IMPACT STUDY: DETERMINING CORROSION RESISTANCE BY EVALUATING PHYSICAL DAMAGE TO LININGS FOR DUCTILE IRON PIPE. MODIFIED ASTM 2497*

Similar documents
SECTION CERAMIC EPOXY LINING DUCTILE IRON PIPE AND FITTINGS

JERRY REGULA PRODUCT ENGINEER MAY 17, 2016

SECTION [ ] MANUFACTURED METAL BOLLARDS

Hydroblasting Standards

PERFORMANCE OF COATINGS OVER WATERJETTED SURFACES J. PETER AULT, P.E. ELZLY TECHNOLOGY CORPORATION

K-100 SYNTHETIC CRANE HOIST LINE. Retrofitting Procedure REVISION 02 { }

Concrete Surface Preparation

REGIONAL CONSTRUCTION STANDARDS

HEAT-FLEX HI-TEMP 1200 Coating Under Insulation

HYDROJETTING INFORMATION. a six page issue October 1999

A. The CONTRACTOR shall provide pipe coating, complete and in place, in accordance with the Contract Documents.

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section DUCTILE IRON PIPE AND FITTINGS

All definitions are defined according to ANSI/AWWA C

PROTECTO 401 CERAMIC EPOXY LINED DUCTILE IRON PIPE AND FITTINGS 2017 EDITION FOR FORCE MAINS, GRAVITY AND INDUSTRIAL SEWER LINES

NAVSEA Documents. Topics. Scope. Learning Outcome. Relevant Documents. NAVSEA Basic Paint Inspector Training: NAVSEA Documents

. SECTION HANGERS AND SUPPORTS

Qualification testing of Humidur FP Single for approval to APCS-19C, 09-SAMSS-70

PRODUCT DATA SHEET SP-3888

2. A preconstruction meeting with the TWA s staff is required prior to initiating construction.

HDSS HIGH DEFLECTION HIGH PRESSURE RESTRAINED PIPE

IMTECH ADHESIVE SYSTEMS

All definitions are defined according to ANSI/AWWA C b. Flanged Joint: The flanged and bolted joint as described in ANSI/AWWA C110/A21.10.

The Importance of Proper Inspection. Rocky Capehart

1. Temperature Change: 120 deg F (67 deg C), ambient; 180 deg F (100 deg C), material surfaces.

FINAL REPORT: LARGE SCALE ACCELERATED CUI TEST OF E-2000 AND E-1100EG

POLYURETHANE COATINGS ON STEEL OR DUCTILE IRON PIPE

KENT COUNTY WATER AUTHORITY. ERRATUM to Rules and Regulations of the Kent County Water Authority

East Central College

Prepared By: Engineering Staff Approved By: Jerome T. Schmitz

DUCTILE IRON PIPE AND FITTINGS

Property Test/Standard Description. calculated US EPA method 24 (tested) (CARB(SCM)2007, SCAQMD rule 1113, Hong Kong)

Final report. Immersion testing on coated and uncoated panels in ozone treated water. Requester: Desmi Ocean Guard. Attn.: Christian Ingvorsen

SURFACE PREPARATION BEFORE PAINTING

B. Shop Drawings: Include plans, elevations, sections, details, and attachments.

Bharat Heavy Electricals Limited Piping Centre Chennai-17. Specification Number Revision Number Sheet Number PC:E:GF: of 7 CONTENTS

Protective Coatings for Steel and Concrete Bridge Components

Heresite P-413 TECHNICAL DATA SHEET. P-413 Typical Properties 1 mil DFT) Our 50 years of coating history speaks for itself.

SECTION HANGERS AND SUPPORTS PART 1 - GENERAL. A. Drawings and Division 1 Specification Sections, apply to this Section.

Northeast Gas Operation School Thursday June 5 th

SP-100 Equipment Wash SP-110 Tool Cleaner

Elastocoat Protective Coatings APPLICATION GUIDE

Tested in accordance with ISO , high expected durability in corrosivity category C5-I. Property Test/Standard Description

ADDENDUM TO THE CONTRACT. for the. East Valley Reservoir Exterior and Lemon Creek Reservoir Interior Repainting. Contract No.

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

Section FLUSHING HYDRANTS

3M Scotchkote Liquid Epoxy Coating 323+

COATING SPECIFICATION HIGH BUILD EPOXY COATING ON BUTTERFLY VALVES COATING SPECIFICATION: D2 ISSUE: 2 DATE: FEBRUARY 2016

Termarust Technologies HRCSA Corrosion Mitigation System.

Field Performance Evaluation of Polymer Coated CSP Structures in

How Passive Fire Protection (PFP) Works

ASTM B Compliant

Bridge Materials / structural plate. A polymer. Structural Corrugated Steel Bridges and tunnel liner. Economical

PPG HI-TEMP 1000 VS. PRODUCT DATA SHEET December 10, 2014 (Revision of June 30, 2014) DESCRIPTION

Cover Page - Series 60 Wafer Check Valves

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

SECTION High Performance Coatings Field Applied Acrylic Urethanes (Solid Color, Pearl and Metallic Finishes)

One-component, heat-resistant silicone acrylic topcoat primarily for the PPG HI-TEMP 1027 primer or the PPG HI-TEMP 222 G primer

1.4 kg/l (11.4 lb/us gal) Maximum 295 g/kg (Directive 1999/13/EC, SED) Maximum 420 g/l (3.5 lb/gal) 50 to 63 μm (2.0 to 2.

TEST PROCEDURE SUMMARY

ENGINEERED COMPOSITE REPAIR SYSTEM

SECTION 1. AMERICAN Standards

1.4 kg/l (11.4 lb/us gal) Maximum 272 g/kg (Directive 1999/13/EC, SED) Maximum 420 g/l (3.5 lb/gal) To 650 C (1200 F) To 538 C (1000 F)

PIPE AND TUBE RAILINGS. Evansville Christian High School RELATED DOCUMENTS 1.1

PPG HI-TEMP 1000 V (AMERCOAT 873) PRODUCT DATA SHEET December 10, 2014 (Revision of June 30, 2014) DESCRIPTION

SP-100 Equipment Wash SP-110 Tool Cleaner SP-120 Internal Storage Lubricant

Metallurgy and Corrosion for Waste Water Facilities

Binding protection at different levels

Corrosion and batteries

About. l Surface of steel structural is blasted by compressed air pressure. l Additional sealant provides barrier protection to the surface.

East Central College HANSEN HALL LEVEL 300/400 RENOVATIONS CONSTRUCTION PACKAGE

PRODUCT GUIDE: ZINC-RICH COATINGS. Version:

Materials & Processes in Manufacturing

SPECIALTY POLYMER COATINGS, INC.

Chambers Creek, WA Pierce County WWTP Digester #1

Belzona Pioneers Multipurpose Metal Repair System for Oil Contaminated and Wet Surfaces, even Underwater

Daytona Beach Pier Building Renovation Jun 2010

SURFACE PREPARATION FOR SYNTHETIC ROPES

STANDARD NO.: Z0254. ECO 13848: Added revision table and standard format. Minor corrections made through out the document.

Application Guide for Internal Flow Efficiency Coating Jotapipe FC 400

Resimac Ltd. Engineered Polymer Solutions

mcu ferroguard technology description single component moisture cure urethane coating technology features

(800) fax (708) Available From: Allied Tube & Conduit Printed in U.S.A. 7/98 ATC-L

PPG Guide Specification

Property Test/Standard Description. US EPA method 24 (tested) (CARB(SCM)2007, SCAQMD rule 1113, Hong Kong)

The Jotatemp range. The way ahead for the Jotatemp product range

Girth Weld Coating With Fusion Bond Epoxy

Solventless two-component crosslinked epoxy

SECTION 200 SANITARY SEWER MATERIAL SPECIFICATIONS

Airblast Tech Tips Surface Preparation in General

Solventless, two-component, cross-linked epoxy. Epoxies lose gloss, discolour and eventually chalk in sunlight exposure.

Resimac Limited, Unit B, Park Barn Estate, Station Road, Topcliffe, Thirsk, YO7 3SE, North Yorkshire, United Kingdom

BRIDGE CROSSINGS. The Same Old Grind...An Investigation of Zinc-Rich Primer Performance Over Steel Corners. No. 17, June By William D.

High Performance Toughened Vinyl Ester Resins

Property Test/Standard Description. US EPA method 24 (tested) (CARB(SCM)2007, SCAQMD rule 1113, Hong Kong)

CONCRETE STEPS, HANDRAILS, AND SAFETY RAIL

PPG HI-TEMP PRODUCT DATA SHEET April 16, 2018 (Revision of September 5, 2017) DESCRIPTION

New Advancements in the Abrasion Resistance of Internal Plastic Coatings

COATING SPECIFICATION HIGH BUILD CERAMIC FILLED EPOXY COATING ON NEW AND EXISTING PUMPS COATING SPECIFICATION: F3 ISSUE: 1 DATE: 12 DECEMBER 2012

Transcription:

IMPACT STUDY: DETERMINING CORROSION RESISTANCE BY EVALUATING PHYSICAL DAMAGE TO LININGS FOR DUCTILE IRON PIPE. MODIFIED ASTM 2497* The film strength and adhesion properties of linings for ductile iron pipe are directly correlated to the success of protecting the interior pipe wall for the life of the pipe in sewer service. In aggressive sewer service, any exposed areas in the pipe lining caused by pipe deflection, over-homing, or damage during shipping will result in corrosion to the pipe wall. The oxide layer in ductile iron pipe created by the annealing process is a valuable asset when combined with Protecto 401 s ability to prevent undercutting. Protecto 401 achieves an unparalleled level of protection by working in conjunction with the oxide layer. Many linings have been tried in the past that called for a surface prep to fully remove the oxide layer, or in steel surface prep terminology, white blast of the surface (SSPC SP 5, ISO SA 3, NACE 1, etc.). None of these surface prep standards are designed for ductile iron pipe. In fact, as a result the annealing process, the oxide layer of ductile, which has it s own measureable film strength, is integral to the pipe wall and cannot be completely removed in a repeatable manner from pipe to pipe. As a result, linings that do not take the oxide layer into account will fail. Deflection and impact occur from normal shipping, handling, installation, and buried service. If a lining shows undercutting or delamination from impact, the lifting mechanisms of corrosion (with a PSI of 1200-1400lbs) will continue to delaminate the lining and completely expose the interior pipe wall. Exposure of the bare pipe wall will result in corrosion failures in a sewer system over time. In the following study, one each were used of both Protecto 401 lined and Series 431 lined coupons cut out of production run, ductile iron pipe. The panels were all reverse-impacted (struck on the opposite side from the lining) with an impact hammer apparatus designed for a modified version of ASTM 2794. The strikes are intended to deflect the coupon so that the lining is severely compromised with a striking force of 1,344 in/lbs. The test was performed repeatedly on six coupons of each lining. All coupons exhibited the same results reported below. The lining was applied by an applicator approved by each lining manufacturer using the specification for each product. TESTING DATED 10/28/13 IMPACTED PANELS: SIDE-BY-SIDE COMPARISON- SERIES 431 and PROTECTO 401 Ceramic Epoxy COUPONS CUT FROM PRODUCTION-RUN DUCTILE IRON PIPE SERIES 431 (GREEN) PROTECTO 401 (BLACK)

IMPACTED PANELS: SIDE-BY-SIDE COMPARISON TOP LEFT PANEL: IMPACTED SERIES 431- EXPOSED METAL- OXIDE LAYER IS BROKEN AND NO FILM IS LEFT ON THE SURFACE BOTTOM RIGHT PANEL: IMPACTED PROTECTO 401- PROTECTIVE FILM LEFT ON THE SURFACE

IMPACTED PANELS: UNDERCUTTING RESISTANCE PROTECTO 401 : ZERO UNDERCUTTING AFTER IMPACT. LINING IS LEFT ON SURFACE- CORROSION CANNOT LIFT THE LINING. SERIES 431: UNDERCUTTING AND DELAMINATION FROM BROKEN OXIDE LAYER AFTER IMPACT. CORROSION WILL LIFT THE LINING AND CONTINUE TO DELAMINATE FURTHER.

IMPACTED PANELS: OXIDE LAYER DAMAGE RESULTS SERIES 431 PANEL: EXPOSED PIPE WALL (ABOVE). SERIES 431 PANEL: BROKEN METAL OXIDE ON THE BACK SIDE OF THE GREEN DELAMINATED CHIP.

SERIES 431 POST IMPACT: DELAMINATED CHIP ON THE LEFT, EXPOSED PIPE SURFACE ON THE RIGHT. NOTICE THE DELAMINATED CHIP ON THE LEFT HAS BROKEN THE METAL OXIDE ON THE INTERIOR OF THE PIPE. THE METAL IS CLEARLY VISIBLE ON THE BACK OF THE DELAMINATED CHIP. PROTECTO 401 POST IMPACT: PROTECTO 401 PANEL: WORKING WITH THE OXIDE LAYER- LINING REMAINS ON THE SURFACE PROTECTING THE IMPACTED AREA.

IMPACTED PROTECTO 401 : THE METAL SURFACE IS NOT EXPOSED. PROTECTO FILM (AND THE OXIDE LAYER) REMAINS ON THE SURFACE OF THE PIPE INTERIOR. PIPE SURFACE IS PROTECTED. EXPLANATION OF MODIFIED ASTM 2794 STANDARD TEST METHOD FOR RESISTANCE OF ORGANIC COATINGS TO THE EFFECTS OF RAPID DEFORMATION There are several parameters of the ASTM 2794 that must be modified to test linings for reverse impact on production-run Ductile Iron Pipe samples: 1. Section 4.1 calls for thin steel panels for the test. Linings on steel will not react like they do on DI Pipe samples due to the difference in oxide layers. 2. Section 6.1.1 calls for the tube housing to be 24 to 48. The tube used in this impact apparatus is 64 due to the force required for deformation of the ductile iron coupons. 3. A 24lb weight is used in the apparatus falling from 56 to achieve the required force necessary for deformation. 4. The ductile iron pipe coupons used were from production run pressure class 350 8 pipe.