Klip-lok Maxima Available in WA only Lysaght Klip-lok Maxima Concealed-fixed deck with extra wide coverage LYSAGHT KLIP-LOK MAXIMA is the newest of our wide-cover concealed-fixed claddings. We call it MAXIMA because it has extra wide 770 mm coverage with excellent performance. Strong ribs rise from flat pans. Extensive research shows long, straight runs are possible because thermal expansion is able to slide along the clips. On long runs, we recommend one end be anchored, usually under the ridge cap. We have patented this outstanding innovation. Because of the ease of installation and the extra economy wide 770mm cover brings, you get outstanding value. KLIP-LOK MAXIMA is available in WA only. Simple, low-cost, concealed-fixing With no exposed fasteners, the long, straight lines of KLIP-LOK MAXIMA remain clean and smooth. At the heart is our fixing clip, which can be laid in place and fixed more simply and faster than ever before. This is because KLIP-LOK MAXIMA is fixed with hex. head screws, which are easier to drive. The smaller number of clips for a given area saves you money. The clip gives roofers the ability to accommodate up to 75 mm insulation. Longitudinal fluting Our longitudinal fluting significantly adds to the performance of KLIP-LOK MAXIMA. Roofing & Walling Products Structural Products Rainwater Products Fencing Products House Framing Products Customer Support Home Improvements www.lysaght.com
Lysaght Klip-lok Maxima Overlap Underlap 31mm 770mm Masses BMT Klip-lok Maxima kg/m kg/m 2 m 2 /t 0.42 ZINCALUME 3.26 4.23 236 0.42 COLORBOND 3.34 4.34 231 0.48 ZINCALUME 3.70 4.81 208 0.48 COLORBOND 3.78 4.91 204 0.60* ZINCALUME 4.59 5.96 168 0.60* COLORBOND 4.67 6.06 165 Material specifications klip-lok maxima is made from: z i n c a l u m e aluminium/zinc alloy-coated steel complying with AS 1397 2001 G550, AZ150 (550 MPa minimum yield stress, 150 g/m2 minimum coating mass); or Stainless steel standard grade designation is AISI/ASTM Type 430; UNS No. S43000 The base metal thickness is 0.42, 0.48 and 0.60 mm. The c o l o r b o n d prepainted steel complies with AS/NZS 2728:2007. Colours k l i p-lok m a x i m a is available in an attractive range of c o l o r b o n d steel colours, plain z i n c a l u m e (aluminium/ zinc alloy coated steel), or c o l o r b o n d stainless steel. c o l o r b o n d metallic steel provides superior aesthetic qualities, and c o l o r b o n d ultra steel is intended for severe coastal or industrial environments. Lengths Sheets are available custom cut. Tolerances Length: + 0 mm, 15 mm Width: + 2 mm, 2 mm Walking on roofs Generally, keep your weight evenly distributed over the soles of both feet to avoid concentrating your weight on either heels or toes. Always wear smooth soft-soled shoes; avoid ribbed soles that pick up and hold small stones, swarf and other objects. Be careful when moving between supports. Do not walk in the pan immediately adjacent to flashings or translucent sheeting. Walk at least one pan away. Minimum roof pitch You can use k l i p-lok m a x i m a on roof pitches from as low as 1º (0.48 & 0.60 BMT) or 2º (0.42 BMT). It can also be used on walls. Maximum support spacings The maximum recommended support spacings are based on testing in accordance with AS1562.1-1992, AS4040.0-1992 and AS4040.1-1992. Roof spans consider both resistance to wind pressure and light roof traffic (traffic arising from incidental maintenance). Maximum roof lengths for drainage (measured from ridge to gutter (m) Peak rainfall Roof Slope (degrees) intensity (mm/hr) 1º 2º 3º 4º 5º 7.5º 10º 100 238 296 347 392 432 516 593 150 159 198 232 261 288 344 395 200 119 148 174 196 216 258 296 250 95 119 139 157 173 206 237 300 79 99 116 131 144 172 198 400 60 74 87 98 108 129 148 500 48 59 69 78 86 103 119 Wall spans consider resistance to wind pressure only. The pressure considered is based on buildings up to 10m high in Region B, Terrain Category 3, R (average recurrence interval) 500, Md=1.0, Ms=0.85. Mt=1.0, with the following assumptions made: Roofs: Cpi=+0.20, Cpe=-0.90, Kl=2.0 for single and end spans, Kl=1.5 for internal spans Walls: Cpi=0.20, Cpe=-0.65, Kl=2.0 for single and end spans, Kl=1.5 for internal spans These spacings may vary by serviceability and strength limit states for particular projects. KLIP-LOK MAXIMA Maximum support spacings (mm) Type of span Roofs 0.42BMT 0.48 BMT 0.60 BMT Single span - - End span 1400 Internal span 2000 Walls Single span 1900 End span 2000 Internal span 2900 1800 3300 2100 2400 3300 For roofs: the data are based on foot-traffic loading. For walls: the data are based on pressures (see wind pressures table). Table data are based on supports of 1 mm BMT. 2200 2600 3600 2400 3200 3900 Self drilling, self tapping screws Self drilling, self tapping screws with hex. washer-head Self drilling, self tapping, wood screws with hex. washer-head LAT 27ºS NON-CYCLONIC AREA LAT 25ºS
Limit State Wind pressure capacities (kpa) KLIP-LOK MAXIMA 0.42 BMT Span (mm) Span type Limit state 900 1200 1500 1800 2100 2400 2700 3000 3300 3600 3900 SINGLE Serviceability 1.63 1.32 1.03 0.77 0.56 0.41 0.31 0.23 0.18 Strength* 3.05 2.56 2.09 1.68 1.36 1.14 1.01 0.93 0.88 END Serviceability 1.43 1.43 1.36 1.19 0.96 0.74 0.58 0.47 0.39 0.34 Strength* 2.86 2.34 1.91 1.62 1.44 1.31 1.18 1.03 0.88 0.72 INTERNAL Serviceability 1.57 1.40 1.23 1.07 0.93 0.81 0.7 0.61 0.53 0.45 0.38 Strength* 2.51 2.26 2.01 1.78 1.58 1.40 1.24 1.11 0.99 0.89 0.78 KLIP-LOK MAXIMA 0.48 BMT Span (mm) Span type Limit state 900 1200 1500 1800 2100 2400 2700 3000 3300 3600 3900 SINGLE Serviceability 2.17 1.79 1.43 1.108 0.84 0.64 0.50 0.39 0.30 Strength* 3.68 3.06 2.47 1.98 1.62 1.42 1.42 1.42 1.42 END Serviceability 2.20 1.84 1.51 1.25 1.04 0.87 0.73 0.62 0.52 0.42 Strength* 3.36 2.87 2.41 2.02 1.69 1.42 1.20 1.02 0.87 0.73 INTERNAL Serviceability 2.00 1.94 1.86 1.74 1.57 1.36 1.12 0.86 0.60 0.36 0.15 Strength* 3.10 2.75 2.43 2.13 1.88 1.67 1.49 1.35 1.23 1.14 1.05 KLIP-LOK MAXIMA 0.60 BMT Span (mm) Span type Limit state 900 1200 1500 1800 2100 2400 2700 3000 3300 3600 3900 SINGLE Serviceability 4.02 3.13 2.29 1.57 1.02 0.67 0.50 0.43 0.42 Strength* 8.33 6.73 5.22 3.92 2.91 2.25 1.89 1.73 1.67 END Serviceability 3.02 2.89 2.66 2.27 1.80 1.35 1.02 0.79 0.63 0.51 Strength* 4.01 3.80 3.54 3.19 2.80 2.43 2.11 1.84 1.61 1.40 INTERNAL Serviceability 2.82 2.70 2.55 2.37 2.12 1.81 1.47 1.18 0.98 0.84 0.74 Strength* 4.59 4.30 4.01 3.70 3.38 3.02 2.67 2.31 1.98 1.67 1.36 *A capacity reduction factor of Ø = 0.9 has been applied to strength capacities. Table values are based on supports of 1 mm minimum BMT. End spans if end lap or expansion joint in sheeting O ES IS IS ES O O ES IS IS IS ES O Spacing definitions IS = Internal span O = Overhang ES = End span Limit states wind pressures Single span k l i p-lok m a x i m a offers the full benefits of the latest methods for modelling wind pressures. The wind pressure capacity table is determined by full scale tests conducted at BlueScope Lysaght s NATA-registered testing laboratory, using the direct pressure-testing rig. Testing was conducted in accordance with AS 1562.1 1992 Design and Installation of Sheet Roof and Wall Cladding Metal, and AS 4040.2 1992 Resistance to Wind Pressure for Noncyclonic Regions. The pressure capacities for serviceability are based on a deflection limit of (span/120) + (maximum fastener pitch/30). The pressure capacities for strength have been determined by testing the cladding to failure (ultimate capacity). These pressures are applicable when the cladding is fixed to a minimum of 1.0 mm, G550 steel. For material less than 1.0 mm thick, seek advice from our information line. Adverse conditions If this product is to be used in marine, severe industrial, or unusually corrosive environments, ask for advice from our information line. Metal & timber compatibility Lead, copper, free carbon, bare steel and green or some chemically-treated timber are not compatible with this product. Don t allow any contact of the product with those materials, nor discharge of rainwater from them onto the product. Supporting members should be coated to avoid problems with underside condensation. If there are doubts about the compatibility of other products being used, ask for advice from our information line. Maintenance Optimum product life will be achieved if all external walls are washed regularly. Areas not cleaned by natural rainfall (such as the tops of walls sheltered by eaves) should be washed down every six months. Storage and handling Keep the product dry and clear of the ground. If stacked or bundled product becomes wet, separate it, wipe it with a clean cloth to dry thoroughly. Handle materials carefully to avoid damage: don t drag materials over rough surfaces or each other; don t drag tools over material; protect from swarf. Turn up-down tools On all roofs of pitches less than 15 degrees, the high end of all sheets must be turned up to stop water from being driven under the flashing and into the building. Similarly, the pans at the gutter end must be turned down to stop water running back along the underside of the sheets. Tools are available for both applications. Notching tool A tool is available for on-site notching of transverse flashings and cappings. Cutting For cutting thin metal on site, we recommend a circular saw with a metal-cutting blade because it produces fewer damaging hot metal particles and leaves less resultant burr than does a carborundum disc. Cut materials over the ground and not over other materials. Sweep all metallic swarf and other debris from roof areas and gutters at the end of each day and at the completion of the installation. Failure to do so can lead to surface staining when the metal particles rust. Fasteners Where insulation is to be installed, you may need to increase the length of the screws given below, depending on the density and thickness of the insulation. When the screw is properly tightened: into metal: there should be at least three threads protruding past the support you are fixing to, but the Shankguard must not reach that support; into timber: the screw must penetrate the timber by the same amount that the recommended screw would do if there were no insulation.
Installation Preparation Before starting work ensure that: The supports for your cladding are truly in the same plane; The minimum roof slopes conform to our recommendations; and The overhangs of sheets from the top and bottom supports don t exceed our recommendations. The first and last supports and clips should be at least 75mm from each end of the sheet to keep maximum holding power. Make any necessary adjustments before you start laying sheets, because they will be difficult to rectify later. Orient sheets before lifting Consider which end of the building is best to start from. For maximum weather-tightness, start laying sheets from the end of the building that will be downwind of the worst-anticipated or prevailing weather (Figure 1). Sheet 3 Prevailing weather Sheet 2 Sheet 1 Direction of laying Figure 1 Lay sheets towards prevailing weather Discard cut here It is much easier and safer to turn sheets on the ground than up on the roof. Before lifting sheets on to the roof, check that they are the correct way up and the overlapping side is towards the edge of the roof from which installation will start. Place bundles of sheets over or near firm supports, not at mid span of roof members. Steps for installation 1. Lay and fix wire mesh to the supports in accordance with the appropriate building requirements. (Figure 2) 2. Position the first clips on each support by placing onto the support nearest the gutter. (Figure 3) 3. Fix the first clip on the support so they point in the direction of laying. Ensure the clip is 90 degrees to the edge of the sheet. 4. Align the clips with the spacer using a string line (or the first sheet as a straight edge) to align the clips as you fix a clip to each support working towards the high end of the roof. 5. Drive hex-head screws through the top of the clip, into the support. 6. Work along the edge of the gutter, ensuring it aligns correctly at its ends in relation to the gutter and ridge (or parapet or transverse wall). 7. Place the glass wool insulation between the supports. 8. Measure the distance from the gutter end of the sheet to the support. 25 mm Standard flashing KLIP-LOK MAXIMA: Starting method 1 Standard flashing Second clip First clip Second clip KLIP-LOK MAXIMA: Starting method 2 Figure 2 Alternative methods for first clips KLIP-LOK MAXIMA Figure 3 Fix the first row of clips. Fix the next (and subsequent) clips and sheets
9. Position the first sheet so that it overhangs the desired amount (usually 50 mm) to the gutter. It is important to ensure this first sheet is placed square to adjacent edges. (Figure 4.) 10. Engage the sheet with clips using vertical foot pressure on all the ribs over each clip. (Figure 5) 11. Fix the next row of clips, one to each support with the slots and tabs engaged. Be sure the clip is 90 degrees to the edge of the sheet. 12. As before, place the next sheet over its clips ensuring you also engage the edge of the preceding sheet. 13. Accurately position the sheet so that it overhangs the desired amount into the gutter. It is important that you keep the gutter-end of all sheets in a straight line. 14. Fully engage the two sheets along the overlapping rib. You can do this by walking along the full length of the sheet with one foot in the centre pan of the previous sheet and the other foot applying vertical pressure to the top of the interlocking ribs at regular intervals. It is important that you don t walk in the unsupported pan beside the overlap (Figure 5) 15. Similarly, engage all the clips by applying vertical foot pressure to the top of the other two ribs over each clip. It is essential that the sheets interlock completely. It is important that your weight is fully on the sheet you are installing. Check alignment occasionally Occasionally check that the sheets are still parallel with the first sheet, by taking two measurements across the width of the fixed sheeting. At about half way through the job, perform a similar check but take the measurements from the finishing line to aim for the final sheet to be parallel with the end of the roof. If the measurements are not close enough, lay subsequent sheets very slightly out of parallel to gradually correct the error. (Figure 6) To allow this to happen, flatten the tabs on the base of subsequent clips the slot in the clip will allow the clips to be fixed out of standard pitch. Figure 4 Placing the first sheet Don't step in this pan until ribs are engaged Overlapping rib Figure 5 Engaging the lapping ribs Start Fixed sheets Early checks = Fix the last sheet If the final space is less than the full width of a sheet, you can cut a sheet along its length and shorten the clips as appropriate. It is desirable to fix the sheet at one end. Installing klip-lok maxima walls The installation procedure for walls is similar to that described for roofs. To prevent k l i p-lok m a x i m a from sliding downward in the fixing clips, you should pierce-fix through each sheet under the flashing or capping, along the top of the sheets. Underlapping rib Purlin Later checks = Early checks = Later checks = Figure 6 Check alignment occasionally Finish Sealed joints For sealed joints use screws or rivets and neutral-cure silicone sealant branded as suitable for use with galvanised or z i n c a l u m e steel. Non-cyclonic areas The information in this brochure is suitable for use only in areas where a tropical cyclone is unlikely to occur as defined in AS/NZS 1170.2 2002, Structural Design Actions, Part 2: Wind Actions. Ask for advice from our information service on designs to be used in cyclonic areas.
Lysaght Klip-lok Maxima design advantages KLIP-LOK MAXIMA is the newest member of our popular concealed fixed claddings vertically or horizontally Disclaimer, warranties and limitation of liability This publication is intended to be an aid for all trades and professionals involved with specifying and installing Lysaght products and not to be a substitute for professional judgement. Terms and conditions of sale available at local BlueScope Lysaght sales offices. Except to the extent to which liability may not lawfully be excluded or limited, BlueScope Steel Limited will not be under or incur any liability to you for any direct or indirect loss or damage (including, without limitation, consequential loss or damage such as loss of profit or anticipated profit, loss of use, damage to goodwill and loss due to delay) however caused (including, without limitation, breach of contract, negligence and/or breach of statute), which you may suffer or incur in connection with this publication. Copyright BlueScope Steel Limited August 24, 2007 Product Literature Warranties Technical Support Online Information Product Samples 9 3 2 0 0 7 5 0 5 0 9 4 8 Information, brochures and your local distributor 1800 641 417 Please check the latest information which is always available at www.lysaght.com LYSAGHT, KLIP-LOK MAXIMA, COLORBOND and ZINCALUME are registered trademarks of BlueScope Steel Limited, ABN 16 000 011 058. The LYSAGHT range of products is exclusively made by BlueScope Steel Limited trading as BlueScope Lysaght. Printed by BMP 2M 0807