Technical Notes. Mandatory Barrier Cable Inspection Requirements

Similar documents
Barrier Cable Systems, Inc.

TAB.3 13 Post Tensioning Terminology (PTT)

1. Cast-in-place concrete is specified in Section

Concrete Prestressed Concrete Pretensioned Concrete Posttensioned Concrete Typical Tendon Layout

***************************************************************************************************************

D D TYPE A1, A2 & B MICHIGAN DEPARTMENT OF TRANSPORTATION 5-40 CONNECTION. L4" x 4" x 3/8" Brace. C8 x 4.25 Strut. WT9 x 17.5.

Post-tensioned Concrete Design PT Installation Guidance

ACI AND PTI REQUIREMENTS FOR ENCAPSULATION SYSTEMS

The Hashemite University Department of Civil Engineering. Dr. Hazim Dwairi. Dr. Hazim Dwairi 1

Barrier Cable Systems, Inc.

EVALUATION & REPAIR OF CORROSION DAMAGED ROOF LIFT SLAB WITH WIRE POST-TENSIONING SYSTEM (BUTTON HEADS)

PRODUCT EVALUATION Effective Date: June 1, 2013 GDR-39

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Value of Specifying Grouted Field Personnel Certification. May 2012 PTI Convention - Nashville Gregory Hunsicker, P.E.

SPECIAL SPECIFICATION 4492 Tie Back Anchors

SECTION CONCRETE FORMWORK AND ACCESSORIES

Evaluation of Corrosion Damage in Unbonded Post-Tensioned Concrete Structures:

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

Pallet Gate Installation Instructions and Operators Manual

SECTION LIGHTNING PROTECTION SYSTEM

SINGLE SWING DOOR PAIRED SWING DOOR

600 SERIES FOUNDATIONLESS JIB CRANE MANUAL ADDENDUM

SPECIAL INSPECTION AND OBSERVATION PROGRAM CITY OF CONCORD BUILDING DIVISION. Project Address:

TILT-UP PRECAST CONCRETE SANDWICH PANELS. A. Work includes, but is not limited to, the following:

Student Services & Classroom Addition SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

SECTION MANUAL FOUR FOLD DOORS MODEL 38 DECORATIVE PANEL DESIGN

B. Related work in other Sections related to Post-tensioned Concrete include: 1. Section Structural Testing Laboratory Services.

NDT in Grouted PT Inspection for Bridges

AcroWall-ES System. Class PB Exterior Insulation and Finish System providing a primary moisture barrier. Typical Details

Interior Hangers. Application

SECTION VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND EQUIPMENT

THE NEW ACI STANDARD SPECIFICATION FOR UNBONDED TENDONS

CTP STITCH-TIE AGAIN! Quick and easy way to re-anchor existing veneers to back-up structures.

SECTION TILT-UP PRECAST CONCRETE SANDWICH PANELS. A. Work includes, but is not limited to, the following:

METALS Commissioning of Metals Structural Steel Framing Steel Studs... 2

Pedestrian Flood Door

MODEL SPECIFICATIONS: Hydraulically Driven Steel Underpinning Pile Specifications

***************************************************************************************************************

SPECIAL SPECIFICATION 4401 Prestressed Ground Anchors

SECTION 2 DIVISION 05 METALS

INSTALLATION INSTRUCTION

Rak Production Technology of Concrete Structures (2015) Concrete Reinforcement

Installation and Use Instructions for the Big Ass Workbench Manufactured by Mercer Innovation, LLC

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

Intermountain Section AWWA Conference - 2.0MG Layton Water Tank. Jake O Brien

EVALUATION REPORT. PFC-5551 Reissued April 1, Filing Category: DESIGN Steel (038)

Requirements for Measuring and Pricing of Structural Concrete

SECTION METAL FABRICATIONS FOR STEAM UTILITY DISTRIBUTION

Insulating Cellular Concrete Steel Joists Painting. A. America Society for Testing and Materials (ASTM):

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF POLES

Code Compliance Research Report CCRR-0238

SECTION ARCHITECTURAL PRECAST CONCRETE. A. American Society for Testing and Materials (ASTM):

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

POST-TENSIONING VS. PRESTRESSING

CONSTRUCTION SPECIFICATION FOR FOOTINGS AND PADS FOR ELECTRICAL EQUIPMENT

PRODUCT EVALUATION Effective Date: June 1, 2013 GDR-40

Code Compliance Research Report CCRR-0187

B. Shop Drawings: Include plans, elevations, sections, details, and attachments to other work.

Stone and Masonry Veneer

Prestress and Precast Products. MeadowBurke

CONSTRUCTION SPECIFICATION FOR POLE ERECTION

American Metal Specialties, Inc.

Code Compliance Research Report CCRR-0118

SECTION A. Product Data: Manufacturer's data sheets on each product to be used, including:

AMSYSCO U N B O N D E D POST-TENSIONING S Y S T E M S + S E R V I C E + E N G I N E E R I N G

CONSTRUCTION SPECIFICATION FOR ERECTION OF POLES

CONSTRUCTION SPECIFICATION FOR ERECTION OF POLES

Table of Contents. List of Drawings

716 - POST-TENSIONING (Haunched Slab Bridges) SECTION 716. POST-TENSIONING (Haunched Slab Bridges)

SECTION AWNINGS

Code Compliance Research Report CCRR-0163

MODELS: 24 SM & 24 SMSS

SECTION A. Product Data: Manufacturer's data sheets on each product to be used, including:

A M E R I C A N A R C H I T E C T U R A L M A N U F A C T U R E R S A S S O C I A T I O N

Special Provision No. 109S17 June 2017

FYPON, LLC. February 2014

1. Temperature Change: 120 deg F (67 deg C), ambient; 180 deg F (100 deg C), material surfaces.

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

US-131 Over the Muskegon River. Corey Rogers, P.E. Bridge Construction Engineer

POST TENSIONED SLABS. Imagineering the possibilities

Wabo ElastoFlex Bridge Series Continuous Membrane Sealing System

Post-tensioned Structures Solutions for Repair and Protection

SECTION STRUCTURAL PRECAST HOLLOW CORE SLABS

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017


SECTION 552 HELICAL ANCHORS AND HELICAL PILES

SECTION ALUMINUM GATES

SECTION A. Product Data: Manufacturer's data sheets on each product to be used, including:

PIP PCEPA003 Process Analyzer System Field Installation Guidelines

Model # 800SM-PS3. 8/3/2016 Page 1 of 8

SECTION WELDED STEEL PICKET FENCE. 1. Fusion welded and rackable ornamental steel picket fence system.

CONSTRUCTION PROCEDURES. AWWA D110 Type I Prestressed Concrete Tanks

Introduction Introduction

INSTALLATION MANUAL RECTANGULAR COLUMN

TORQUE TESTING & INSTALLATION INSPECTION OF DRILLED - IN ANCHORS

Introductory Chapter

SERIES G1A, G1B & G1C SLIDE GATES

In Association with. DSE PROJECTS - Lebanon

Model # BT238-U6. 9/30/2014 Page 1 of 12

Transcription:

Technical Notes From M-10: Unbonded Tendon Committee Issue 20 December 2015 Mandary Barrier Cable Inspection Requirements Inspection of barrier cable installation in accordance with the PTI M10.4-07, Specification for Seven-Wire Prestressing Steel Strand for Barrier Cable Applications, 1 is required ensure proper functioning and durability of the barrier cable (BC) system. The BC system shall be inspected by a PTI 2 Unbonded PT Inspecr and shall include the following: Note: The following definitions shall be used for the entire document: The terms verify, verified, and verification indicate spot-checking, observations at critical steps, or forensic observations after an operation. The terms monir, monired, and moniring indicate that an on-site inspecr shall be present during the specified operations. The term BC installation drawings refers the latest update issued for construction. Items listed below may not all be applicable the BC system. Refer the BC installation drawing for project-specific details. 1 INSTALLATION OF EMBEDDED ITEMS PRIOR TO CONCRETE PLACEMENT Before concrete is placed in any columns or walls that contain barrier cable embedded hardware, the following items shall be verified be in compliance with the BC installation drawings and applicable codes: Proper installation of the BC system, including anchors with pocket formers, polyvinyl chloride (PVC) sleeves, and inserts; Spacing between anchors, sleeves, and inserts; Height of the pmost anchors, sleeves, and inserts; Anchorage zone reinforcement; Steel plates with studs or bent reinforcing bar used attach surface-mounted steel members; and Correct grade and size of steel plates located at the specified location. 2 INSTALLATION OF SURFACE-MOUNTED STEEL MEMBERS Before any stressing or is performed, the following items shall be verified be in compliance with the BC installation drawings and applicable codes: Proper installation of the BC system, including surface-mounted steel members, threaded insert anchors, and barrel anchors with wedges; Correct type, grade, and size of the steel members located at the specified location; Surface-mounted steel members secured the concrete with the specified quantity, size, and length of anchor bolts; Surface-mounted steel members secured steel plates with studs or bent reinforcing bar that were previously cast in the concrete, as a minimum, continuously welded on both sides of the steel members or as otherwise specified in the BC installation drawings; BC spacing; and Height of the pmost barrier cable. 3 BARRIER CABLE JACKING FORCE BC jacking force in each barrier cable shall be monired by one of the following methods: Inspecr present during all stressing operations moniring BC jacking force in each barrier cable; or Other method as approved by the licensed design professional. Each barrier cable shall be stressed the BC jacking force specified on the BC installation drawings. Note: Barrier cables are stressed a force significantly less than the typical 80% f pu that is used for structural posttensioning applications (refer the BC installation drawings and the jack calibration and/or gauge reading supplied by the BC supplier). 4 BACK STRESSING Back stressing force in each barrier cable shall be monired by one of the following methods: Inspecr present during all operations moniring force in each barrier cable; or Other method as approved by the licensed design professional. Each barrier cable shall be back stressed the force specified on the BC installation drawings and recorded in the BC inspection log. Back stressing should be done immediately 1

after each barrier cable is stressed. Monir that wedges are seated evenly. For jobsite-installed anchorages only, an indication that has occurred is the presence of jack gripper marks (Fig. 2) on the barrier cable on the backside of the column/channel/end terminal condition; verification of the jack gripper marks should not be considered as a confirmation that the full required force has been applied. Jobsite or plant preinstalled anchorages may not have visible jack gripper marks. The full wedge seating in this case should be verified by the installer or supplier. 5 RESTORATION OF CORROSION PROTECTION AFTER BACK STRESSING Verify that corrosion protection of barrier cables was resred after according the BC installation drawings. Check that damaged coating was repaired using methods and materials as specified or approved by the licensed design professional (LDP). Damaged coating materials can be repaired using repair materials and methods compatible with the coating material such as heat-shrink sleeve, silicone caulk, epoxy coating, zinc-rich coating, or other approved materials that will provide protection against corrosion. (a) Barrier cable being stressed specified force (refer the BC installation drawings for BC jacking force) (b) Barrier cable being back stressed (refer the BC installation drawings for force) Note: For in recessed areas, a level bearing surface must be created by either using an oversized special bearing plate spanning over the recess or by using shims create a level area. Fig. 1 (a) Barrier cable stressing; and (b). Fig. 2 Galvanized barrier cable with jack gripper marks after. 2 PTI Technical Note Technical Note No. 20

6 SEALING SLEEVES IN COLUMNS (WHEN APPLICABLE) Verify that sleeves in end columns have been sealed per the BC installation drawings avoid moisture penetration. Use an elastic material that will remain pliable, watertight, and be compatible with the coating material. It shall extend at least 1 in. (25 mm) inside the face of the column (Fig. 1(b)). 7 FINISHING Verify that strand tails were trimmed the specified length and protected against corrosion as specified, maintaining required concrete cover. Verify that stressing pockets were properly filled with specified or approved material. 2 Verify that stressing pockets were filled within the time period specified. If the strand tails are left exposed the elements in their final configuration, verify that the strand tails have been protected according the BC installation drawings. 8 BARRIER CABLE INSPECTION LOG Submit the BC inspection log (Attachment A) LDP with verification of spacing/height, BC jacking force, and finishing for each barrier cable. Recording the required inspection items on the BC installation log. a. During the initial inspection, inspect items for barrier cable fixed ends, spacing and height, stressing, and finishing. If all the items are in compliance with BC installation drawings, enter Yes in the appropriate column. If any item is not in compliance, enter No in the appropriate column and indicate which barrier cable(s) (numbering p botm) and what is out of compliance. This information is recorded in the noncompliance/notes column. The installer or inspecr enters their initials and the date of the initial inspection. b. Any items that were out of compliance during the initial inspection will need be corrected. Once corrected, a follow-up inspection is required (shaded cells in Appendix A). The inspecr will review the noncompliance items and if they have been corrected, will enter Yes in the noncompliance items corrected column. The action taken correct the noncompliance is recorded in the notes column. The inspecr enters their initials and the date of the follow-up inspection. c. If the BC installation drawings specify different BC jacking forces for each barrier cable (for example, higher BC jacking forces in the impact area), multiple BC installation logs should be used during the inspection. The form is designed inspect the barrier cables at a single BC jacking force. 9 REFERENCES 1. PTI Committee M10, Specification for Seven-Wire Prestressing Steel Strand for Barrier Cable Applications (PTI M10.4-07), second edition, Post-Tensioning Institute, Farmingn Hills, MI, 2007, 16 pp. 2. PTI FAQ No. 11, Proper Filling of Single-Strand Tendon Stressing Pockets, Post-Tensioning Institute, Farmingn Hills, MI, 2010, 1 p. Technical Note, December 2015 38800 Country Club Drive, Farmingn Hills, MI 48331 Phone: (248) 848-3180 Fax: (248) 848-3181 Web: www.post-tensioning.org This document is intended for the use of professionals competent evaluate the significance and limitations of its contents and who will accept responsibility for the application of the materials it contains. The Post-Tensioning Institute reports the foregoing material as a matter of information and therefore disclaims any and all responsibility for application of the stated principals or for the accuracy of the sources other than material developed by the Institute. The Post-Tensioning Institute in publishing these Technical Notes makes no warranty regarding the recommendations contained herein, including warranties of quality, workmanship, or safety, express or implied, further including, but not limited, implied warranties or merchantability and fitness for a particular purpose. The Post-Tensioning Institute and the author shall not be liable for any damages, including consequential damages beyond refund of the purchase price of this issue of Technical Notes. The incorporation by reference or quotation of material in the Technical Notes in any specifications, contract documents, purchase orders, drawings, or job details shall be done at the risk of those making such reference or quotation and shall not subject the Post-Tensioning Institute or the Author any liability, direct or indirect, and those making such reference or quotation shall waive any claims against the Post-Tensioning Institute or the Author. Copyright 2015 by Post-Tensioning Institute All Rights Reserved Printed in U.S.A. 3

Inspection of Barrier Cable Installation Through or Attached Concrete Columns Site Address General contracr Gauge Serial # of For Construction BC installation drawings Barrier Cables at the exterior on lines and Specified distance from p of slab middle of pmost cable Surface mounted steel members secured columns per dwgs Stressed BC force indicated on dwgs Back stressed force indicated on dwgs Resration of corrosion protection after Botm cable # varies & Specified Jacking Force (kips): Specified Gauge Reading (psi): Specified Back stressing Force (kips): Cable Numbers: & Exterior Slabs 4 PTI Technical Note Technical Note No. 20

Inspection of Barrier Cable Installation Through or Attached Concrete Columns Site Address General contracr Gauge Serial # of For Construction BC installation drawings Barrier Cables at the exterior on lines D and A Specified distance from p of slab middle of pmost cable Surface mounted steel members secured columns per dwgs Stressed BC force indicated on dwgs Back stressed force indicated on dwgs Resration of corrosion protection after 1 23 Botm cable # varies N D A D & 1 23 Specified Jacking Force (kips): 3.5 Specified Gauge Reading (psi): 900 Specified Back stressing Force (kips): 33 Cable Numbers: #1 #6 and #10 #11 2 Yes Yes Yes Yes Yes Yes No Yes N/A DJS 10/26 3 Yes No No Yes Yes Yes Yes Yes N/A DJS 10/26 Cable #7 did not get epoxy coating. Angles at lines 10 thru 14 were o low. Yes PS 11/15 Cable was coated with epoxy. Yes DJS 11/28 All 5 angles were raised 4" so cable #1 was 42". 4 Yes Yes Yes Yes Yes Yes Yes Yes N/A DJS 10/26 5 Yes Yes Yes Yes Yes Yes Yes Yes N/A DH 11/2 6 Yes Yes Yes Yes Yes No No Yes N/A DH 11/2 Cable #1 not back stressed & c. p. resred. Yes DH 11/3 Cable was back stressed and epoxy coated. A & 1 23 2 Yes Yes No Yes Yes Yes Yes Yes N/A DJS 10/28 Line 23 tube not welded correctly steel plate. Yes PS 11/21 Tube was cont. welded embed on both sides. 3 Yes Yes Yes Yes Yes Yes Yes Yes N/A DJS 10/28 4 Yes Yes Yes Yes Yes Yes Yes Yes N/A DJS 10/28 5 Yes Yes No Yes Yes Yes Yes Yes N/A DH 11/2 Inter. angle at line 14 had only one anchor bolt. Yes DH 11/3 Additional anchor bolt was added at the botm. 6 Yes Yes Yes Yes Yes Yes Yes Yes N/A DH 11/2 Example Exterior Slabs 5

Inspection of Barrier Cable Installation Through or Attached Concrete Columns Site Address General contracr Gauge Serial # of For Construction BC installation drawings Barrier Cables at the ramp along line: Specified distance from p of slab middle of pmost cable Surface mounted steel members secured columns per dwgs Stressed BC force indicated on dwgs Back stressed force indicated on dwgs Resration of corrosion protection after Botm cable # varies Ramp Specified Jacking Force (kips): Specified Gauge Reading (psi): Specified Back stressing Force (kips): Cable Numbers: Flat Ramped Slabs 6 PTI Technical Note Technical Note No. 20

Inspection of Barrier Cable Installation Through or Attached Concrete Columns Site Address General contracr Gauge Serial # of For Construction BC installation drawings Barrier Cables at the ramp along line: C Specified distance from p of slab middle of pmost cable Surface mounted steel members secured columns per dwgs Stressed BC force indicated on dwgs Back stressed force indicated on dwgs Resration of corrosion protection after 3 20 Botm cable # varies Ramp N C B 3 20 Specified Jacking Force (kips): 3.5 Specified Gauge Reading (psi): 900 Specified Back stressing Force (kips): 33 Cable Numbers: #1 #6 and #10 #11 1 2 Yes Yes Yes Yes Yes Yes No Yes Yes DJS 10/25 2 3 Yes Yes Yes Yes Yes No Yes Yes Yes DJS 10/25 Cable #5 did not get Cable #3 was not back stressed Yes PS 11/15 Yes DH 11/2 Cable was covered with Cable was back stressed & corrosion protected 3 4 Yes Yes Yes Yes Yes Yes Yes Yes Yes DJS 10/25 4 5 Yes Yes Yes Yes Yes Yes Yes Yes Yes DJS 10/25 5 6 Yes Yes Yes Yes Yes Yes Yes No Yes DJS 10/25 Cable #6 needs pocket grouted Yes DJS 10/30 Flat 3 20 2 Yes Yes Yes Yes No No No No N/A DJS 10/25 Cables #1 thru #11 were not stressed or finished Yes DH 11/2 All 4 non compliance items were corrected 3 Yes Yes Yes Yes Yes Yes Yes Yes N/A DJS 10/25 4 Yes Yes Yes Yes Yes Yes No Yes N/A DJS 10/25 Cables #10 & #11 did not get Yes PS 11/8 Both cables were covered with 5 Yes Yes Yes Yes Yes Yes Yes Yes N/A DJS 10/25 6 Yes Yes Yes Yes Yes Yes DH Yes N/A DJS 10/25 Example Ramped Slabs 7