Mechanical response of local rapid cooling by spray water on constrained steel frame structure at high temperature in fire

Similar documents
COVER SHEET. Title: Component-Based Element of Beam Local Buckling Adjacent to Connections in Fire. Authors: Guan Quan Shan-Shan Huang Ian Burgess

SIMPLE INVESTIGATIONS OF TENSILE MEMBRANE ACTION IN COMPOSITE SLABS IN FIRE

Large scale fire test on tunnel segment: Real boundary conditions in order to evaluate spalling sensitivity and fire resistance

BEHAVIOUR OF COLD-FORMED Z-SHAPED STEEL PURLIN IN FIRE

Behavior of Concrete Filled Steel Tubular (CFST) triple-limb laced columns subjected to ISO 834 Standard Fire

The need to design for robustness in fire. Ian Burgess

SHEAR PANEL COMPONENT IN THE VICINITY OF BEAM-COLUMN CONNECTIONS IN FIRE

Long-term Stress of Simply Supported Steel-concrete Composite Beams

The behaviour of multi-bay, two-way reinforced concrete slabs in fire

THE BEHAVIOUR OF LIGHTWEIGHT COMPOSITE FLOOR TRUSSES IN FIRE

Fire Safety Day Fire Behaviour of Steel and Composite Floor Systems Simple design method

Post-earthquake fire behaviour of composite steel-framed structures

To have a clear idea about what really happened and to prevent the

DYNAMIC BEHAVIOUR OF PORTAL FRAME AT ELEVATED TEMPERATURE

Basic quantities of earthquake engineering. Strength Stiffness - Ductility

An example of finite element modelling of progressive collapse

The Chinese Performance-based Code for Fire-resistance of Steel Structures

Mechanical behavior and design method of weld-free steel structure with knee brace damper using square tube column

LESSONS FROM A FULL SCALE FIRE TEST

Finite element analysis of bending performance on polyurethane composite panel

Thermal Stress Analysis of Beam Subjected To Fire

International Journal of Civil and Environmental Research Volume 02, Issue 01, Pages 1-9, Structural Analysis of Steel Beam under Fire Loading

NON-LINEAR MODELLING OF THREE FULL-SCALE STRUCTURAL FIRE TESTS

Level 6 Graduate Diploma in Engineering Structural analysis

UNIVERSITY OF BOLTON WESTERN INTERNATIONAL CENTRE FZE. BEng (HONS) CIVIL ENGINEERING SEMESTER ONE EXAMINATION 2015/2016

Analysis of Shear Wall Transfer Beam Structure LEI KA HOU

Improving the Seismic Response of a Reinforced Concrete Building Using Buckling Restrained Braces

Fire response of a 3D multi-storey building with buckling restrained braces

Vertical Incremental Dynamic Analysis for Assessing Progressive Collapse Resistance and Failure Modes of Structures

1/29 PUSHDOWN ANALYSIS USFOS. PushDown, Rev

Wire-rope Bracing System with Central Cylinder,

UNIVERSITY OF BOLTON WESTERN INTERNATIONAL COLLEGE FZE. BEng (HONS) CIVIL ENGINEERING SEMESTER ONE EXAMINATION 2018/2019

Example of a modelling review Roof truss

Composite floor systems in highrise towers A very cost-effective construction using membrane action in fire design

The fire behaviour of multi-bay, two-way reinforced concrete slabs

Angle Cleat Base Connections

Chapter 7. Finite Elements Model and Results

DUCTILITY REQUIREMENTS FOR BUILDINGS

British Steel Fire Test3: Reference ABAQUS model using grillage representation for slab. Research Report

Finite Element Study on Thermal Fatigue Depth of Aluminum Alloy Die Casting Die

FIRE DESIGN METHOD FOR COLD-FORMED STEEL SHEETING SYSTEM

Flexural Behavior of Casing Joint of Square Steel Tube

EXPERIMENTAL STUDY ON SEISMIC BEHAVIOR OF REINFORCED CONCRETE CORE WALL

School of Civil Engineering, Shenyang Jianzhu University, Shenyang , China.

Influence of the design fire scenario on the response of a 10-storey steel frame: travelling fires and Eurocode

LOAD TESTS ON 2-SPAN REINFORCED CONCRETE BEAMS STRENGTHENED WITH FIBRE REINFORCED POLYMER

Belleville Spring. The relation between the load F and the axial deflection y of each disc. Maximum stress induced at the inner edge

THE APPLICATION OF ADVANCED FINITE ELEMENT ANALYSIS FOR STRUCTURAL FIRE DESIGN

Application of Fiber Model for Progressive Collapse Analysis of Reinforced Concrete Frames *

THE EFFECT OF AXIAL COMPRESSION RATIO ON SEISMIC BEHAVIOR OF INFILLED REINFORCED CONCRETE FRAMES WITH PROFILED STEEL SHEET BRACING

Analysis on Local Compression Bearing Capacity of Reinforced Concrete Corbels Constrained by Prestress YIN Xinsheng1,a, LIU Yang1,b,WANG Jing1,c

Analysis of the effect of shoring in the behaviour of reinforced concrete slabs. Extended abstract

EFFECTS OF SOIL CONDITION ON BEHAVIOR OF STIFFENED RC FRAME STRUCTURES SUBJECTED TO EARTHQUAKES

FRP Strengthening of RC Flexural Members - Ductility Issues

Numerical Analysis of the Durability of Retaining Wall with Anchor

THE ROLE OF COMPOSITE JOINTS ON THE PERFORMANCE OF STEEL-FRAMED BUILDINGS IN FIRE. Prof. Khalifa S. Al-Jabri

Fatigue Strength Analysis on the Automobile Stabilizer Bar Based on ANSYS

Experiment of Reinforce Concrete Beams at Different Loading Rates

Research on the Key Technology of Hinge Joint Diseases Treatment without Traffic Interruption for Plate Girder Bridge

Journal of Asian Scientific Research EVALUATION OF RECTANGULAR CONCRETE-FILLED STEEL-HOLLOW SECTION BEAM-COLUMNS

DYNAMIC RESPONSE ANALYSIS OF THE RAMA 9 BRIDGE EXPANSION JOINT DUE TO RUNNING VEHICLE

Finite Element Investigation on Load Carrying Capacity of Corroded RC Beam Based on Bond-Slip

HIGH-TEMPERATURE EXPERIMENTS ON JOINT COMPONENT BEHAVIOUR

Code No: R Set No. 1

ULTIMATE LOAD-CARRYING CAPACITY OF SELF-ANCHORED CONCRETE SUSPENSION BRIDGE

Structural Performance of Long-Span Composite Truss and Beam Systems in Fire

Building Investigation: Material or Structural Performance

Extreme Loading for Structures Version 3.1

THE EXPERIMENTAL STUDY ON INNER SHIFT LINING STRUCTURE OF FREEZING SHAFT IN DEEP THICK AQUIFEROUS SOFT ROCK**

UNIVERSITY OF BOLTON SCHOOL OF ENGINEERING. BEng (Hons) CIVIL ENGINEERING

Structural Design of Pergola with Airfoil Louvers

Design of Laterally Unrestrained Beams

beni-suef university journal of basic and applied sciences 5 (2016) Available online at ScienceDirect

BEHAVIOUR OF REINFORCED CONCRETE STRUCTURES IN FIRE

THERMAL-MECHANICAL BEHAVIOR OF SANDWICH PANELS WITH CLOSED-CELL FOAM CORE UNDER INTENSIVE LASER IRRADIATION

VERIFICATION OF A REINFORCED CONCRETE COLUMN COMPUTER MODEL UNDER UNIAXIAL AND BIAXIAL BENDING LOADING CONDITIONS

Effect of beam dimensions on structural performance of wide beam-column joints

EXPERIMENTAL AND ANALYTICAL INVESTIGATIONS OF STEEL AND COMPOSITE TRUSSES

Temperature distribution of intumescent coated steel framed connection at elevated temperature.

Full-scale tests on steel frames under cyclic loading

APOLLO CRADLES LTD 1.5M DEEP -BEAM TEST REPORT AND LOAD EVALUATION

Study of rigid Bolt Joint in Beam-column connection of Gabled Portal Frames Xuan Guo 1, a, Xiaoxin Zhang2, b

Comparison between Seismic Behavior of Suspended Zipper Braced Frames and Various EBF Systems

CHAPTER 6 FINITE ELEMENT ANALYSIS

ANALYSIS OF P-DELTA EFFECT ON HIGH RISE BUILDINGS

Behavior of Steel Beam to Concrete Filled Tubular Steel Joints after Exposure to Fire

FINITE ELEMENT ANALYSIS OF REINFORCED CONCRETE BRIDGE PIER COLUMNS SUBJECTED TO SEISMIS LOADING

Heat transfer analysis of hybrid stainless-carbon steel beam-column joints

STRUCTURAL INTEGRITY FIRE TEST

Academia Arena 2014;6(1) Seismic performance evaluation of steel knee-braced moment frames

NUMERICAL ESTIMATION OF MECHANICAL PROPERTIES OF STRUCTURAL STEEL COMPONENTS AT ELEVATED TEMPERATURES

Study of Load Bearing Capacity of Profiled Steel Sheet Wall Subjected to Combined Bending and Vertical Compression in Electrostatic Precipitator

IJSRD - International Journal for Scientific Research & Development Vol. 5, Issue 06, 2017 ISSN (online):

Optimization of Intumescent Fireproofing Via Structural Analysis. Alex D Tsiolas Fire Engineer

UNIT V PLASTIC ANALYSIS

EXPERIMENTAL BEHAVIOUR OF A STEEL STRUCTURE UNDER NATURAL FIRE

Introduction to Statically

Modelling of shrinkage induced curvature of cracked concrete beams

CHAPTER 4 STRENGTH AND STIFFNESS PREDICTIONS OF COMPOSITE SLABS BY FINITE ELEMENT MODEL

Comparison of Chevron and Suspended Zipper Braced Steel Frames

Transcription:

MATEC Web of Conferences 35, 17 ( 215) DOI: 1.151/ matecconf/ 215351 7 C Owned by the authors, published by EDP Sciences, 215 Mechanical response of local rapid cooling by spray water on constrained steel frame structure at high temperature in fire 1 Yunchun XIA 1,a School of Civil Engineering, Anhui Jianzhu University, Hefei, 2322, P.R. China Abstract. Locally rapid cooling of spray water had strong impact on high temperature steel structure. When temperature of beam reached 6 and cooling rate was more than 2 /s, the maximum axial tension could reach more than 5 times of the originally compressive force. The compressive bending moment at joint of beam-to-column changed to tensile bending moment, and the maximum bending moment could reach above 4 times as that when heated. After rapid cooling by spray water, deflection at mid-span increased slightly. 1 Introduction Steel structure had many advantages, such as high strength, light weight, good toughness, convenience in construction, so it was widely used for various constructions. However, although steel was not burning, it was poor of fire prevention. In absence of fire protection, steel structure building was extremely vulnerable to be damaged or even collapsed in fire. To effectively prevent steel structure from damage, the major method was local spray water cooling or protective coating [1-2,5-12]. When rapidly cooled by local spray water, A large thermal stress would produced because of large temperature difference and stress concentration would happened in the region of structural break, that would produced a strong impact on the stability for the structure. Therefore, when a high temperature steel structure was cooled by the wrong fire fighting water, it had not only no protection for the building, but also a strong destructive impact on the building, sometimes it might also cause stress-strain to increase rapidly, and it might lead to the building to collapse in short time. 2.1 Modelling Fire happened in the middle bottom of room in the middle span. The dimension of steel frame structure was shown in Fig.1. The constraint and loading and water cooling method of the frame were shown in Fig.2. 3 3 6 6 6 spray water ( a ) Dimension of frame 12 2 8 2 ( b ) Section of column 9 6. 5 1 5 3 ( c ) Section of beam Fig.1. Calculation model of steel frame 2. Mechanical Modelling The temperature field of fire and thermal property of component would change when cooled by spray water. Therefore, temperature field inside of component was nonlinear transient temperature field. To simplify mechanical and thermal analysis, this based on the following assumptions: (1) The temperature field along the length of the member is unchanged.(2) Both the element local buckling and plane deformation were omitted.(3) The influence of component stress field on the temperature field was omitted.(4) (4) The component section met the assumption of plane section. 2.2 Physical Parameters x Fig.2. Constraint and loading a Corresponding author: author@e-mail.org This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4., which permits distribution, and reproduction in any medium, provided the original work is properly cited. Article available at http://www.matec-conferences.org or http://dx.doi.org/1.151/matecconf/2153517

MATEC Web of Conferences The chosen steel was Q235 H-type, its physical parameters would change at high temperature. The main physical parameters at different temperature were shown in table 1. Table 1. Physical parameters of steel at different temperature Physica Parameter Temperature [ ] 25 1 2 3 4 5 6 7 K 53.3 5 47.4 44.1 4.7 37.4 34. 31.1 (c)3s Cp 469 482 482.8 52.6 515.2 536.3 565.7 63.6 ET/E 1. 1..92.81.712.65.311.132 ST/S 1. 1..88.615.421.361.182.75 Physical Parameter Temperature [ ] 25 1 2 3 4 5 6 7 K 53.3 5 47.4 44.1 4.7 37.4 34. 31.1 Cp 469 482 482.8 52.6 515.2 536.3 565.7 63.6 ET/E 1. 1..92.81.712.65.311.132 ST/S 1. 1..88.615.421.361.182.75 (d)4s Fig.3. The temperature distribution at fire span at different time *K was the thermal conductivity [W/(m. )]. Cp was specific heat [J/(kg. )]. ET/E was the reduction factor of elastic modulus, ST/S was the reduction factor of relative strength. At High temperature, Poisson's ratio of structural steel was stable, the influence of temperature on it was very small. Here, ν =.3. Thermal expansion coefficient α s=1.41 1-5m/(m. ), steel density ρ =785kg/m3. At ambient temperature, the yield stress fy=278n/mm2, its elastic modulus E = 2.12 15 N/mm2. (a)1s 3 Results and Analysis Steel frame was fixed by high strength bolts at bottom end, the whole steel frame was heating up according to practical fire (it was similar to the HC standard fire curve). After heating up to 6, it was cooled by spray water. When the cooling rate was 15 /s, the temperature distribution was shown in Fig.3. When water was sprayed until beam and column failed, Mises stress of the structure was shown in Fig.4. (b)2s (c)3s (a)1s (d)4s Fig.4. Mises stress nephograms of beam and column until failed (b)2s As shown from Fig.3 to Fig.4, after high temperature steel frame was acted by spray water, its local temperature rapidly decreased, deflection at mid span of fire span increased rather than decreased, but its increase rate was limited, it had the hysteresis at beginning of 17-p.2

ICMCE 215 cooling. At joint of beam-to-column, the deformation was small. However, according to Mises stress nephogram, stress increased at joints of beam-to-column, and the high stress area also increased. That was the essential difference between rapid cooling and slow cooling. As shown in Fig.5 and Fig.6, after rapidly cooled by spray water, the deflection at mid span increased at first, and the higher the temperature of structure was, the larger the final variation of deflection at mid span was. But for column, the maximum lateral displacement gradually increased at the beginning of cooling, and the higher the temperature of structure was, the faster of the maximum lateral displacement increased, its change was also larger. After cooling for some time, the maximum lateral displacement of column slowly decreased, but it was still larger than that at beginning of cooling after it was cooled near ambient temperature. Deflection / mm Max lateral displacement / cm 2 3 4-2 5-4 6-6 7-8 8-1 1 2 3 4 Fig.5. Deflection at mid-span - 5-1 - 1 5-2 1 2 3 4 5 6 7 8 9 2 3 4 Fig.6. Max lateral displacement of bean After the whole steel structure was heated up to different temperature, and then it was cooled by spray water. When cooling rate was 5 /s, 1 /s and 2 /s respectively, the changes of axial forces of beam were shown in Fig.7. 6 3-3 1 2 3 (a) Cooling from 3 1 / s 2 / s 4 1 5-5 1 5 1 5-5 3 1 5-1 5 1 2 3 (b) Cooling from 5 1 1 / s 2 / s 2 1 / s 2 / s 3 (c) Cooling from 7 1 1 / s 2 / s 2 3 (d) Cooling from 9 Fig.7. Axial forces of beam at mid-span at different cooling rate According to Fig.7, during rapid cooling, the stress at cooling area quickly changed from compressive stress to tensile stress, and after cooled for some time, the maximum tensile stress was far larger than the maximum compressive stress produced during heating, and the maximum tensile stress increased with the increase of cooling rate. Moreover, the maximum axial tensile force increased with the increases of cooling rate and temperature of beam, especially the temperature of beam was above 6, the maximum axial stress reached more than 5 times of the original compressive stress when cooling rate was at 2 /s, the force inside of beam main was thermal stress. Therefore, the joints of beam-tocolumn could cause the joints to be destructed quickly. After the whole structure was heated up to different temperatures and the cooling rate was 5 /s, 1 /s and 2 /s respectively, the changes of bending moment at joints of beam-to-column were shown in Fig.8. 4 4 4 17-p.3

MATEC Web of Conferences Bending moment / kn m Bending moment / k N m Bending moment / k N m Bending moment / kn.m 1 5-5 2 1 4 3 2 1-1 8 6 4 2-2 1 1 / s 2 / s 2 3 (a) Cooling from 3 1 1 / s 2 / s 2 3 (b) Cooling from 5 1 1 / s 2 / s 2 3 (c) Cooling from 7 1 1 / s 2 / s 2 3 (d) Cooling from 9 4 4 4 Fig.8. Bending moment at the joint of beam to column Seen from Fig.8, when rapidly cooled by spray water, the bending moment at joints of beam-to-column rapidly decreased until zero, and then it changed from compressive bending moment to tensile bending moment and rapidly increased to the maximum, and the max tensile bending moment increased with the increase of cooling rate, and then it reduced. When temperature of beam was over 6 and cooling rate was 2 /s, the maximum tensile bending moment could reached above 4 times the original maximum compressive moment within just 1 minute, while the deformations of beam and 4 column did not recover, it might lead to the instability for whole structural or collapsed. Therefore, the impact produced by rapid cooling of spray water was much larger than that of heating for high temperature steel structure buildings. 4 Summary Rapid cooling of spray water had a huge impact on high temperature steel structure buildings, and the impact produced by rapid cooling of spray water was much larger than that of heating. When rapid cooled by water spray, very high level of axial force would produced inside of beam, the axial force and bending moment decreased until zero at first, and then they increased from zero and they quickly reached the maximum, the axial force increased with the increase of cooling rate, and the max axial force was much larger than that produced by heating, and it also changed from compressive force to tensile force. When the temperature of beam was over 6 and cooling rate was above 2 /s, the maximum axial tensile force could reach above 5 times the compressive force by heating. Moreover, the bending moment also increased with the increase of cooling rate, and the max bending moment also increased with the increase of cooling rate, too. When the temperature of beam was over 6 and cooling rate was above 2 /s, the maximum tensile bending moment could achieve more than 4 times that of the maximum compressive moment produced by heating. The deflection of beam at mid-span increased, and it increased with the increase of cooling rate, the maximum lateral displacement of column had a little increase within a period of cooling time, and then it slowly decreased, but it was a slightly larger than that at the end of heating. Acknowledgements The research work was supported by National Natural Science Foundation of China under Grant No. 514782. References 1. C G Bailey, D B Moore, T Lennon, The structural behavior of steel columns during a compartment fire in a multi-storey braced steel frame. Journal of constructional steel research, 55,pp.137-146,1999. 2. Rubert A and Schaumann P., Critical temperatures of steel columns exposed to fire. Fire Safety Journal, 13,pp.39-45,1988. 3. Bing Yao, Hongxue Li, JC Yang, Study on the probability distribution characteristics of actual construction fireproof performance under action of spray water, Journal Fire Science, 13,pp.29-217,24. 4. Leonard Y Cooper, The interaction of an isolated sprinkler spray and a two-layer compartment fire environment, International Journal of Heat and Mass Transfer, 38,pp.1115-1123,1995. 17-p.4

ICMCE 215 5. Purkiss J A, Developments in the fire safety design of structure steelwork, Journal of Constructional Steel Research, 13,pp.149-156,1988. 6. Izzuddin B. A., Song L., An integrated adaptive environment for fire and explosion analysis of steel frames-part II: verification and application, Journal of Construction Research, 58,pp.991-12,2. 7. E-Rimawi J. A., The influence of connection stiffness on the behavior of steel beams in fire, Journal of constructional steel research, 43,pp.l- 12,1997. 8. Bailey C.G et al, The influence of the thermal expansion of beams on the structural behavior of columns in steel-framed structures during a fire, Engineering Structures, 22,pp.755-766,2. 9. Amer G.S.T. and Moor D.B., Full scale testing on composite multi-storey structure, The Structural Engineer, 72,pp.3-41,1994. 1. Wang Y.C. Lenon T. & Moor D.B., The Behavior of Steel Frames Subject to Fire, Journal Construct. Steel Research, 35,pp.291-297,1995. 11. Franssen JM, Cooke GME, Latham DJ., Numerical Simulation of a Full Scale Fire Test on a Loaded Steel Framework, Journal of Constructional Steel Research, 51,pp.1199-1212,1995. 12. Zhao Jincheng, Application of the Direct Interaction Method for Non-Linear Analysis of Steel Frames in Fire, Fire Safety Journal, 33, pp.51-63, 2. 17-p.5