BUILDING AND PLANT ENERGY ANALYSIS REPORT

Similar documents
The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

Gerald R. Ford Museum

Building and Plant Energy Analysis Report. Instructor: Dr. Freihaut. October 6, Thesis Building Sponsor s: INOVA Fairfax Hospital

CREDIT COMPLIANCE (Please complete the color coded criteria(s) based on the option path selected)

Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal

Building and Plant Energy Analysis Report

Reed Berinato Mechanical Option. Building and Plant Energy Analysis Report October 27, Contents

Technical Assignment 2: Building and Plant Energy Analysis Report. Jason Jones Mechanical Option Multipurpose Athletic Center West Long Branch, NJ

Keith Beidel Mechanical Option Centre Community Hospital East Wing Expansion State College, PA 9/30/02

What s My Baseline? ASHRAE

how to read an energy model

Mechanical Technical Report Three Mechanical Systems Existing Conditions Evaluation

EnergyPro Building Energy Analysis. Nine-story Office Building

Building Energy Analysis for a Multi-Family Residential Building (Multi V III VRF Heat-Pump System)

EnergyPro Building Energy Analysis. Single-story School Building

SURNA Grow Facility: Systems Comparison - IEA

Energy Efficiency Analysis for a Multi-Story Research Office Building (LG Multi V Water IV Heat Recovery VRF System)

Technical Report Two: Building and Plant Energy Analysis Report

University of Minnesota Duluth Civil Engineering Building

Technical Report Three Mechanical Systems Existing Conditions Evaluation

Retail Effects of ANSI/ASHRAE/IES Standard

OPTION 1: PERFORMANCE RATING METHOD

Chapter 4. Analysis of Building Energy Performance

Analysis of the Energy Savings Potential in K-5 Schools in Hot and Humid Climates. Jeff S. Haberl, Ph.D., P.E.

Freetown Elementary School

Italcementi Center for Research and Innovation

Technical Report Three

BETA OPTION 1: PERFORMANCE RATING METHOD. Section General Information

Coppin State University Physical Education Complex - Technical Report 2

COMcheck Software Version Envelope Compliance Certificate

Georgetown University New Science Center

Technical Report: Three

Appendix E-1f: Small Building Methodology for Pre-SB2030 Projects

The Impact of VISIONWALL High Performance Windows on the Northern Telecom Building in Ottawa, Ontario

Thesis Proposal for Berks Classroom and Lab Building

Building Energy Efficiency Analysis for a High School

Technical Report 2: Building and Plant Energy Analysis

Building Energy Efficiency Analysis for a High School

Sustainable Building Operations & Upgrades

Technical Report 2. Bellevue Ambulatory Care Pavilion New York, NY. Building and Plant Energy Analysis

The baseline building system for compliance with Senate Bill 668 is defined by Appendix G,

WEST VIRGINIA UNIVERSITY ALUMNI CENTER Morgantown, West Virginia

White Paper ENVELOPE-FIRST APPROACH TO NET-ZERO ENERGY BUILDINGS

Building Envelope

Professional Educational Series BSP716 USGBC # Commercial Building Science Thermal Control in Building Envelopes

IECC 2006 with Hawaii Amendments

Final Thesis Report: Mechanical Alternative Systems

1. PREINSPECTION RESIDENTIAL ENERGY EFFICIENCY 7

Analysis II Energy Considerations for Green Roofs

South Jefferson High School Huyett Road Charles Town, WV 25414

City of High Point Airport Overlay District Noise Level Reduction Design Standards

Mechanical Systems Redesign Proposal. Thesis Proposal. Morton Hospital Expansion

780 CMR: 9 th Edition Massachusetts State Building Code. Presented to: BSA Codes Committee. DATE: January 20, 2016

ENSURING A PRODUCTIVE ENERGY MODELING PROCESS

Energy Code Analysis - Current Requirements & What is Coming International Energy Conservation Code & ASHRAE Standard 90.1

THE NEW YORK TIMES BUILDING

2-Pipe fan coil terminal units were selected as the parallel system to handle the remaining sensible cooling load.

Chilled Beams. The new system of choice?

Chapel House- Design Process- Envelope and Energy savings

Walter Reed National Military Medical Center Bethesda, MD

Energy Codes and the Building Envelope

Energy 10/19/2011. Inc. New. Castle, DEE. Image. By: Skanska

Michigan Energy Code Training and Implementation Program

LEED And Your Indoor Environment

LEED Energy Performance Summary Report

Tenant Fit-Out for PLCB / Waynesboro Mall

1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural %

Compliance Certificate

CAE 331/513 Building Science Fall 2017

AE 481W Thesis Proposal

Water Bottling Facility

MANHATTAN COLLEGE STUDENT COMMONS

Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort

BUILDING ENCLOSURE AIR TIGHTNESS TESTING Course Number: BCLUNA018-01P

Energy Analysis: The Impacts of the Curtain Wall System

GATES-HILLMAN CENTERS

NEW FOUR STORY MIXED USE RESTAURANT, RETAIL, LODGING, AND OFFICE BUILDING OWNER S PROJECT REQUIREMENTS

Presentation to Appalachian State University

CITY AND COUNTY OF DENVER DEPARTMENT OF PUBLIC WORKS STATEMENT OF QUANTITIES. Item No. Description Quantity Estimated Mobilization 1 LS

Analysis 1. LEED Analysis of Laboratory Buildings. Penn State School of Forest Resources University Park, PA

Mechanical Tech Report 2

NASA Langley Research Center Administration Office Building One Hampton, VA TECHNICAL REPORT 2. Building and Plant Energy Analysis Report

Energy Code Compliance:

IECC 2006 with Hawaii Amendments

Thermal Performance of Northern Facades ISO Clip System Summary

R-Value. Effective. Energy efficiency of masonry s thermal mass is recognized by code 9" 2" R21 + R18 THERMAL MASS +13 R13 R18

PURCHASE ORDER AMENDMENT A. Purchase For: Indiana University Unique Purchase Order Number: Purchase Order Effective Date: April 30, 2009

Technology and Engineering Development (TED) Building. ASHRAE Std and Std Compliance Report

Feature Zone IECC 2009 IECC

Technical Report #2. Matthew R Peyton

2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES)

Applying Geothermal Technology for Large Scale Projects

Dayton Chapter February 9, Bob Thomson, P.E., LEED-AP, CDT

NAME OF PROJECT Design Development. General Objectives of Phase. Phase Task Checklist. Quality Management Phase

G703 Continuation Sheet Minimum Schedule of Values Please use the breakdown listed below when submitting your billing for the project

Depth: Mechanical Redesign

Recommended Amendments to the

Technical Assignment 2 Building and Plant Energy Analysis

2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES)

Transcription:

BUILDING AND PLANT ENERGY ANALYSIS REPORT Alicia Carbin Longwood University s New Science Building in Farmville, VA 10-27-04

TABLE OF CONTENTS. 1.0 Executive Summary.........1 2.0 LEED Green Building Certification........2 3.0 ASHRAE Std. 90.1.....3 3.1 Building Envelope Compliance to ASHRAE Std. 90.1...3 3.2 Lighting Compliance to ASHRAE Std. 90.1...8 4.0 Lost Rentable Space due to Mechanical System.......9 5.0 Annual Energy Consumption and Emissions.......9 6.0 Mechanical System First Cost........12 7.0 Design Load Estimation.13 8.0 Cost Estimates, Life Cycle Analysis, and Operating Costs... 15 9.0 References.. 18

1.0 EXECUTIVE SUMMARY. This report is a plant and energy analysis of Longwood University s New Science Building. The LEED Certification system was discussed, however the building was not rated due to the fact that is not an office building. Even though the building was not rated, it has green building elements including a greenhouse and an energy control system. The science building s roof and glazing were found to comply with ASHRAE Standard 90.1 in regards to envelope compliance, however only half of the wall types comply with the standard. Most of the spaces comply to ASHRAE Standard 90.1 in regards to lighting compliance. The standard values were found using the Space by Space Method and the only spaces which did not comply were the enclosed offices and the corridors. The lost rentable space due to the mechanical system was found to be 2,886 square feet, which is 4% of the total building area. The building HVAC load and energy analysis procedures were discussed in this report. The load analysis was done by Trane Trace 700. The total electrical usage of the building was found to be 2,501,300 kwh in design. This building electrical consumption resulted in chemical emissions of 19,810 lbm of SO 2, 11,556 lbm of NO x, and 3,376,755 lbm of CO 2. A life cycle cost analysis for the building s mechanical system was done by the mechanical engineer for the science building, and was found to be $2,713,431 over the course of 20 years. The total mechanical costs for the science building were determined to be $2,826,619 which is 20% of the total building cost. This value is high compared to normal buildings, but the laboratories are reason for a more energy-intensive and costly building system. Page 1

2.0 LEED GREEN BUILDING CERTIFICATION. The U.S. Green Building Council is a national coalition of leaders from across the building industry that work to promote buildings that are environmentally responsible, profitable and healthy places to live and work. Members of the U.S. Green Building Council, representing all segments of the building industry, developed the LEED (Leadership in Energy and Environmental Design) Green Building Rating System. LEED was created to define a green building by a common standard of measurement. LEED raises awareness of green building benefits and has transformed the building market to produce high-performance, sustainable, greener buildings. This system is a voluntary, consensus-based national standard. The 6 major categories of the LEED Green Building Certification Rating System are: Sustainable Sites, Water Efficiency, Energy and Atmosphere, Materials and Resources, Indoor Environmental Quality, and LEED Innovation Credits. The four levels of certification that a building design could obtain are: LEED Certified (26-32 points), Silver (33-38 points), Gold (39-51 points), and Platinum (52+ points). Overall, the LEED certification for Longwood University s Science Building was not applicable due to the fact that it is not an office building. There are a few elements of the building design that add to the greenness of the building. A major green element of the science building is the greenhouse on the south end of the 4 th floor. Another energy friendly element in the design is a DDC energy management and temperature control system with pneumatic actuators for large dampers and valves. It is manufactured by an open protocol temperature control manufacturer and is Lonmark compatible. This control system is provided for the HVAC system of the science building. Page 2

3.0 ASHRAE STD. 90.1. ASHRAE Standard 90.1 provides guidelines on economical design, construction, and operation of systems. It gives building design data and information to help maintain and operate healthy indoor environments in buildings. The two sections of the standard that will be covered in this report are section 5: Building Envelope and section 9: Lighting. The compliance of the building envelope and lighting of Longwood University s New Science Building are discussed in the following sections of this report. The science building is located in Farmville, VA. The closest location included in ASHRAE Standard 90.1 is Lynchburg, VA. Table D-1 of ASHRAE Std. 90.1 gives the weather data for Lynchburg, VA where the cooling design is at 90db/74wb, and heating design at 12db. 3.1 BUILDING ENVELOPE COMPLIANCE TO ASHRAE STD. 90.1. The building materials of the science building were found on the architectural drawings. The building was found to have four typical types of exterior walls, each with its own R-value. The R-value of the roof was also found. These R-values were found using the ASHRAE Fundamentals Handbook as well as various Internet sources. After the individual R-values for each material was found, they were added up to find a total R value for each wall. The U-value of the wall was found by the following equation: U-value = 1. (R-values) Page 3

The following are typical exterior wall sections of the science building: (a) (b) (c) (a) Brick wall section (c) Pre-cast Pilaster wall section (d) (b) Concrete, CMU, and Brick wall section (d) Metal closure section Page 4

The U-Values of the exterior walls were calculated as follows: Wall Type Material R-Value Brick Wall Outside surface, 15 mph wind 0.17 4 Brick Veneer 0.44 Air gap 1.00 15# Felt 0.06 5/8 Exterior Sheathing 0.56 6 Metal Studs, 16 O.C. 1.20 Batt Insulation 13.0 Inside surface, still air 0.68 Total R-Value: 17.11 Total U-Value: 0.058 Concrete, CMU, and Brick Wall Outside surface, 15 mph wind 0.17 4 Brick Veneer 0.44 4 CMU 0.80 Air gap 0.06 Bituminous damp proofing 0.56 Cast-in-place concrete 0.64 Inside surface, still air 0.68 Total R-Value: 3.31 Total U-Value: 0.302 Pre-Cast Pilaster Wall Outside surface, 15 mph wind 0.17 Type P4 Pre-cast Pilaster 0.64 Air gap 1.00 15# Felt 0.06 5/8 Exterior Sheathing 0.56 2 ½ Metal Studs, 16 O.C 0.60 Batt Insulation 13.0 Inside surface, still air 0.68 Total R-Value: 16.71 Total U-Value: 0.060 Metal Closure Wall Outside surface, 15 mph wind 0.17 Pre-finished Alum Curtain wall 2.22 3 Layers of 5/8 Gyp. Bd. 1.68 6 Metal Studs 1.20 Inside surface, still air 0.68 Total R-Value: 5.95 Total U-Value: 0.168 Page 5

The U-value is a measure of the heat transfer characteristics of an assembly of materials. The lower the U-value number, the greater the heat transfer resistance (insulating) characteristics of the wall. The wall with the lowest U-value (0.058) was found to be the Brick wall. Therefore, the brick wall has the highest insulating characteristics in the science building. The wall with the highest U-value (0.302) was found to be the exterior wall made of concrete, CMU, and brick. Therefore, this wall was found to have the lowest insulating characteristics in the science building. The roof with a U-value of 0.046 was found to have high insulating characteristics. Below is a typical section and calculated U-value of the roof: Type Material R-Value Roof Outside surface, 15 mph wind 0.17 3 Ply Built up Roofing w/ Bitumen 0.33 4 R20 Rigid Roof Insulation 20.0 3 Concrete Slab 0.64 Metal Deck 0.00 Horizontal Inside surface, still air 0.61 Total R-Value: 21.75 Total U-Value: 0.046 The Building Envelope Requirements of Table B-n of ASHRAE Standard 90.1, were used to determine if the calculated U-values of the science building would comply to the standard. To decide which B-n table is needed, the Heating Design Day and Cooling Page 6

Design Day values were found for Lynchburg, VA in table D-1 of ASHRAE Standard 90.1. It was found that the HDD65=4,340 and the CDD50=3,728. These values refer us to Table B-13 of the standard. Table B-13 sets forth maximum U-values for non-residential buildings for wall assemblies. It was found that the walls which would be classified as Steel Framed as well as the roof classified as Insulation Entirely above Deck comply with ASHRAE Standard 90.1 in regards to envelope compliance. The walls which would be classified as Other did not comply with ASHRAE Standard 90.1 in regards to envelope compliance. To summarize, the envelope types with high insulation characteristics complied with the standard, and those with lower insulation characteristics did not comply. The following table shows the calculated U-values compared to the U- values required by the standard: Type Calculated U-values ASHRAE Std. 90.1 Maximum U-Value (from Table B-13) Comply to ASHRAE Std. 90? Brick Wall 0.058 0.124 Yes Concrete, CMU, and Brick Wall 0.302 0.089 No Pre-Cast Pilaster Wall 0.060 0.124 Yes Metal Closure Wall 0.168 0.089 No Roof 0.046 0.063 Yes The SHGC of the science building glazing was found using the 2001 ASHRAE Fundamentals Handbook. Assuming the windows are insulating glass on extruded aluminum frames, the SHGC=0.34. Using Table B-13, the required SHGC by the standard is 0.49 for 15% glazing. Therefore, it can be concluded that the glazing of the science building complies with ASHRAE Standard90.1 in regards to envelope compliance. Page 7

3.2 LIGHTING COMPLIANCE TO ASHRAE STD. 90.1. The Space by Space Method from section 9.3.1.2 of ASHRAE Standard 90 was used to determine the interior lighting power allowance of Longwood University s Science Building. These allowable values were then compared to the lighting power taken off of the lighting fixture schedule used in design. The Space by Space Method requires the use of Table 9.3.1.2 for which the building type as well as space type needs to be known. The science building falls under the building type School/University. The space types used were: enclosed offices, classroom/lecture, lounge/recreation, restrooms, corridor/ transition, active storage, and electrical/mechanical. The floor areas of each of the spaces also need to be known to use this method. The floor areas were then multiplied by the allowed lighting power density from Table 9.3.1.2 to give the lighting power allowance for each space. When the values are compared, it is found that all spaces were compliant with the standard with the exception of the office and the corridors. The office was very close to compliance, and the corridors were probably designed to have more light because of the large amount of occupants the building holds. Specific Room (typ. for space type) Space Type Floor Area (ft 2 ) Lighting Power Density (W/ft 2 ) Design Lighting Power for the Space (W) Allowable by ASHRAE Lighting Lighting Power Power for the Density (W/ft 2 Space (W) ) Comply to ASHRAE Std. 90? Room 324 Enclosed Office 140 1.83 256 1.5 210 No Room 103 Classroom/ Lecture 882 1.31 1152 1.6 1411 Yes Room 100 Lounge/Recreation 615 0.63 390 1.4 861 Yes Room 124 Restrooms 182 0.99 180 1.0 182 Yes Room 114 Corridors/Transition 842 1.62 1364 0.7 589 No Room 116 Active Storage 184 1.04 192 1.1 202 Yes Room 113 Electrical/Mechanical 2100 0.43 896 1.3 2730 Yes Lighting Compliance Results Page 8

4.0 LOST RENTABLE SPACE DUE TO MECHANICAL SYSTEM.. The total building area is 71,800 square feet, and the lost rentable space due to the mechanical system was found to be 2,886 square feet. This lost space is 4% of the total building area. The following is a detailed break down of the lost rentable space caused by the mechanical system of Longwood University s New Science Building. Floor Type of Space Total Area 1st Mechanical Room 113 2,100 2nd Main Mechanical Chase 133 Vertical Shafts 150 3rd Main Mechanical Chase 133 Vertical Shafts 87 4th Main Mechanical Chase 133 Vertical Shafts 150 Total Area Lost = 2,886 sf` Lost Rentable Space due to Mechanical System. 5.0 ANNUAL ENERGY CONSUMPTION AND EMISSIONS SUMMARY. The electricity consumption for educational facilities was obtained from the 1999 Electrical Consumption and Expenditure Intensities (Table C10) on the Department of Energy website. Assuming that the Longwood Science building fits into the educational facility category, it was found that the building consumes 8.7 kwh per square foot of energy. Since the science building is approximately 71,800 square feet, the energy consumed by the science building is 624,660 kwh. However, this value is not a good enough estimate because even though the science building is an educational facility, it requires more kwh than an average educational facility due to the fact that it has more Page 9

electrical equipment, including laboratory equipment and many computers. For this reason, it was found that a better estimate for the electrical consumption of the science building would be something with a higher rate, so the floor space category rate was used from Table C10. It was found that the building consumes 14.4 kwh per square feet, considering that the building falls into the 50,000-100,000 square feet range. This rate gives us a higher approximation for the building electricity consumption of 1,033,920 kwh. When this number is compared to the design kwh of electricity consumption, it was still found to be a low estimate. The value used in design was 2,501,300 kwh. This designed value was calculated by the Trane Trace 700 program and is considered to be fairly accurate. The reasons that the electrical consumption rates in Table C10 of the 1999 Electrical Consumption and Expenditure Intensities were not accurate enough were because it does not list values for this specific building type. The science building consumes much more electricity that an average educational facility, as well as more than an average facility in the same building floor space category or any other category in the table. The total energy consumption by fuel type for the state of Virginia was obtained from the 2000 data provided on the Energy Information Administration website. Table 7 was used to obtain the amount of coal, nuclear power, and hydroelectric power that produces electricity per year. Table 12 was used to obtain the amount of natural gas that produces electricity per year. It was assumed that petroleum (Oil) does not produce any electricity. The total amount of electricity produced was found, and the % Energy Mix of each fuel type was calculated. The table on the following page shows the breakdown of the emissions associated with the on-site electricity produced by the fuels. Page 10

Fuel % Energy Mix lbm Pollutant j Particulates SO 2 /kwh NO x /kwh CO 2 /kwh Coal 62.0 6.82E-04 7.92E-03 4.59E-03 1.33E+00 Oil 0.0 0.00E+00 0.00E+00 0.00E+00 0.00E+00 Nat. Gas 1.0 0.00E+00 1.35E-07 2.54E-05 1.34E-02 Nuclear 36.0 0.00E+00 0.00E+00 0.00E+00 0.00E+00 Hydro/Wind 1.0 0.00E+00 0.00E+00 0.00E+00 0.00E+00 Totals 100.0 6.82E-04 7.92E-03 4.62E-03 1.35E+00 Breakdown of Emissions Associated with On-Site Electricity Use in Virginia Approximate amounts of sulfur dioxide (SO 2 ), NO x, and carbon dioxide (CO 2 ) produced by Longwood University s Science Building electrical usage were determined from the rates provided by the Energy Information Administration s Estimated Emission Associated with Onsite Electrical Usage calculations. It was found that no particulates are generated from oil, natural gas, nuclear power, or hydroelectricity. The total emitted SO 2 pollutants were 7.92E-03 lbm/kwh. The total emitted NO x pollutants were 4.62E-03 lbm/kwh. The total emitted CO 2 pollutants were 1.35 lbm/kwh. Since 2,501,300 kwh of energy was found to be consumed by the science building, the pounds of mass of the pollutants is able to be calculated. The results are: 19,810 lbm of SO 2, 11,556 lbm of NO x, and 3,376,755 lbm of CO 2 produced by Longwood University s Science building electrical usage. In a study done by the University of California, through the U.S. Department of Energy, it was found that laboratorytype facilities are much more energy-intensive than typical buildings in California, as illustrated in Figures 2a. This conclusion is a major assumption of this report as well. Page 11

6.0 MECHANICAL SYSTEM FIRST COST. The final estimate for Longwood University s New Science Building was computed by the estimating company Project Cost, Inc. The detailed report breaks up the cost into major building systems, which include: Foundations Slab on Grade Structural Frame Supported Floor Roof Structure Roofing, Stairs Elevators Exterior Walls Interior Walls Interior Finishes Doors and Hardware Windows & Glazed Walls Specialties Plumbing HVAC System Fire Protection Power Lighting Special Electrical Special Systems/Equip. For the final estimate they also include additional costs for: General Conditions (8%) Bonds and Insurance (1.5%) Overhead & Fee (5%) Escalation (4%) Design Contingency (2.5%) The Mechanical system is broken down into Plumbing, the HVAC system, and the Fire Protection system. The total mechanical system first cost, as well as the cost per square foot is summarized as follows: System Total Cost Cost per sf Plumbing $219,406 $3.10/sf HVAC $2,442,913 $34.49/sf Fire Protection $164,300 $2.32/sf Total Mechanical System $2,826,619 $39.91 Mechanical System First Cost Summary Page 12

The total mechanical system cost of $2,826,619. This amounted to 20% of the total building cost which was $14,084,660. According to RS Means Mechanical cost data, the mechanical cost percentage should be between 4.10% and 12% of the total building cost. The reason the percentage of mechanical cost is so high for the science building is because the mechanical system is much more complex than that of a typical building. The science building requires 100% outside air for many of the laboratory spaces, as well as hood exhaust. For these reasons, there is much more ductwork in this building than a typical building, and it requires additional equipment that increase the costs of the system as well. 7.0 DESIGN LOAD ESTIMATION. The load design estimation was determined using Trane Trace 700. There were many assumptions used to perform the analysis, which included: Lighting loads were determined using ASHRAE Standard 90.1 (W/sf) Equipment loads were estimated using manufacturer s data (W/sf) The weather data was based on Roanoke, VA The space cooling and heating were chosen to be 78F db and 70F db, respectively The relative humidity chosen for thermal comfort was chosen to be 45% Other factors that were taken into account in the analysis were: Room areas and occupancy from design documents Floor to floor and plenum heights Dimensions and orientation of exterior walls Room cooling and heating airflows Envelope materials and U-values Location of room with respect to conditioned or unconditioned spaces All system types were chosen to be Series Fan-Powered VAV Air handling units Page 13

The design cooling load was calculated in Trane Trace 700, and yielded the following results: System Cooling Capacity (MBh) Supply Airflow (cfm) Ventilation Airflow (cfm) Percent OA Tons of Cooling Floor Area Supplied by System Cooling (ft^2/ton) Supply Ventilation (cfm/ft^2) (cfm/ft^2) AHU-1 1,267.9 24,541 10,624 43% 105.7 25,528 242 0.96 0.42 AHU-2 1,142.8 15,091 15,091 100% 95.2 9,550 100 1.58 1.58 AHU-3 1,998.8 26,829 26,829 100% 166.6 16,067 96 1.67 1.67 AHU-4 106.6 1,321 1,321 100% 8.9 1,171 132 1.13 1.13 The following is the breakdown of cooling peak load: Cooling Peak Loads Btu/hr Envelope Loads 269,165 Lighting Load 168,165 Occupant Load 144,900 Misc. Load 83,097 Ventilation Load 518,331 Supply Fan Heat 85,685 Return Fan Heat 29,967 Supply Fan Heat, 6% Ventilation Load, 41% Return Fan Heat, 2% Misc. Load, 6% Envelope Loads, 21% Lighting Load, 13% Occupant Load, 11% Page 14

8.0 COST ESTIMATES, LIFE CYCLE ANALYSIS, AND OPERATING COSTS The initial capitol cost estimate is not a complete cost estimate, only a comparison between different rooftop air handling units and their accessories. The cost estimates were derived from Manufacturer s Data as well as the 2001 RS Means Mechanical Cost Data. The following data shows the breakdown of data used to find this value: Description Unit Cost Cost Material Labor Material Labor Total Cost Chillers CH-1, CH-2 $49000 $8700 $98000 $17400 $115400 OH & P $44541 $12044 $56585 Sub Totals $142541 $29444 $171985 (Including Contractor OH & P) Totals with 4.5% Escalation $148955 $30769 $179725 Cost Estimate for New Construction of Chillers The engineers that designed the science building performed a life cycle energy analysis on the building. The assumptions for their analysis are as follows: Energy consumption based on Trane Trace 700 Program. Economic Analysis based on a building HVAC system life of 20 years per 1999 ASHRAE HVAC Applications Handbook. The efficiencies for the chillers used are based on values from Trane: 0.590 kw/ton. The efficiency of the run around loop heat recovery system is assumed at 65% as an economical value. The cost estimates for the life cost analysis are based on a differential cost comparison between HVAC system alternatives with different system components. They are not complete cost estimates for each HVAC system alternative. The life cycle analysis performed by the engineers was broken into: replacement cost, fuel/energy cost, Page 15

operating cost, maintenance and repair cost, and the salvage value. No replacement cost was used in the life cycle cost analysis because the life cycle study period equals the expected life of the mechanical equipment. The maintenance cost was derived from 1999 ASHRAE Applications Handbook Estimating Maintenance Costs. For the base system with screw compressor chillers: (33.38 + 0.188*[number of years] + 0.77) * 71,800 ft 2 /100 = $24,313 Year 1+ $127.48 each Years 2-20. No mechanical equipment had any salvage value based on a 20-year system life. Electric consumption cost includes Basic Customer Charge, Power Supply Demand Charge, Distribution Demand Charge, Energy Charge, and Ratchet Charge. The electrical cost rate for Virginia Electric Power Company, which supplies Longwood University, was found to be 6.23 cents/kwh in Virginia on the Utility Retail Sales Statistics table from the Department of Energy website. The gas cost rate was found to be $0.19/square foot for an educational facility greater than 50,000 square feet. The estimated electrical operational cost of the science building was found to be $155,830 and the estimated gas operational cost was found to be $13,640 using the following calculations: Electrical operational cost = 6.23 cents/kwh x 2,501,300 kwh x ($1/100 cents) = $155,830 Gas operational cost = $0.19/square foot x 71,800 square feet = $13,640 The water rate used for Longwood University is $14.30 for first 3,000 gallons + $2.20/1000 gallon for additional gallons. This rate would be used to determine the operational cost for water usage, if the amount of water is known. Page 16

The life cycle energy analysis (over 20 years) is summarized in the following table: Year Initial Capitol Cost Estimate Escalation Rates 4% 4% 4% 4% 4% Replacement Cost Fuel/ Energy Cost Operating Cost (Steam) Maint. & Repair Cost. Salvage Value Total Escalated Cost Present Worth Discount Factor at 6% Per Annum Total Present Value 1 $179725 0 103938 21751 24313 0 329727 1.000 329727 2 0 108096 22621 25418 0 156135 0.943 147235 3 0 112420 23526 26567 0 162513 0.890 144637 4 0 116916 24467 27763 0 169146 0.840 142083 5 0 121593 25446 29006 0 176045 0.792 139427 6 0 126457 26464 30299 0 183219 0.747 136865 7 0 131515 27522 31643 0 190680 0.705 134430 8 0 136776 28623 33041 0 198440 0.665 131963 9 0 142247 29768 34496 0 206510 0.627 129482 10 0 147936 30959 36008 0 214903 0.592 127223 11 0 153854 32197 37581 0 223632 0.558 124787 12 0 160008 33485 39217 0 232710 0.527 122638 13 0 166408 34824 40918 0 242151 0.497 120349 14 0 173065 36217 42687 0 251969 0.469 118174 15 0 179987 37666 44527 0 262181 0.442 115884 16 0 187187 39173 46441 0 272801 0.417 113758 17 0 194674 40740 48431 0 283845 0.394 111835 18 0 202461 42369 50501 0 295332 0.371 109568 19 0 210560 44064 52654 0 307277 0.350 107547 20 0 218982 45827 54892 0 319701 0.331 105821 Total Present Value Life Cycle Cost: $2,713,431 Page 17

9.0 REFERENCES. 2001 ASHRAE Fundamentals Handbook. I-P Edition. ASHRAE Standard 90.1-2001. Energy Standard for Buildings Except Low-Rise Residential Buildings. IP Edition. 2001. Commercial Buildings Energy Consumption Survey Detailed Tables. Table C10, Electricity Consumption and Expenditure Intensities, 1999 http://www.eia.doe.gov/emeu/cbecs/pdf/alltables.pdf. Energy Efficiency in California Laboratory-Type Facilities. Report done by the University of California, through the U.S. Department of Energy. July 31, 1996. Green Building Rating System for New Construction & Major Renovations. (LEED- NC). Version 2.1 November 2002, revised 3/14/03. Leadership in Energy and Environmental Design online: http://www.usgbc.org/leed Project Cost, Inc: Estimate of Probably Construction Cost Final Estimate for Longwood University s New Science Building. Prepared by: John Billings. February 6, 2003. U.S. Green Building Council online: http://www.usgbc.org Colorado Energy Online. R-value tables. http://coloradoenergy.org/procorner/stuff/rvalues.htm Page 18