A FIELD STUDY OF A VENTILATED BEAM SYSTEM FEASIBILITY IN THE TROPICAL CLIMATE

Similar documents
Sustainable Chilled Beam Design

Taking flexibility into account in designing beam systems

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1

Human response to individually controlled micro environment generated with localized chilled beam

Ministerio Público Fiscal de la Ciudad de Buenos Aires Fiscalía General Departamento de Infraestructura y Apoyo Operativo

The influence of a capture jet on the efficiency of a ventilated ceiling in a commercial kitchen.

ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS

Thermo Active Building Systems Using Building Mass To Heat and Cool

ENERGY SAVING INNOVATION IN CHINESE TRADITIONAL BUILDINGS. L. Zhu Nanjing University of Technology China

UNDERFLOOR AIR DISTRIBUTION INTEGRATED WITH AN INDIRECT AND DIRECT EVAPORATIVE COOLING ASSISTED 100% OUTDOOR AIR SYSTEM

Optimisation of an HVAC system for energy saving and thermal comfort in a university classroom

Individually controlled localized chilled beam in conjunction with chilled ceiling: Part 1 Physical environment

A, B, C, D VENTILATION SYSTEMS: COMPARISON

What simulation can tell us about building tuning

An experimental investigation of a passive chilled beam system in subtropical

Individually controlled localized chilled beam in conjunction with chilled ceiling: Part 2 Human response

Study of the energy performance of a retrofitting office

SYSTEM SETBACKS ENERGY-SAVING STRATEGIES: Description of Potential

The bitterness of poor quality is remembered long after the sweetness of low price is forgotten!

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models

IMPACT OF THE AIRFLOW INTERACTION ON OCCUPANTS THERMAL COMFORT IN ROOMS WITH ACTIVE CHILLED BEAMS

ENERGETIC MONITORING AND OPTIMIZATION OF A SOLAR HOUSE

A Study on the Operational Status of the Chamber for Testing the Thermal Performance of Curtain Walls

Asset Energy Calculator Guidance

Ceiling Radiant Cooling Panels

AMENDMENT NO. 4 AUGUST 2010 TO IS 1391 (PART 1) : 1992 ROOM AIR CONDITIONERS SPECIFICATION

Ceiling Radiant Cooling Panels

Chilled Beams. The new system of choice?

BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1

REPORT ON THE BENEFITS OF ICE- BASED THERMAL STORAGE FOR DISTRICT COOLING IN THE UAE MARKETS

Monitoring of Advanced Facades and Environmental Systems

AREN 3050 ENVIRONMENTAL SYSTEMS FOR BUILDINGS I FALL 2005

Metal Buildings and Condensation. Welcome to Metalcon Condensation Description. Program Objectives. Dew Point Temperatures

Analysis of Heat Gain in Computer Laboratory and Excellent Centre by using CLTD/CLF/SCL Method

Case Studies for Radiant Cooling in Hot & Humid Climate

Dynamic simulation of buildings: Problems and solutions Università degli Studi di Trento

Energy Efficient and Good Indoor Climate in Buildings

CIBSE LOW CARBON CONSULTANTS REGISTER SESSION 10 ENERGY EFFICIENCY IN BUILDINGS. I Prophets energy services

Load Estimation. Ir. Dr. Sam C. M. Hui Faculty of Science and Technology

Minimum Energy Consumption 84% energy heating savings*

Experimental Study to Evaluate the Performance of Iraqi Passive House in Summer Season

Modular Active Chilled Beams

FUNDAMENTALS OF CHILLED BEAMS ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS

Work Package 2: Performance of naturally ventilated buildings

This is an electronic reprint of the original article. This reprint may differ from the original in pagination and typographic detail.

Center for Energy Education Laboratory

The pros and cons of chilled beams

CLCF Climate Changer for comfort applications. Next generation air handling performance from Trane

ENERGY ANALYSIS AND ENERGY CONSERVATION OPTION FOR THE WAREHOUSE FACILITY AT THE HUMAN SERVICES CENTER COMPLEX DRAFT REPORT.

Performance-Risk Methodology for the Design of High-Performance Affordable Homes

Design and retrofitting of a hybrid building in Athens

Two-Pipe Chilled Beam System for Both Cooling and Heating of Office Buildings

Advanced Cooling Technology with Thermally Activated Building Surfaces and Model Predictive Control

Investigation of indoor climate in a naturally ventilated building

Aalborg Universitet Two-Pipe Chilled Beam System for Both Cooling and Heating of Office Buildings General rights Take down policy

Solutions for Office Buildings. E f f i c i e n t H e at i n g, C o o l i n g, a n d P l u m b i n g

CERTIFICATE OF FIELD VERIFICATION & DIAGNOSTIC TESTING (Page 1 of 8)

You Can t Afford Discomfort. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

Theory versus practice of energy and comfort in 4 low energy houses in Belgium

AIRCOOL VENTILATORS FURTHER INFORMATION

Analysis of Uniformity and Energy Consumption in. Supermarket installed DurkeeSox Air Dispersion System. with PE Air Dispersion Model

Energy Efficiency in Building Active Design Part II

Energy efficient thermal comfort. Bin Yang Assistant Professor (Umeå University) Mar 24 th, 2017

Chilled Beams Selection BY DAN INT-HOUT, FELLOW ASHRAE; AND LILLI WILBAR

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

EFFECTS OF WEATHERS AND INDOOR TEMPERATURES ON PERFORMANCE OF ENERGY RECOVERY VENTILATOR. Yanping Zhou, Jingyi Wu, Ruzhu Wang

Georgetown University New Science Center

CAE 331/513 Building Science Fall 2017

Tage Møller Architect office building

Performance Rating of Air-to-Air Exchangers for Energy Recovery Ventilation Equipment

Upgrade your Home Insulation

SECTION AIR TERMINAL UNITS

RESULTS OF LONG-TERM ENERGY EFFICIENCY MONITORING OF TEST BUILDINGS UNDER REAL CLIMATIC CONDITIONS

Cooling coil optimisation in hot and humid climates for IAQ and energy considerations

THE ANALYSIS OF A THERMAL STORAGE SYSTEM UTILIZING BUILDING MASS IN A COLD REGION. Katsuhiro Miura 1

SMART BUILDINGS. Always the best climate for. Zehnder ComfoAir Q ventilation units

Effect of energy renovation on thermal sensation and comfort

Monitoring thermal conditions during transport of racing pigeons on a vehicle equipped with controlled ventilation

Make way for fresh air, live and work healthier

Chapter 2 Literature Review

Renovation of a Detached Single-Family House into an Energy Efficient Low Energy House Larsen, Tine Steen; Maagaard, Steffen; Jensen, Rasmus Lund

Mechanical ventilation with a heat recovery system in renovated apartment buildings

Impacts of energy retrofits on hygrothermal behavior of Finnish multi-family buildings

ENERGY SIMULATION AND ANALYSIS OF AN INTERMITTENT VENTILATION SYSTEM UNDER TWO CLIMATES

Air distribution and temperature control in classrooms

Core Building Advances: Introduction to Sustainable Building & Building Science

ROOF TOP SPACE. SELF-CONTAINED REVERSIBLE AIR-AIR UNITS OF 23 TO 281 kw EVERY EFFICIENT SOLUTION FOR UNIVERSAL COMFORT NA C

The BIG Energy Upgrade Energy Innovation for Retrofitting Deprived Community Housing in the UK

Ventilation and Cooling

CI/SfB (57.7) Xy Uniclass Ss_65_40_33_56 March 2018 U-VALUE IMPROVED BY 22 % AIRCOOL VENTILATORS HYBRID PLUS2 AIRCOOL NEW ...

Is it possible to build near zero energy single family buildings in very cold arctic climate?

Chapter 6. Space heating load

F. Flourentzou Lefkosia new townhall passive bioclimatic Minergie design. Flourentzos Flourentzou: Innovation park EPFL Lausanne, Switzerland

Ventilated Illuminating Wall (VIW): Natural ventilation and daylight experimental analysis on a 1:1 prototype scale model

Transcription:

A FIELD STUDY OF A VENTILATED BEAM SYSTEM FEASIBILITY IN THE TROPICAL CLIMATE Risto Kosonen 1, Freddie Tan 2 and Maija Virta 1 1 Halton Oy 2 CapitaLand Commercial ABSTRACT Ventilated beams systems are quite common in temperate climate. With the ventilated beams systems, it is possible to reach good indoor air quality with reasonable life-cycle costs. Still, the applications of ventilated beam systems in hot and humid climate have been limited. The main reason for that is high risk of condensation. A case-study measurement was conducted in a typical Singaporean office building to investigate the feasibility of a ventilated beam system in hot and humid climate. Based on the measurements, the condensation in the beam system is possible to prevent and to maintain dry cooling if infiltration is minimized, supply airflow rate is sufficient to extract humidity of people and tuning of the automation system has conducted probably. KEYWORDS Ventilated beams, hot and humid climate, humidity control INTRODUCTION In the Tropical climate, it is important to control relative humidity concurrently with temperature. Many studies have been carried out to investigate the effect of humidity on human health and indoor pollution such as fungi, dust mites, particles, bacteria, viruses, pollutant emissions from building materials, respiratory and skin diseases. The effect of temperature and humidity on the perception of indoor air quality has been researched [1]. Decreasing the indoor air temperature and humidity could improve the perceived air quality significantly. The results have shown that the acceptability of indoor air increases linearly with decreasing enthalpy of air. The majority of air conditioning systems installed in the Tropics are designed based on the mixing strategy. That is, for example, variable and constant volume all-air systems. On correct design, these systems can offer high standards of comfort and air quality. It may be however that they do this at the expense of high running costs. Ceiling mounted ventilated beam system could be other attractive approaches for improving energy and ventilation efficiency. These systems minimize the quantity of air handled and have ability to provide a high quality indoor environment. This means that the space requirement of ductworks and air-handling units are much smaller than with traditional mixing systems. This means savings in the structural and building services costs. In the building process, the initial cost is still the main criterion when making choices between different systems. With life-cycle cost (LCC) calculations, it is possible to get better overview of the total cost. The ventilated beam system was analyzed and compared to other typical system. The LC cost of the ventilated beam was lower than the variable air-volume and fan-coil systems in the temperate climate [2].

In this paper, the feasibility of a ventilated beam system in the Tropical climate is studied using a case-study approach. Field measurements were conducted in two rooms of an office building, located in Singapore, served by a ventilated beam system. RESEARCH METHODS The feasibility of a ventilated beam system is evaluated using field measurement in an office building. The condensation risk during the morning start-up period and operation hours is studied by monitoring room conditions. The measurements were conducted in a typical office building in Singapore. This three-storeybuilding was initially a light factory. Recently, the floor that was used for study has been renovated. In the renovation, all internal building materials were replaced and the present open space converted to partly open and partly personal room office layout. There was no retrofitting of the external walls and the windows that improves the air tightness of any part of the building envelope. The windows are a non-openable one panel with metal frame and sealed gaskets. The total area of the office in is 3,970 m 2. In the office, two rooms were installed with a ventilated beam system. The rest of office rooms are served by the mixing system. Figure 1 shows the layout of the studied office floor and pointed out the location of the studied ventilated beam rooms. Office Conference Room D B DB DB DB Figure 1. The office layout and the locations of the ventilated beam office and conference rooms.

An office of 20 m 2 is located in the perimeter zone where possible air infiltration increase humidity level. The other room is a conference room of 56 m 2, which is located in the central area. This internal room is not affected by infiltration and the main humidity source is from the people. In the office room, there are installed four beams and six beams in the conference room. The length of each beam is 2.1 m. In the beam system, there is the connection to the supply air ductwork from which the air enters in the plenum of the ventilated beam. Further in the ventilated beam, the air supplied from nozzles induces the room air through water-coil. The mixture of the supply air and induced air is introduced into the room space through longitudinal slots along both side of the ventilated beam. In the temperate climate, the temperature of the supply air is typically 16-18 o C and the water inlet 14-16 o C. In the Tropical conditions, the supply air temperature should be designed to be lower and the temperature of the water inlet higher to prevent condensation. In Table 1, it is shown the values of the main design parameters of the system. Table 1. The design conditions of the ventilated beam system in the case-study office. Design Conditions Conference Office Room Indoor Temperature 23 23 ( o C) Relative Humidity (%) 60 60 Room area (m 2 ) 56 20 Sensible Load (W) 2,360 1,780 Specific Load (W/m 2 ) 42 89 Number of Persons 20 3 Off-Coil Temperature 14 14 ( o C) Air Flow Rate (l/s) 147 56 Water Inlet ( o C) 16 16 Water Outlet ( o C) 18 18 The supply air flow rate is totally coming from outside and there is no re-circulation applied in the system. The designed specific airflow rate was 2.8 l/s per m 2 (19 l/s per person) in office and 2.5 l/s per m 2 (11 l/s per person) in the conference room. The return air is extracted to the other air-handling unit, which served other part of the office. The used supply and return air flow rates are equal. In the measurement arrangement, the room temperature and humidity is measured with portable data logger. The same system is used to measure the supply air and outdoor conditions. The portable data logger calculates automatically all requested parameters of humid air e.g. dewpoint and humidity ratio from the measured drybulb temperature and relative humidity. The supply air flow rate to the room spaces is measured using a pressure measurement tap of the ventilated beam. Using the technical specification of the product, the supply air flow rates are determined. The water inlet and outlet temperatures were measured with the thermocouples installed on the water pipe. The good contact of the thermocouples is secured using glue and covered the thermocouples with the insulation..

RESULTS In Figures 2-4, it is shown the measurement results in the case-study building. The room temperatures are 21-23 o C in the conference room and about 23 o C in the office room. The dewpoint of the conference room is about 17 o C and 14.5 16.5 o C in the office. The relative humidity is 65 70 % in the office and 70-75 % in the conference room. Conference Room 24.0 Room Air 22.0 Beam Water Outlet Temperature ( o C) 20.0 18.0 16.0 Dew Point Beam Water Inlet 14.0 Off-Coil 12.0 26 27 28 29 30 31 01 Wed Thur Fri Weekend Mon Figure 2. The operation temperatures in the conference room during six days. Office Room 24 Room Air 22 Temperature ( o C) 20 18 16 Dew Point Beam Water Outlet Beam Water Inlet 14 Off-Coil 12 26 27 28 29 30 31 01 Wed Thur Fri Weekend Mon. Figure 3. The operation temperatures in the office room during six days.

During this measurement period, the water inlet and the off-coil temperature temperatures were adjusted to be 17 o C and 13 o C. With these set points, the target was to prevent condensation in the beam unit and to get dry cooling. The dewpoint of the conference and office rooms are quite close the water inlet temperature. Anyhow only during short time slot, the water inlet temperature is higher than dewpoint. The humidity level is high in the room spaces because the supply air flow rate is much lower than the design values due to undersized fan capacity. In the conference room, the airflow rate is 39 % lower than design value an in the office 42 % lower. The actual air flow rate in the conference room is 1.4 l/s per m 2 (7 l/s per person) and 1.7 l/s per m 2 (11 l/s per person) in the office. 34 Outdoor Conditions 32 30 Dry Bulb Temperature ( o C) Humidity Ratio (g/kg) 28 26 24 22 20 Humidity Ratio Dew Point 18 16 26 27 28 29 30 31 01 Wed Thur Fri Weekend Mon Figure 4. The outdoor conditions during measurement period of six days. If the supply air flow rate is according designed values, the dewpoint of the room spaces would be notably lower that the inlet water temperature. This means that in this building, where the leakage is limited, it is possible to prevent condensation and to obtain dry cooling during working hours. It should be noted that the humidity level is not significantly increased during nights. The dewpoint raised up only about 1 o C during the night-time from the day-time value. As well, during the weekend the humidity level will remain almost constant. This indicates that the infiltration is negligible. The estimated infiltration from the humidity measurement is less than 0.05 1/h. DISCUSSION The cooling loads of the room spaces are at the same level in the Tropical climate and in the temperate climate if the direct solar radiation is prevented. The main difference compared is the high outdoor humidity. The main features of the Tropical climate are uniform temperature, high humidity and abundant rainfall throughout the year. In Singapore, the average dew point is about 24 o C and the humidity ratio of 18.5 g/kg during the nights and 19.5 g/kg in the daytime almost constantly all year-round.

In the Topical climate where the humidity is always high, it is important to maintain the dewpoint of the room space lower than the water inlet to prevent condensation. The most challenging time period is mornings. In Scandinavia, the suitable water inlet is 14 o C and 15-16 o C in the central Europe. In the Tropics, the inlet temperature should be higher to prevent condensation in the ventilated beams. The conducted measurements indicate that the infiltration could be quite small if the windows frames and doors are airtight. Thus, the night-time generated humidity is possible to ventilate by starting the operation of fans about 30-60 minutes earlier than water-based cooling. Anyhow, the dehumidified period must be longer and the supply air flow rate should be higher if the building are less airtight. The room design conditions of 23 o C and 65 % is attainable with the water inlet and the supply temperatures 17 o C and 14 o C when the specific supply air flow rate is 10 l/s per person. Together with the previous design parameter and with dehumidified the indoor air properly prior the operation of the water-based cooling, it is possible to maintain dry cooling without any condensation in the ventilated beam system. In the mornings, the air-based cooling should start earlier and after certain time when the humidity level will be at the design level water-based cooling should start. This means that control strategy should be designed taken into account the characteristic of the building. Also, the commissioning and the tuning of the automation system have to conduct probably. In the Tropical conditions, faults in the automation system are much more critical than in the temperate climate. CONCLUSION A case-study measurement was conducted in a typical Singaporean office building to investigate the feasibility of a ventilated beam system in hot and humid climate. Based on the measurements, the condensation in the beam system is possible to prevent and to reach dry cooling if infiltration is minimized, supply airflow rate is sufficient to extract humidity of people and tuning of the automation system has conducted probably. ACKNOWLEDGEMENTS The study is supported by Technology Agency of Finland (TEKES) and CapitaLand Limited. The authors wish to thank to Mr. Weijiang Yu, Mr. Yongheng Xie, Mr Mika Ruponen and Miss June Gan for the assistance during this project. Special thanks to Dr. David Cheong for his comments. REFERENCES [1] Fang L, Clausen G, Fanger PO. Temperature and humidity: important factors for perception of air quality and for ventilation requirements. ASHREA Transactions 2000. Part 2, pp. 503-510 [2] Laine T, Kosonen R, Horttanainen, P, Laitinen A. LCC comparison of air-conditioning systems. Indoor Air 99. Edinbugh, Scotland 8-13.8. 1999. The 8 th International Conference on Indoor Air Quality and Climate. pp. 602-603