Dynamic Compensation of Reactive Power for Integration of Wind Power in a Weak Distribution Network

Similar documents
SYNOPSIS OF THE THESIS. Enhanced Power Quality Management of Grid Connected Wind Farm

International Journal of Advance Engineering and Research Development

Fault Current Contributions from Wind Plants Dean Miller PacifiCorp July 25, 2012

Comparative Analysis between IG and DFIG for Wind Energy Conversion Systems using STATCOM

Investigation of Impacts of Solar PV on Transmission System Voltage Stability Considering Load Characteristics and Protection

ISSN Vol.07,Issue.16, November-2015, Pages:

Wind Energy Conversion Using Shunt Active Power Filter

CENTRE FOR WIND ENERGY TECHNOLOGY CHENNAI INDIAN WIND GRID CODE

Daniel Feltes Phone: Fax:

What makes a Wind Plant Grid Friendly?

Wind Farms in Weak Grids Compensated with STATCOM

Analysis of Wind Power Integration for Power System Transient Stability

Dynamic Behaviour of Large Scale Wind Farm

Low SCR Wind Identification and Mitigation. Will Lovelace MIPSYCON 2015 November 11 th, 2015

Steady-state and transient voltage stability analysis of a weak distribution system with a remote doubly fed induction generator-based wind farm

Wind Farm Performance on the Grid: Perception and Reality

ISSN Vol.09,Issue.04, March-2017, Pages:

All Rights 1

Power Quality Improvement in Distribution System Using Distribution Static Compensator

Voltage Stability Assessment of a Power System Incorporating Wind Turbine Using Power System Analysis Toolbox (Psat)

Capacity and Location Effects of Wind Turbine Energy Systems on Power Systems Stability

Coordination of Multiple Voltage Controllers of Adjacent Wind Plants Connected to João Câmara II with Droop Function

Power Quality and Voltage Stability of Power Systems with a large share of Distributed Energy Resources

POWER QUALITY ASPECTS IN A WIND POWER PLANT IMAMHUSEN M PATIL. MASTER OF TECHNOLOGY IN ELECTRICAL ENGINEERING (Computer Controlled Industrial Power)

WIND TURBINES IN WEAK GRIDS CONSTRAINTS AND SOLUTIONS. J O G Tande and K Uhlen. SINTEF Energy Research, Norway SUMMARY

California Independent System Operator Renewable Integration Study

Principles of modeling large wind parks

Comparative Analysis of Wind Energy Conversion System using DFIG and IG

Power Quality Assessment of Large Motor Starting and Loading for the Integrated Steel-Making Cogeneration Facility

Generation Application Part B: Technical Form

Refinement of Hydel power by implementing FACTS at Narangwal hydroelectric power plant

Technical and economical analysis of the wind turbines interconnection with the windfarm substation

Voltage Disturbances Improvement of Gird-Connected Wind Turbines in Distribution System Using STATCOM at Weak-Grid Connection Point

Technical considerations for integration of distributed renewables on the grid

Large-scale Wind Power Integration and Voltage Stability Limits in Regional Networks

BASIC CONCEPTS. Yahia Baghzouz Electrical & Computer Engineering Department

A New Connection Concept to Connect an Offshore Wind Park to an Onshore Grid

Control of a Microgrid in Islanded Mode

J. Electrical Systems 10-2 (2014): Regular paper

Lesson Learned Loss of Wind Turbines due to Transient Voltage Disturbances on the Bulk Transmission System

Strathprints Institutional Repository

Renewable Energy in Power Systems

MEASUREMENTS AND SIMULATION FOR POWER QUALITY OF A WIND FARM

AGGREGATED MODELLING ANALYSIS OF POWER FLOW FROM WIND POWER PLANT INTO GRID SYSTEM USING MATLAB/ SIMULINK SOFTWARE

Wind turbine model validation with measurements

ADVANCES in NATURAL and APPLIED SCIENCES

ANALYSIS OF THE BEHAVIOR FOR REACTIVE POWER COMPENSATION USING SVC CONTROLLED HYBRID SOLAR/WIND POWER GENERATING SYSTEMS

Optimization of Power Factor and Energy Management in Wind Energy Station

DISTRIBUTED GENERATION AND POWER QUALITY

ENABLING FREQUENCY AND VOLTAGE REGULATION IN MICROGRIDS USING WIND POWER PLANTS

Mitigation of Voltage Fluctuations in Power System Using STATCOM

GOLDEN VALLEY ELECTRIC ASSOCIATION

Effects of Unbalanced Faults on Transient Stability of Cogeneration System

Grid Tied RES Source Control Technique to mitigate harmonic and Reactive Power Compensation by using UPQC.

The Effect of the Volt/Var Control of Photovoltaic Systems on the Time-Series Steady-State Analysis of a Distribution Network

VOLTAGE STABILITY LIMITS FOR WEAK POWER SYSTEMS WITH HIGH WIND PENETRATION ALA TAMIMI AN ABSTRACT OF A DISSERTATION

WIND TURBINE PLANT CAPABILITIES REPORT

Economic Selection of Generators for a Wind Farm

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

A. Behaviour of the Wind

Seminar on African Electrical Interconnection. Module 8 - Interconnected Systems Operating Conditions

STATCOM for Improved Dynamic Performance of Wind Farms in Power Grid

UNOFFICIAL TRANSLATION SUPPLY OF REACTIVE POWER AND MAINTENANCE OF REACTIVE POWER RESERVES

Dynamic Reactive Power issue in Wind Integrated Power Systems and LVRT Compliance of WPPs

ENERCON. Wind Farms with Power Plant Capabilities. Tokyo, October 27 th Werner Bohlen / Eckard Quitmann

Load Frequency Control for Hybrid Microgrid using Battery Storage System

Adjoint wind turbine modeling with ADAMS, Simulink and PSCAD/EMTDC

Power Flow Control Scheme for Wind Energy Conversion System

Impact of Different Types of Wind Turbines Generators on Voltage Sag

Connection Study Requirements

Electric Power Systems An Overview

ISSN Vol.03,Issue.06, August-2015, Pages:

Operating High Variable, Renewable Generation Power Systems Lessons Learned from Ireland and Northern Ireland

EFFECT OF WIND SPEED VARIATIONS ON WIND GENERATOR OUTPUT IN TROPICAL CLIMATE WEATHER CONDITION

LARGE WIND FARM AGGREGATION AND MODEL VALIDATION MULUMBA PROSPER PANUMPABI THESIS

Investigation of Wind Farm Interaction with Ethiopian Electric Power Corporation s Grid

Optimal Location of Star and Delta connected Capacitor Bank for Loss Minimization in a Five Bus Power System

Modeling of Wind Power Plant with Doubly-Fed Induction Generator

Hydro-Quebec s experience with HYPERSIM Real-time Power System Simulator

POWER QUALITY IMPROVEMENT OF A GRID CONNECTED WIND ENERGY SYSTEM USING STATCOM-CONTROL

Enhancement of power quality of Grid connected wind energy system using STATCOM

BPA Wind Voltage Control Requirements

Power quality improvement by using STATCOM control scheme in wind energy generation interface to grid

Impact of Wind Integration on National Transmission Network

Connection of generation plant to distribution networks. Guidance on completing the application form

Emerging ancillary service products in large-scale renewable energy integrated system

Harnessing Renewables in Power System Restoration

A REVIEW ON POWER CONTROL SYSTEM INVERTERS WITH VARIATION POWER SYSTEM

Analysis of System Stability in Developing and Emerging Countries

Cascaded Two-Level Inverter-Based Multilevel STATCOM for High-Power Applications with Comparisions of DFIG and SCIG

Impacts of the Decentralized Wind Energy Resources on the Grid

Performance of a Wind-Diesel Hybrid Power System with STATCOM as a Reactive Power Compensator

Dynamic analysis of renewable energy systems and their impact on smart grid

ReliabilityFirst Regional Criteria 1. Verification and Data Reporting of Generator Gross and Net Reactive Power Capability

Department of Electrical Engineering. Industrial Visit Report. Sardar Sarovar Narmada Nigam Limited Hydro Electric Power Station

Electric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas

Modeling and Operation Analysis of Meshed Distribution Systems with Distributed Generation

WIND ENERGY GENERATION

Optimal Location and Sizing of DG using Fuzzy logic

Fault Current Limiters for the Smart Grid

Transcription:

INTERNTIONL ONFERENE ON ONTROL, UTOMTION, OMMUNITION ND ENERGY ONSERVTION -2009, 4th-6 th June 2009 Dynamic ompensation of Reactive Power for Integration of Wind Power in a Weak Distribution Network 1 S. M. Shinde, K. D. Patil, and W. Z. Gandhare bstract s a promising renewable alternative, the wind power is highly expected to contribute a significant part of generation in power systems in the future, but this also bring new integration related power quality issues, which mainly consist of voltage regulation and reactive power compensation. Wind power, as a rule, does not contribute to voltage regulation in the system. Induction machines are mostly used as generators in wind power based generations. Induction generators draw reactive power from the system to which they are connected. Therefore, the integration of wind power to power system networks; especially a weak distribution networks is one of the main concerns of the power system engineers. Voltage control and reactive power compensation in a weak distribution networks for integration of wind power represent main concern of this paper. The problem is viewed from MTL/Simulink simulation of weak distribution network and wind power integration in this network. Without reactive power compensation, the integration of wind power in a network causes voltage collapse in the system and under-voltage tripping of wind power generators. For dynamic reactive power compensation, when, STTOM (Static Synchronous ompensator) is a used at a point of interconnection of wind farm and the network; the system absorbs the generated wind power while maintaining its voltage level. Index Terms Induction generators, Non-linear dynamic simulation, Reactive power compensation, STTOM, Voltage regulation. 1 INTRODUTION O VER recent years there has been a continuous increase in installed wind power generation capacity throughout the world. In fact, the grid connected wind capacity is undergoing the fastest rate of growth of any form of electricity generation. Fig.1 shows the global annual installed capacity growth from 1996 to 2008 [1]. Fig.2 shows year wise installed capacity (MW) in INDI. t the end of 2008, the total wind power installed capacity in India has gone to 8697.925 MW. The Indian Wind Turbine Manufacturers ssociation (IWTM) estimates the potential to be of the order of 65,000 MW [2]. Recently, Government of India has de-regularized the power sector. Ministry of New and Renewable Energy (MNRE) has issued guidelines to all state governments to create an attractive environment for the export, purchase, wheeling and banking of electricity generated by wind power projects. Hence, sustainable growth of wind power generation is expected in the years to come. This growth of wind power generation is likely to influence the operation and planning of the existing power system networks. ecause integration of wind power in a power systems presents problem of voltage regulation and reactive power compensation [3]. The wind turbines are composed of an aerodynamic rotor, a mechanical transmission system, squirrel cage induction generator, a control system, limited reactive power compensation and a step-up transformer. The conventional wind turbine is even at the present time, the most common type of wind turbine installed. S. M. Shinde is with the Department of Electrical Engineering, Government ollege of Engineering, urangabad (India). E-mail:sanjayshind@ gmail.com K. D. Patil is with the Department of Electical Engineering, Government Polytechnic, Dhule (India). E-mail: kesharsingp@rediffmail.com. Prof. W. Z. Gandhare is the Principal of Government ollege of Engineering, urangabad (India). E-mail: wz_gandhare@yahoo.co.in Therefore, this paper deals about such conventional squirrel cage induction generator system. n important operating characteristic of the squirrel cage induction generator is that this type of Fig. 1. Global annual installed capacity growth from 1996 to 2008 Fig. 2. Yearwise installed capacity (MW) in India Manuscript received: 21 st February 2009

2 generator always consumes reactive power, which is undesirable for the transmission system. Particularly in the case of large turbines and weak distribution system. nother characteristic of the squirrel cage induction generators is that, in general, this type of generator tends to slow down voltage restoration after a voltage collapse and this can lead to voltage and rotor speed instability. When the voltage restores, the generator will consume reactive power, impeding the voltage restoration. When the voltage does not return quickly enough, the generator continues to accelerate and consumes even larger amount of reactive power [4]. This process eventually leads to voltage and rotor speed instability if the wind turbine is connected to a weak system. To prevent these types of instabilities; conventionally, shunt capacitor banks are connected at the generator terminals to compensate its reactive power consumption. To minimize the reactive power exchange between wind farms and distribution network, dynamic compensation of reactive power can be employed [5]. Power electronics based FTS devices such as SV and STTOM are useful for dynamic compensation of reactive power. The STTOM performs the same function as the SV. However at voltages lower than the normal voltage regulation range, the STTOM can generate more reactive power than the SV. This is due to the fact that the maximum capacitive power generated by a SV is proportional to the square of the system voltage (constant susceptance) while the maximum capacitive power generated by a STTOM decreases linearly with voltage (constant current). This ability to provide more capacitive reactive power during voltage collapse is one important advantage of the STTOM over the SV. In addition, the STTOM will normally exhibit a faster response than the SV because with the VS, the STTOM has no delay associated with the thyristor firing [6]. In his paper the reactive power compensation capability of STTOM for wind power integration into a weak distribution network is evaluated. The study is based on the three phase non-linear dynamic simulation, utilizing the Simpowersystem blockset for the use with MTL/Simulink [6]. 2 TEST SYSTEM The single line diagram of a test system employed in this study is shown in Fig.3. The network consists of a 132 kv, 50 Hz, grid supply point, feeding a 33 kv distribution system through 132/33 kv, 62.5 MV step down transformer. There are two loads in the system; one load of 50 MW, 0.9 pf (lag) and another load of 6 MW, 0.9 pf (lag) at 50 km from the transformer. The 33 kv, 50 km long line is modeled as line. 9 MW wind farm consisting of six 1.5 MW wind turbines is to be connected to the 33 kv distribution network at 6 MW load point. The total MV loading on the system is 62.22 MV; considering the T & D losses in the system it is over loaded; thus, truly, representing Fig. 3. Single line diagram of a test system weak distribution network. Dynamic compensation of reactive power is provided by a STTOM located at the point of wind farm connection. The 9 MW wind farm have conventional wind turbine systems consisting of squirrel-cage induction generators and variable pitch wind turbines. In order to limit the generator output power at its nominal value, the pitch angle is controlled for winds exceeding the nominal speed of 9 m/s [4]. Each wind turbine has a protection system monitoring voltage, current and machine speed. 3 SIMULTION OF TEST SYSTEM Distribution systems are inherently unbalanced in most of the cases due to the asymmetrical line spacing and imbalance of consumer load. In view of this, single phase models can not be used for accurate studies on the operation of distribution systems [4]. Therefore in this work all network components are represented by the three phase models. Test system is simulated in MTL/Simulink. Fig.4. shows the Simulink model of the test system. Phasor simulation is used to simulate the test system; so as to make it valid for intended purpose. Variable-step ode23tb solver is used for simulation. The simulation time is 20 sec. The simulation is run in four different modes, as follows i. Without wind farm and STTOM, ii. With wind farm and without STTOM, iii. With wind farm and STTOM (without fault), iv. With wind farm and STTOM (with fault). In each case the pu voltage, active and reactive power at 33 kv bus - 1 and bus 2, active and reactive power at load -1 and load - 2 and active and reactive at the wind farm are measured. When the STTOM is connected to the system reactive power supplied by the STTOM is also measured. For all the measurements, base power taken as 50 MV and base voltage is 33 kv. Suitable sign convention is followed for measurement and subsequent analysis of active and reactive power at the buses as well as at the load points. The same quantities at different locations are muxed to multiplex the signals [7] for respective measurement.

3 Phasors pow ergui _1 33kV us_1 Three Phase Fault _2 33kV us_2 c a a b c a b b m m c c c Grid Supply Point 132 kv 132 kv / 33 kv 62.5 MV 50 km Line a b a b 0 9 MW Wind Form No trip 1 Trip Manual Switch Trip Load_1 50 MW, 0.9 pf (lag) Load_2 6 MW, 0.9 pf (lag) STTOM m mstatcom Data acquisition V(pu)_1_2 9 MW Wind Farm Data acquisition V_pu P1_3 (MW) P_1_L1_L2_2 Q_1_L1_L2_2_STT P_MW Q1_3 (Mvar) P1_3_MW Dynamic ompensation of Reactive Power For Integration of Wind Power in a Weak Distribution Network Q_Mvar Q1_3_Mvar Fig. 4. The Simulink model of the test system 4 SIMULTION RESULTS 4.1 Without wind farm and STTOM In this mode the wind farm and STTOM were skipped while running the simulation. Only the distribution system and two loads were kept in the model. The purpose of running the simulation in this mode is to ascertain that, the test system is a weak system. Thus, in this mode only voltages at 33 kv us 1 and us 2 are measured. Fig. 5 shows the voltages at 33 kv us 1 and us 2. From this Fig. it seen that the voltage at 33 kv us 1 is below 0.94 pu. Where as the voltage at 33 kv Fig. 6. ctive power supplied by wind turbine generators Fig. 5. Voltages at 33 kv us 1 and us 2 us 2 is 0.9 pu. s these voltages are below 0.95 pu the distribution network taken for this study is really weak. Fig. 7. Reactive power drawn by induction generators 4.2 With wind farm and without STTOM In this mode of simulation the wind farm is connected to the weak distribution network in above mode. The purpose of running simulation in this mode is to try integration of 9 MW wind power in weak distribution network, without dynamic compensation of reactive power i.e. without using the STTOM. Fig.6 shows active power supplied by wind turbine generators to the distribution network. From Fig. it seen that the wind turbine generators are tripped one by one. First set number-2, then set number-3 and finally set number-1 is tripped. The cascade tripping of wind power generators is due under voltage at 33 kv us 2. This shows that as such, the wind power can not be integrated in a weak distribution network. This is due to fact that, weak network is not capable of supplying reactive power demanded by induction generators [8]. Fig.7 shows the reactive power

4 drawn by induction generators from the network before tripping. The active power at various points in the network is shown in Fig.8. From this Fig. it is seen that, before the tripping the wind turbines have supplied active power to the network. 4.3 With wind farm and STTOM (without fault) In this mode of simulation the wind farm with dynamic compensation by STTOM is connected to the weak distribution network in above mode. The purpose of running simulation in this mode is to integrate 9 MW wind power in weak distribution network, with dynamic compensation of reactive power using the STTOM. Fig.11 shows active power supplied by wind turbine generators to the distribution network. From Fig. it seen that, in this case the wind turbine generators are not tripped. ut they are supplying (3 x 3) MW power to the distribution network. Fig.12 shows the reactive power drawn by induction generators from the network. From Fig. it is seen that initially wind turbine generators draw more reactive Fig. 8. ctive power at various points in the network The reactive power at various points in the network is shown Fig.9. From this figure it is seen that, before tripping the wind turbine generators have drawn reactive power from the network. s a result the voltage at 33 kv us 2 as well as us 1 is decreasing, thereby causing under voltage tripping of wind turbine generators. Fig.10 shows the voltages at 33 kv us 1 and 33 kv us 2. Fig. 12. Reactive power drawn by induction generators Fig. 9. Reactive power at various points in the network Fig. 13. ctive power at various points in the network power, but later on the reactive power demand is stabilized at (1.5 x 3 ) Mvar. The active power at various points in the network is shown in Fig.13. The reactive power at various points in the network is shown in Fig.14. From Fig. it is seen that, the STTOM is supplying 3 Mvar reactive power to the network. This is to meet the reactive power demand of the wind turbine generators, while maintaining the system voltage. Fig. 10. Voltages at 33 kv us -1 and us 2 Fig. 11. ctive power supplied by wind turbine generators Fig. 14. Reactive power at various points in the network

5 Fig.15 shows the voltages at 33 kv us 1 and 33 kv us 2. From Fig. it is seen that initially the voltage at us 2 is less than that at us 1, but due to reactive power injection by STTOM the voltage at us 2 goes beyond voltage at us 1. The reactive power at various points in the network is shown in Fig.19. From Fig. it is seen that, the STTOM is supplying reactive power to the network even in the event of short duration fault at its point of interconnection. Fig. 15 Voltages at 33 kv us -1 and us 2 Fig. 18. ctive power at various points in the network 4.4 With wind farm and STTOM (with fault) This mode is same as above mode of simulation, but in this case a three phase fault for 2 cycles i.e. 0.04 sec is made at 33 kv us 2. The fault is initiated after 5 sec from starting of the simulation. The purpose of running simulation in this mode is to verify the dynamic reactive power compensation capability of STTOM during the event of fault, while integrating wind power in a weak distribution network. Fig. 19. Reactive power at various points in the network Fig. 16. ctive power supplied by wind generators Fig.16 shows active power supplied by wind turbine generators to the distribution network. From fig. it seen that, in this case also the wind turbine generators are not tripped. ut they are supplying (3 x 3) MW power to the distribution network. Fig.17 shows the reactive power drawn by induction generators from the network. Fig. 20. Voltages at 33 kv us -1 and us 2 Fig.20. shows the voltages at 33 kv us 1 and 33 kv us 2. From Fig. it is seen that the voltage recovery after the fault is accelerated due to STTOM and the system voltage restores before the initiation of protection systems. Thus the wind turbine generators do not trip even in the event of short duration fault. Fig. 17. Reactive power drawn by induction generators The active power at various points in the network is shown in Fig.18. 5 ONLUSIONS This paper presented an evaluation study about the dynamic power compensation capability of STT- OM for the integration of wind power in a weak distribution network. The dynamic power compensation capability of STTOM is also evaluated during an external three phase fault. The study reveals that, reactive power

6 compensation by STTOM makes it possible the integration of wind farm in a weak distribution network. STTOM prevents large deviations of bus voltage due to reactive power drawn by wind turbine generators and also after fault the rapid recovery of voltage is resulted. KNOWLEDGEMENT This work was performed at The Government ollege of Engineering, urangabad (India). uthor gratefully acknowledges the kind permission, advices and contributions of Prof. Dr. W. Z. Gandhare (Principal) and Prof. Ms. rchana Thosar (ssistant Professor and Head of the Electrical Engineering Department). REFERENES [1] Global Wind Energy ouncil (GWE) US and hina in Race to the Top of Global Wind Industry News dated 02/02/2009, nnx. Tables and Graphs (online) available www.gwec.net [2] Ministry of New and Renewable Energy (MNRE), Govt. of India, official website: www.mnes.nic.in [3] Rolf Grünbaum, Voltage nd Power Quality ontrol In Wind Power pplications Means of Dynamic ompensation Power Systems, Power Division Vasteras, Sweden. [4] Sidhartha Panda and N.P.Padhy, Power Electronics ased FTS ontroller for Stability Improvement of a Wind Energy Embedded Distribution System, International Journal of Electronics, ircuits and Systems Volume 1 Number 1 [5] S. Kahrobaee, S. fshania, V. Salehipoor (University of Tehran), Reasonable Reactive Power ontrol and Voltage ompensation for Wind Farms Using FTS Devices, Nordic Wind Power onference 22 23 May 2006, ESPOO, Finland. [6] Hydro-Quebec, SimPowerSystems TM 5 User Guide October 2008, (online) available: www.mathworks.com [7] Simulink 7 User Guide October 2008, (online) available: www.mathworks.com [8] hmed Maria, Mauro Facca & John Diaz De Leon IESO Philosophy On Reactive Power ompensation North merican WINDPOWER June 2007 issue [9] www.mathworks.com