Field Studies of Subjective Effects on Thermal Comfort in a University. Classroom

Similar documents
A Field Study of the Thermal Environment in Residential Buildings in Harbin

PREDICTION OF THERMAL SENSATION IN NON-AIR- CONDITIONED BUILDINGS IN WARM CLIMATES

SUBJECTIVE AND MEASURED THERMAL COMFORT IN ITALIAN UNIVERSITY CLASSROOMS IN HEATED AND FREE RUNNING CONDITIONS

REDEFINING APPROPRIATE THERMAL COMFORT STANDARD FOR NATURALLY VENTILATED BUILDINGS IN TROPICS (SINGAPORE AND INDONESIA PERSPECTIVE)

Environmental and human factors influencing thermal comfort of office occupants in hot-humid and hot-arid climates

Thermal environment and thermal comfort in a passive residential building in the severe cold area of China

RADIANT SLAB COOLING: A FIELD STUDY OF OCCUPANT THERMAL COMFORT. Zhen Tian 1, James A. Love 2

A Field Study of Thermal Comfort in Open-plan Office Buildings during Transition Seasons in Harbin. Yunsong Han 1, 2, Huixuan Sun 1, 2, Cheng Sun 1, 2

A Comparison of Calculated and Subjective Thermal Comfort Sensation in Home and Office Environment

Investigation and Analysis of Winter Classroom Thermal Environment. In Chongqing

Thermal Comfort Zone for Thai People

A PRELIMINARY THERMAL COMFORT STUDY IN TROPICAL BUILDINGS LOCATED IN MALAYSIA

AN ASSESSMENT OF THERMAL COMFORT IN NATURALLY VENTILATED ARCHITECTURAL STUDIO IN ABIA STATE UNIVERSITY, UTURU

Thermal comfort assessment of Danish occupants exposed to warm environments and preferred local air movement

Energy and indoor temperature consequences of adaptive thermal comfort standards

Designing Air-Distribution Systems To Maximize Comfort

Shifting Comfort Zone for Hot-Humid Environments

A Thermal Comfort Investigation of a Facility Department of a Hospital in Hot-Humid Climate: Correlation between Objective and Subjective Measurements

Available online at ScienceDirect. Procedia Engineering 169 (2016 )

Findings of Field Survey for Thermal Comfort and Ventilation in US Office Buildings

Radiant Floor Cooling Combined with Mixing Ventilation in a Residential Room Thermal Comfort and Ventilation Effectiveness

REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS. Galway, Ireland

Comparison between thermal comfort predictive models and subjective responses in Italian university classrooms

THERMAL COMFORT OF A COURTYARD IN GUANGZHOU IN SUMMER

PERSONAL COOLING USING THERMAL CONDUCTION ON THE DESK

Prediction of Thermal Comfort. mech14.weebly.com

Optimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016

Energy simulation of traditional vs. adaptive thermal comfort for two

Thermal Environment evaluation in commercial kitchens

ATBU, Journal of Science, Technology & Education (JOSTE); Vol. 3 (4), December, 2015 ISSN:

Energy and Buildings

STUDIES ON THERMAL COMFORT AND ENERGY CONSUMPTION OF HVAC SYSTEM

Thermal Environment evaluation in Commercial kitchens: Procedure of data collection

Evaluation methods for indoor environmental quality assessment according to EN15251

An Employee Thermal Comfort Model for Semiconductor Manufacturing

CLIMATE CONTROL: INTENT/CRITERIA

COMFORT MODEL FOR LOCAL COOLING. Yufeng Zhang 1 and Rongyi Zhao 2. Beijing, , P.R. China

THERMAL COMFORT IN LECTURE HALLS IN THE TROPICS

Air Movement Preference and Thermal Comfort A survey in classrooms during summer season in Brazil

Energy simulation of traditional vs. adaptive thermal comfort for two moderate climate regions Hensen, J.L.M.; Hensen Centnerová, L.

Thermal comfort recent challenges

Thermal Comfort Evaluation of HDB flats

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

An Assessment of Thermal Comfort in Hot and Dry Season (A Case Study of 4 Theaters at Bayero University Kano)

Adaptive thermal comfort explained by PMV

Thermal comfort evaluation of natural ventilation mode: case study of a high-rise residential building

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

EXPERIMENTAL AND THEORETICAL THERMAL COMFORT ANALYSES IN HIGHER EDUCATION BUILDINGS IN BUCHAREST

The applicability of the ISO 7730 (Fanger's comfort model) and the adaptive model of thermal comfort in Jakarta, Indonesia.

INVESTIGATING THE EFFECT OF CO 2 CONCENTRATION ON REPORTED THERMAL COMFORT

Allowing for Thermal Comfort in Free-running Buildings in the New European Standard EN15251

ISO 7730 INTERNATIONAL STANDARD

Research of Thermal Comfort for Side Air Supply Pattern in Office

COMPUTER MODELING OF UNDERFLOOR AIR SUPPLY SYSTEM

Thermal Comfort Assessment Based on Measurement and Questionnaire Surveys in a Large Mechanically Ventilated Space

Assessment of thermal comfort in shopping centre transitional spaces

CLIMATE CONTROL: OPR

Human response to individually controlled micro environment generated with localized chilled beam

FIELD MEASUREMENT OF A RESIDENTIAL FLOOR COOLING SYSTEM AND EVALUATION OF HUMAN THERMAL COMFORT

The Response of Human Thermal Perception and Skin Temperature to Step-Changed Activity Level

Information paper 17. Prepared by: David Clark. book:

Short-term acclimatization effects in an outdoor comfort study

Thermal comfort under transient seasonal conditions of a bioclimatic building in Greece

IMPLICATIONS OF CLIMATE CHANGE AND OCCUPANT BEHAVIOUR ON FUTURE ENERGY DEMAND IN A ZERO CARBON HOUSE

Thermal Comfort Survey in Office Buildings in Bandung, Indonesia

Quantifying Comfort to Assist in the Window Selection Process

Work environment. Microclimate - definition. Main microclimate elements. Core temperature. Microclimate

SET. An analysis of thermal comfort in primary schools in Vietnam BOLOGNA. Thi Ho Vi LE 1, Mark GILLOTT 2, Lucelia RODRIGUES 3

Perception of Thermal Comfort for Naturally Ventilated High School Classrooms in San Rafael, CA

Thermal comfort and occupant adaptive behaviour in university offices with cooling and free running modes

Artificial Neural Network Models Using Thermal Sensations and Occupants Behavior for Predicting Thermal Comfort

Experimental investigation on a ceiling capillary radiant heating system

Comfort models as applied to buildings

COMFORT IN AUSTRALIAN OFFICES

Thermal Comfort Model for Educational Institutions in Kerala

Assessment of thermal comfort near a glazed exterior wall

Adaptive Thermal Comfort in Warm Dry Climate: Economical dwellings in Mexico

Thermal Comfort in a Naturally-Ventilated Educational Building

Performance Investigation of Building Ventilation System by Calculating Comfort Criteria through HVAC Simulation

Micheal Okpara University of Agriculture Umudike. Abstract

Available online at ScienceDirect. Procedia Engineering 145 (2016 ) 18 25

Energy and Comfort in School Buildings in the South of Portugal

VARIABILITY OF THERMAL STRATIFICATION IN NATURALLY VENTILATED RESIDENTIAL BUILDINGS. Stephanie Gauthier 1, David Shipworth 1

Evaluation of Thermal Comfort of Men and Women in Food Courts

SIMULATION OF BUILDING THERMAL PERFORMANCE IN AN INSTITUTIONAL BUILDING IN SUBTROPICAL CLIMATE

Assessing the ability of PMV model in predicting thermal sensation in naturally ventilated buildings in UK

BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1

ENERGY SIMULATION AND ANALYSIS OF AN INTERMITTENT VENTILATION SYSTEM UNDER TWO CLIMATES

Mechanical Engineering Department, Suresh Gyan Vihar University, Jaipur India 3

Impacts of Indoor Temperature and Velocity on Human Physiology in Hot Summer and Cold Winter Climate in China

GREEN CONCEPT OF THERMAL COMFORT DESIGN FOR SUSTAINABLE HOUSING IN THE TROPICS: Learning from Thermal Comfort in School Buildings 1 INTRODUCTION

Towards Adaptive PMV/PPD Indices for European Climates

THE ROLE OF ENVIRONMENTAL AND PERSONAL VARIABLES IN INFLUENCING THERMAL COMFORT INDICES USED IN BUILDING SIMULATION. Stephanie Gauthier 1

Thermal comfort study of residents in Mlaten housing Semarang, Indonesia

Designing for thermal comfort near a glazed exterior wall. * School of Engineering, Auckland University of Technology, Auckland, New Zealand

Thermal Comfort Evaluation of a Heat Pump System using Induced-air Supply Unit

Do the constants used in adaptive comfort algorithms reflect the observed responses of children in junior school classrooms?

Indoor comfort and air quality in spaces equipped with eco-ventilation systems

Thermal comfort study of hospital workers in Malaysia

Transcription:

Field Studies of Subjective Effects on Thermal Comfort in a University Classroom Jian Wang Zhaojun Wang Master Associate Candidate Professor School of Municipal & Environmental Engineering, Harbin Institute of Technology Harbin P. R. China,159 wj9481424@sohu.com Abstract: Two field studies were conducted in a university classroom in the autumn of 24 in Harbin. The objective of these studies was to assess the thermal conditions and the subjective effects on occupant thermal comfort. A field study was carried out when the undergraduate students were not taught the theory of thermal comfort. A second study was conducted after the undergraduate students knew something about thermal comfort. The thermal comfort variables were measured when the students were filling in the subjective questionnaires on thermal sensation and thermal comfort. A total of 167 sets of questionnaire responses were obtained. The indoor thermal environmental data for the two days are almost the same; however the thermal acceptability is different. The acceptability of the first study is 96.%, which is higher than the acceptability of 91.5% according to the PPD. In contrast, the acceptability of the second study is 57.4%, which is very low compared with the acceptability of 95.% according to the PPD. The students thermal acceptability of the thermal environment before learning the theory of thermal comfort is higher than after learning about thermal comfort. These results confirm the existence of subjective effects on thermal comfort. Key words:thermal environment, thermal sensation, thermal comfort, field study, subjective effect 1. INTRODUCTION Because of the limitation of the climate chamber, many field studies on the thermal comfort have been performed around the world (Webb 1949-195, Schiller et al. 1988, Leow 1988, Busch 199, Dedear and Fountain 1994, Donnini et al. 1996, Sharples 1997, Cena and Dedear 1999, Xia et al. 1999, Wang et al. 23, Wang et al. 26). This field study was carried out in September 24 in order to investigate the thermal environment and thermal comfort in a university classroom in Harbin, situated in the northeast of China. 2. OBJECTIVES The object of this field study is to assess the thermal conditions and the subjective effect on human s thermal comfort. 3. RESEARCH METHODS The field study was carried out on 16 th September 24 when the undergraduate students were not taught the theory of thermal comfort. The second one was done on 3 th September 24 after the undergraduate students knew something about the thermal comfort. We measured the hourly values of the outdoor dry bulb temperature and relative humidity. And the thermal comfort variables of indoor were measured from 13:3 to 14:3 on these two days when the students were filling in the subjective questionnaires on the thermal sensation and thermal comfort. To avoid the effect of outdoor environment, the study was conducted after the students had been at the classroom for half an hour at least. Objective physical measurements were carried out at five points in each classroom. The approximate locations of five points are shown in Fig. 1.

Fig. 1 Plane of measurement points for physical parameters in the classroom An indoor climate analyzer made in Denmark was used to collect the measured parameters of the indoor environment. The physical data include air temperature, relative humidity, radiant asymmetry, and air velocity. Air temperature and air velocity were measured at the.1,.6, and 1.1 meter levels, representing the immediate environment of sedentary occupants ankles, mid-body, and neck, respectively. Relative humidity was measured at the 1.1 meter level. Radiant asymmetry was measured at the.6 meter level for seated occupants. The subjective questionnaires include background survey, clothing and activity checklists, thermal sensation, thermal preference and thermal acceptability survey, thermal comfort and air condition survey and adapted measures survey. 4. RESULTS 4.1 The Outdoor Dry Bulb Temperature and Relative Humidity The hourly values of the outdoor dry bulb temperature and relative humidity on these two days are presented in Fig. 2 and 3, respectively. On 16 th September, there was a drizzle all day. The mean value of outdoor dry bulb temperature and relative humidity were 2.9 and 79.2%, respectively. And those were 22.5 and 71.3% from 13: to 15:. On 3 th September, a shower occurred at 13:. The mean value of outdoor dry bulb temperature and relative humidity were 6.7 and 63.4%, respectively. And those were 6.8 and 69.3% from 13: to 15:. During this field measurement, the windows were open and natural ventilation was used in classrooms. Outdoor environmental parameters may influence indoor physical data as well as subjective evaluation on thermal sensation. When a subject comes into a warm room from outdoor with lower temperature, he feels warmer than before, vice versa. The outdoor air temperature of 3 th September is lower than that of 16 th September. On the other hand, indoor air temperature of 3 th September is 12~15 higher than outdoor temperature. Students should felt warmer when they came into the classroom from outside. However, they felt cold. Dr y bul b temper at ur e ( ) Out door dr y bul b t emperature and rel ati ve humi dity 25 2 15 1 5 7: 9: 11: 13: 15: Ti me( hour s) 17: 1 8 6 4 2 The out door dr y bul b t emper at ur e The outdoor rel ati ve humidity Rel at i ve humi dity(%) Fig. 2 Outdoor hourly dry bulb temperature and Dr y bul b temperature ( ) relative humidity on 16 th September Out door dr y bul b t emperature and rel ati ve humi dity 1 8 6 4 2 7: 9: 11: 13: 15: Ti me( hour s) 17: 1 8 6 4 2 The out door dr y bul b t emperature The out door r el at i ve humi dity Rel at i ve humi dity(%) Fig. 3 Outdoor hourly dry bulb temperature and relative humidity on 3 th September 4.2 The Indoor Physical Data The indoor physical data of 16 th September and 3 th

September are shown in Table 1. The indoor physical data include air temperatures(t a ), relative humidities (φ), air velocities(v), mean radiant temperature(t r ) and operative temperatures(t o ). Table 1 Indoor physical data 16 th September 3 th September t a / 26. 21.6 φ 55% 34% v/m s -1.15.12 t r / 25.9 22.8 t o / 25.9 22.2 4.3 The Background of the Occupants 167 sets of questionnaire responses were obtained. The results about the background of the subjects are given in Table 1 and 2. And the subjects participating on 16 th were composed of 69 females (69.7%) and 3 males (3.3%) and that on 3 th were composed of 49 females (72.1%) and 19 males (27.9%). Table 2 and 3 show that most students adapted the climate of Harbin when they have been in Harbin for more than 4 years averagely. Table 2 Statistics on the subjects on 16 th September Age / years Length of time Living in Harbin/years Mean 23.2 4. Standard deviation.99 5.31 Maximum 26 23 Minimum 2 2 Table 3 Statistics on the subjects on 3 th September Age / years Length of time Living in Harbin/years Mean 23.1 4.8 Standard deviation 1.2 6.72 Maximum 26 24 Minimum 2 2 4.4 The Insulation of Clothes The insulation of clothes (clo) is obtained from tables (ISO 773) based on clothes checklists. The insulation of clothes of 16 th is.57clo (.88 m 2 K / W) and that of 3 th is 1.clo (.155 m 2 K / W). On average, the chair insulation increment amounts to clo (McCullough et al. 1994). 4.5 Metabolic Rates During the measuring, the students were sitting and filling in the questionnaires, the metabolic rates (met) of the subjects are estimated to be, on average, 1.2 met (7 W/m 2 ). 4.6 PMV-PPD The values of calculation of PMV(Predicted Mean Vote) and PPD(Predicted Percentage of Dissatisfied) indices are given in Table 4. The thermal comfort condition regulated by ASHRAE 55-22 comfort standard is PPD<2% (the natural ventilation). The indoor environment of 16 th September is slightly warmer than neutral, and PPD is 8.5%, which is less than 2%. And that of 3 th September is slightly cooler than neutral, and PPD is 5.%, which is less than 2%. The indoor environment of 3 th September is more comfortable than that of 16 th September. Table 4 Results of PMV-PPD indices 16 th September 3 th September PMV.496 -.197 PPD 8.4971 5.8 4.7 Thermal Sensation The distribution of TSV (Thermal Sensation Vote) on 16 th and 3 th September is shown in Fig. 4 and 5. Di s t r i but i on/ % 5% 4% 3% 2% 1% % -3-2 -1 1 2 3 TSV Fig. 4 Distribution of thermal sensation votes on 16th September

Di s t r i but i on/% 35% 3% 25% 2% 15% 1% 5% % -3-2 -1 1 2 3 TSV Fig. 5 Distribution of thermal sensation votes on 3th September The statistics of thermal sensation votes is given in Table 5. Table 5 Statistics of thermal sensation votes 16 th September 3 th September Mean.32-1.72 Standard deviation 1.21 1.5 Maximum 3 Minimum -3-3 From the table we can see that there are deflections between MTS (Mean Thermal Sensation) and PMV. MTS (.32) of 16 th September is lower than PMV (.496), which shows that the students thermal sensations of 16 th September are closer to the thermal neutrality than the prediction. MTS (-1.72) of 3 th September is lower than PMV (-.197), which shows that the students thermal sensations of 3 th September are more uncomfortable than the prediction. 4.8 Thermal Acceptability The indoor thermal environmental data for the two days are almost the same, however the acceptability is different. The acceptability of the first study is 96.%, which is higher than the acceptability (91.5%) according to the PPD. On the opposite, the acceptability of the second study is 57.4%, and it is very low compared with the acceptability (95.%) according to the PPD. 5. CONCLUSIONS The indoor thermal environment is comfortable according to the PMV-PPD indices. MTS of 16 th September is close to PMV, but MTS of 3 th September is much lower than PMV. The deflection between MTS and PMV of 3 th September is more evident than that of 16 th September. The acceptability of the first study is closer to the acceptability according to the PPD than that of the second study. PPD of 16 th September is higher than that of 3 th September. However, the acceptability of that day is higher than the latter. Because the students had not learned some knowledge about thermal comfort until 28 th September. This shows that students are sensitive to the environment after they have some knowledge about thermal comfort. And they are more expected to the environment than before. The students thermal acceptability for thermal environment before learning the theory of thermal comfort is higher than that after they have learned the knowledge about thermal comfort. This indicates that the subjective effect on the thermal comfort exists. REFERENCES [1] C.G. Webb, An analysis of some observations of thermal comfort in an equatorial climate, British Journal of Industrial Medicine. 1959.16: 297 31. [2] G.E. Schiller, E.A. Arens, F.S. Bauman, et al. A Field Study of Thermal Environment and Comfort in Office Buildings. ASHRAE Trans. 1988,94(2):28~38 [3] K.G. Leow, Thermal Neutrality of Nonair-Conditioned Building Occupants in Singapore. Unpublished Thesis, Department of Geography, National University of Singapore, 1988. [4] J.F. Busch. Thermal Responses to the THAI Office Environment. ASHRAE Trans. 199,96(1):859~872 [5] R.J. Dedear, M.E. Fountain. Field Experiments on Occupant Comfort and Office Thermal Environments in a Hot-Humid Climate. ASHRAE Trans.1994, 1(2):457~475 [6] G. Donnini, J. Molina, C. Martello, et al. Field Study of Occupant Comfort and Office Thermal Environments in a Cold Climate. ASHRAE Trans. 1996,12(2):795~82 [7] S. Sharples, A. Malama. A Thermal Comfort Field Survey in the Cool Season of Zambia. Building and Environment. 1997, 32(3):237-243

[8] K. Cena, R.J. Dedear. Field Study of Occupant Comfort and Office Thermal Environments in a Hot, Arid Climate. ASHRAE Trans. 1999,15(2):24~217 [9] Y.Z. Xia, R.Y. Zhao, and Y. Jiang. Thermal comfort in naturally ventilated houses in Beijing. HV&AC. 1999.29(2): 1-5. [1] Zhao-jun Wang, Gang Wang. Le-Ming Lian. A Field Study of the Thermal Environment in Residential Buildings in Harbin. ASHRAE Transactions. 23. 19(2): 35-355. [11] Zhaojun Wang. A Field Study of the Thermal Comfort in Residential Buildings in Harbin. Building and Environment. 26. 41(3) : 134-139. [12] McCullough.E.A, B.W. Olesen, and S. Hong. Thermal insulation provided by chairs. ASHRAE Transactions.1994.1(1): 795-82. [13] ISO 773. Moderate Thermal Environment- Determination of the PMV and PPD Indices and Specification of the Conditions for Thermal Comfort[S]. Geneva: International Standard Organization. 1994. [14] ASHRAE 55-22. Thermal Environmental Conditions for Human Occupancy[S]. Atlanta: American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc. 22.