Deformation Control of Scroll Compressor for CO2 Refrigerant

Similar documents
A Study of a New Oil Injection to Compression Chambers on Scroll Compressors

Scroll Expander for Carbon Dioxide Air Conditioning Cycles

A Study on High Efficiency Wing-vane Compressor

Application Of Oil Flooded Compression With Regeneration To A Packaged Heat Pump System

Heating Performance with a Volume Ratio on 2-Stage Compressor

Experimental Study on Journal Bearing Characteristics in Reciprocating Compressors for HFC-134a

A Simplified Thermal Model for a CO2 Compressor

Compressor Mechanism Comparison For R744 Application

Noise and Vibration Studies in a CO2 Compressor

The Friction And Wear Characteristic Of Fe-based P/M Materials In Scroll Compressor

The Friction And Wear Characteristic Of Fe-based P/M Materials In Scroll Compressor

Compressor Performance Comparison When Using R134 and R1234YF as Working Fluids

Application of Taguchi Robust Design Method for Energy Efficiency Ratio and Noise of Compressors

Experimental Investigation of a Hermetic Scroll Expander-Generator

Performance of Scroll Expander for CO2 Refrigeration Cycle

Performance of Scroll Expander for CO2 Refrigeration Cycle

Experimental Results on a New Prototype Packaged Heat Pump System Retrofitted with Oil Flooded Compression and Regeneration Technology

Using Simulation Model to Reduce System Design Time and Cost

Conversion Factors for Comparing the Performance of Variable Refrigerant Flow Systems

A Scroll Expander with Heating Structure and Their Systems

Performance Comparison of Air-source Heat Pumps Using Economizer Vapor Injection and Internal Heat Exchanger in Cold Regions

Seasonal Energy Efficiency Rating Improvement Of Residential HVAC Systems Using A Low Power Inverter With A PSC Compressor

Investigation of the Discharge Flow of a Reciprocating Compressor Using PIV

Increase of Efficiency for a Vertical Scroll Water Pump using Oldham Ring with Ball bearings.

Development of high efficiency VRF systems under partial heat load for commercial buildings

Multi-Variable Optimisation Of Wet Vapour Organic Rankine Cycles With Twin-Screw Expanders

Surface of Flow and Force Effective Areas Applied to Development of Reciprocating Compressors

Numerical Study on Rotor Deformation of Multiphase Twin-Screw Pumps Under High Gas Volume Fraction Conditions

Noise Reduction of Commercial Applications: Compressor Approach

Experiments on Flow Boiling Heat Transfer of Pure CO2 and CO2-Oil Mixtures in Horizontal Smooth and Micro-Fin Tubes

Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis

High Efficiency. 7 % on average. EFFICIENCY RATIO WHAT'S IMPROVED? APF: Annual Performance Factor. NS Type

Experimental Performance of a Prototype Carbon Dioxide Compressor

Beating Characteristics at the Small End of a Connecting Rod in Reciprocating Compressors for HFC-134a

Energy Simulation And Optimized Retrofit Practices Applied To A Real Dwelling

Stress and Deformation Analyses of Twin-Spirals Scroll Plates Based on CAE

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

Component-Based Vapor Compression Simulation Tool With Integrated Multi-Objective Optimization Routines

Accelerated Evaluation of Capillary Clogging in HFC Air Conditioners

Recent Technologies for Steam Turbines

Research On The Properties Of Rotary Compressor Vane Coating

Experimental Investigation of Heat Transfer in Components of a Hermetic Reciprocating Compressor

Normalized Effect Of Condenser Fouling And Refrigerant Charge On Performance Of Vapor Compression Air Conditioning Systems

Performance Mapping for Variable Ductless Heat Pump Systems in Heating, Cooling and Defrost Operation

The Part-Load Efficiency Benefit of Oil-Free, High- Speed, Direct-Drive Centrifugal Compressors

Design And Manufacturing Of An Accelerated Lifetime Tester For Non-Metallic Materials Used For Compressor Valve Sealing Elements

Research on the Effect of Nano-materials Used in Rotary Compressor

NUMERICAL APPROACH TO A LOW PRESSURE GAS-INJECTION SCROLL COMPRESSOR

A Comprehensive Evaluation of Regression Uncertainty and the Effect of Sample Size on the AHRI-540 Method of Compressor Performance Representation

Performance Characteristics and Mapping for a Variable-Speed Ductless Heat Pump

Hydraulic Resistance and Flow Pattern at Design and Off Design Flow Rates Among Axial Flow Machines

CFD Analysis of Oil Flooded Twin Screw Compressors

A Study on the Oil Supply System of a Rotary Compressor

Experimental Study of a CO2 Thermal Battery for Simultaneous Cooling and Heating Applications

CO2 in Vending Machine

Modeling Component Assembly of a Bearing Using Abaqus

Friction Coefficient Of Oil/Refrigerant Mixtures At A Pressure of 2.5 GPa

Recent U. S. R&D results from IEA HPP Annex 41

Study on Ejector - Vapor Compression Hybrid Air Conditioning System Using Solar Energy

Development of New H-Section Steel Shape with Inner Rib, J-grip H, and Its Application to Steel Concrete Composite Diaphragm Wall

Heat Pump With a Condenser Including Solid- Liquid Phase Change Material

ON THE ULTIMATE STRENGTH OF RC SHEAR WALL UNDER MULTI-AXES SEISMIC LOADING CONDITION

An Integrated Solution for Commercial AC Chillers Using Variable Speed Scroll Compressors

Computational Analysis Of Ejector With Oscillating Nozzle

Welded Joint Analysis for Pressure Vessels with Medium and Large Diameters

Deployment of a New Series of Eco Turbo ETI Chillers

Experimental and Finite Element Analysis of Base Frame for Rigidity

COP Improvement Of A CO2 Refrigeration System With An Expander-Compressor-Unit (ECU) In Subcritical And Transcritical Operation

The Benefit of Variable-Speed Turbine Operation for Low Temperature Thermal Energy Power Recovery

Performance Evaluation under the Actual Operation Condition of a Ground Source Multiheat Pump System

A Investigation of the Performance of Two-Stage Compression Refrigeration/Heat pump System with Dual-cylinder Rolling Piston Compressor

SCORG TM Setup for CFD Simulation of Twin Screw Machines with STAR-CCM+

Analysis on Viscous Flow of VAD Silica Glass During Heat Forming

LCCP Analysis of Energy-Saving Effect of Defaulting to Recirculated Cabin Air in EV Mobile Air Conditioning System

Properties of High Strength Steels

Seismic Design Guidelines To Mitigate Upheaval Buckling Of Small Diameter Pipes

Steady State And Transient Validation Of Heat Pumps Using Alternative Lower-GWP Refrigerants

Reducing Operating Costs with Optimal Maintenance Scheduling

Numerical Simulation of Welding Deformation produced in Compressor Impeller

SEISMIC ENERGY DISSIPATION SYSTEM OF 12-STOREY COUPLED SHEAR WALLS

Under the Scenes of our Lives High-pressure Pump

Development of Measurement Method for Verification of Multi-Stage Axial Compressor with Improved Performance

The Evolution of Polymer Bearing Processing for Scroll Compressor Performance and Life Enhancement

Two-Phase Distribution of R-134a in a Header of a Parallel Flow Heat Exchanger

Performance of Vapor Compression Systems with Compressor Oil Flooding and Regeneration

Fuji Electric s Medium-capacity Steam Turbines FET Series

The Impact of Evaporator Fouling on the Performance of Packaged Air Conditioners

Model EVMS Vertical Multistage Pumps for the Global Market

BTO s Heat Pump Research Efforts

Modelica-Based Heat Pump Model for Transient and Steady-State Simulation Using Low-GWP Refrigerants Paper 2264

Dynamic Parameter Optimization of an Automobile A/C Compressor Using Taguchi Method

Fundamental Investigation Of Whole-Life Power Plant Performance For Enhanced Geothermal Systems

Opportunities and Limitations of Building Precooling

Measurement and Simulation of Startup and Shut Down of Heat Pumps

INELASTIC SEISMIC PERFORMANCE OF RC TALL PIERS WITH HOLLOW SECTION

Seismic Design Guidelines to Mitigate Upheaval Buckling Of Small Diameter Pipes

450mm PIC Interoperability Report. International 450 mm PIC Task Force PI&C Global Technical Committee

Operating Status of Uprating Gas Turbines and Future Trend of Gas Turbine Development

Transcription:

Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2006 Deformation Control of Scroll Compressor for CO2 Refrigerant Akira Hiwata Matsushita Electric Industrial Co. Yoshiyuki Futagami Matsushita Electric Industrial Co. Takashi Morimoto Matsushita Electric Industrial Co. Hideki Murakami Matsushita Electric Industrial Co. Noriaki Ishii Osaka Electro-Communication University Follow this and additional works at: http://docs.lib.purdue.edu/icec Hiwata, Akira; Futagami, Yoshiyuki; Morimoto, Takashi; Murakami, Hideki; and Ishii, Noriaki, "Deformation Control of Scroll Compressor for CO2 Refrigerant" (2006). International Compressor Engineering Conference. Paper 1731. http://docs.lib.purdue.edu/icec/1731 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

C140, Page 1 DEFORMATION CONTROL OF SCROLL COMPRESSOR FOR CO 2 REFRIGERANT *Akira HIWATA 1, Yoshiyuki FUTAGAMI 1, Takashi MORIMOTO 1, Hideki MURAKAMI 1, Noriaki ISHII 2 1 Refrigeration, Air Conditioning and Heating Research Laboratory, Matsushita Home Appliance Company, Matsushita Electric Industrial Co., Ltd., 2-3-1-1 Nojihigashi, Kusatsu City, Shiga, Japan Tel.: +81-77-567-9801; Fax: +81-77-561-3201 E-mail: hiwata.akira@national.jp *Author for Correspondence 2 Professor, Faculty of Engineering, Osaka Electro-Communication University, 18-8 Haccho, Neyagawa City, Osaka, Japan Tel.: +81-728-20-4561; Fax: +81-728-20-4577; E-mail: ishii@isc.osakac.ac.jp ABSTRACT The compressors for CO 2 refrigerant have a lot of difficulties to achieve its high efficiency and reliability, because of its very high operating pressure. For the fixed scroll, we decreased the deformation under operation by conducting an adequate initial deformation control in order to cancel the pressure deformation. For the orbiting scroll, we made a slope shape on the tip and bottom of the wrap to decrease the losses due to friction and leakage. 1. INTRODUCTION From the viewpoint of ozone-layer protection, production of fluorocarbon that contains chlorine is to be phased out by 2020. In addition, HFC refrigerant that is now popularly substituted as alternative refrigerant has been designated as an excretion control gas in COP3 held in the end of 1997 due to its high global warming potential. Thereupon, movements have occurred to review the natural substances as refrigerants for heat pumps, and recently research and development of heat pump systems, using natural refrigerants is being actively promoted. In particular, carbon dioxide (hereinafter called CO 2 ), with its advantageous non-flammable and non-toxic properties, is becoming a focus of attention from the viewpoint of low global warming potential, and aggressive works are being made to apply CO 2 to the heat pump water heater systems, which have already been commercialized in Japanese markets. However, compressors for CO 2 heat-pump systems have many problems to be solved in improving performance and securing reliability because of smaller displacement volume per unit capacity and extremely high operating pressure, etc. as compared with conventional air-conditioner compressors. Therefore, with respect to the fixed scroll, examinations were carried out to analytically grasp characteristics of pressure deformation and thermal deformation during operation, as well as to analytically and experimentally grasp welding deformation and bolt tightening deformation. From those examinations, the deformation control is adopted to minimize the deformation during operation. With respect to the orbiting scroll, a slope shape is adopted to compensate leakage pressure deformation and thermal deformation during operation. The slope shape realizes the high efficiency by reducing both the wrap contact friction and the leakage across the tip of the wrap.

C140, Page 2 2. DEFORMATION OF FIXED SCROLL Deformations of the fixed scroll during operation fall into the following four categories: (1) pressure deformation due to pressure differences; (2) thermal deformation due to temperature difference; (3) deformation caused by welding for fixing the frame to the shell; and (4) bolt tightening deformation of the compression mechanism. In this study, in order to minimize deformations during operation, deformations (1) and (2) are grasped by numerical calculations in detail, and deformations (3) and (4) are controlled to cancel the deformations (1) and (2) by adjusting the stiffness of fixed scroll. 2.1 Deformation by Pressure Difference Figure 1 shows the cross-sectional view of our CO 2 scroll compressor that adopts a high-pressure shell. The fixed and orbiting scrolls are mated to form a multiple number of compression chambers. With the orbiting motion, these compression chambers move towards the center while reducing their volume to compress the refrigerant. The orbiting scroll is connected to the crankshaft driven by the motor. The Oldham s ring plays the role of preventing the orbiting scroll from self-rotation. The seal ring is attached between the orbiting scroll and the frame to divide the high-pressure section inside the seal ring and the intermediate pressure section outside the seal ring. By pressing the orbiting scroll against a fixed scroll by that intermediate pressure section, the clearances between the tips of the wrap are reduced to prevent refrigerant leakage in the compression process. Discharge pipe Muffler Discharge port Control valve Fixed scroll Orbiting scroll Seal ring Frame Stator Rotor Shell Compression chamber Suction pipe Suction chamber Throttle valve Oldham s ring Eccentric bearing Journal bearing Crankshaft Oil pump : Refrigerant flow : Oil Flow Fig.1 Cross section of the CO 2 scroll compressor Under the rated operating conditions of CO 2 heat-pump water heater (outdoor air temperature: 16 C; entry water temperature: 17 C; heating up temperature: 65 C), the FEM analysis was carried out on the fixed scroll and the frame. In this analysis, the fixed scroll was approximated as a disk that has equivalent stiffness. Figure 2 shows the analysis results, where the fixed scroll is pressed down by pressure difference (to be concave). We found that the maximum deformation is -11.6 μm with the compressor upward direction designated to be positive.

C140, Page 3 Fig.2 FEM result of pressure deformation of fixed scroll and bearing 2.2 Deformation by Temperature Difference Under rated operating conditions of the CO 2 heat-pump water heater, we conducted an experiment, where there is about 15 C temperature difference between the surface temperature of the fixed scroll near the suction chamber and the surface temperature of the fixed scroll on the counter-compression chamber side. Figure 3 shows the FEM analysis result with the temperature distribution given as the boundary conditions based on the experimental result. The fixed scroll is pressed up by temperature difference (to be convex). We found that the maximum deformation is 6.9 μm with the compressor upward direction designated to be positive. (a) (b) Fig.3 (a) Thermal boundary condition and (b) FEM result of thermal deformation of fixed scroll and frame 3. DEFORMATION CONTROL OF FIXED SCROLL In a conventional air-conditioner refrigerant compressor, approaches to prevent the welding deformation have been made as adopting flexible structure of welded parts, using separate parts, etc. However, as compared with airconditioner compressors, CO 2 refrigerant compressors provide remarkably high operating pressure that causes the more deformation during operation. We investigate the characteristics of the welding and bolt tightening deformations. From these results, we determine the initial deformation of the fixed scroll to cancel the pressure and temperature deformations during operation. 3.1 Deformation by Welding - Modeling of Welding Analysis For welding analysis, the deformation of the fixed scroll at room temperature after welded is found by tracing deformations caused by thermal expansion and contraction in the welding process using heat-stress coupled nonlinear analysis. Figure 4 shows the numerical analysis model used for welding. For the fixed scroll, it was also approximated as a disk of equivalent stiffness. In addition, since our CO 2 scroll compressor has the three welding spots to fix the frame to the shell, the analysis was carried out with the welding spots designated as a 120 equally divided 1/6 symmetrical model. For the thermal boundary conditions given to the welding spots, the time history of temperature shown in Fig.5 measured by a thermo-viewer was used. In this study, because before welded, the welding spot was a space where no material existed, the maximum temperature was substituted for the mechanical property of the welding part until the outer edge of the welding part reached the maximum temperature, and in the cooling process, the mechanical property that had the temperature dependency was substituted.

C140, Page 4 Fig.4 Analysis model for 3 spots welding Fig.5 Time history of temperature under the welding process 3.2 Deformation by Welding - Welding Analysis Results Figure 6 represents the maximum deformation of the fixed scroll in contour when the maximum temperature is varied to 1300, 1650, and 2000 C and heating-up time to 1, 2, 3, and 5 seconds. As shown in Fig. 6, the analysis results indicate that the higher the maximum temperature and the longer the heating-up time, the more the fixed scroll is deformed to be convex upward. Fig.6 Deformation characteristics for welding condition 3.3 Deformation by Welding - Welding Experimental Results The welding time was varied to 2, 3, and 5 seconds. In addition, the maximum temperature was measured by a thermo-viewer to be 1300 C. Table 1 shows the welding time and maximum deformation of the fixed scroll. As shown in Table 1, the welding causes to deform the fixed scroll by about 2.0 μm in upward convexity. However, even when the welding time was varied in the range more than 2 seconds, no significant change was observed in the maximum deformation of the fixed scroll. We also found the distortion of the formation of the welding spot at 3 and 5 seconds welding time. The distortion of the formation has the great influence on the heat transfer in the welding process. That is the reason why the tendency of the analysis results is in discord with that of the experimental results in this welding process. Table 1 Experimental results of the relationship between deformation and welding time Welding time Amount of deformation [μm] 2[sec] 2.3 3[sec] 2.0 5[sec] 2.1 3.4 Deformation by Bolt Tightening The fixed scroll is tightened to the frame by 8-evenly distributed bolts in the peripheral direction. It was experimentally verified that before and after bolt tightened, the fixed scroll deforms by 5.0 μm in upward convexity. Based on this result, the FEM analysis was conducted to get the bolt tightening force and friction coefficient, which were used for the study of the deformation control.

C140, Page 5 3.5 Deformation Control - Effects of Stiffness of the Fixed Scroll Calculations and experiments were carried out on (1) pressure deformation by pressure difference; (2) thermal deformation by temperature difference; (3) deformation by welding for fixing the frame to the shell; and (4) deformation of bolt tightening, respectively, and the characteristics of the deformation were grasped. When the thickness of the fixed scroll is increased, now we can calculate the pressure, thermal, welding and bolt tightening deformations respectively from the characteristics of our study, as shown in Fig.7. Figure 7 indicates that as the thickness of the fixed scroll increases, the deformation during operation increases. As the stiffness increases with changing the thickness of the fixed scroll, the pressure deformation, welding deformation and tightening deformation decrease, while the amount of thermal deformation increases. In order to keep the deformation during operation to its minimum, the fixed scroll thickness must be properly chosen in such a manner that the total of deformations should be minimized. Table 2 shows the components of the fixed scroll deformation when the thickness of the fixed scroll is chosen to minimize the fixed scroll deformation under the rated operating conditions of the CO 2 heat pump water heater. Table 2 clearly indicates that examination of stiffness and proper initial deformation can minimize its total amount of deformation during operation. Deformation [μm] 10 5 0-5 -10-15 base base+5mm base+10mm Thickness of fixed scroll Pressure load Thermal load Welding Bolts Total Fig.7 Influence of fixed scroll thickness on the total deformation Table 2 Summarization of deformation factors Factor Amount of deformation [μm] Pressure load -11.6 Thermal load 6.9 Welding 2.0 Bolts 5.0 Total 2.3 4. DEFORMATION CONTROL OF ORBITING SCROLL 4.1 Pressure Deformation of the Orbiting Scroll During Operation Figure 8 shows the pressure deformation of the orbiting scroll when it is supported by the outer peripheral part of the fixed scroll under the rated operating condition. In addition, Figure 9 and 10 shows deformation along the tip of the wrap when the orbiting scroll is rotated at every 90. The pattern of the compression chamber varies in accord with the orbiting angles. As shown in Fig.9 and 10, we found that the orbiting scroll is deformed by pressure by 5-9 μm with the compressor upward direction designated to be positive. Fig.8 An example of FEM result of pressure deformation

C140, Page 6 Deformation [mm] 9.00E-03 90[deg] 8.00E-03 7.00E-03 6.00E-03 5.00E-03 4.00E-03 3.00E-03 2.00E-03 1.00E-03 0.00E+00 0[deg] 270[deg] 180[deg] 0 1 2 3 4 5 0.00E+00 5.00E+01 1.00E+02 1.50E+02 2.00E+02 2.50E+02 Reference position on the tip of the orbiting wrap 0[deg] 90[deg] 180[deg] 270[deg] Fig.9 Reference position on the orbiting scroll Fig.10 Deformation of the tip of the orbiting wrap 4.1 Optimum Slope Shape of the Orbiting Scroll The pressure deformation of the orbiting scroll can be calculated, because the pattern of compression chamber also can be calculated by using CFD or other numerical analysis. But, the thermal deformation cannot be calculated, because we cannot measure the temperature distribution on the orbiting scroll, as same as for the case of the fixed scroll. Moreover, the orbiting scroll is unable to be controlled by providing the initial deformation from the outside. Thereupon, in order to cancel the pressure and thermal deformation, a slope shape is adopted for both the tip of the wrap and the bottom of the wrap. The FEM analyses were made under the high load condition. Based on that analysis results, with respect to the tip of the wrap, we made the tip slope shape that the height of the wrap decreases, as the orbiting scroll wrap comes closer to the center. With respect to the bottom of the wrap, we made the bottom slope shape that the depth of the bottom becomes deeper from the outside than that in the outside. Figure 11 shows the performance characteristics under the rated conditions by changing the amount of slope at the tip of the wrap, where the horizontal axis indicates the ratio of the amount of tip slope to that of bottom slope. The amount of slope at the bottom of the wrap was fixed to the maximum deformation calculated under the high load condition. As shown in Fig. 11, as the amount of slope at the tip of the wrap increases, the refrigeration capacity reduces, thus causing the increase of leakage from the tip of the wrap. With respect to the compressor input, the increase of input resulting from the increase of re-compression loss caused by leakage was observed. In the meantime, when the ratio of the amount of tip slope to that of bottom slope became 1.5 times or lower, severe contact occurred at the tip of the wrap under high load conditions. This result indicates that the wrap deformation caused by temperature difference must be taken into account in addition to the pressure deformation. By adopting the slope shape, even if the orbiting scroll is deformed by pressure during operation, the clearance at the tip of the wrap can be reduced, thus reducing the sliding loss and local contact caused by contact between the orbiting scroll and the fixed scroll, and thereby the leak loss can be also reduced. 1.005 1.06 Q: Ref. Capacity ratio 1 0.995 0.99 0.985 0.98 Q W 1.05 1.04 1.03 1.02 1.01 1 W: Comp. Input ratio 0.975 0.99 1 1.5 2 2.5 3 tip slope / bottom slope Fig.11 Performance characteristics of the tip/bottom slope

C140, Page 7 5. CONCLUSIONS We examined a scroll compressor for a CO 2 heat-pump system to obtain the following conclusions: Deformations of the fixed scroll were analytically and experimentally investigated for significant factors during operation. Based on the analysis results, deformations during operation can be minimized by providing proper stiffness and initial deformation to the fixed scroll. A slope shape was introduced, taken into account with pressure and thermal deformations of the orbiting scroll, and both high efficiency and high reliability were satisfied. Based on the above developments, the present study contributed to achievement of the industry s top-class COP in CO 2 heat-pump water heaters, which can be maintained at its high performance, even when high-pressure CO 2 refrigerant is used. NOMENCLATURE Q W Refrigeration capacity ratio Compressor input ratio REFERENCES Kawabe, I., 2005, Technologies for Improvement of Rotary Compressor Efficiency, Refrigeration, 80(933), 10-13. Hiwata, A., Iida, N., Futagami, Y., Sawai, K., Ishii, N., 2002, Performance Investigation with Oil-injection to Compression Chambers on CO 2 -Scroll Compressor, 16 th International Compressor Engineering Conference at Purdue, West Lafayette, Indiana, USA, C18-4. Ishii, N., Kawamura, S., Yamamoto, S., Sawai, K., Hiwata, A., Kawano, H., Ting, K. S., 2002, Efficiency Simulations of a Compact CO 2 Scroll Compressor and its Comparison with Same Cooling Capacity R410A Scroll Compressor, 16 th International Compressor Engineering Conference at Purdue, West Lafayette, Indiana, USA, C22-3. Hiwata, A., Futagami, Y., Morimoto, T., Iida, N., Sawai, K., Aiba, O., 2004, Stability Improvement of the Orbiting Scroll in CO 2 Scroll Compressor, Proc. of 9 th National Symposium on Power and Energy Systems, 443-448. Hiwata, A., Iida, N., Futagami, Y., Sawai, K., Ishii, N., 2004, New Thrust Bearing Groove to Control the Overturning for CO 2 Scroll Compressor without Accumulator, 17 th International Compressor Engineering Conference at Purdue, West Lafayette, Indiana, USA, C078. Hiwata, A., Futagami, Y., Morimoto, T., Iida, N., Sawai, K., Aiba, O., 2004, Development of Accumulator- less CO 2 Scroll Compressor, Proc. of Int l Symposium on New Refrigerants and Environmental Technology, 216-221. ACKNOWLEDGEMENT The authors would like to express their sincere thanks Sawai, K., Aiba, O., Shintaku, H., and Shimada, K. for their supports in developing the present CO 2 scroll compressor with high performance.