Quality Built, LLC Tech Alert April 2016 Volume 3, Issue 3

Similar documents
Quality Built, LLC Tech Alert March 2016 Volume 3, Issue 2

The Enduring Mystery of Weather Resistive Barriers and the Need for Standards

Keene Building Products

breathability to prevent the potential for moisture condensation within exterior walls...

Forensics Engineering 8th Congress Forging Forensic Frontiers November 29 December 2, 2018, Austin, TX

DuPont RainVent Batten Installation Guidelines

Moisture Considerations for Insulated Building Assemblies

PlyDry is specified by builders who need a perforated housewrap that meets code requirements at a very affordable price...

Rainscreen Gaps in Exterior Walls

Technicalbulletin #16

Understanding High Perm vs. Low Perm

How-to: Commissioning Design Reviews for the Building Envelope

A. This Section provides information regarding vapor permeable roof underlayment for the exterior roof.

Rain. Building Science. Rain is the largest source of moisture We need better control for better insulation and airtightness Rain penetration control

BREATHABLE MEMBRANES. Canada Inc. Water Vapour Permeable, Air Barriers for Sloped Roofs & Rain Screen Wall Systems

BULLETIN FROM THE FIRST COAST CHAPTER ICC~BOAF

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS SECTION: AIR BARRIERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS SECTION: AIR BARRIERS

SRP-AirOutshield UV Issued:

The Right Balance of Breathability.

NOVAWRAP ASPIRE Q & A

SINGLE FAMILY USER S BULLETIN FOR INSTALLATION OF DUPONT WEATHERIZATION SYSTEMS PRODUCTS

INSTALLING WATER-RESISTIVE BARRIERS & FLASHING

Insulation. First Revison October DC14 Drainage Mat INSTALLATION GUIDE FOR RESIDENTIAL & COMMERCIAL APPLICATIONS

DuPont. Tyvek Sheathing Membrane Installation Guidelines. Version 2. Canadian Version

SELECTION TOOL FOR WATER-RESISTIVE BARRIERS WITH SUITABLE VAPOUR PERMEABILITY

8/14/2015. Course Description. Course Objectives AIR, WATER, AND MOISTURE MANAGEMENT IN LIGHT COMMERCIAL BUILDING ENVELOPES

FirstEnergy Program Overview

Inspection Fundamentals: Stucco & EIFS

BENJAMIN OBDYKE INCORPORATED

SECTION SELF-ADHERING SHEET FLASHING

Bituminous Building Paper

SECTION SELF-ADHERED WATER-RESISTIVE ROOF UNDERLAYMENT

SPECIFICATION GUIDELINE

Henry NFPA 285 Air Barrier Assemblies

SRP-AirOutshield ROOF Issued:

REPORT HOLDER: SOPREMA, INC. 310 QUADRAL DRIVE WADSWORTH, OHIO EVALUATION SUBJECT:

New Air and Vapor Barrier Technologies

80201 StoColor Acryl Flat Acrylic-Based, Vertical Above-Grade Exterior Wall Coating for New Concrete, Stucco, and Masonry Construction

2019 IAQA Annual Meeting

SECTION CONCRETE AND MASONRY COATINGS

80230 StoColor Coat Sand Acrylic-Based, Vertical Above-Grade Exterior Wall Coating for New Concrete, Stucco, and Masonry Construction

WEB BASED APPLICATION SPECIFIC INSTALLATION INSTRUCTIONS

Building Science Control Layer Glossary. Façade Visible exterior face of a building, usually vertical or nearly so, but imprecisely used.

GLOBAL PROPERTY INSPECTIONS TECHNICAL BULLETIN

Effective Envelope Design Mitigating Risk with High Performance Panels and Acrylic Flashing Systems

Compliance for Continuous Insulation, Water Resistive Barriers & NFPA-285 What you need to Know

80657 StoColor Texture - Fine Textured Acrylic-Based, Vertical Above-Grade Exterior Wall Coating for New Concrete, Stucco, and Masonry Construction

MOISTURE VAPOR MOVEMENT AND VAPOR PERMEANCE

Integrated Air & Water Barrier Systems

Table Weather-Resistant Siding Attachment and Minimum Thickness. Omission of Weather-Resistant Membrane

REPORT HOLDER: BASF CORPORATION EVALUATION SUBJECT: MASTERSEAL AWB 660 I VAPOR RETARDER, AIR AND WATER-RESISTIVE BARRIER AND FLEXIBLE FLASHING

Innovating Continuous Exterior Insulation. Theresa A. Weston, PhD. 1

Incorporating Insulating Sheathing into the Design of the Thermal and Moisture Management System of the Building Enclosure

PRODUCT CERTIFICATE THIS IS TO CERTIFY THERMAKRAFT STEELWRAP 290 WALL UNDERLAY

Gensler 2014/06/16 Hertz Global Headquarters ISSUE FOR BUILDING PERMIT Estero, Florida SECTION

December 1, 2014 PARTIES INTERESTED IN WATER-RESISTIVE BARRIERS

MULTI-FAMILY USER S BULLETIN FOR INSTALLATION OF DUPONT WEATHERIZATION SYSTEMS PRODUCTS

DuPont Tyvek Wall Underlay Install Guide

GA APPLICATION OF GYPSUM SHEATHING

Armourwall Stucco Systems

StoGuard Air Barrier Installation Manual

AIR BARRIERS & WATER-RESISTIVE BARRIERS

SECTION THERMAL INSULATION

Session: Foam Plastic Insulation Exterior Wall Fire Safety

Wall Selection Guide Section 1.1

80648 StoColor Acryl Plus Acrylic-Based, Vertical Above-Grade Exterior Wall Coating for New Concrete, Stucco, and Masonry Construction

SECTION FLUID-APPLIED VAPOR PERMEABLE MEMBRANE AIR BARRIER SYSTEM ASSEMBLY (August 2013)

SPECIFICATION GUIDELINE

2. The building envelope shall comply with all applicable requirements in Section of ANSI/ASHRAE/USGBC/IES Standard

A. Section includes fluid applied, vapor permeable membrane air barriers.

2002 Advanced Building Products, Inc., P.O. Box 98, Springvale, Maine TEL: ; FAX: ; WEBSITE:

Bituminous Roofing Underlay & Valley Guard

Building Code Compliance Building Science

WEB BASED APPLICATION SPECIFIC INSTALLATION INSTRUCTIONS

ESR-2072 Reissued September 1, 2013 This report is subject to renewal September 1, 2015.

Top 7 Reasons to Include a Drainage and Ventilation Plane in Adhered Masonry Walls

CALIFORNIA COMMERCIAL BUILDING INSPECTOR CONTENT OUTLINE 01. GENERAL ADMINISTRATION 6% Project Administration 1%

Technical Data Sheet

SECTION FLUID-APPLIED MEMBRANE AIR BARRIERS, VAPOR PERMEABLE

LISTING INFORMATION OF Epilay - Superior, Ultra and Platinum Roofing Underlayments SPEC ID: Epilay Inc S. Main Street, E1 unit C

DIVISION 7 THERMAL AND MOISTURE PROTECTION

80657R StoColor Texture Fine Textured Acrylic-Based, Vertical Above-Grade Exterior Wall Coating for Recoating Prepared, Previously Painted Surfaces

80657R StoColor Texture Fine Textured Acrylic-Based, Vertical Above-Grade Exterior Wall Coating for Recoating Prepared, Previously Painted Surfaces

DUPONT TYVEK COMMERCIAL SOLUTIONS

REPORT HOLDER: PAREX USA, INC EAST LA PALMA AVENUE, SUITE 250 ANAHEIM, CALIFORNIA EVALUATION SUBJECT:

BSC Information Sheet 500 Building Materials Property Table for All Climates

RevealShield SA Penetrations

Weather Resistive Barriers and Flexible Flashings. AAMA WESTERN REGION MEETING September 16 17, 2003 Ontario Airport Marriott

Competitive Product Analysis

80201R StoColor Acryl Flat Acrylic-Based, Vertical Above-Grade Exterior Wall Coating for Recoating Prepared, Previously Painted Surfaces

Product and System Specifications DuPont Flashing Systems

Finestone Stucco System

** NOTE TO SPECIFIER ** Delete any sections below not relevant to this project; add others as required. A. Section Mechanical Insulation.

Remediating Building Envelope Walls: Drainage Plane Designs

United States R E S I D E N T I A L. The Value of Residing With STYROFOAM Brand XPS Insulation

0103 Plan Reading 4% Read plans to verify the project conforms with the code, approved plans, and construction documents.

ACCEPTANCE CRITERIA FOR WATER-RESISTIVE BARRIERS PREFACE

Section COATING RESTORATION

Transcription:

Quality Built, LLC Tech Alert April 2016 Volume 3, Issue 3 By:Jeff Hoch & Clay Highfill THE EVER-EVOLVING BUILDING ENVELOPE A Three Part Series On Flashing, Air Barriers and Stucco Part 3: Stucco Over DuPont Tyvek HomeWrap Question: What do you do when the building codes require the Air Barrier and Weather- Resistive Barrier (WRB) to be installed per the manufacturer s specifications, and those specifications seem to result in improper lapping and/or possible water entrapment? Many well-known Building Science Consultants have determined that exterior cement plaster, AKA stucco, has a tendency to bond with the weather-resistive barrier (WRB) installed beneath. With this being said, many consultants and manufacturers recommend installing two layers behind the stucco, even if not required by the building code. The building code requires two layers, or equivalent, over wood-based sheathings when the cladding is a cementitious product; however, many consultants still advise that two layers are the best practice, even when not applied over wood-based sheathings. Additionally, some manufacturers may refer to the installation of a second layer as a bond break. For more information on this and how this affects flashing installations, see Part One of our series on The Ever-Evolving Building Envelope - Flashing Integration.

In addition to those who recommend this bond break layer approach, Tyvek also suggests using a bond break layer over wood-based sheathings. While this process is effective, questions such as, What is a bond break layer? and How does it impact the system as a whole? continually arise. The extending concern tends to be in relation to the compatibility of products, both from the point of chemical compatibility, as well as whether the different permeability ratings for the different products will work together. Tyvek s preferred recommendation is that both layers be a Tyvek wrap. While this seems logical, based on chemical compatibly, in terms of permeability ratings, it is rare to see this as the installed condition while in the field. Generally, we observe Tyvek as the first or inner layer of the air barrier, with a black Grade D 60-minute building paper, such as Super Jumbo Tex installed as the bond break layer. Instead of discussing the reason for this, we will focus on the compatibility of the two products when used together as a complete system. As of the writing of this Tech Alert, there are no known chemical compatibility issues between Tyvek wraps and the black asphalt-saturated building papers, made by major manufacturers meeting the Grade D 60-minute specifications of ASTM. Moreover, Tyvek lists this as one of the possible options for the bond break layer between stucco and the air barrier. While determining whether their permeability ratings are compatible, and how this process affects the system as a whole, it is important to understand that permeability is a measure of the ability for moisture vapor to pass through a given material. For a more detailed

Vapor Barriers and Permeability Ratings. Tyvek indicates that their wraps have permeability rates of 28 to 58 perms. In their Building Science Bulletin titled Understanding High Perm vs Low Perm, Tyvek reveals that building paper has a permeability rate of 5 perms. However, some building scientists indicate that Building Paper has a rate of as low as 5 perms when dry, but that the perm rate increases in the presence of high humidity levels, and may exceed 60 perms when the relative humidity is as much as 95%. High humidity can increase permeability rates of home wraps by as much as 12x A potential problem with building paper is that it has the ability to absorb water. This is a generally accepted fact being that the amount of water the paper will absorb varies from brand-to-brand, as well as by the age of the product, and any prior UV exposure before installation of the cladding system. When used as the outermost layer in a two-layer system with Tyvek wrap as the innermost layer, the properties of the black paper may prove beneficial, especially when the cladding is an exterior cement plaster or adhered-masonry veneer. With Tyvek s high permeability rate drying of the wall cavity is promoted. Some have raised concerns about the lower permeability of the asphalt-saturated paper blocking or impeding the vapor transmission. This is less of a problem than anticipated based on the way permeability rates are tested. Permeability rates are tested on the field of the membrane and do not take into account the laps and seams, which are numerous in the installation of an asphalt-saturated paper WRB. The ability of the asphalt-saturated paper to absorb moisture may allow it to act as a buffer between the exterior cement plaster and the Tyvek wrap. With a vapor permeable

differential. Vapor will drive from areas of high pressure to areas of low pressure; therefore, if the plaster is saturated and the wall cavity is dry, the drive could be from the wet plaster into the dry wall cavity. In this case, the lower perm paper may slow transmission from the plaster to the wall cavity. When the transmission is from the wall cavity to the exterior, the paper may absorb and hold the moisture until the plaster can dry enough to allow the vapor to transfer through it. However, if we install the two layers using the outer layer as a bond break layer and draining the flashings between these two layers as indicated in the IBC Section 2510.6 and further discussed in our Tech Alert on Flashing Integration, do we meet the requirement to protect wood-based sheathing with the equivalent of two layers of WRB? We would argue that unless the innermost layer is equal to two layers of Type I WRB that the sheathing is not properly protected. The building code does allow for an exception to the two layers where the WRB over the sheathing is equal to or greater than a 60-minute Grade D paper in its ability to resist water penetration and the stucco cladding is separated from this WRB by a substantially nonabsorbent layer or drainage space. To better understand why the manufacturer, consultant, or building code may want to separate the bond breaker from the air barrier, read our Tech Alert on Air Barrier Fundamentals. We recommend that you work with a building envelope consultant to determine which materials or combination of materials you will be using for your project s building envelope. The installation of the building envelope is a high risk with the potential for damage and future litigation, and should be reviewed and inspected by a third-party quality assurance firm. Care should be taken to comply with codes, and to follow the best building science recommendations, while taking into consideration that the code is the minimum standard.

About the Authors Consultant and Technical Services Technician at Quality Built. Jeff has been a Licensed Architect for over 18 years. Jeff has worked as a forensic plans examiner and inspector for 18 of the past 25 years, as well as performing construction quality assurance inspections for over 10 years. He has performed thousands of inspections, while providing plans review, forensic inspections, and testing in many states. Jeff has an in-depth knowledge of Building Codes, Design Standards, Local Ordinances, Forensic Building Failure Analysis, and Construction Defects. You can reach Jeff at: jhoch@qualitybuilt.com Clay Highfill is a Checkpoint Template Creator, Field Consultant, and Technical Services Technician at Quality Built. Clay has been a certified building inspector for over 20 years. He has performed thousands of structural inspections, while providing plan review, code enforcement, and consulting services for an abundance of clients. Clay withholds an in-depth knowledge of building codes, design standards, and local ordinances. You can reach Clay at: clay@qualitybuilt.com