Plumbing Pipe Insulation Specification Submitted by: Armacell LLC. Plumbing Pipe Insulation Specification Armacell LLC 1

Similar documents
Master Insulation Guide Specification for Mechanical Systems

GUIDE SPECIFICATION: MECHANICAL SYSTEMS

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section PIPE AND EQUIPMENT INSULATION

EFRIGERATION INSTALLATION GUIDE

Tube Insulation. Fiber Free

GUIDE SPECIFICATION: DUCT LINER

PRODUCT SELECTION GUIDE

A. Deliver material to job site in original, nonbroken, factory packaging, labeled with manufacturer's density and thickness.

DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION HVAC INSULATION

TOTALINE COPPER TUBING

K-FLEX USA MECHANICAL INSULATION CONTENTS: SPECIFICATION GUIDE PRODUCT SELECTION GUIDE LEED CONTRIBUTION GUIDE

A. Section Fire Procection, HVAC & Plumbing Penetration Firestopping. B. Section Interior Painting: Painting insulation jacket.

We solved the science of safely insulating air ducts.

FIRE STATION 55 June 14, 2010

SECTION PIPING INSULATION

EXPERIENCE COUNTS! Specializing in more than just products we put the competitive advantage at your fingertips.

SECTION HVAC PIPING INSULATION

B. Refer to Section : Air Distribution for lined ductwork requirements.

PRESTON HEALTH SERVICES ARCHITECT S NO. 2700

SECTION DUCT INSULATION

ARIFLEX. Rubber Insulation Foam Tube & Foam Sheet

FM APPROVED. FIRE PERFORMANCE Differences Between Elastomeric and Polyethylene/Polyolefin Insulations

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION

SECTION HVAC INSULATION

The Right Insulation for Cold Systems

SECTION MECHANICAL INSULATION

A. ASTM E84 Standard Test Method for Surface Burning Characteristics of Building Materials

BuildingName The Description of the Project P DOCUMENTS

Design & Construction Standards, Revised January

Pipe and Equipment Insulations. Zeston. PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems

PITTWRAP CW PLUS JACKETING Product Datasheet

1. Division 23 Section "Hangers and Supports for HVAC Piping and Equipment" for pipe insulation shields and protection saddles.

D. Provide UL-approved assemblies for pipes and ducts passing through fire-rated floors, walls, or partitions as required.

Division 15 INSULATION Section 15100

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS

SECTION HVAC INSULATION

UBC Technical Guidelines Section Edition Thermal Insulation for Piping Page 1 of 5

University of Delaware

SECTION MECHANICAL INSULATION. A. Types of insulation specified in this section include the following:

TECHNICAL BULLETIN TA77

Pipe Supports Comparison

This specification describes the minimum requirements for industrial thermal insulation.

HVAC INSULATION. A. General Requirements for Flexible Elastomeric Insulation: 3. Use pre-molded roll on pipe sizes 3.5" and below.

.1 Thermal insulation for insulated piping and piping accessories affected by construction and new pipe sections as indicated on drawings.

SECTION Arisfor WallGuard

PRESTON HEALTH SERVICES ARCHITECT S NO. 2700

UBC Technical Guidelines Section Edition Insulation of Tanks, Steam and Condensate Piping Page 1 of 6

A. ASTM E 84 - Standard Test Method for Surface Burning Characteristics of Building Materials

ITW INSULATION SYSTEMS

ITW INSULATION SYSTEMS

SECTION COMPOSITE WALL PANELS PART 1 GENERAL 1.01 SECTION INCLUDES

INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS

SILICONE ROOF COATING RESTORATION (RCR) SYSTEM OVER METAL ROOF PANEL

SECTION PLUMBING INSULATION

ACOUSTICAL INSULATION (LAGGING) FOR PIPING AND EQUIPMENT

INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS

We solved the science of safely insulating air ducts.

B C M T e c h n i c a l, L L C A v o n I n d u s t r i a l D r. R o c h e s t e r H i l l s, M I P h o n e : T o l

Armacell Product Selection Guide

RELIABLE, FLEXIBLE INSULATION TRUSTED TO PREVENT CONDENSATION

ITW INSULATION SYSTEMS

Chilled Water. Product performance for insulation of chilled water piping

SUPERIOR CAL-SHIELDS Features & Benefits FAST

HVAC Piping Insulation FIBERGLAS Insulation. General Specification Guide SECTION

SECTION PROJECTED SCHEDULE

INSTALLATION GUIDELINE FOR TRYMER INSULATION ITW INSULATION SYSTEMS

This Design guideline contained herein includes the requirements for mechanical insulation at The University of Texas at Austin

RENEW ELASTOMERIC ACRYLIC COATING (PAINT GRADE) MANUFACTURERS SPECIFICATION / SECTION

Quality NBR Insulation

TAPE SOLUTIONS FOR HVAC SHURTAPE.COM TAPE

University of New Hampshire Scholars' Repository

1. Section 04300: Concrete Masonry Units

Standard and Mini Split Line Sets

Redi-Klad 1000 Pipe Insulation

INDUSTRIAL SYSTEMS. Application Manual for Piping Equipment. ARMASOUND INDUSTRIAL SYSTEMS - Application Manual for Piping Equipment

Technical Data Sheet

HVAC Piping Insulation- FIBERGLAS Insulation

Ammonia. Product performance for insulation of ammonia piping

SECTION MECHANICAL SYSTEMS INSULATION

SECTION PLUMBING PIPING SYSTEM

Addendum 1 Section THERMAL INSULATION FOR PIPING Burrow Avenue Pumping Station Upgrades Page 1 of 5

NCCER Progress Blvd, Alachua, Florida Tel: (888)

Value Engineered Products

GENERAL SPECIFICATION FOR FIRE RATED APPLICATIONS

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for LIQUEFIED NATURAL GAS (LNG) CRYOGENIC REFRIGERATION CHILLED WATER

SECTION METAL FRAMED SKYLIGHT. A. Engineering, preparation of fabrication drawings and structural calculations for the entire skylight system.

BITUTHENE Deck System

PITTWRAP CF JACKETING Product Datasheet

International Fireproof Technology Inc.

Addendum to Specifications

The Right Insulation for Indoor Air Quality

Insulation for VRF/VRV HVAC Systems. Variable Refrigerant Flow(VRF) and Variable Refrigerant Volume(VRV) System Insulation Needs

HPW Protocol Reference Manual

International Fireproof Technology Inc.

GigaCrete Specification PlasterMax. PlasterMax : Fire Rated Plaster for Direct Application over Cement Masonry Units (CMU) Interior Walls

GigaCrete Specification PlasterMax. PlasterMax : Fire Rated Plaster for Direct Application to Insulated Concrete Forms (ICF) Interior Walls

A. Product Data: Identify thermal conductivity, thickness, and jackets (both factory and field applied, if any), for each type of product indicated.

Insulation engineered to prevent condensation and energy loss

Transcription:

Plumbing Pipe Insulation Specification 2005 Armacell LLC 1

Part 1 General 1.01 Scope of Work: A. Provide piping insulation as specified below. The purpose of the thermal pipe insulation is for condensation control, energy and water savings, noise reduction and freeze protection. 1.02 Definitions: A. Domestic Piping: Pipes where the normal operating temperature is between 40 F and 180 F. B. Thermal Conductivity: The amount of heat in BTUs transferred in one hour through one square foot of homogeneous material one-inch in thickness when there is a temperature difference of 1 F. C. Compression Fit Method: To allow for expansion and contraction of the insulation, the insulation must be installed in compression of at least 2 percent of overall length. 1.03 Quality Assurance: A. Material shall be delivered in nonbroken, factory furnished packaging and stored in a clean, dry indoor space that provides protection against the weather. B. Insulation shall be applied by qualified personnel skilled in this trade. C. Progressive testing of the systems to be insulated shall have been completed, inspected and approved by the owners' representative before the insulation is applied. D. Insulation shall not be applied until all surfaces are clean, dry, and free of dirt, dust, grease, frost, moisture and other extraneous elements. E. Work shall be performed at the temperatures recommended by the product manufacturer. 2005 Armacell LLC 2

Part 2 Products 2.01 Polyolefin/Polyethylene -- Elastomeric Insulation: 2.01.1 Acceptable Manufacturers These specifications are based on products and data of Armacell and designate the type and quality of work intended under this section. Products of other manufacturers proposed as equivalent must be submitted for written approval by the specifying engineer ten days prior to the bid date. Supporting technical data, samples, published specifications and the like must be submitted for comparison. The contractor should warrant that proposed substitutions, if accepted, will provide performance equal to the materials specified herein. A. Insulation material shall be a flexible, closed-cell 1. Polyolefin/polyethylene insulation in tubular form: TUBOLIT, TUBOLIT SS, TUBOLIT W, SSA 2000. This product meets the requirements as defined in ASTM C 1427, Specification for Preformed Flexible Cellular Polyolefin Thermal Insulation in Sheet and Tubular Form. 2. Flexible elastomeric in tubular foam. AC/Accoflex, AP/Armaflex, AP/Armaflex SS. This product meets the requirements as defined in ASTM C 534, Grade 1, Type I, Specification for Preformed Flexible Elastomeric Cellular Thermal Insulation in Sheet and Tubular Form B. Materials shall have a flame spread index of less than 25 and a smokedeveloped index of less than 50 when tested in accordance with ASTM E 84, latest revision. C. Materials shall have a maximum thermal conductivity of 0.27 Btu-in./h-ft2- F at a 75 F mean temperature when tested in accordance with ASTM C 177 or ASTM C 518, latest revisions. D. Materials shall have a maximum water vapor transmission of 0.08 perminches when tested in accordance with ASTM E 96, Procedure A, latest revision. 2.02 Adhesives and Finishes A. Adhesive shall be the insulation manufacturer's recommended contact adhesive: Armaflex 520, Armaflex 520 BLV. B. Insulation finish shall be the insulation manufacturer's recommended finish: WB Armaflex Finish. C. Accessories such as adhesives, mastics and cements shall have the same properties as listed above and shall not detract from any of the system ratings as specified above. 2005 Armacell LLC 3

Part 3 Installation 3.01 Piping: A. Install pipe insulation by slitting tubular sections and applying onto piping or tubing. Alternately, whenever possible, slide unslit sections over the open ends of piping or tubing. All seams and butt joints shall be adhered and sealed using Armaflex 520 or 520 BLV Adhesive. A thin coat of adhesive must be applied to both surfaces, allowed to tack and join both surfaces with firm pressure. When using AP/Armaflex SS, TUBOLIT SS, SSA 2000 only the butt joints shall be adhered using Armaflex 520 or 520 BLV Adhesive. B. The insulation must be installed in compression to allow for expansion and contraction. Install an additional 1.5 inches of insulation for every six feet of installed pipe or an additional 2 percent of measured pipe length. C. Insulation shall be pushed onto the pipe, never pulled. Stretching of insulation may result in open seams and joints. D. Tape the ends of the copper tubing before slipping the Armaflex or TUBOLIT pipe insulation over the new pipes to prevent dust from entering the pipe. E. All edges shall be clean cut. Rough or jagged edges of the insulation shall not be permitted. Proper tools such as sharp knives must be used. F. On heat traced systems, the tracer shall not exceed the allowable temperature limit of the insulation material. Insulation ID may need to be oversized to accommodate heat trace tape. G. Seams shall be staggered when applying multiple layers of insulation. 3.02 Outdoors Exposed Piping: A. All outdoor exposed piping shall be painted with two coats of WB Armaflex Finish. Prior to applying the Finish, the insulation shall be wiped clean with denatured alcohol. The Finish shall not be tinted. To insure good adhesion, the temperature should be above 50 F during application and drying. B. All outdoor exposed piping shall have the seams located on the lower half of the pipe. C. As an alternative to WB Armaflex Finish, metal or aluminum jacketing may be used and should be applied according to the manufacturer s recommendations. 3.03 Insulation Thickness Recommendations A. The insulation thickness recommendations are based on heat loss calculations, consult local energy code requirements for minimum insulation thickness. Up to Over 2 Over 4 Piping System 2 to 4 to 6 Over 6 Plumbing: Cold Water 1/2 1/2 1/2 3/4 Hot Water 1/2 1/2 3/4 3/4 Hydronic Systems (Use AP/Armaflex or AC/Accoflex only) Heating Hot Water 3/4 3/4 1 1 2005 Armacell LLC 4

For More Information Contact Us Via: Phone: (919) 304-3846 Fax: (919) 304-3847 Email: info.us@armacell.com Website: www.armacell.com Armacell provides this information as a technical service. To the extent the information is derived from sources other than Armacell, Armacell is substantially, if not wholly, relying upon the other source(s) to provide accurate information. Information provided as a result of Armacell's own technical analysis and testing is accurate to the extent of our knowledge and ability, as of date of printing, using effective standardized methods and procedures. Each user of these products, or information, should perform their own tests to determine the safety, fitness and suitability of the products, or combination of products, for any foreseeable purposes, applications and uses by the user and by any third party to which the user may convey the products. Since Armacell cannot control the end use of this product, Armacell does not guarantee that the user will obtain the same results as published in this document. The data and information are provided as a technical service and are subject to change without notice. 999P 028 06 05 NA NA 2005 Armacell LLC 5