The Initial Assessment of Earthquake Prone Buildings: A Wairarapa Experience

Similar documents
Damage ratios for brick buildings in the 1942 Wairarapa earthquake

MASTERTON DISTRICT COUNCIL EARTHQUAKE PRONE BUILDINGS POLICY

Christchurch City Council. PRK_3575_BLDG_001 Port Levy Fire Shed Detailed Engineering Evaulation Report

Animal Control Administration Team Dog Pound Portacom Detailed Engineering Evaluation BU EQ2 Qualitative Report

Luggate Hall Initial Seismic Assessment. 51 Main Road Luggate. Luggate Hall ISA March

Christchurch City Council

EARTHQUAKE PRONE BUILDINGS POLICY

Mayor and Councillors. Community Services Manager

Detailed Assessment of St. Patrick Church, Paraparaumu, NZ. 09 January 2013 MIL Phase 05

Guidance for Territorial Authorities and Property Owners on Initial Seismic Assessments. New Zealand Society for Earthquake Engineering

Jura Courts Housing Complex PRO 0840 Detailed Engineering Evaluation Quantitative Assessment Report

Guidance for Territorial Authorities and Property Owners on Initial Seismic Assessments

Detailed Engineering Evaluation. Quantitative Assessment Report Buller X-Ray Building

INITIAL SEISMIC ASSESSMENT REPORT (ISA PLUS) 50 Tay Street, Invercargill

Sockburn Depot North East End Store BU EQ2 Detailed Engineering Evaluation Quantitative Assessment Report CHRISTCHURCH CITY COUNCIL

Toilet Rimu Park PRK 1645 BLDG 001 Detailed Engineering Evaluation Qualitative Report Version Final. Buchanans Rd

Hagley Park North Rugby Club Toilet Shelter

CHRISTCHURCH CITY COUNCIL PRK_0895_BLDG_007 EQ2 Ruru Lawn Cemetery Toilets Raymond Road, Bromley QUALITATIVE ASSESSMENT REPORT FINAL

City Care Milton Street Depot Vehicle Garage / Bitumen Sprayer Detailed Engineering Evaluation PRO_1141_010 EQ2 Quantitative Report

CHRISTCHURCH CITY COUNCIL PRK_0894_BLDG_002 EQ2 Cypress Garden Reserve Toilet 41 Keighleys Rd, Bromley QUALITATIVE ASSESSMENT REPORT FINAL

Detailed Seismic Assessment Report. Islington Substation August 2011

CHRISTCHURCH CITY COUNCIL PRK_2347_BLDG_007 EQ2 Travis Wetland Cottage 280 Beach Road, Burwood QUALITATIVE ASSESSMENT REPORT FINAL

Redwood Plunket PRK 2179 BLDG 003B Detailed Engineering Evaluation Quantitative Assessment Report

SEISMIC ASSESSMENT OF BUILDINGS IN WELLINGTON: EXPERIENCES AND CHALLENGES

Review of seismic provisions of historic New Zealand loading codes

Veronica Place Housing Complex PRO 0317 Detailed Engineering Evaluation Quantitative Assessment Report

Ka Wahine Trust Halfway House PRO 2538 Detailed Engineering Evaluation Quantitative Assessment Report

CHRISTCHURCH CITY COUNCIL PRK_0895_BLDG_001 EQ2 Ruru Lawn Cemetery Toilets Raymond Road, Bromley

Bruce Terrace Cottages Housing Complex PRO 3652 Detailed Engineering Evaluation Quantitative Assessment Report

Spencer Park Paddling Pool Tank Qualitative Engineering Evaluation

Southland Museum & Art Gallery

Sheldon Park - Cricket Shed Qualitative Engineering Evaluation

North Hagley Park Pavilion Qualitative Engineering Evaluation

PRK 3742 BLDG 001 EQ2

INITIAL SEISMIC ASSESSMENT REPORT (ISA PLUS) Suzie's Tapas, Kim's Sunshine Sushi, Tasti Blitz, and Cargill Tea Kelvin Street, Invercargill

Christchurch City Council PRK_2204_BLDG_001 EQ2 Washington Reserve - Toilet Washington Way/ Waltham Rd QUALITATIVE ASSESSMENT REPORT FINAL

Gisborne District Council

HISTORICAL REVIEW OF MASONRY STANDARDS IN NEW ZEALAND

CHRISTCHURCH CITY COUNCIL PRK_2347_BLDG_006 EQ2 Travis Wetland Plant Nurseries 280 Beach Road, Burwood QUALITATIVE ASSESSMENT REPORT FINAL

Seismic Assessment of 91 Willow Street Campus Buildings

P. Armaos & D.M. Thomson

ENG.ACA.0001F Madras. New Zealand significant. (a) spandrel 2010) were solid

Establishing the resilience of timber framed school buildings in New Zealand

ResQ: An Earthquake Risk Prioritisation Tool

Displacement Based Assessment and Improvement of a Typical New Zealand Building by an Average Engineer

Victoria Park Toilets (Disabled) Qualitative Engineering Evaluation

MacKenzie Courts Housing Complex PRO 0921 Detailed Engineering Evaluation Quantitative Assessment Report

Tulett Park Toilet Qualitative Engineering Evaluation

Englefield Reserve Toilet Qualitative Engineering Evaluation

Project: Council Revision: 1. Room. Evaluationn. Functional Location ID:

Rawhiti Golf Course Implement Shed Qualitative Engineering Evaluation

Hagley Park North Band Rotunda Quantitative Engineering Evaluation

Parklands Community Centre Qualitative Engineering Evaluation

Christchurch City Council

Earthquake-Prone Buildings Policy

A seismic engineer s note book

NSET EXPERIENCE ON SEISMIC RETROFITTING OF MASONRY AND RC FRAME BUILDINGS IN NEPAL

Note on the assessment:

REPORT TO CANTERBURY EARTHQUAKE RECOVERY AUTHORITY

Potential benefits of strengthening earthquake-prone buildings

"Impact of New IS 1893 & Related Codes on Design of tall Buildings, Including Trend Setting Structures

Seismic Retrofit of Government House. Matthew Ireland, Jason Milburn and John Trowsdale April, 2009

Earthquake-prone, Dangerous and Insanitary Buildings Policy 2011

Quantitative Assessment Report THE ROSE CHAPEL 866 COLOMBO STREET

Waimakariri Road Soil Store PRO Detailed Engineering Evaluation Qualitative Report

EARTHQUAKE DAMAGE AND RISK EXPERIENCE AND MODELLING IN NEW ZEALAND

STRUCTURAL EVALUATION OF WASHINGTON ELEMENTARY SCHOOL WEST CONTRA COSTA UNIFIED SCHOOL DISTRICT (WCCUSD)

Linwood Library & Service Centre Building PRO Detailed Engineering Evaluation Quantitative Assessment Report

Volume 1. HOW TO MAKE A DREAM HOUSE EARTHQUAKE RESISTANT Contents

Qualitative Engineering Evaluation

POLICY EARTHQUAKE PRONE DANGEROUS & INSANITARY BUILDINGS

Akaroa Court House PRO Detailed Engineering Evaluation Quantitative Assessment Report

Seafield Park Multi-Aviary Building Qualitative Engineering Evaluation

Beam-column joint tests with grade 500E reinforcing

A Tale of Two Earthquakes. Christchurch - Sept and Feb. 2011

CHRISTCHURCH CITY COUNCIL PRK_1385_BLDG_005 EQ2 Bexley Park Underground Bunker 194 Bexley Road, Bexley

Experimental study on the seismic performance of RC moment resisting frames with precast-prestressed floor units.

SEISMIC RETROFITTING OF EXISTING BUILDINGS

Wenchuan Earthquake May 12 th, 2008

CHRISTCHURCH CITY COUNCIL PRO_0862 Maurice Carter Court Owner/Occupier 16 Dundee Place, Spreydon QUANTITATIVE ASSESSMENT REPORT FINAL

Quantifying Seismic Strengthening in Wellington s Commercial Building Stock

Quantifying Seismic Strengthening in Wellington s Commercial Building Stock

Strengthening Buildings for Earthquake Implementing New Zealand Legislation David C Hopkins 1 Mike Stannard 1 Graeme Lawrance 1 Ian Brewer 1 1

CHRISTCHURCH CITY COUNCIL PRK_1823_BLDG_006 EQ2 Coronation Hill Reserve - Storage Shed Cnr Dyers Pass & Summit Road, Governors Bay

Pavilion/Toilet Buckleys Road / Bromley Park PRK_0766_BLDG_001 EQ2 Detailed Engineering Evaluation Qualitative Report Version Final

Report Information. Report Title: Authors: Country: Region: Summary of building Typology

b~êíüèì~âé=éêçåé= ÄìáäÇáåÖ=éçäáÅó=

Evaluation of Earthquake Risk Buildings with Masonry Infill Panels

Earthquake Resistant Design. Dr. S. K. PRASAD Professor of Civil Engineering S. J. College of Engineering, Mysore

for Hamilton City Council

Waltham Pool Staff Room BU EQ2 Detailed Engineering Evaluation Qualitative Report

Masonry and Cold-Formed Steel Requirements

Furthering the Understanding of Seismic Resilience in the Ministry of Education Buildings. Wellington 18 November 2015.

A Displacement Focused, Force Based Structural Design Procedure

Project Seismic Vulnerability Assessment For SFCC District Building 33 Gough Street San Francisco, California 94103

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 09, 2014 ISSN (online):

A PROCEDURE FOR ESTABLISHING FRAGILITY FUNCTIONS FOR SEISMIC LOSS ESTIMATE OF EXISTING BUILDINGS BASED ON NONLINEAR PUSHOVER ANALYSIS

Pushover Analysis Of RCC Building With Soft Storey At Different Levels.

Wainoni Community Centre. Detailed Engineering Evaluation. Quantitative Assessment Report BU EQ2 31 Hampshire Street Aranui, Christchurch

BUILDING INTEGRITY SUMMARY REPORT

Transcription:

The Initial Assessment of Earthquake Prone Buildings: A Wairarapa Experience M.L. Rafferty Eastern Consulting Limited, Masterton, New Zealand. 2009 NZSEE Conference ABSTRACT: This paper presents the practical application of earthquake risk assessment of buildings in the Wairarapa area. An outline of the specific seismic hazard in the Wairarapa and a brief history of the development of the definition of earthquake prone buildings, is followed by an overview of the application of the NZ Society for Earthquake Engineering document Assessment and Improvement of the Structural Performance of Buildings in Earthquakes to buildings in the Masterton locality. Focus is given to the Initial Evaluation Procedures outlined in the document, including a review of the alternative methods available, with local examples of varying types of materials and construction. 1 INTRODUCTION 1.1 Earthquake Prone Buildings As defined by the NZ Building Act 2004, a building is earthquake prone (EPB) if its ultimate capacity is exceeded in a moderate earthquake at that site and likely to collapse involving life safety or damage to other property. The regulations define a moderate earthquake as one third as strong as the earthquake shaking used to design a new building at that site. The requirements are not applicable to smaller residential buildings. The New Zealand Society for Earthquake Engineering (NZSEE) study group recommendations, June 2006, provide information on the evaluation of the structural performance of existing buildings to determine whether or not they are EPBs in terms of S122 of the Building Act. 1.2 Legislative control of EPB in NZ Since 1968 territorial authorities have had the powers, if they chose to apply for them, to declare Unreinforced Masonry (URM) buildings and their parts potentially dangerous in an earthquake. In spite of these powers, at risk URM buildings and parts still exist in many NZ towns and cities. The Gisborne earthquake of December 2007 highlighted some of the risks involved with these buildings and parts. Figure 1 illustrates URM end gables on buildings. Figure 1a. URM Gable, Queen St, Masterton Figure 1b. Collapsed URM Gable, Gisborne EQ Dec2007 Paper Number 50

1.3 Masterton District Council Earthquake Prone Building Policy The Building Act 2004 required local territorial authorities to adopt a policy on earthquake prone building within their region. Masterton District Council (MDC) policy on earthquake prone buildings was adopted in 2006. The MDC policy sets out the local requirements for assessing EPBs. In 1988, MDC assessed and identified a group of buildings within the town central business district that were classed as EPBs under the then requirements of Section 624 of the Local Government Act 1974. Those buildings, previously identified as EPB and subsequently strengthened, have been excluded from the current review. MDC policy states that natural justice would imply it is unfair to doubly penalise such structures by now requiring further strengthening as such a process inadvertently suggests these buildings should previously have been demolished rather than strengthened. The majority of structures requiring assessment are those that were not previously identified. They are generally commercial structures built prior to 1976. The MDC policy dictates that should these buildings be classified as EPBs, they need to be strengthened to a minimum of 50% new building standard (NBS). Depending on the structural condition, a timeframe of a maximum of ten years is set to remove the seismic risk. MDC complete a preliminary assessment of the structure, but it remains the responsibility of the building owner to carry out the initial evaluation. 2 SEISMICITY OF THE WAIRARAPA 2.1 Seismicity of the Wairarapa The Wairarapa is one of New Zealand s most seismically active areas and can lay claim to the nation s biggest recorded earthquake the 1855 Wairarapa Earthquake (WELA, 2003). Masterton Urban Area Figure 2. Wairarapa Fault Lines (from Shores & Fellows) - Wellington fault added In the past 104 years, the Wairarapa has been subjected to four earthquakes which have caused significant to extensive building damage. They are: 1. The 1904 Cape Turnagain. Mw 7.0-7.2. Masterton MM7 2

2. The 1934 Pahiatua (Waione). Mw 7.4. Masterton MM7 3. The 1942 Wairarapa I. Mw 7.2. Masterton MM8-9 4. The 1942 Wairarapa II. Mw 6.8. Masterton MM7 The greatest current seismic hazard facing Masterton is rupture on the Tararua-Putara segment of the Wellington Fault. In 2002 this was regarded as the most likely segment of the fault to rupture in the future (Berryman et al 2002). The active fault lines in the region are illustrated in Figure 2. 3 EVALUATION PROCESS 3.1 Evaluation Process There are three basic stages to the assessment process; Stage 1 Research the structure. All information held by the local authority is reviewed. Copies are taken of any relevant information, ie structural drawings and specifications. From this information a chronological history of the structure is compiled. A special note is made of any pertinent features to be reviewed during the site visit, or any ambiguities in the structural form which will need to be confirmed on site. The quality of the structural documents available vary from simple plan sketches from the early 1900s to drafted plans detailing all structural components to sometimes none at all. Stage 2 Visit the site. The site inspection checks that the building s structural elements are as per the plans. Any differences from the plan details are recorded. The general condition of the building is noted, identifying any deterioration. Photographic records are taken of the structure. Stage 3 Complete the relevant assessment. Various methods to assess a structure can be used, depending on the structure type and age. The methods generally employed include the Initial Evaluation Procedure (IEP) from the NZSEE Recommendations, Appendix 3b attribute scoring process from the NZSEE Recommendations and specific simple calculations. 3.2 NZSEE Initial Evaluation Procedure The IEP provided by the NZSEE Recommendations provides a quick process for assessing structures. It is generally based on the structure type and age, and then modified by several factors, as illustrated in Figure 3. Step 3 Step 2 Step 1 Determine (%NBS)nom Based on Year built Soil type Estimated period Determine (%NBS)baseline Based on (%NBS)nom x AxBxCxDxE factors A derived from near fault factor, N(T,D) B derived from hazard factor, Z C derived from return period D ductility scaling factor E structural performance factor Figure 3. Diagrammatical representation of the IEP Process Assess Performance Achievement Ratio (PAR) Based on Plan irregularity Vertical irregularity Short columns Pounding potential Site characteristics Other factors scaling Steps 4, 5 & 6 Determine %NBS Equals (%NBS)baseline x PAR For URM buildings constructed prior to 1935, the NZSEE Recommendations provide an attribute scoring method in Appendix 3b as an alternative to the IEP process. These calculations are both a qualitative assessment of the structure condition and a quantitative assessment of the structural 3

characteristics. Structures that do not fall easily into the mould for the above two assessment methods can be evaluated using simple calculations. These can be calculations from first principles, or for light timber framed structures, can simply be a bracing plan with estimated bracing units for the materials present. It should be noted that the IEP process is aimed at Life Safety not damage control. For engineers completing the assessment, an important thing to remember is that: In the event of an earthquake, the decisions taken and the reasons for it will need to be easily seen as reasonable and defensive, especially in hindsight. (NZSEE Recommendations) 4 DETAILED EXAMPLES 4.1 Example 1 NZSEE Initial Evaluation Procedure Hunting & Fishing Building 4.1.1 Stage 1 Research the Structure This building in the central business area of Masterton was originally constructed in the late 1800s to early 1900s as two storey brick. Repair works were completed on the building after it was damaged in the 1934 earthquake. These 1934 repairs involved the installation of steel bracing in the roof and wall spaces and a central concrete pier in the front, with the original brick pier retained. Figure 4a. 1934 structural steel system Figure 4b. Internal intermediate frame The building was entirely reconstructed after damage in the 1942 earthquakes. New concrete foundations and wall columns were constructed, with brick infill panels. The condition of the building after the 1942 earthquakes was recorded in the Masterton Borough Surveyors report: The showroom portion at the front has an exceptionally high storey height into which had been introduced after the 1934 earthquake, a system of RSJ columns and beams at third points of span. These proved effective in supporting the roof after partial failure of the poorly constructed 16-inch cavity brick side walls. Nothing appears to be required at the front except to tie (reinforced concrete) bands into existing work. The latter work was not completed. Unknown Table 1. Abridged Chronological History of Structure Year Structure History Note Original building 1934 EQ damage repairs Structural steel system installed 1943 EQ damage repairs Building entirely rehabilitated 1971,1974,1991 Internal fit out Non structural 2004 Mezzanine floor added at rear 4

Records for this structure were located at the MDC, though changes over time mean that it is now filed under a different street number to the current. Reasonably detailed records were available for the post 1942 works, while only one plan was on file for the post 1934 works. A chronological history of the structure was compiled, refer Table 1. 4.1.2 Stage 2 Visit the Structure The building was inspected internally and externally. Generally the structure was in good condition, with structural elements as shown on the 1934 and 1942 plans. The main portion of the building has a high suspended ceiling. There is no continuous diaphragm present at mid-floor. Two cast-iron columns were present in the front façade. Brick piers were also visible in the façade structure. During the site visit, it was confirmed that the first 1943 reinforced concrete frame was set back from the original façade, as shown on the drawings. The façade of the building remains as per the original construction, with the exception of the concrete pier addition in 1934. Brick pier 2 Cast iron columns Brick pier w/ 1934 RC pier at rear Brick pier Figure 5. Hunting & Fishing building façade 4.1.3 Stage 3 Evaluate the structure For this type of structure, the NZSEE IEP is the best tool for assessment. It provides a quick and simple method to evaluate the relative performance of this building in an earthquake. It is likely that this reinforced concrete frame structure was subject to engineering input relevant to the code of the time. Therefore scaling the relevant codes, as applied in the IEP, is an applicable coarse filter assessment method Based on the structure type and age, this building was assigned a percent of a new building standard (%NBS) nominal of 4%. With a building importance level of 2 and a structure ductility of 2, this building achieved a (%NBS) baseline of 21.4%. The building does not suffer significantly from any of the identified critical structural weaknesses (CSWs), meaning the Performance Achievement Ratio (PAR) is set by the F Factor. For this building, the F factor was set as 2.5 longitudinally, and 1.0 transversely. The final %NBS for this building was therefore 53.5% longitudinally and 21.4% transversely. 4.1.4 Structure Classification The IEP result classifies this building as an EPB. The IEP results for this structure were forced by the F Factor. The rational for the F factor relates to the façade. In the longitudinal direction, there are reasonably regular reinforced concrete frames present. In the transverse direction, the concrete frames are present at the rear of the building and intermediate location, offset towards the rear. This will produce an irregularity and will lead to increased transverse deformations at the front of the 5

structure. F a c a d e 6 U-Frames -refer Fig 6b 2 Rectangular frames -refer Fig 6c Figure 6a. Structural drawings of the 1942 reconstruction of the Hunting & Fishing building, with annotations Figure 6b. Reinforced concrete U-frames Figure 6c. Rear reinforced concrete rectangular frame The front façade gravity loads are supported by a characteristically brittle system, consisting of bricks and cast iron. Deformations are likely to affect the stability of the gravity support system of the façade. Figure 7a. View of side of facade. Note first 1942 RC frame set back from the remaining original brick facade. Figure 7b. Original cast iron column 6

Thus this building should be classed as an EPB, and further investigation should be done on the transverse capacity of the U-frames, and the likely deformations of the facade. 4.2 Example 2 Simple Calculations Seminis Seeds Warehouse (Adjacent Masterton Railway Yards) 4.2.1 Stage 1 Research the Structure There was no information available for this structure from the MDC. 4.2.2 Stage 2 Visit the Structure The warehouse was constructed around the 1920s, and is a 61m x 15m timber building with 19 timber truss frames at approximately 3.1m centres. The transverse frames are timber trusses and columns of dual studs and bolted knee braces at the truss-column connection. A number of the truss frames had their knee braces removed to facilitate pallet storage in the warehouse. The walls and roof are close sarked timber, with corrugated galvanised roofing. There have been minor additions for plant and a new internal office has been added. Figure 8a. External view of warehouse Figure 8b. Internal view of warehouse 4.2.3 Stage 3 Evaluate the structure The NZSEE IEP is not the best tool for the evaluation of this type of structure. The coarse filter IEP provides a comparison between the design code likely to have been applied at the time and the current loading code. This type of building is unlikely to have had engineering input at the time of construction, and therefore scaling between the relevant codes is not the best assessment method. In addition, structures consisting of more ductile materials like timber will generally have more capacity for overstrength than other common construction materials of this era such as reinforced concrete or masonry. The IEP may penalise this type of structure by not allowing for this. Specific calculations are quick and easy to complete for this structure, and will be more indicative of performance. Specific simple calculations were adopted. Using AS/NZS 1170, the earthquake and wind loadings on the structure were derived. In both directions, 33% of the current standards earthquake loading is less than the wind loading. NIWA data for the Masterton area documents a mean annual wind gust speed event of greater than 25.8 m/s on two days per year. 33% of NBS earthquake loading is equivalent to a wind speed of 22m/s. From this we can assume the buildings transverse capacity is greater than 33% NBS. 7

Transverse (load per frame) Longitudinal (load per wall) Table 2. Transverse forces on Seminis Seeds Warehouse building AS/NZS 1170 load 13kN 45kN Wind Equiv. Gust speed 38m/s (148km/hr) 38m/s (148km/hr) AS/NZS 1170 load Earthquake 33% NBS Equiv. wind gust speed of 33% NBS 12.6kN 4.2kN 22m/s (79km/hr) 120kN 40kN 35m/s (126 km/hr) Longitudinally, the earthquake forces are resisted by the two close sarked timber external walls. Two sets of data were used to verify their capacity. The superseded Light Timber Frame Code NZS3604:1990 Appendix K Table K1 provided a bracing unit value for close timber sarking. A first principles calculation was also completed on the likely shear capacity of the sarking, determined by the nail connections. Both gave a value of 2.1kN/m. With 61m length of wall, the resistance available is 128kN per wall, which is greater than 33% NBS. 4.2.4 Structure Classification This building exceeds the 33% NBS threshold and should not be classed as an earthquake prone building. However, the structural integrity of the frames, and their capacity to resist lateral loads as designed should be restored by replacing the missing knee braces. This work has now been completed. Figure 9a. Knee braces missing Figure 9b. Knee braces reinstated 5 NOTES ON THE NZSEE IEP 5.1 IEP The maths As provided by the NZSEE Recommendations, buildings in Masterton will be assigned (%NBS) nominal based on their age. The common factors for a building in the Masterton urban area are detailed in Table 3, below. The information on soil conditions in the Masterton urban area is limited. The limited number of boreholes show gravels and SPTN results which indicate they were medium dense to dense (Brabhaharan 1993). For the Wairarapa I earthquake of 24 June 1942, the mean PGA in Masterton has been estimated at 0.3-0.6g. (Downes et al 2003). The soils in the urban area are mostly of a firm to stiff character, which would be classed as Ground Class C (Dowrick & Rhoades 2002). 8

Table 3. Factors generally common to building in the Masterton Urban area Period Soil Type Near Fault Factor Hazard Factor, Z Value <0.4 secs C-Shallow soil 1 0.42 2 Building Importance Level IEP value Figure 3.3(a) to 3.3(h) Factor A=1 Factor B=2.38 Factor C=1 Generally the structures under consideration locally have a low period of less than 0.4 seconds. The IEP Step 2 factors D and E rely on the structure ductility. If =1, then DxE=2.245, while if =2, then DxE=1.0. Keeping in mind the requirement for 33% of NBS, we can calculate the IEP maths for the Masterton Urban area. Table 4 sets out the different age groupings set out in the NZSEE Recommendations, and their associated factors. The (%NBS) nominal is set, there is no engineering judgement involved. The Product of Baseline Factors is also generally set, with period and ductility as the only variables. The PAR for a building with no critical structural weaknesses (CSWs) is set entirely by the F Factor. In this case, a building with no CSWs, the F Factor will determine if buildings pass or fail. Basically the assessment comes down to the judgement of the engineer. While pounding, plan and vertical irregularity are a factor, buildings generally pass or fail determined by the F Factor. There is nominal guidance on the appropriate application of the F Factor in the NZSEE Recommendations, which states that a well designed and constructed regular building of its type and vintage on the site in question would have a PAR=1. Pre 1935 1965-1935 1976-1965 Ductility (%NBS) nom Table 4. The F Factor Product of Baseline Factors (%NBS)b PAR (excl Factor F) =1 3.2% x 2.38 = 7.62% 1 4.4 =2 x 5.38 = 17.22% 1 2.0 =1 4% x 2.38 = 9.52% 1 3.5 =2 x 5.38 = 21.4% 1 1.6 =1 7.5% x 2.38 = 17.85% 1 1.9 =2 x 5.38 = 40.35% 1 0.9 Required Factor F to %NBS>33% Referring to Table 4, if the PAR, inclusive of the F Factor =1, the only buildings in the Masterton locality that would pass the evaluation process are buildings with high ductility, and no CSWs constructed between 1965 and 1976. 6 CONCLUSIONS The necessity for the Building Act requirement to evaluate the seismic capacity of all buildings constructed prior to the introduction of modern codes and not only URMs is quite clear and supports the long held view of NZSEE The initial evaluation procedure outlined in the Recommendations of the NZSEE Study Group on Earthquake Risk buildings is a practical workable basis on which to initially assess the seismic performance of ERBs and should produce relatively uniform seismic grading outcomes. It is in effect a coarse sieve 9

The IEP outcome is very sensitive to the Factor F used in determining the PAR. Factor F is entirely based on the judgement of the assessor and has a significant affect on the % NBS achieved and the seismic grading In the Masterton urban area, a good (µ=2) pre-1935 buildings requires an F value of 2.0 to achieve a %NBS greater than 33 Single storey timber framed structures which do not fit comfortably into the IEP procedure can be evaluated using simple calculation procedures, such as bracing units, to produce a %NBS value Life safety and the likelihood of damage to any other property are critical requirements In Masterton, the time taken to carry out an IEP assessment is generally around 10-15 hours. This could be less in other areas where the territorial authority carry out the research and locate the building permit / consent information. Having a very experienced local Engineer to consult with is a valuable resource, particularly with historical information on construction methods and materials over time. ACKNOWLEDGEMENTS This paper is based on a presentation given by Michelle Rafferty and George Butcher to IPENZ Wellington branch at a 2008 Wairarapa meeting. The author is grateful to George Butcher, Peter Davenport and Sheena Bennett for their reviews of this paper. The author wishes to extend special thanks to George Butcher, as without his guidance, advice and support this paper would not have been possible. REFERENCES: Australian/New Zealand Standard AS/NZS 1170.2:2002. Structural Design Actions Part 2: Wind actions and AS/NZS 1170.5:2004. Structural Design Actions Part 5: Earthquake actions New Zealand Berryman, K., Dissen, R.V. & Mouslopoulou, V. 2002. Recent rupture of the Tararua Section of trh Wellington Fault and Relationships to Other Fault Sections and Rupture Segments. Earthquake Commission Research 97/248 Brabhaharan, P. & Jennings, D.N. 1993. Liquefaction Hazard Study, Wellington Region Study Area 5- Wairarapa. Works Consultancy Services Ltd. Wellington Regional Council. Downes, G.L., Dowrick, D.J., Van Dissen, R.J., Taber, J.J., Hancox, G.T., & Smith, E.G.C. 2001. The 1942 Wairarapa, New Zealand, Earthquakes: Analysis of Observational and Instrumental Data. Bulletin of the New Zealand Society for Earthquake Engineering 34(2), 125-157. Dowrick, D.J. & Rhoades D.A. 2002. Damage ratios for low-rise non-domestic brick buildings in the magnitude 7.1 Wairarapa, New Zealand, Earthquake of 24 June 1942. Bulletin of the New Zealand Society for Earthquake Engineering. 35 (3). 135-147. Mabson, C.R. 1942. 1942 Earthquake Damage. Masterton Borough Surveyors Report. Masterton District Council 2006. Earthquake Prone Building Policy New Zealand Society for Earthquake Engineering 2006. Assessment and Improvement of the structural performance of buildings in Earthquakes. Recommendations of a NZSEE Study Group on Earthquake Risk Buildings New Zealand Building Act 2004 New Zealand Building Act Building (Specified Systems, Change the Use, and Earthquake-prone Buildings) Regulations 2005 (SR 2005/32) Shore, M. & Fellows, D. 2006. Final Report, Wairarapa Fault Trace Project. URS Report prepared for Greater Wellington Regional Council, Carterton District Council & South Wairarapa District Council Wairarapa Engineering Lifelines Project (WELA) 2003. Risk to Lifelines from Natural Hazards, a Wairarapa Engineering Lifelines Project 10