Ordinances of the Plainview Water District Town of Oyster Bay, Nassau County, New York ARTICLE VII CONTROL OF BACKFLOW AND CROSS-CONNECTIONS

Similar documents
DIVISION 2: BACKFLOW PREVENTION PROGRAM

CITY OF HAMILTON Codified Ordinance CHAPTER 941

CHAPTER 6 SECTION 6.19 AN ORDINANCE OF THE TOWN OF MAYODAN TO PROTECT THE QUALITY OF THE PUBLIC POTABLE WATER SUPPLY

CROSS CONNECTION CONTROL PROGRAM

HOLLEY NAVARRE WATER SYSTEM, INC. BACKFLOW PREVENTION & CROSS CONNECTION CONTROL POLICIES & REGULATIONS

WEST JACKSON COUNTY UTILITY DISTRICT

CROSS-CONNECTION CONTROL AND BACKFLOW PREVENTION PROGRAM THE ISLAND WATER ASSOCIATION, INC. SANIBEL, FLORIDA

ROCHESTER PUBLIC UTILITIES PUBLIC WATER SYSTEM CROSS-CONNECTION CONTROL AND BACKFLOW PREVENTION PROGRAM FOR ROCHESTER, MINNESOTA

Missouri American Water Cross Connection Control Program

The rules and regulations, as part of this document, shall apply to all premises serviced by the public water system of the Northeast Water System.

DIVISION 3. CROSS CONNECTION CONTROL* Sec Definitions.

The following words and terms, when used in this article, shall have the following definitions, unless the context clearly indicates otherwise:

Backflow Prevention by Containment & Cross-Connection Control Program Easton Suburban Water Authority

December Illinois American Water Cross Connection Control Program

MODEL ORDINANCE FOR CROSS CONNECTION CONTROL BE IT ORDAINED BY THE GOVERNING BODY OF THE CITY OF, STATE OF WYOMING:

Premises Isolation Cross-Connection Control Program

EL DORADO IRRIGATION DISTRICT

ORDINANCE NO. 519 AN ORDINANCE ADOPTING THE RULES AND REGULATIONS RELATING TO WATER SUPPLY CROSS-CONNECTIONS AND REPEALING ORDINANCE NO. 459.

ARTICLE IV CROSS CONNECTION CONTROL AND BACKFLOW PREVENTION

JACKSON COUNTY WATER AND SEWERAGE AUTHORITY. Cross-Connection Control Program

THE CONSOLIDATED MUTUAL WATER COMPANY CROSS CONNECTION CONTROL PROGRAM GENERALLY

ORDINANCE NO AN ORDINANCE OF THE COASTSIDE COUNTY WATER DISTRICT

City of Weiser Cross Connection ordinance 1217

SECTION XIV: BACKFLOW PREVENTION AND CROSS-CONNECTION CONTROL Backflow Prevention & Cross-Connection Control Program Purpose

DIVISION 5. BACKFLOW PREVENTION AND CROSS-CONNECTION CONTROL

CROSS-CONNECTION CONTROL/BACKFLOW PREVENTION

ARTICLE VI. The Town of Trappe Cross Connection and Backflow Prevention Program is contained in

PROVIDENCE WATER SUPPLY BOARD CROSS-CONNECTION CONTROL PROGRAM RULES AND REGULATIONS

C R O S S - C O N N E C T I O N C O N T R O L

THE CONSOLIDATED MUTUAL WATER COMPANY CROSS CONNECTION CONTROL PROGRAM GENERALLY

QUONSET DEVELOPMENT CORPORATION QUONSET & LADD WATER SYSTEMS CROSS CONNECTION CONTROL & BACKFLOW PREVENTION POLICY

Elmira Water Board Cross Connection Control Program

TITLE 17. (b) Auxiliary Water Supply is any water supply other than that received from a public water system.

CITY OF GLENVILLE 20 North Court Street Glenville WV

130 CROSS CONNECTION CONTROL

CROSS-CONNECTION CONTROL PROGRAM HARVEST-MONROVIA WATER, SEWER AND FIRE PROTECTION AUTHORITY

RURAL WATER DISTRICT

HIGHLANDS WATER COMPANY Lakeshore Drive Clearlake, California {707}

Cross-Connection Control and Backflow Prevention Program

Florida Administrative Codes and

ORD-3182 BE IT ORDAINED BY THE COUNCIL OF THE CITY OF VIRGINIA BEACH, VIRGINIA:

PORTLAND WATER DISTRICT CROSS-CONNECTION CONTROL PROGRAM 1989 REVISED MAY, 2006 REVISED SEPTEMBER, 2009 REVISED JUNE, 2017

Town of Chocowinity Backflow and Cross Connection Ordinance

CROSS-CONNECTION CONTROL PROGRAM

Cross-Connection Control Program

Cross Connection Control Rules

SECTION 3 CROSS CONNECTION CONTROL

ORDINANCE NO. 124 SECTION 1 - GENERAL POLICY. 1.0 PURPOSE- The purpose of this ordinance is:

ORDINANCE NO Chapter 203B of the Glencoe Municipal Code is established to read in its entirety as follows:

Premises having a repeated history of cross-connections being established or reestablished.

CHAPTER 53: BACKFLOW PREVENTION AND CROSS CONNECTION CONTROL

WEST MEMPHIS UTILITY COMMISSION

Orange County Utilities Cross Connection Control Manual November 2017 Revision 3

Cross-Connection Control Program and Plan of Operation

Policy Number: 6030 Cross-Connection & Backflow Prevention 1. GENERAL 2. PURPOSE 3. AUTHORITY 4. DEFINITIONS

DUPLIN COUNTY BACKFLOW PREVENTION ORDINANCE This ordinance shall be known as the Duplin County Backflow Prevention Ordinance.

8.04 Protection Requirements

310 CMR Cross Connection Distribution System Protection - Effective Date: 01/05/2001 Page 1 of 15

SECTION CROSS CONNECTION CONTROL TABLE OF CONTENTS

KING COUNTY WATER DISTRICT NO. 125 KING COUNTY, WASHINGTON. RESOLUTION NO. ~ S D * \k: - dj (j

RULES AND REGULATIONS FOR WATER AND WASTEWATER SERVICE APPENDIX G BACKFLOW PREVENTION AND CROSS CONNECTION CONTROL (BPCCC) PROGRAM

DEQ CROSS CONNECTION CONTROL UPDATE MAY 9, 2018

Backflow Prevention:The Forefront of Responsible Irrigation

Policy Number: 6030 Cross-Connection & Backflow Prevention 1. GENERAL 2. PURPOSE 3. AUTHORITY 4. DEFINITIONS

WATER DEPARTMENT STANDARD SPECIFCATIONS SECTION 301 CROSS CONNECTION POLICY

Effective Date: November 2, 2010 Reaffirmed Date: June 19, 2012 Reaffirmed Date: July 21, 2015

Shannon Water and Sanitation District Backflow Prevention and Cross-Connection Control Program

; WATERMAINS SPECIFICATIONS FOR CROSS CONNECTIONS and BACKFLOW PREVENTION SECTION C5.0

AS APPROVED ON FIRST READING JUNE 14. Additions To The Current Breckenridge Town Code Are Indicated By Bold + Double Underline; Deletions By Strikeout

TITLE 64 LEGISLATIVE RULE BUREAU FOR PUBLIC HEALTH SERIES 15 CROSS-CONNECTION CONTROL AND BACKFLOW PREVENTION. use.

CROSS CONNECTION CONTROL PROGRAM POLICY Adopted March, 1990 Revised October, 2006

Cross Connection Control. WAC It s the Law Hydraulics Terms & Applications Backflow Assembly Assistance Program Questions

CROSS CONNECTION CONTROL PROGRAM

FRWA SAMPLE ORDINANCE

DRINKING WATER STANDARDS, MONITORING, AND REPORTING

Sec Backflow prevention and cross-connection control.

Backflow & Cross Connection Control Program

Newport Water District CROSS CONNECTION CONTROL PROGRAM

LAKE CRYSTAL MUNICIPAL UTILITIES CROSS CONNECTION AND BACKFLOW PREVENTION POLICY

GASPARILLA ISLAND WATER ASSOCIATION, INC. (GIWA) BACKFLOW PREVENTION AND CROSS-CONNECTION CONTROL PROGRAM

CITY OF GAINESVILLE DEPARTMENT OF WATER RESOURCES

Backflow Prevention Containment Policy

Riviera Beach DIVISION 2. CROSS CONNECTION CONTROL

Cross Connection Control & Backflow Assembly Testing

Chapter 82 UTILITIES [1]

CROSS-CONNECTION CONTROL PROGRAM MANUAL. Resolution

Backflow Device Inspections & Cross Connections Policy

Charlotte County Utilities Manual of Rules and Regulations Governing Cross- Connection Control FEBRUARY 2008

(Contaminant) Backsiphonage or Backpressure Backsiphonage or Backpressure

DALTON UTILITIES CROSS CONNECTION CONTROL RULES AND REGULATIONS. Enacted By THE WATER, LIGHT & SINKING FUND COMMISSION OF DALTON, GEORGIA

REGULATIONS FOR USERS OF THE NORTHBOROUGH WATER SUPPLY AND DISTRIBUTION SYSTEM

qwertyuiopasdfghjklzxcvbnmqwertyui opasdfghjklzxcvbnmqwertyuiopasdfgh jklzxcvbnmqwertyuiopasdfghjklzxcvb nmqwertyuiopasdfghjklzxcvbnmqwer

A BRIEF LOOK AT BACKFLOW PREVENTION AND CROSS-CONNECTION CONTROL LES O BRIEN

ARTICLE 11 - Backflow Prevention and Cross Connection Control

BACKFLOW PREVENTION ASSEMBLY INSTALLATION STANDARDS

CROSS CONNECTION CONTROL PROGRAM PLAN CCCPP 8/13/2012 THE TOWN OF WRENTHAM WATER DIVISION

NEW WATER SERVICE TAPS AND SPECIFICATIONS FOR REQUIRED METER SETTINGS

BEAU CHÊNE HOMEOWNERS ASSOCIATION, INC. CROSS CONNECTION CONTROL RULE

Cross Connection Control And Backflow Prevention Program. City of Rifle, Colorado Utility Department

ORDINANCE NO. 17. Series 2016 AN ORDINANCE AMENDING TITLE 12 OF THE BRECKENRIDGE TOWN CODE CONCERNING THE TOWN S MUNICIPAL WATER SYSTEM

Transcription:

ARTICLE VII CONTROL OF BACKFLOW AND CROSS-CONNECTIONS Section 7.1 STATEMENT OF POLICY It is the policy of the Water District to protect the public water system by containing potential contamination within the premises of the user. Consumers are required to follow the applicable provisions of the New York State Sanitary Code, as well as the requirements set forth in the Department's Cross Connection Control Handbook and all applicable federal, state and local regulatory requirements. Section 7.2 STATUTORY AUTHORITY Chapter I, Title 10, New York State Sanitary Code, Part 5, Drinking Water Supplied, 5-1.31, Cross Connection Control requires that a supplier of water shall protect the public water system in accordance with acceptable procedures by containing potential contamination within the premises of the user in the following manner: By requiring an acceptable air gap, double check valve assembly, reduced pressure zone device or equivalent protective device acceptable and consistent with the degree of hazard posed by the premises served by the connection. By requiring the users of such connections to submit plans for the installation of protective devices to the supplier of water and the Nassau County Department of Health for approval; and By assuring that all protective devices installed be tested at least annually. Section 7.3 RESPONSIBILITY OF THE DISTRICT The Board of Commissioners, Superintendent or their designated agent shall inspect plumbing in every building or premises in the Plainview Water District as frequently as in their judgment may be necessary to ensure that such plumbing has been installed in such a manner as to prevent the possibility of pollution of the water supply of the District by the plumbing. The Board of Commissioners shall notify or cause to be notified in writing the owner or authorized agent of the owner of any such building or premises, to correct, within a reasonable time set by the Board of Commissioners, any plumbing installed or existing contrary to or in violation of the rules and regulations and which in their judgment, may, therefore, permit the pollution of the District s water supply, or otherwise adversely affect the public health. The Board of Commissioners, or their designated agent, shall have the right of entry into any building, during reasonable hours, for the purpose of making inspection of the plumbing systems installed in such building or premises provided that with respect to the inspection of any single family dwelling, consent to such inspection shall first be obtained from a person of suitable age and discretion therein or in control thereof. This Section is particularly applicable to lawn sprinklers, air conditioning, refrigeration, and aspirating equipment installations. 2-9-16 1

Section 7.3.1 Inspection Ordinances of the Plainview Water District The District shall cause a routine inspection of all premises served which are not already provided with the approved backflow prevention devices. Such inspections shall be conducted at an interval of no longer than one (1) year for non-residential services and five (5) years for residential services. For the purpose of this ordinance, a multiple dwelling and a residence used in part for business purposes shall be considered to be non-residential. Once it has been determined that a premises requires a backflow prevention device, the owner of said premises shall be notified and required to install and maintain an approved double check valve (DCV), reduced pressure zone (RPZ) device or equivalent protective device as appropriate in accordance with the requirements of this ordinance. Section 7.3.2 Right of Entry The District, or their authorized agent, shall have the right of entry into any premises during reasonable hours for the purpose of making an evaluation of the premises provided that with respect to the inspection of any single family dwelling under this Article consent to such inspection shall first be obtained from a person of suitable age and discretion therein, or in control thereof. Section 7.3.3 Multiple Dwellings and Commercial and Industrial Buildings The District, or its designated agent, may require the owner of any multiple dwelling, commercial or industrial building to designate some qualified person to be in charge of the water supply for that building. Section 7.4: DEFINITIONS When used in this Article, unless otherwise indicated, the following words shall have the following meanings: APPROVED BACKFLOW PREVENTION DEVICE is an air gap, reduced pressure zone device, double check valve assembly or equivalent protective device, as applicable and approved by the New York State Department of Health, to contain existing or potential contamination within a customer s facility. AESTHETICALLY OBJECTIONABLE FACILITY is one in which substances are present which, if introduced into the public water supply system, could be a nuisance to other water customers, but would not adversely affect human health. Typical examples of such substances are: food grade dyes, hot water, stagnant water from fire lines in which no chemical additives are used, etc. AIR GAP means the unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe or faucet supplying water to a tank-plumbing fixture or other device and the flood level rim of the receptacle. The differential distance shall be at least double the inside diameter of the supply pipe. In no case shall the air gap be less than one (1 ) inch. 2-9-16 2

BACKFLOW means a flow condition, induced by a differential in pressure that causes the flow of water or other liquids and/or gases into the distribution pipes of a public water supply from any source other than the intended source. BACKPRESSURE means the resulting backflow of water from a plumbing fixture or other customer source(s) into a public water supply system due to a greater pressure within the customer s water system. BACKSIPHONAGE means the backflow of water from a plumbing fixture or other customer source(s) into a public water supply system main due to a temporary negative or sub-atmospheric pressure within the public water supply system. CERTIFIED BACKFLOW PREVENTION DEVICE TESTER is a person having completed the required training course and holding a current certification issued by the New York State Department of Health. CONTAINMENT means cross-connection control that isolates the consumer s entire facility from the public water system so as to provide the protection necessary to prevent contamination of the public water supply in the event of backflow from the consumer s facility. CROSS-CONNECTION means a physical connection through which a water supply could be contaminated. DEGREE OF HAZARD means whether a facility is rated as hazardous, aesthetically objectionable or non-hazardous. DOUBLE-CHECK VALVE (DCV) ASSEMBLY means two single independently acting check valves, including tightly closing shutoff valves located at each end of the assembly and suitable connections for testing the water tightness of each valve. HAZARDOUS FACILITY is one in which substances may be present which, if introduced into the public water system, would or may endanger or have an adverse effect on the health of other water customers. Typical examples are laboratories, sewage treatment plants, hospitals, and mortuaries. INTERCONNECTION is a joining of two independently operated public water distribution systems. LOCAL HEALTH DEPARTMENT ENGINEER is the Nassau County Health Department Engineer. NON-HAZARDOUS FACILITY is one, which does not require the installation of an acceptable backflow prevention device. OUTLET is the open end of the water supply pipe through which the water is discharged. 2-9-16 3

POTABLE WATER is that which complies with the drinking water quality provisions of the State Sanitary Code, Part 5, Drinking Water Supplies. REDUCED PRESSURE ZONE (RPZ) DEVICE means a minimum of two (2) independently acting check valves, together with an automatically operated pressure differential relief valve located between the two (2) check valves. During normal flow and at the cessation of normal flow, the pressure between these two (2) checks shall be less than upstream (supply) pressure. In case of leakage of either check valve, the differential relief valve, by discharging to the atmosphere, shall operate to maintain the pressure between the checks at less than the supply pressure. The unit must include tightly closing shutoff valves located at each end of the device and each device shall be fitted with properly located test cocks. INDIVIDUAL WATER SUPPLY means any water source or system other than the Plainview Water District supply, which may be available in the building or on the premises. Section 7.5 CROSS CONNECTIONS Cross-connections between the customer s water system in premises served by the District, which are rated aesthetically objectionable and/or hazardous, are prohibited except where an approved backflow prevention device has been installed to prevent contamination of the potable system. The District shall determine the degree of hazard posed by the service connection to the premises and shall determine the type of backflow prevention device that is required to be installed. In each instance where a condition, device or practice has a potential for a cross connection with the water supply, an approved air gap, reduced pressure zone device, a double check valve assembly or equivalent protective device must be installed commensurate with the degree of hazard encountered. Individual Water Supply Cross-connections between an individual water supply (i.e. private well) and the potable water supply of the District shall not be made unless specifically approved by the Board of Commissioners and the New York State Department of Health. Section 7.6 INTERCONNECTIONS Interconnections are prohibited except for emergency interconnections with other public water purveyors. Section 7.7 DISTRICT REQUIRED BACKFLOW DEVICES a) All new residential services must be equipped with, at the very least, an approved double check valve assembly (DCVA). b) All non-residential services must be equipped with an approved reduced pressure zone (RPZ) device. 2-9-16 4

c) All fire service and by-pass lines must be equipped with an approved DCVA. d) Where underground sprinkler systems employ chemicals, an approved RPZ device shall be required. e) Services with a private well that is interconnected or has the potential to be interconnected with the public water supply must be equipped with an approved RPZ device. f) All underground sprinkler systems and swimming pools with direct fill capability must have installed a minimum of a DCVA. g) All wet-pipe systems utilizing antifreeze, corrosion control additives or any other foreign substance, or which are located near an alternative source of supply (canals, ponds, etc.) shall be equipped with an approved RPZ device. Section 7.8 APPROVALS, PROCEDURES AND INSTALLATIONS OF BACKFLOW DEVICES Applications and instructions for the installation of backflow devices are available at the District. Applications are subject to review and approval by the District. The fee associated with the District s review can be found on the Plainview Water District Fees and Charges schedule located on our website at www.plainviewwater.org. If a device is installed on a 2 or larger service line, a separate application must be made to the Nassau County Department of Health for their approval. The Nassau County Department of Health also charges for their review of plans in accordance with their latest fee schedule. In order to insure full containment, backflow devices must be installed immediately after the water meter. No connections shall be made between the meter and the backflow device. All installations shall be made by a duly licensed plumber of the Town of Oyster Bay. A New York State certified tester must test Backflow devices at least once a year. Records of such tests must be filed with the District as required by New York State law. The approval procedure is as follows: a. For Devices Less Than 2 : The applicant must file with the District an application on the current New York State Health Department form, together with plans and specifications for the installation of the proposed backflow prevention device. Copies of the form, typical plans previously approved by the Nassau County Department of Health, and specifications for the installation of the backflow devices, as well as a list of devices acceptable to the New York State Department of Health for containment control are available from the District. 2-9-16 5

b. For Devices 2 and Larger: Ordinances of the Plainview Water District A separate application must be made to the Nassau County Department of Health and a copy filed with the District. After approval is obtained from the Department of Health, the customer shall have the backflow prevention device installed in accordance with the plans and specifications. Certification that the device was installed in accordance with the approved plan shall be made to the District by the installer. At the completion of the installation, and within forty-five (45) days, the device shall be tested by a Certified Backflow Prevention Device Tester. A report of the results of the test shall be submitted to the District within thirty (30) days of the test. Section 7.9 TECHNICAL REQUIREMENTS a) New Water Supply Connections 1. Residential An approved reduced pressure zone (RPZ) backflow prevention device or double-check valve (DCV) shall be installed in an appropriate meter pit or other approved location on all new water supply connections supplying water to any residential premises. 2. Commercial, industrial or other non residential structure connected to the potable water system of the District shall have an RPZ backflow prevention device. b) Existing Water Supply Connections Retroactive hereto, an approved backflow prevention device shall be retrofitted in an appropriate meter pit or location as approved by the District for all existing water supply systems or services, which include but are not limited to: 1. An irrigation system; 2. A private well that is interconnected or has the potential to be interconnected with the public water supply; 3. A solar heating system; and 4. Any system rated aesthetically objectionable and/or hazardous by the Nassau County Department of Health or the District. The same retrofit requirements apply to all industrial, commercial and other nonresidential structures. 2-9-16 6

c) Maintenance Requirements 1. General Requirements It shall be the responsibility of the building and premises owners to perform required testing and to maintain all backflow prevention devices within their building or on their premises in good working order and to make no piping or other arrangements for the purpose of bypassing the backflow devices. The owner at his sole cost and expense is responsible for complying with the New York State and Nassau County Department of Health s Rules and Regulations for control of backflow and cross-connections. 2. Testing and Repair of Backflow Prevention Devices Backflow prevention devices installed for the purpose of containment shall be tested annually (when required) starting from the date of the initial test performed at the time of installation. A New York State Department of Health Certified Backflow Prevention Device Tester shall conduct testing. Each backflow device tested shall bear an inspection certificate tag indicating the date of the latest test and the name and address of the Certified Tester who conducted the test. The owner or tester shall file a report of the test on the appropriate Department of Health form with the District within thirty (30) days of conducting the test. Any device, which fails a test, shall be repaired and retested within thirty (30) days. 2-9-16 7