accelerations in vertical and horizontal directions. From the observations, all of the shear-off phenomenon occurred in the rubber layer. Therefore the adhere force was enough to bear the breaking rubber shear strength. Figure 0 also shows the horizontal restoring force characteristics before the point of the breaking. In figure 1, the relation of the vertical stress and shear strain is shown. 5

Figure 18 Time record of 35 cm/sec input Figure 19 Time record of failure input 45cm/sec Figure 0 Restoring Force Characteristics Figure 1 Vertical Stress and Horizontal Strain STATIC FAILURE TEST RESULTS Static failure tests were conducted by the bi-axial loading test machines. In this test, the isolator was loaded a vertical load of 500kN and sheared up the its breaking displacement with a constant shear velocity of 1cm/s. The ultimate strength of the S=5 sample was measured as shown in Figure. The laminated rubber isolators of slender shape (S=.76) were also performed by v static bi-axial loading tests. In this test, the isolator also was loaded with a vertical load of 500kN and sheared up its buckling 6

displacement with a constant shear velocity of 1cm/s. The horizontal restoring force and vertical displacement characteristics were measured. Figure 6 shows the statically measured restoring force in comparison with dynamically measured result. From Figure 6 it can be seen that the restoring forces of the isolator of slender shape which were obtained from the dynamic loading tests were slightly larger than that of static loading tests. Figure 3 shows the vertical load that is measured in the static loading test of the slender shape isolator. It was confirmed from this figure that the vertical load acting on the laminated rubber isolator was reduced when the horizontal displacement was increased. Therefore the difference of restoring force characteristic may larger than that of Figure 6 because of the shortage of a vertical load acting on the laminated rubber isolator in the static test as shown in Figure 3. Figure Static test of flat shape rubber bearing Figure 3 Vertical load measured in the static test CONCLUSION From the dynamic and static loading tests, we have following conclusions. (1)Horizontal restoring force could be estimated by measuring the acceleration of the mass. ()In the case of the mass supported by the slender shape isolators, after the drop-down the mass was jumping up and was back to the original position without reduction of the restoring force and damage of the isolators. On the other hand, in the case of the mass supported by the flat shape isolators, after the shear-off the mass was continued to stay on the restraints because of no restoring force, and some shocks were occurred in the mass. Some increments of the ultimate strength in dynamic loading tests were confirmed. This phenomenon probably was caused by the deformation speed dependency of the elastic modules of the rubber materials. When the laminated rubber isolators is deformed with the slow deformation speed, the contribution of bending deformation to the horizontal displacement becomes larger, and as a result, restoring force reduced. However the cause of this increment may be simply a dispersion of restoring force characteristic of laminating rubber isolators. Therefore we plan to measure the deformation speed dependency of the elastic modules of the rubber materials used for these isolators and the dispersion of the restoring force characteristic of laminating rubber isolators. ACKNOWLEDGEMENTS The authors wish to express sincerely thanks to Professor Akiyama, the University of Tokyo, for his useful advice for this study. We also thank Mr. Y. Suizu and Mr. T. Yokoi of Bridgestone Corporation, Mr. Daniel Batt, Duke University student who visited NIED as summer institute student, for their helps of executing this experiment. 7

REFERENCES [1]T.Fujita, Seismic isolation rubber bearings for nuclear facilities,nuclear Engineering and Design, Vol.17, pp379-391,1991 []M.Kato, Y.Watanabe, A.Kato,H.Koshida, K.Mizukoshi, Y.Fukushima, O.Nojima, G.Yoneda and S.Onimaru, Dynamic breaking tests on base-isolated FBR plant, Transactions of the 1th International Conference on Structural Mechanics in Reactor Technology, Vol.K, pp67-78,aug., 1993. [3]K.Mizukoshi, A.Yasaka, M.Iizuka and K. Takabayashi, Failure test of laminated rubber bearings with various shapes, Proceedings of Tenth World Conference on Earthquake Engineering, Vol.4, pp77-80, July, 199 [4]M. Moteki, N. Kawai, K.Ishida, S.Yabana and O. Nojima,Shaking table test on ultimate behavior of seismic isolation system Part 1: Outline of the test and response of superstructure, Proceedings of Tenth World Conference on Earthquake Engineering, Vol.4, pp71-76, July, 199. [5]S.Suzuki, T.Fujita, S.Fujita, Ultimate Strength of Seismic Isolation System Using High Damping Rubber Bearing For Building (Ist Report, Analytical Method for Ultimate Strength) Transaction of JSME ( C ) Vol. 57-544, pp189-196, 1991-1 8