Structural Performance of Long-Span Composite Truss and Beam Systems in Fire

Similar documents
THE BEHAVIOUR OF LIGHTWEIGHT COMPOSITE FLOOR TRUSSES IN FIRE

BEHAVIOUR OF REINFORCED CONCRETE STRUCTURES IN FIRE

ANALYSIS OF COMPOSITE FLOORS WITH DIFFERENT FIRE PROTECTION REGIMES SUBJECT TO COMPARTMENT FIRES

SIMPLE INVESTIGATIONS OF TENSILE MEMBRANE ACTION IN COMPOSITE SLABS IN FIRE

NON-LINEAR MODELLING OF THREE FULL-SCALE STRUCTURAL FIRE TESTS

Fire Safety Day Fire Behaviour of Steel and Composite Floor Systems Simple design method

Theory Composite Beam Design

SIMPLIFIED ESTIMATION OF CRITICAL TEMPERATURES OF PORTAL FRAMES IN FIRE

THE MECHANICS OF TENSILE MEMBRANE ACTION IN COMPOSITE SLABS AT HIGH TEMPERATURES

This is a repository copy of A structural fire engineering prediction for the Veselí fire tests, 2011.

SHEAR PANEL COMPONENT IN THE VICINITY OF BEAM-COLUMN CONNECTIONS IN FIRE

COVER SHEET. Title: Component-Based Element of Beam Local Buckling Adjacent to Connections in Fire. Authors: Guan Quan Shan-Shan Huang Ian Burgess

STRUCTURAL FIRE ENGINEERING ASSESSMENTS OF THE FRACOF AND MOKRSKO FIRE TESTS An Engineering Prediction

STEEL DESIGNERS MANUAL

BS EN :2004 EN :2004 (E)

THE APPLICATION OF ADVANCED FINITE ELEMENT ANALYSIS FOR STRUCTURAL FIRE DESIGN

EXPERIMENTAL STUDY ON FLEXIBLE END PLATE CONNECTIONS IN FIRE

Short Term Scientific Mission to the University of Sheffield. Scientific Report of Dr. Sébastien Durif

This is a repository copy of An alternative simplified model of tensile membrane action of slabs in fire.

The need to design for robustness in fire. Ian Burgess

The University of Sheffield and

THE ROLE OF COMPOSITE JOINTS ON THE PERFORMANCE OF STEEL-FRAMED BUILDINGS IN FIRE. Prof. Khalifa S. Al-Jabri

HIGH-TEMPERATURE EXPERIMENTS ON JOINT COMPONENT BEHAVIOUR

PERFORMANCE-BASED SIMPLIFIED MODEL FOR A STEEL BEAM AT LARGE DEFLECTION IN FIRE.

FIRE DESIGN METHOD FOR COLD-FORMED STEEL SHEETING SYSTEM

Contents. Tables. Notation xii Latin upper case letters Latin lower case letters Greek upper case letters Greek lower case letters. Foreword.

British Steel Fire Test3: Reference ABAQUS model using grillage representation for slab. Research Report

BEHAVIOUR OF COMPOSITE FLOOR SLABS UNDER FIRE CONDITIONS

7. SPECIFIC RULES FOR STEEL CONCRETE COMPOSITE BUILDINGS

CHAPTER FIVE 5.1 MODELING OF A TEN-STOREY BUILDING

Marian A. GIZEJOWSKI Leslaw KWASNIEWSKI Wael SALAH

The Steel Construction Institute

BEHAVIOUR OF COLD-FORMED Z-SHAPED STEEL PURLIN IN FIRE

Fire Behaviour of Cellular Composite Floor Steel Beams with Different Web Opening Shapes

Section A A: Slab & Beam Elevation

The Passive Fire Protection Handbook. Chapter 3: Structural Steel

LESSONS FROM A FULL SCALE FIRE TEST

Design of Double Composite Bridges using High Strength Steel

Austral Deck Design for Construction Loading. Permanent formwork and Span capability

Concrete Design Guide

Example of a modelling review Roof truss

3.4.2 DESIGN CONSIDERATIONS

CADS A3D MAX. How to model shear walls

CHAPTER 2. Design Formulae for Bending

SHEAR BEHAVIOR OF RC DEEP BEAMS WITH SOLID CIRCULAR CROSS SECTION UNDER SIMPLY SUPPORTED CONDITION AND ANTI-SYMMETRIC MOMENT

Nonlinear Analysis of Reinforced Concrete Column with ANSYS

Post-earthquake fire behaviour of composite steel-framed structures

Diploma in Civil Engineering. Term-End Examination June, BCE-041 : THEORY OF STRUCTURES II

Investigating the Use of Spliced Swimmer Bars as Shear Reinforcement in Reinforced Concrete Beams

NEW COMPOSITE CONSTRUCTION OF HYBRID BEAMS COMBINING STEEL INVERTED T-SECTION AND RC FLANGE

Contents. Foreword 1 Introduction 1

ASSIGNMENT 1 ANALYSIS OF PRESTRESS AND BENDING STRESS BFS 40303

BEHAVIOUR OF COMPOSITE SLIM FLOOR STRUCTURES IN FIRE

Non Linear Analysis of Composite Beam Slab Junction with Shear Connectors using Ansys.16

BEHAVIOUR OF PRE-FIRE AND POST-FIRE PERFORMANCE OF ECCENTRICALLY LOADED SRC COLUMNS AND JOINT

FIRE RESISTANCE OF CONCRETE SLABS ACTING IN COMPRESSIVE MEMBRANE ACTION

Heat transfer analysis of hybrid stainless-carbon steel beam-column joints

Keywords: Fire engineering, design fires, structural response, thermal expansion, performance based design, prescriptive design, approvals process.

Flexure and Serviceability Limit State

Structural Design of Pergola with Airfoil Louvers

ST7008 PRESTRESSED CONCRETE

THE INFLUENCE OF CONNECTIONS ON THE ROBUSTNESS OF COMPOSITE STRUCTURES IN FIRE

Behavior of Structures in Fire and Real Design A Case Study

The Use of Bolted U-Link Swimmer Bars in the Reinforced Concrete Beams

Sabah Shawkat Cabinet of Structural Engineering 2017

STABILITY AND DUCTILITY OF CASTELLATED COMPOSITE BEAMS SUBJECTED TO HOGGING BENDING

(a) Pin-Pin P cr = (b) Fixed-Fixed P cr = (d) Fixed-Pin P cr =

The Chinese Performance-based Code for Fire-resistance of Steel Structures

CHAPTER 1 INTRODUCTION

CHAPTER 3 BEHAVIOUR OF FERROCEMENT HOLLOW SLABS

RECENT ADVANCES IN THE DESIGN AND CONSTRUCTION OF COMPOSITE FLOOR SYSTEMS

FIRE PERFORMANCE OF AN UNPROTECTED COMPOSITE BEAM Behavior with finite beam end restraints, rebar size and locations

Hybrid-steel concrete connections under reversed cyclic loadings

RESTRAINT OF FIRE-EXPOSED CONCRETE FLOOR SYSTEMS

Renovation of Buildings using Steel Technologies (ROBUST)

Erector Connector Meadow Burke Company In- Plane Performance

FIRE RESISTANCE ASSESSMENT OF PARTIALLY PROTECTED COMPOSITE FLOORS (FRACOF) DESIGN GUIDE

twenty two concrete construction: flat spanning systems, columns & frames Reinforced Concrete Design Reinforced Concrete Design

Seismic Behaviour of RC Shear Walls

Thermal Stress Analysis of Beam Subjected To Fire

Effect of upgrading concrete strength class on fire performance of reinforced concrete columns

DESIGN OF HIGH-RISE MODULAR OPEN BUILDINGS

Ce 479 Reinforced Masonry Fall 2005

5.4 Analysis for Torsion

OXFORD ENGINEERING COLLEGE (NAAC Accredited with B Grade) Department of Civil Engineering LIST OF QUESTIONS

Finite Element Analysis of Litzka Beam

twenty two concrete construction: flat spanning systems, columns & frames ARCHITECTURAL STRUCTURES: FORM, BEHAVIOR, AND DESIGN

Encased Beam with Variable Upper Steel Flange Position

Compression Members. Columns I. Summary: Objectives: References: Contents:

Interaction between ductile RC perimeter frames and floor slabs containing precast units

FRA COF. Design Guide. O. Vassart B. Zhao. Fire Resistance Assessment of Partially Protected Composite Floors

Module Title: Advanced Structural Design

The behaviour of multi-bay, two-way reinforced concrete slabs in fire

Nonlinear Models of Reinforced and Post-tensioned Concrete Beams

Effect of Flange Width on Flexural Behavior of Reinforced Concrete T-Beam

Part 3: Mechanical response Part 3: Mechanical response

DIAPHRAGM BEHAVIOR OF DECONSTRUCTABLE COMPOSITE FLOOR SYSTEMS

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 3, No 2, 2012

STRUCTURAL PERFORMANCE OF STEEL-CONCRETE-STEEL SANDWICH COMPOSITE BEAMS WITH CHANNEL STEEL CONNECTORS

Level 6 Graduate Diploma in Engineering Structural analysis

Transcription:

Structural Performance of Long-Span Composite Truss and Beam Systems in Fire *Seng-Kwan Choi 1), Ian Burgess 2) and Roger Plank 3) 1), 2) Department of Civil & Structural Engineering, University of Sheffield,Sheffield S1 3JD, UK 3) School of Architecture, University of Sheffield,Sheffield S10 2TN, UK ABSTRACT Composite truss and composite beam systems have recently been widely applied in longspan multi-storey floor construction. In a fire resistance design according to BS5950 Part 8, two alternative calculation approaches, a limiting temperature method and a moment capacity method, are used to assess the fire resistance of composite structures. The in-fire performance of the structures and insulation materials are required to satisfy a limiting strain level and a simple deflection criterion during the structure s specified fire resistance period. However, it is difficult to estimate the deflection of long span structures at elevated temperatures, due to the significant thermal effects on both the materials and structural mechanics. This project uses the Sheffield FE package Vulcan to investigate numerically the in-fire performance of two types of long span structure which are passively protected against fire. INTRODUCTION There have been significant improvements in the structural design of commercial multistorey buildings in recent years, based on the development of long-span (12 to 20m) composite systems. The wide variety of automatically fabricated long-span composite structures has not only economic benefits due to fast, light-weight and accurate construction, but also allows the potential advantage of maximising flexibility in internal layout, which is one of the major trends in modern commercial buildings. The configuration of a composite truss, which generates large voids between the chord and bracing members, provides that the services can pass at any location through the floor zone without modification. A composite cellular beam may also offer a similar advantage by using its web openings. With regard to the optimum integration of structure and services within the same horizontal zone, composite beams and composite trusses

are two of the most common structural systems which have been widely used for long span floors. In a typical design procedure, after a composite structure has been designed for ultimate limit state, its design for the fire limit state is subsequently done for the specified fire resistance period. Two fire safety design philosophies, prescriptive and performance-based, may be used to achieve the required fire resistance against standard time-temperature curves, such as the Standard Fire (ASTM E119 (ASTM 1995), BS476 Part20 (BSI 1987) or ISO 834 (IOS 1975)), or the parametric fire of Eurocode 1 Part1.2 (CEN 2001). In prescriptive design manufacturers data is used to estimate a protection thickness based solely on keeping the structure temperatures below certain fixed values (550 C is the most usual of these). In the performance-based design philosophy, the behaviour of the structures under fire may be presented as a specified deflection against time using numerical analysis. More simply, for individual members, both BS5950 Part 8 (BSI 1990) and Eurocode 3 Part 1.2 (CEN 1993) provide critical temperature methods based on previous testing, in which the critical temperature is a function of the member s load ratio. The fire performance of such members may be improved by varying the section size, the protection material thickness etc. The fire resistance of the members may also be calculated using the moment capacity method in accordance with Eurocode 4 Part1.2 (CEN 1994). In the UK, the fire performance of composite members and protection materials are typically specified up to a 2.0% maximum strain level according to BS5950 Part 8 (BSI 1990) and a deflection limit of span/20 is commonly used in structural fire design practice. However, due to the significant thermal effects on the material properties and the structural mechanics of load-carrying, it is difficult to calculate the deflection of such long-span composite systems at elevated temperatures. The current understanding of structural behaviour in fire reaches beyond individual member performance. Each member contributes to the overall performance of a structural assembly in fire, but this is also affected by their interaction in a truly performance-based design method. The purpose of this study is to investigate numerically the performance of a composite truss with a supporting column, for 60 minutes of the standard ISO fire. This is compared against the fire performance of equivalent composite beams, which are protected using the prescriptive method. MODELLING A standard model of a Warren Truss, of 15m span and 750mm depth, spaced at 2.5m centres and made composite with a concrete slab and profiled steel decking, has been used for this study (Figure 1). The top and bottom chords were adapted from a unique S350 METSEC cap section (300mm wide 100mm deep 8mm thick) and the web members from RHS60 60 5.0. The model has been designed to satisfy ultimate strength and deflection criteria at an ultimate limit state loading of 13.2kN/m 2, according to BS5950 Part1 (BSI 2000). The steel decking acts as permanent formwork to the underside of the lightweight C30 concrete slab. A142 anti-crack steel mesh reinforcement is placed in the concrete slab. Imposed loading at the fire limit state is 7.81kN/m 2, which is a typical office floor loading factored according to BS5950 Part 8 (BSI 1990), for this composite truss.

Figure 1: Half span of the composite truss (dimensions in mm) Two composite beams, shown in Figure 2, were designed according to BS5950 Part1 (BSI 2000), for conditions identical to those which applied to the composite truss. The cellular beam of Type A, which had a 150mm 10mm top flange, 220mm 15mm bottom flange, 8mm thick web and 400mm diameter web-openings at 600mm centres, was assumed to be fabricated from welded S355 steel plates. The Type B model also contained 450mm diameter of web-openings, in this case at 650mm centres, and was constructed from two standard universal beams (S355) cut along their webs. It had dimensions of 152.4mm 10.9mm flange and 7.6mm thick web top tee; 190.4mm 14.5mm bottom flange and 9.0mm thick web bottom tee. Figure 2: Half span of Type A (above) and B (below) composite beams (dimensions in mm) A symmetric half of the composite truss was numerically modelled with a 4m supporting column (UC 356 368 129). A pinned beam-to-column connection was assumed between the steel members. The model was designed assuming a continuous bottom chord and top chord with the LWC slab, excluding the steel decking from the model. The pin-ended web members were connected between the centroids of the top and bottom chords. All transverse loading was applied at the connections of the top chord and bracing members. No eccentricity was assumed at the connections. For numerical modelling of the composite cellular beams, the circular holes of diameter d were transformed into effective rectangular openings of depth d and width d/2.

TEMPERATURE ESTIMATION In order to achieve a fire resistance of 60 minutes in the standard fire, the web members and the bottom chord of the composite truss, and the whole surface area of the composite cellular beams, were assumed to be insulated by applying a thin-film intumescent coating. The design temperature of the protected steel was considered to be 620 C. The temperature development of the protected members was assumed to increase to about 200 C in a similar fashion to the unprotected members. The temperature development at this stage was calculated on the basis of the section factor, A/V, using a formula provided by Eurocode 4 Part1.2 (CEN 1994). The temperature increase, θ a, of unprotected steel chords during a short time interval, t, may be determined by the following formula: α c + α r A θ a = ( θt θ a ) [ C] Ca ρ a V [1] where α c is the coefficient of convective heat transfer α r is the coefficient of radiative heat transfer 8 5.67 10 ε res 4 4 = Φ ( θ t + 273) ( θ a + 273) ) θ t θ a in which Φ is the configuration factor (conservatively taken as 1.0 ) ε res is the resultant emissivity of the fire compartment and the surface (conservatively taken as 0.5 for steel and 0.56 for concrete) C a is the specific heat of steel (600 J/kgK) ρ a is the density of steel (7850kg/m 3 ) A is the exposed surface area of the part of the steel cross section per unit length (m 2 /m) V is the volume of the part of the steel cross section per unit length (m 3 /m) θ t is the average gas temperature during the interval t ( o C) θ a is the steel temperature at the end of the interval t ( o C) t is time interval (sec) 1000 Temperature [ C] 800 600 400 200 Web Bottom Chord Top Chord Column 0 0 10 20 30 40 50 60 Time [mm] Figure 3: Temperature development of composite truss

After this the temperature was assumed to progress linearly up to 620 C at 60 minutes for beams and 550 C for the supporting column, as shown in Figure 3. The temperature profiles of the cellular beams were calculated in the same manner for the top flange, web and bottom flange parts of the section respectively, using their individual section factors. BS5950 Part8 (BSI 1990) and Fire Protection for Structural Steel in Buildings (ASFP 2002) recommend that the protection thickness of the cellular beams should be obtained based on the original cross-section and then increased by 20%, as the temperature of the cellular beams increases at a faster rate than conventional sections. A thermal analysis was conducted, using heat transfer software (Huang et al. 1996), to generate the temperature development of the 70mm LWC slab topping, divided into 9 layers with the steel decking, in the standard fire (Figure 4). The moisture content was taken to be 2% of concrete weight, and heat transfer coefficients were chosen from generic data (Purkiss 1996). Temperature [ C] Figure 4: 1000 800 600 400 200 0 Bottom surface 60mm 50mm 40mm 30mm Top surface 20mm 10mm 0 10 20 30 40 50 60 Time [min] Temperature development of 70mm topping of the LWC slab PARAMETRIC STUDY Numerical analyses of the structural behaviour of the composite truss and composite beams, subject to 60 minutes exposure to the ISO834 standard fire, were conducted using the finite element program Vulcan, which has been developed by the Sheffield Structural Fire Engineering Group in order to investigate structural performance at elevated temperatures. The performance of concrete and steel at elevated temperatures varies inelastically with their temperature-dependent characteristics such as strength, stiffness, thermal expansion, specific heat and thermal conductivity. For numerical analysis the mechanical and thermal characteristics of these materials were formulated in accordance with Eurocode 3 Part 1.2 (CEN 1993) and Eurocode 4 Part 1.2 (CEN 1994). The tensile strength of the concrete at elevated temperatures was also taken into account by adapting a tensile stress-strain curve. The curve was modelled to have linear behaviour up to the peak tensile strength f t (ө)=0.3321 f c (ө), and then a bilinear curve (Rots et al.1984) for tensile strain-softening after cracking, up to the maximum tensile strain ε ct (ө)=15f t (ө)/e c (ө). After tensile cracking the concrete was still capable of carrying compressive stress, but was ignored after crushing in compression.

Composite Truss The normal equilibrium of one symmetric half of the composite truss, under simply supported conditions at ambient temperature, is illustrated in Figure 5. Double black- and white-filled arrowheads indicate compression and tension respectively. Single black vertical arrows represent resultant shear forces. The critical elements of this standard model can be identified at ambient temperature by examining the load ratios in the members. The peak value of load ratio under tension occurs in the mid-span member of the bottom chord, 6.75-7.5m from the support. For members in compression the critical member is the first compressive diagonal strut at 0.75 1.5m from the support. As shown in a similar model study in previous publication (Choi et al., 2002), these may also be critical elements under elevated-temperature conditions. Figure 5: Equilibrium of the composite truss at ambient temperature It was observed that the first and the second compressive web diagonals may buckle, causing a local instability within the fire resistance period. Once this condition occurs, the moment resistance of the composite truss, generated by the lever arm between top and bottom chords, ceases to be valid. The load-carrying mechanism of the composite truss is transformed, so that the slab and top chord both begin to carry the imposed load in tension rather than in compression. This phenomenon is called catenary action, and relies on the truss undergoing large deflection in the process. In this situation the top chord and slab, with an embedded 25mm reinforcement bar, may possibly be able to survive during the fire resistance period, although with large deflections. In order to reduce the severity of this deflection, web instabilities were avoided by adopting RHS100 6 0 6.3 for the web diagonal members. With this modification the composite truss maintained a flexural mechanism during the fire resistance period and deflected by approximately span/20 (750mm) at 60 minutes of the Standard Fire, as shown in Figure 6. The strain in the bottom chord remained within 2.0% during the fire resistance period. Composite Cellular Beam The structural behaviour of Type A and B composite beams, with and without openings, for 60 minutes of the standard ISO fire, was numerically investigated using Vulcan. The mid-span deflection of each of the models is plotted against time in Figure 7. In the cases of the composite beams without web-openings, which are represented by solid lines, Type B shows the better performance, due to its increased beam depth. When openings are included (dotted lines), Type A deflects less because of its larger bottom flange area, smaller ratio of opening to overall beam depth and longer distance from the first opening to the support.

Deflection [mm] 0-100 -200-300 -400-500 -600-700 -800-900 0 10 20 30 40 50 60 Time [min] Figure 6: Mid-span deflection of the composite truss The load ratios of the composite beams, with and without openings, were 0.52/0.39 for Type A and 0.53/0.38 for Type B respectively. With respect to both of the prescriptive methods, the protection temperature of 620 C was conservative for the composite beams. Therefore, the models, with and without web openings, deflected by approximately span/15 and span/20 during the fire resistance period. Deflection [mm] 0-200 -400-600 -800-1000 Type B without openings Type A without openings Type A with openings Type B with openings -1200 0 10 20 30 40 50 60 Time [min] Figure 7: Mid-span deflections of the composite beams CONCLUSIONS The structural behaviour of composite beams and composite trusses, as alternative long-span (15m) floor systems at 2.5m spacing, for 60 minutes of the standard ISO834 fire, was numerically investigated using Vulcan. It was shown that the composite truss (750mm depth), designed at ULS and protected using the prescriptive method, may need further consideration in design for fire, specifically to avoid web instability, which would induce a sudden transition to a

large-deflection load-carrying mechanism. The numerical study shows that the composite truss, protected to reach steel temperatures no higher than 620 C under a load ratio of 0.5 at the fire limit state, deflects by approximately span/20 during the fire resistance period. The equivalent Type A (600mm depth) and Type B (655mm depth) composite beams with and without web openings, which were also protected to 620 C under load ratios of 0.52/0.39 & 0.53/0.38, were demonstrated to deflect by approximately span/15 and span/20 during the fire resistance period. All of the cases satisfied the limiting strain criterion of 2.0% throughout the analyses. However, despite the conservative protection temperature under the load ratios considered in the limiting temperature method, the results show that the deflection limit of span/20 is difficult to achieve from either long-span composite beams or trusses in fire. ACKNOWLEDGMENT The authors gratefully acknowledge the support of METSEC Building Products Ltd, and the collaboration of Buro Happold FEDRA, in the research programme of which this study forms a part. REFERENCES American Society for Testing and Materials. (1995), ASTM E119-95a Standard Test Methods for Fire Tests of Building Construction and Materials, West Conshohocken, PA. American Society of Civil Engineering. (1984), Finite Element Analysis of Reinforced Concrete, NY. Association for Specialist Fire Protection. (2002), Fire Protection for Structural Steel in Buildings, UK. British Standards Institution. (1987), BS476: Fire Tests on Building Materials and Structures: Part20: Method for Determination of the Fire Resistance of Elements of Construction (General Principles), UK. British Standards Institution. (2000), BS5950: Part1: Code of Practice for Design: Structural Use of Steelwork in Building: Rolled and Welded Sections, UK. British Standards Institution. (1990), BS5950: Part8: Code of Practice for the Fire Protection of Structural Steelwork, UK. Choi, S.K, Burgess, I.W. and Plank, R.J. (2002), Structural behaviour of unrestrained composite truss systems in fire, 3 rd European Conference on Steel Structures, Coimbra, Portugal, pp 1459-1468. Comité Européen de Normalisation. (2001), ENV 1991-1-2: Eurocode 1: Actions on Structures. Part1.2: General Actions: Actions on Structures Exposed to Fire. Brussels. Comité Européen de Normalisation. (1993). ENV 1993-1-2: Eurocode 3: Design of Steel Structures. Part1.2: General Rules: Structural Design for Fire, Brussels. Comité Européen de Normalisation. (1994), ENV 1994-1-2: Eurocode 4: Design of Composite Steel and Concrete Structures. Part 1.2: General Rules: Structural Fire Design, Brussels. Huang, Z., Platten, A., and Roberts, J. (1996), Non-linear finite element model to predict temperature histories within reinforced concrete in fires. Building and Environment, Vol. 31, No. 2, pp 109-118.

International Organization for Standardization. (1975), ISO834: Fire resistance tests - Elements of building construction, Geneva. Purkiss, J.A. (1996), Fire Safety Engineering Design of Structures, Butterworth Heinemann, Oxford, UK. Rots, J.G., et al. (1984), The need for fracture mechanics options in finite element models for concrete structures, Proc. Int. Conf. on Computer Aided Analysis and Design of Concrete Structures Part1, F. Damjanic., ed., Pineridge Press, pp 19-32.