Product Information Sheet

Similar documents
Product Information Sheet

FyreWrap Elite TM 1.5 Duct Insulation Grease Duct ASTM E2336 System

Product Information Sheet

FyreWrap Elite 1.5 Duct Insulation Air Distribution System (ADS Ducts)

Product Information Sheet. FyreWrap 1.5 Duct Insulation. Introduction. Product Components. Typical Product Parameters

Product Information Sheet

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 11

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 17

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MINERAL FIBER FIREPROOFING REPORT HOLDER: UNIFRAX I LLC

Fire Barrier Duct Wrap 615+

FireMaster FastWrap XL

Pyroscat Duct Wrap XL

FireMaster FastWrap XL

FastWrap+ 1 1 /2 Commercial Kitchen Grease Duct Air Ventilation Duct

3M Fire Barrier Duct Wrap 615+ Product Data Sheet and Installation Guide (Condensed Version)

Duct Wrap 2x2 Duct Wrap 2x2+ Commercial Kitchen Grease Duct

Duct Wrap Flexible Wraps

ICC-ES Evaluation Report Reissued May 1, 2010 This report is subject to re-examination in two years.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MINERAL-FIBER FIREPROOFING REPORT HOLDER: THERMAL CERAMICS, INC.

Design No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1

28408 Lorna Ave. Warren, MI 48092

LISTING INFORMATION OF International Fireproof Technology Inc. - Joint Systems SPEC ID: 43848

FIRESTOP JOINT SPRAY CFS-SP WB. 2mm (0.079") WET FILM ± 7.5 ± 5

A. Product Data: Identify thermal conductivity, thickness, and jackets (both factory and field applied, if any), for each type of product indicated.

A. This Section includes duct and plenum insulation; accessories and attachments; and sealing compounds.

St. Monica Food Pantry

Document Reference Number - CL4 CL4FIRE

System No. C-AJ-8133

CAJ. Combos. C-AJ of 5. Through Penetrations Series. Concrete. 3Fire Protection Products

PROJ. NO SECTION HVAC DUCT INSULATION

GOWANDA, NEW YORK SEPTEMBER 18, 2008 ARCH PROJECT NO

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION

System No. C-AJ-8048

SECTION HVAC INSULATION

FIRE STATION 55 June 14, 2010

System No. SP777 (FOR HORIZONTAL OR VERTICAL SEPARATIONS)

FIRESTOPPING & SMOKE SEALS

LLOYD INDUSTRIES INC. DAMPER INSTALLATION INSTRUCTIONS

System No. C-AJ-8096

Design & Construction Standards, Revised January

RATING: Consult factory for availability Consult factory for availability

Endotherme Mat ES-5A-12

Section Roof/Ceiling Thermal Insulation

UL Design System HW-D-1012 continued

UBC Technical Guidelines Section Edition Insulation of Tanks, Steam and Condensate Piping Page 1 of 6

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

System No. HW-D-0119

D. Provide UL-approved assemblies for pipes and ducts passing through fire-rated floors, walls, or partitions as required.

installation instructions Combination Fire & Smoke Damper

A. ASTM E84 Standard Test Method for Surface Burning Characteristics of Building Materials

1 of 17. PO Box Bellevue Rd, Newark, DE V F

Insulation. First Revison October DC14 Drainage Mat INSTALLATION GUIDE FOR RESIDENTIAL & COMMERCIAL APPLICATIONS

Marine & Offshore Fire Divisions

Assemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance

3M Fire Protection Products 3M Interam Endothermic Mat For Commercial Buildings

A. Source Limitations: Obtain each type of building insulation through one source.

I-STUD Shaftwall System

DIVISION 7 THERMAL AND MOISTURE PROTECTION SECTION PENETRATION FIRESTOPPING

2012 & 2015 International Building Code. Section Section Section Section Section Section 713.4

COOK COUNTY ILLINOIS CONTRACT FOR WORK DOCUMENT NO Countywide Warehouse and Records Storage Center Hawthorne Project TKB No.

SECTION GYPSUM BOARD ASSEMBLIES

FireMaster Marine Plus Profile Wrap Systems for Composite Bulkheads and Decks

Union County Vocational - Technical Schools Scotch Plains, New Jersey

SECTION BUILDING INSULATION. Display hidden notes to specifier. (Don't know how? Click Here)

Assemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance

Copyright 2013 IFC. All Rights Reserved. No further reproduction or distribution authorized. Any Unauthorized reproduction or distribution is a

Mechanical Penetrations

LISTING INFORMATION OF International Beams - IB Series Joists SPEC ID: 27316

FIRESTOP SUBMITTAL PACKAGE

RECEIVING AND INSPECTION

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Modular Pan System

Chevy Chase Club June 30, 2008 Bowie Gridley Architects

GUIDE SPECIFICATION: DUCT LINER

Project No: Pakenham Branch Library, Pakenham, Ontario Section DECEMBER, 2016 Page 1 of 6

RECOMMENDED STANDARDS for the INSTALLATION of WOODBURNING STOVES

PinkWood Ltd. Revised September 29, 2017

GYPSUM BOARD

LISTING INFORMATION OF Weyerhaeuser - TJI Joists SPEC ID: 26948

LISTING INFORMATION OF Metl-Span, LLC THERMALSAFE 8" Thick 3 Hour Fire Rated Panels SPEC ID: 29868

mcr Silboard self-supporting ventilation and smoke extraction ducts

AUTHORIZATION TO MARK

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: KINGSPAN INSULATED PANELS, INC.

SECTION HVAC DUCTS AND CASINGS

SECTION HVAC DUCTS AND CASINGS

Technical Data Sheet

Expansion Joint Covers (079513)

Following contains common verbiage found in major model building codes and has been edited for the purpose of inclusion on this CD.

Expansion Joint Covers

FYREWRAP. fyrewrap.com.au V Lightweight Fireproofing for Ducts. The Trafalgar fire stopping range includes:

SECTION (15081) - HVAC INSULATION

Over 98% of our products meet the requirements of the Buy American Act. Below is a list of our product categories that comply with this act.

CERTIFICATE OF APPROVAL No CF 5073 LEMINAR AIR CONDITIONING INDUSTRIES L.L.C.

PARKING PLAZA MEXICO COVERED GAS PUMP ISLAND PARKING BUS PARKING AREA. The Evans Group COVERD AREA TACO STAND COVERD AREA AREA FREEZER EXIT EXIT

Instruction and Safety Manual Resilient Sound Isolation Clips (SIC Clips)

Knauf Data Sheet AH-DS-5E Friendly Feel. Duct Wrap. with ECOSE Technology

SECTION GYPSUM BOARD PART 1 - GENERAL

FIRESTOP 101: An Introduction to Firestopping

2012 & 2015 International Building Code. Section Section Section 713.4

FCIA Apprenticeship Manual. Bob Hasting, FCIA Apprenticeship Chair

Transcription:

Product Information Sheet FyreWrap Elite 1.5 Duct Insulation Hazardous Duct Single-Layer System Introduction Unifrax s is a singlelayer flexible enclosure for 1- and 2-hour fire-rated hazardous exhaust ducts including chemical fume ducts (CFD). This slim, compact design offers the lightest system available and results in significant weight, space and labor savings when compared to tradi tional fire-rated shafts or competitive wrap systems. The system was tested per UL 1978 and ASTM E 119, and complies with the International Mechanical Code (IMC). FyreWrap Elite 1.5 provides the following features: Zero clearance to combustibles at all locations on wrap 1- and 2-hour fire endurance rating Alternate to fire-rated shaft enclosure Saves weight, space, labor Thinnest, lightest system available High-temperature, biosoluble insulation GREENGUARD listed for Microbial Resistance Product Components Core Material: FyreWrap Elite 1.5 incorporates Insulfrax Thermal Insulation as its core material. Insulfrax is a hightemperature insulation made from a calcia, magnesia, silica chemistry designed to enhance biosolubility. It provides excellent insulation in a noncombustible blanket product form. Typical System Properties Intertek Laboratories (OPL) Listed, File 14870...Duct System: Design Nos. UNI/FRD 120-10, UNI/FRD 120-11 UL 1978 Internal Fire (June 2002)...Zero Clearance to Combustibles at All Locations on Wrap ASTM E119 Full Scale Engulfment Test...2-hour Fire Resistance Rating ASTM E814 Through-Penetration Firestop Test...Firestop System: UNI/FRD 120-12, UNI/FRD 120-13, F-Rating = 2 hrs., T-Rating = 2 hrs. UNI/FRD 120-18, UNI/FRD 120-20, UNI/FRD 120-22 ASTM E84/UL/ULC 723, UL File No. R14514 Unfaced Blanket Encapsulated Flame Spread Rating...Zero <25 Smoke Developed Rating...Zero <50 ASTM E136 Noncombustibility Test...Passes ASTM C518 Durability Test...Passes, R-Value = 4.8 per inch @ 75 F ASTM C518 Thermal Resistance...R-Value of Elite 1.5 (1 1 2") = 7.2 ASTM C411 Hot Surface Performance...Passes ASTM D6329-03 Microbial Resistance...Resistant to Mold Growth California State Fire Marshal Listing...No: 2440-1478:100 Complies with: International Mechanical Code (IMC), Sect. 510.6 Encapsulating Material: The core insulation blanket is completely encapsulated in an aluminum foil fiberglass reinforced scrim covering. This scrim provides additional handling strength as well as protection from grease and moisture absorption and tearing. Typical Product Parameters Thickness 1.5" Nominal Density 6pcf Standard Product Form Scrim Encapsulated Product Availability 24"w x 25LF 48"w x 25LF

Installation The FyreWrap Elite 1.5 Duct Insulation consists of a singlelayer system applied directly on to the duct surface. Only encapsu lated blanket should be utilized to ensure the outer surface of the insulation is protected. The insulation system may be installed at zero clearance to combustibles at all locations on the wrap, at material overlaps, and in the field between overlaps. To minimize waste, FyreWrap Elite 1.5 should be rolled out tautly before measuring and making any material cuts. Install insulation with a 3" minimum overlap on all joints. Seal all cut edges with aluminum foil tape. The transverse overlap of adjacent blanket may be installed using the following three techniques. See Figure 1 for details. Telescoping Overlap Wrap Technique: This wrap technique is the most common method of installing FyreWrap Elite 1.5 where each adjacent blanket has one edge exposed and one edge covered by the next blanket, to form a 3" overlap. Checkerboard Overlap Wrap Technique: This installation uses a 3" overlap pattern with both edges of each alternating blanket covered by each adjacent blanket whose edges are exposed. The overlap joints in alternate layers of blanket resemble a checkerboard pattern in the completed installation. This technique is often utilized when a small section of duct wrap must be repaired. Butt Splice with Collar Wrap Technique: This wrap technique permits installation with the blanket edges butted together and a 6" wide collar of blanket that is centered over the butt splice, overlapping each adjacent blanket 3". The collar can be field fabricated from FyreWrap Elite 1.5 rolls or purchased separately. Attachment Option Banding Only Duct Width 24" Single Layer Hazardous/Chem Fume Exhaust Duct System 1- or 2-Hour Fire-Rated Enclosure Zero Clearance To Combustibles at All Locations Telescoping Overlap Technique Cross-Section View 1, One Layer 2 Filament Tape (Temporary Hold) 3 Carbon or SS Banding Straps (Permanent Hold) 4 3" Minimum Longitudinal Overlap 5 3" Minimum Transverse Overlap Checkerboard Technique Cross-Section View Attachment Option Banding and Pins Duct Width up to 24" x 48" Butt Joint & Collar Technique Cross-Section View Attachment Option Pins Only Any Duct Width Notes: Pin on Bottom/Backside only Place in max. 12" rows Spaced max. 10.5" on center (not shown) FP-497 Figure 1. FyreWrap Elite 1.5 Single-Layer Installation Techniques Page 2 of 8

Butt Splice with Pins Wrap Technique: This wrap technique permits the blanket to be installed with 2" compression joints at all material seams and no material overlaps. This technique is allowed only when pins are used on all sides of the duct to attach the blanket. Pins shall be spaced in 8" rows and on 8" centers. The compression joint is made by overlapping the blanket a minimum two inches. The ends of the blanket are then raised to align the edges, then pushed down together so the ends of the two pieces are under compression and butted together. See Figure 2 for additional details. Hazardous/Chem Fume Exhaust Duct System 1- or 2-Hour Fire-Rated Enclosure Zero Clearance To Combustibles (Butt Joint with Pins Installation Technique) FP-499 FyreWrap Elite 1.5 Figure 2. FyreWrap Elite 1.5 Butt Splice with Pins Wrap Technique Page 3 of 8

Vertical Duct Runs For vertical duct runs, insulation may be applied to the duct in a continuous length parallel to the vertical length of the duct as opposed to wrapping around the duct. All overlaps shall be maintained at a minimum 3" and are to occur a minimum 6" from any corner of the duct. Pins spaced a maximum 8" on center are to be placed at the centerline of all vertically oriented overlaps. Pins may be pre-welded or cup head style pins. See Figure 3 for details. Insulation Technique Vertical Duct Runs Note: Pins may be pre-welded or cup head style pins. Figure 3. Optional Installation Technique Vertical Duct Runs Attachment Options (Summary Chart): FP-466 Attachment Options Three attachment options are available for installers. Choices are limited by the duct width dimension. Details on each option are provided below. Banding Only: For Duct Widths 24" or Less To temporarily secure the insulation, optional use of filament tape is permitted. Place carbon steel or stainless steel bands (min. 1 2" wide, nom. 0.015" thick) over joints and within the field between joints, around the wrap. Locate bands 1 1 2" from each edge of the blanket, centered on the overlap, and on 10 1 2" centers. Tighten banding to firmly hold the wrap system in place but not so tight as to cut or damage the blanket and secure with minimum 1" long steel crimp clips. Pins are NOT required when this banding technique is used. Banding and Pins: For Duct Widths 48" Weld 12-gauge steel insulation pins to the underside of horizontal runs and backside (side of duct having largest dimension) of vertical runs. Place pins at maximum 12" rows and on maximum 10 1 2" centers. To temporarily secure the insulation, optional use of filament tape is permitted. Impale FyreWrap Elite 1.5 over the pins and hold in place with 2 1 2" square galvanized steel speed clips (washers). Turn down or cut off exposed ends of pins to eliminate safety hazards. Locate carbon steel or stainless steel bands (min. 1 2" wide, nom. 0.015" thick) 1 1 2" from each edge of the blanket, centered on the overlap, and on 10 1 2" centers. Tighten banding to firmly hold the wrap system in place but not so tight as to cut or damage the blanket and secure with minimum 1" long steel crimp clips. Cup head style pins are also permitted and shall be located at the same spacing as pre-welded pins. Pins Only: For Duct Width > 48" Weld 12-gauge steel insulation pins on all sides of the duct. Place insulation pins in rows (perpendicular to the length of the duct) spaced maximum 10 1 2" on center. Pins in each row are maximum 6" from each duct edge and maximum 8" on center. Locate insulation overlaps so they are centered on the pins. Impale FyreWrap Elite 1.5 over the pins and hold in place with 2 1 2" square galvanized steel speed clips (washers) to keep the system from sagging. Turn down or cut off exposed ends of pins to eliminate safety hazards. Cup head style pins are also permitted and shall be located at the same spacing as pre-welded pins. The pin only attachment method can be used for duct widths less than 48", but is optional. Banding Banding & Pins Pins Only Duct Dimension Only (Pins on Bottom) (All Four Sides) Width 24" Width 48" Width > 48" Page 4 of 8

Access Door Field fabricated and prefabricated duct access doors are permitted for use with FyreWrap Elite 1.5 Duct Insulation. Installation details are provided below and in Figure 4. Field fabricated-access doors are protected with two layers of FyreWrap Elite 1.5 Duct Insulation. Cut away the one layer of FyreWrap Elite 1.5 already installed and covering the duct to a dimension that matches the door opening to be used. Mark and cut a clean-out access opening in the duct. Weld 1 4 inch dia meter threaded rod to each corner on the access door opening. Cover with hollow steel tubes (optional) for easy removal of blanket. Cut a 16 gauge cover plate with dimen sions two inches larger than the opening. Drill holes in the door to match the rod pattern. Use a gasket of 0.5" thick unfaced FyreWrap or ceramic fiber blanket between the duct and the access door cover. Install the cover over the threaded rod overlapping the opening 1" on all sides. Weld at least four steel insulation pins to the outside of the door cover panel, approximately 1" from each corner. Cut a piece of FyreWrap Elite 1.5 that matches the door opening size and install over pins to fit within the insulation area cut away. Cut an additional piece of FyreWrap Elite 1.5 with perimeter dimen sions that extend 1" beyond the layer below. Install over the insulation pins. Throughout the installation process, seal all cut edges with aluminum foil tape. Secure with washers and bend over excess pin lengths to eliminate safety hazards. Place washers on threaded rod and secure with nuts. Do not install banding over this area. Prefabricated Ductmate Ultimate and Ductmate F2-HT prefabricated access doors are permitted and must be installed in accordance with Ductmate Industries, Inc. installation instructions and the applicable code. The first layer of FyreWrap Elite 1.5 is cut to the size of the door. An additional layer is required and is sized to create an overlap of 1" beyond the lower layer. All edges of insulation blanket must be protected with aluminum foil tape. A No. 16 gauge outer plate the same dimension as the outer layer of insulation blanket is held in place over the insulation using threaded rod and wing nuts. The outer plate is supplied with the Ultimate door and F2-HT door. Access doors are available from Ductmate Industries, Inc. Contact www.ductmate.com or 1-800-245-3188 for additional information or local distributors. Ask for the Access Door Product Line manager. FP-518 Duct Access Door Systems Ductmate Ultimate Door System Field Fabricated Door System Ductmate F2-HT Door System 1 Access Door Opening 2 All Thread Rods 3 Access Door Cover Panel 16 Gauge (field fab. only) 4 Insulation Pins Welded to Cover 5 First Layer FyreWrap Elite 1.5 6 Second Layer FyreWrap Elite 1.5, 1" Overlap 7 Speed Clips/Washers 8 Cut Edges Sealed With Aluminum Foil Tape 9 Spool pieces for threaded rods (optional field fab. only) 10 Wing Nuts 11 Washers 12 Insulation plate 13 Unfaced FyreWrap blanket or ceramic fiber gasket, 1 2" thick 14 Prefabricated access door Figure 4. Access Door Installation Page 5 of 8

Duct Support Horizontal duct support systems are not required to be insulated (wrapped) when constructed using a minimum 3 8" diameter uninsulated all-thread steel rod and 1 1 2" x 1 1 2" x 1 4" uninsulated steel angle spaced a maximum 72" on center along the length of the duct or accordingly, not to exceed 200 lbs between supports. Spacing of 120" on center requires the use of 1 2" all-thread and 2" x 2" x 1 4" angle. A minimum clearance of 1" is required between the protected duct and the steel rod. For all other duct support configurations, please contact Unifrax and ask for Fire Protection Application Engineering. Firestop Systems Refer to Figures 5 through 9 for details. Contact Unifrax and ask for Fire Protection Application Engineering or visit www.unifrax.com for the latest information on available firestop systems. 1 3 6 5 4 FP-681 Intertek Design No. UNI/FRD 120-13 F-Rating = 2 hour, T-Rating = 2 hour 2 2 3 4 6 1 5 FP-521 Intertek (OPL) Design No. UNI/FRD 120-12 F-Rating = 2 hours, T-Rating = 2 hours 1 Concrete or CMU block wall assembly, 6 1 8" 2 Hazardous/Chem Fume Exhaust Duct, 16 gauge, max. 50" x 50" 3, One Layer 4 Annular Space; 3 4" to 3" 5 Mineral Wool (4 pcf), compressed 25% or Unfaced FyreWrap Elite 1.5 blanket 6 Tremco Fyre-Sil Non-Sag, 3 8" depth, overlap onto wall surface and duct insulation a nom. 1 2". Figure 6. Firestop Installation 1 Gypsum Wallboard Assembly, 2 hr. rated 2 Hazardous/Chem Fume Duct, 16 gauge, max. 50" x 50" 3, One Layer 4 Annular Space min. 3 4" to max. 3" 5 Mineral Wool (4 pcf), compressed 25% or Unfaced FyreWrap Elite 1.5 blanket 6 Tremco Fyre-Sill Non-Sag, 1 4"- 1 2" depth, both sides of wall and overlapped 1 2" onto duct and wall surfaces Figure 5. Firestop Installation Page 6 of 8

FP-682 Intertek Design No. UNI/FRD 120-18 F-Rating = 2 hour, T-Rating = 2 hour FP-520 Intertek (OPL) Design No. UNI/FRD 120-22 F-Rating = 2 hours, T-Rating = 2 hours 1 3 4 5 1 3 4 5 6 2 2 6 1 Gypsum Wallboard Assembly, 2 hr. rated 2 Hazardous/Chem Fume Exhaust Duct, 16 gauge, max. 70" x 70" 3, One Layer 4 Annular Space; min. 1 1 4" to max. 4 3 4" 5 Unfaced FyreWrap Elite 1.5 blanket compressed 48%. 6 Specified Technologies spec seal SSS100 intumescent firestop sealant 5 8" nominal depth, both sides of wall and overlapped 1 2" onto duct and wall surfaces. 1 Concrete Floor Assembly, 4 1 2" depth 2 Hazardous/Chem Fume Duct, 16 gauge, max. 50" x 50" 3, One Layer 4 Annular Space 1" to 5" 5 Mineral Wool (4 pcf), compressed 25% or Unfaced FyreWrap Elite 1.5 blanket 6 Tremco Fyre-Sill Non-Sag, 3 8" depth, overlap onto concrete and duct insulation a nom. 1 2" Figure 7. Firestop Installation Figure 8. Firestop Installation Intertek Design No. UNI/FRD 120-20 F-Rating = 2 hours, T-Rating = 2 hours FP-522 1 Concrete Floor Assembly, 4 1 2" depth 2 Hazardous/Chem Fume Duct, 16 gauge, 2704 in 2 area, max. 52" width 3, One Layer 4 Unfaced FyreWrap Elite 1.5 Blanket, 4 1 4" depth Compressed 33% 5 STI SpecSeal SSS, 1 4" 6 Annular Space, 1" to 2" Figure 9. Firestop Installation Page 7 of 8

Other Fire Protection Products and Applications Unifrax offers many UL-listed Fiberfrax and FyreWrap product forms and FyreWrap fire protection materials for passive fire protection applications, such as: Product UL File Number FyreWrap Duct Insulation R14514 Insulfrax S Blanket R14514 FyreWrap XFP Expanding Fyre Paper R15435 Fiberfrax Durablanket Ceramic Fiber Blanket R14514 Fiberfrax Duraboard Ceramic Fiber Board LD E75289 Fiberfrax Ceramic Fiber Papers (110/440) E75289 Fiberfrax Ceramic Fiber Papers (970) MH7030 Fiberfrax Lo-Con TM Felt MH7030 Fiberfrax Moist Pak-D E75289 FyreWrap products offer solutions in applications such as: Grease, Air Ducts Railroad Tank Cars Cable Trays, Conduit Transit Cars Control System Covers Ships Above Ground Storage Tanks Expansion Joints Marine Bulkheads, Decks Fire Door Seals Structural Steel Chimney Liners Construction Joints Ceiling Air Diffusers Curtain Walls/Safing Hazardous Material Circuit Protection Storage Containers Unifrax has a wide range of FyreWrap fire protection materials available to provide passive fire protection solutions in a variety of applications in the commercial building, industrial facility and transportation industries. For additional information about product performance or to identify the recommended product for your fire protection application, please contact Unifrax at 716-278-3800 and ask for Fire Protection Application Engineering. Listed W/N 14870 Reference Intertek Directory of Listed Products www.intertek.com/directories/ APPLIED FIRE PROTECTION UNIFRAX I LLC New Carlisle, IN Nominal Density: 6 pcf Tested Per: ASTM E119 Fire Resistance Rating: 2 hour ANSI/ASTM E814 T-Rating: 2 hr F-Rating: 2 hour ASTM E2336 CAN/ULC-S144 UL 1978 Sec. 14 & 15 - Passed UL 2221 AC 101 (Engulfment) Passed AC 101 (Internal) Passed ISO 6944 Duct Type: A Data are average results of tests conducted under standard procedures and are subject to variation. Results should not be used for specification purposes. Refer to the product Material Safety Data Sheet (MSDS) for recommended work practices and other product safety information. Page 8 of 8 The following are registered trademarks of Unifrax: FyreWrap, Elite, Insulfrax, XFP, Lo-Con, Moist Pak-D, Fiberfrax, Durablanket, and Duraboard. The test data shown are average results of tests conducted under standard procedures and are subject to variation. Results should not be used for specification purposes. Product Information Sheets are periodically updated by Unifrax. Before relying on any data or other information in this Product Information Sheet, you should confirm that it is still current and has not been superseded. A Product Information Sheet that has been superseded may contain incorrect, obsolete and/or irrelevant data and other information. Unifrax I LLC Corporate Headquarters 2351 Whirlpool Street Niagara Falls, New York 14305-2413 Telephone: 716-278-3800 Canada: 1-800-635-4464 Telefax: 716-278-3900 Internet: www.unifrax.com Email: info@unifrax.com