High efficient heat reclaim with CO2

Similar documents
THE INSTITUTE OF REFRIGERATION

Danfoss and Controls for CO2

Module 05 Lecture 35 : Low temperature process design Key words: Refrigeration system

WELCOME! 欢迎 光临. Roadmap

Eurammon Symposium Ammonia Absorption Refrigeration. Colibri b.v.

HEAT PUMPS FOR THE EXPLOITATION OF GEOTHERMAL SOURCES IN MILANO. University of Brescia. Studio Associato di Ingegneria - Milano

CO 2 the natural refrigerant for MT and LT in discounters, super- and hypermarkets PE4, Bernd Heinbokel

CO2 solutions February 2018

Type CTM 6 High Pressure (HP) and Low Pressure (LP)

Analytical model of a multichannel double tube CO2 gas-cooler for a water heater

Performance Comparison of Air-source Heat Pumps Using Economizer Vapor Injection and Internal Heat Exchanger in Cold Regions

About Hot Gas Defrost. Hot Gas Defrost Benefits

A NOVEL DESIGN OF COMPACT BRAZED PLATE HEAT EXCHANGER FOR CO2 TRANSCRITICAL APPLICATIONS

ANNEXES. to the REPORT FROM THE COMMISSION

Advanced heat driven cooling cycles for low-temperature waste heat recovery

Postprint. This is the accepted version of a paper presented at 13th IIR Gustav Lorentzen Conference.

Problems in chapter 9 CB Thermodynamics

pinch 70 C 70 C 4 We want to cool both the hot streams to the pinch temperature. The next step is to find the duty for the two heat exchangers:

Carbon Dioxide as an Eco-Friendly Refrigerant for Electric Vehicles

NATURAL REFRIGERANTS

Industrial Heat Pumps

Utilization of THERMOPTIM Optimization Method

Chapter 5: Thermodynamic Processes and Cycles

Design considerations for integration of two 5 MW vapour compression heat pumps in the Greater Copenhagen district heating system

Experimental Study of a CO2 Thermal Battery for Simultaneous Cooling and Heating Applications

CO 2 Heat Pump System for Combined Heating and Cooling of Non-Residential Buildings

Nilan VPL Active heat recovery and cooling (air/air)

Multi Ejector Solution Transcritical CO 2 refrigeration systems in all climates

Low temperature cogeneration using waste heat from research reactor as a source for heat pump

CO2 refrigeration and Its applications. Benoit Rodier, P.Eng.

2 nd Law of Thermodynamics

Plant Utilities and Energy Efficiency CH505

Opportunities for combined heating and cooling A case study from Nestle Halifax

Appendix 4: Calculations on Different Concepts for LTDH HP

Research on CO 2 Heat Pumps and Other CO 2 Novel Systems at The Energy Department of KTH

COP-OPTIMISED PRESSURE CONTROL FOR A CENTRALISED CO 2 COOLING SYSTEM IN AIRCRAFT APPLICATIONS

Energy efficient cooling of data centers with hybrid dry coolers. > Engineering a sustainable future

Multi Ejector Solution TM for R744 (CO 2 ) Product type - CTM 6 Low Pressure (LP)

Chapter Six{ TC "Chapter Six" \l 1 } System Simulation

Total Energy Energy efficient food chilling and freezing plant

COP Improvement Of A CO2 Refrigeration System With An Expander-Compressor-Unit (ECU) In Subcritical And Transcritical Operation

Trends in Refrigeration System Architecture and CO 2. Derek Gosselin Hillphoenix

Compound ejectors with improved off-design performance

Refrigeration System with Booster Hot Gas Bypass in Tropical Climate

Multi Ejector Solution TM for R744 (CO 2 ) Type - CTM 6 High Pressure (HP)

Rajan Rajendran, Ph.D. Vice President Engineering Services And Sustainability

Ontwikkelingen van hoge temperaturen warmtepompen Kenneth Hoffmann

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

System cost and efficiency optimization by heat exchanger performance simulations

AREN 2110: Thermodynamics Spring 2010 Homework 7: Due Friday, March 12, 6 PM

State of the Art of Air-source Heat Pump for Cold Regions

EU F Gas Regulations Creating Innovation in Supermarket Innovation Robert Kebby

Simulation Study on Geothermal Direct Supply Combined with Water Source Heat Pump Qing HAO 1, a, Meng SI 2, b

Energy Saving Report. Frigi-Tech Oil Additive. Application. In HKU Central Plant. Chiller No. 3

- 2 - SME Q1. (a) Briefly explain how the following methods used in a gas-turbine power plant increase the thermal efficiency:

innovative accumulator tanks

Natural is what we design for AMMONIA HIGH TEMPERATURE HOT WATER HEAT PUMP. Mar$n Millow Mayekawa Australia Pty Ltd

CO 2 Transcritical Cycle for Ground Source Heat Pump

Chapter 3.7: Cooling Towers

Trends in Refrigeration System Architecture and CO 2. Andre Patenaude Emerson Climate Technologies

Application Of Oil Flooded Compression With Regeneration To A Packaged Heat Pump System

Refrigeration Cycle. Definitions , , 11-46, 11-49,

Cold Plate economy and ecology in supermarkets

Thermally operated mobile air-conditioning system

HEAT PUMP WITH HIGH OUTLET TEMPERATURES

Seasonal performances and compression technology

FACT SHEET 6 Transport Refrigeration

The efficiency of the heat pump water heater, during DHW tapping cycle

Stefan Elbel Pega Hrnjak University of Illinois at Urbana-Champaign

Space Engineering Services

Second Law of Thermodynamics

SIMULATION AND SENSITIVITY ANALYSIS OF A MIXED FLUID CASCADE LNG PLANT IN A TROPICAL CLIMATE USING A COMMERCIAL SIMULATOR

BINARY BLEND OF CARBON DIOXIDE AND FLUORO ETHANE AS WORKING FLUID IN TRANSCRITICAL HEAT PUMP SYSTEMS

GeoExchange TM Systems Using Natural Gas

Gas Turbine Inlet Air Cooling System

EXPERIMENTAL STUDY OF ALTERNATIVE REFRIGERANTS TO REPLACE R134a IN A DOMESTIC REFRIGERATOR

RESEARCH ON INTEGRATION OF VAPOR CYCLE/LIQUID-COOLED REFRIGERATION SYSTEM FOR HELICOPTERS

Eng Thermodynamics I: Sample Final Exam Questions 1

Technical Papers. 32nd Annual Meeting. International Institute of Ammonia Refrigeration. March 14 17, 2010

Customized Absorption Heat Pumps for Utilization of Low-Grade Heat Sources

DISTRICT HEATING AND COOLING WITH LARGE CENTRIFUGAL CHILLER-HEAT PUMPS

Integration of trigeneration and CO2 refrigeration systems for energy conservation in the food industry AFM 251

Recent U. S. R&D results from IEA HPP Annex 41

a.k.a. David N. Shaw, P. E.

for refurbishing future?

NATIONAL CERTIFICATION EXAMINATION 2004 FOR ENERGY MANAGERS

1st October Robert Kebby Marketing Manager

SUPERCRITICAL CO2 RANKINE CYCLE TEST LOOP (ROMA) - OPERATION AND INITIAL RESULTS

PERFORMANCE ANALYSIS OF TRANSCRITICAL CO2 REFRIGERATION SYSTEM FOR SUPERMARKET APPLICATION

Study of Performance Improvement of Air Conditioning using Various Heat Recovery Techniques

Presentation Topic. Woolworths investment in the Australian industry to deliver sustainable HFC-free refrigeration innovation

CONDENSING BOILERS EX3 & 6. Floor Standing Gas Fired. Condensing Boilers. Condensing 69kW 542kW. Cascading options up to 8,672kW

Copeland Transcritical 4MTLS CO 2 Compressors. June 2016

Green economy with natural refrigerants

HIGH EFFICIENCY SHOWERS WASTE WATER HEAT RECOVERY UNIT. Saved power 80kW. Showers waste water 9 C Power consumption 3,1kW. Showers waste water 31 C

Steam balance optimisation strategies

Methodology of Modeling and Comparing the Use of Direct Air-Cooling for a Supercritical Carbon Dioxide Brayton Cycle and a Steam Rankine Cycle

THERMAL POWER PLANT SIMULATOR TPP 200 LABORATORY EXERCISE TUTORIAL N4: INTRODUCTION TO THE HEAT PRODUCTION SYSTEM

High Temperature Energy Storage based on Hot Air Turbine and Pebble-Heater Technology

HPC 2017 Performance simulation and exergy analysis on multi-stage compression high temperature heat pumps with R1234ze(Z) refrigerant

Transcription:

High efficient heat reclaim with CO2 Refrigeration systems with transcritical CO 2 has been taking market shares the last years. Since 2007 the market in Denmark has turned from conventional refrigeration systems with HFC or cascade systems with CO 2 and HFC towards transcritical CO 2 systems. At this moment transcritical systems is everyday business and the technology is mature. The field studies carried out looking at refrigeration only shows that the annual energy consumption is on the same level as HFC DX systems. The article contains a short back ground on the theory behind heat reclaim in transcritical systems, and the efficiency will be compared with the efficiency of HFC systems. Transcritical systems back ground In normal systems with condensing refrigerants the pressure and temperature are tied together, but on transcritical systems pressure and temperature can be controlled individually. This gives some possibilities regarding heat reclaim. During normal operation with out heat reclaim the high pressure is kept at a level where the optimum COP is obtained. This is done automatically by an electronic controller. During cold periods the pressure in normally kept at minimum 40 bar ~ 5 ºC or higher. At this pressure there is almost no heat to reclaim. If the pressure is raised the amount of heat that can be reclaimed is increasing. Example Water is heated from 15 ºC to 55 ºC. The ambient temperature is -5 ºC and the heat load on the system needs to be reclaimed with the lowest possible energy consumption. The temperature difference of the heat reclaim HX is set to 5 K at in or outlet. The temperature out of the gas cooler is kept at 4 ºC in all cases where the gas cooler is active. The system used consists of one or more compressors, heat reclaim heat exchanger with pump, 2 3- way valves, air cooled gas cooler and a high pressure control valve with electronic controller.

Under these conditions the discharge temperature from the compressors is approx 35 ºC and therefore it is not possible to make 55 ºC hot water. To make the system able to do 55 ºC the discharge needs to be at least 55 ºC and therefore the pressure needs to be pushed upwards.

At 50 bar high pressure the discharge temperature is 55 ºC and therefore it is possible to start reclaiming heat from the system but there is no temperature difference of the heat exchanger. By increasing the pressure further the amount of heat taken out of the system is increasing. 80% heat reclaim At 80 bar approx 80 % of the heat is reclaimed at a cooling COP of 3,13. To increase the ratio to more than 80 % the pressure can be pushed up and the gas cooler can be by passed. By doing this the ratio will go to 100% because there is no heat lost to the ambient, but all heat is reclaimed. This will put in more compressors to compensate for the lower heat rejection.

100 % heat reclaim W heat W ref Under this conditions all heat is reclaimed and the COP of the system is approx 2,6. Since the heat output from the system varies with the pressure it is interesting to look at what the heating COP of the system is. The system consumes energy in the condition there it is running with optimised pressure (in this example 40 bar). This means that no mater how much heat we pull out of the system it will consume energy. Therefore the heating COP of the system is calculated at the heating capacity divided with the extra energy consumed by the compressors. This is done because then it is possible to compare the heating COP with alternative heating sources. P_gc [bar] COP ref [-] Ratio COP Heat [-] 40 8,8 0% - 50 5,7 0% - 60 4,3 25% 2,6 70 3,6 40% 3,1 80 3,1 80% 5,1 80 3,1 100%* 5,1 *By-pass of air cooled gas cooler The ratio is the ratio between the maximum heat available and the heat used. The heating COP is varying with the ambient temperature. At high ambient temperatures the compressor work used for refrigeration is higher and therefore the compressor work for heating is less. At lower ambient temperatures the pressure can not be decreased, and therefore this will not effect the heating COP. If the ambient temperature was chosen to be 3 ºC instead of -5 ºC then the result will be a shown in the table below.

P_gc [bar] COP ref [-] Ratio COP Heat [-] 50 5,7 0% - 60 4,3 25% 5,6 70 3,6 40% 5,0 80 3,1 80% 7,3 80 3,1 100%* 7,3 *By-pass of air cooled gas cooler The results show that the ambient temperature has a significant impact on the heating COP and the heating COP is highest at full load. If the high COP is wanted at part load the system can be build as a CO2 heat pump on top of the refrigeration system. Comparing CO2 transcritical with other heat sources In the section above the heating COP is calculated, but the interesting part is if it is cheaper or more expensive compared to other heat reclaim systems and other energy sources. Other heat reclaim systems To be able to compare the COP from CO 2 to the COP of other refrigerants it has to be done in a fair way. For the other refrigerants it is chosen to run at -10 C evaporation and to condens at 55 C to be able to supply 55 C hot water. Sub cooling is set to 2K. The minimum condensing temperature is set to 15 C. CO 2 VS R134A in heat reclaim applications 6 5 4 COP heating 3 COP HP CO2 - - COP HP R134A 2 1 0 25% 50% 75% 100% Ratio

From the chart above it can be seen that the heating COP for CO 2 is from approx 25 % to 150 % better that R134A and best at part load witch is the main part of the year. Heat pump systems To get around the problem with part load a heat pump can be put on top of the system. This makes the COP of the system as good as possible regardless of the load on the system. The COP in heating mode has been calculated at 5 C evaporating (equivalent to the lowest possible condensing for the transcritical CO 2 system), 55 C condensing and 2 K sub cooling. The calculation has been done for most of the most used refrigerants on the market. Refrigerant COP heating R134A 3,7 R290 3,7 R404A 3,3 R410A 3,4 CO 2 transcritical heat pump 5,1 The table above shows the COP for different refrigerants. From the data it shows that CO 2 has a COP that is from 38 % to 55 % higher that the conventional refrigerants. Other energy sources An alternative to a CO 2 heat reclaim system could be an oil or gas burner. The question is what is the most economical choice? The COP calculated in this example for a CO 2 heat reclaim system is between 2,6 and 7,3. The exact COP is a question of what type of systems it is (Heat pump or heat reclaim), the load profile for the heat reclaim and the ambient temperature. This can be matched with other energy sources with the following equation. Price Alternative Energy kwhr Ratio Price Electricity kwhr COPHeat If this ratio is smaller than 1 then the CO 2 solution is the most economical solution. In most cases a heat reclaim or heat pump solution is economical attractive. In many cases a heat reclaim solution is attractive if the COP is higher that 2 or 3, but this of cause depends of the energy prices and local taxes. Conclusion The example above shows Heating COP in a transcritical heat reclaim system from 2,6 to 7,3 depending on load and ambient temperature. CO 2 is from 25% to 150% better than R134A in a heat reclaim system depending on the load. In a heat pump system CO 2 is from 38% to 55% better than the HFC refrigerants comared with.

The COP in a heat pump system is higher than a heat reclaim system at part load, but at full load the difference is very little. If it is feasible to install a heat pump system relays on the load profile and the investment costs. Very often CO 2 heat pumps or heat reclaim systems are a very attractive alternative to a oil or gas burner The conclusion is made on the data in the example. If the data are different the conclusion will be different, but there are some guide lines. CO 2 is feasible at high temperature lifts. The lower temperature the inlet water or media the better efficiency CO 2 will have. The exit temperature is not that important. Up to 80 C is realistic with good efficiency CO 2 is not the refrigerant to chose if the outlet media temperature is low and the temperature difference between inlet and outlet is low. There are systems in operation from 5 kw to 1,5 MW heat reclaim at this moment. There are more than 500 installations world wide with transcritical CO 2, not all with heat reclaim. This is not rocket science but everyday business!