Key Points in Curtain Wall Firestopping. March 27, Fouad Hajj

Similar documents
Perimeter Fire Containment

FIRE MITIGATION IN FACADE DESIGN & MATERIAL CHOICE

Managing Vertical Fire Spread in Multi-Story Buildings Through Effective Perimeter Fire Barrier Systems

Key Points in Firestopping Fire Barrier Walls FCIA, DOHA

FIRESTOP JOINT SPRAY CFS-SP WB. 2mm (0.079") WET FILM ± 7.5 ± 5

Copyright 2013 IFC. All Rights Reserved. No further reproduction or distribution authorized. Any Unauthorized reproduction or distribution is a

FANNING INNOVATION. with HVLS Design

FIRESTOPPING & SMOKE SEALS

DIIM & Firestopping. Firestopping Joints FCIA 2018

Design No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1

LISTING INFORMATION OF International Fireproof Technology Inc. - Joint Systems SPEC ID: 43848

Foil Back Gypsum Board

St. Monica Food Pantry

SECTION BUILDING INSULATION. Display hidden notes to specifier. (Don't know how? Click Here)

NATIONAL GYPSUM COMPANY 2-Hour Area Separation Wall System

ROXUL SAFE Applications Guide

ICC-ES Evaluation Report Reissued May 1, 2010 This report is subject to re-examination in two years.

Duct Wrap Flexible Wraps

NATIONAL GYPSUM COMPANY 3-Hour Area Separation Wall System

Enthusiastic customers We create success for our customers by Identifying their needs and providing Innovative and value adding solutions.

FIRESTOP 101: An Introduction to Firestopping

PERIMETER FIRE BARRIER SYSTEM GUIDE LIFE SAFETY CODES AND COMPLIANCE COMPONENTS AND SYSTEMS

Fire performance of curtain walls and rainscreens

GOWANDA, NEW YORK SEPTEMBER 18, 2008 ARCH PROJECT NO

FIRE STOP & SMOKE SEAL

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 11

Tender No Section St. James - Assiniboia Centennial Pool Fitness Facility Addition Page 1

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 07 Thermal and Moisture Protection 8400 Firestopping

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION

System No. C-AJ-8048

Fire Performance of Glass Curtain Wall

ROCKWOOL Board Insulation Section Master Guide Specification Page 1 Jan 2017

ALPOLIC /fr for External Cladding

SWING DOOR SPECIFICATION

Following contains common verbiage found in major model building codes and has been edited for the purpose of inclusion on this CD.

Fire Barrier Duct Wrap 615+

Unitised Curtain Wall Beaded

Impact of NFPA 285 on Air Barrier Specification and Design

PERIMETER FIRE BARRIER SYSTEM GUIDE LIFE SAFETY CODES AND COMPLIANCE COMPONENTS AND SYSTEMS

ROCKWOOL Board Insulation Section Master Guide Specification (CURTAINROCK 80) Page 1 January 2018

SECTION THROUGH-PENETRATION FIRE STOP SYSTEMS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MINERAL-FIBER FIREPROOFING REPORT HOLDER: THERMAL CERAMICS, INC.

LISTING INFORMATION OF Metl-Span, LLC THERMALSAFE 8" Thick 3 Hour Fire Rated Panels SPEC ID: 29868

A. Source Limitations: Obtain each type of building insulation through one source.

Product Information Sheet

FCIA Webinar Gypsum Wall Patching

Sept 30, 2004 Page 1

3M Fire Barrier Duct Wrap 615+ Product Data Sheet and Installation Guide (Condensed Version)

Protecting Penetrations in Fire Rated Construction

WHY I SHOULD SPECIFY AND USE FAS TRACK 1000?

NEW CONSTRUCTION (digital copy available Firestop Solutions Inc.) FIRESTOPPING SPECIFICATION SECTION FIRESTOPPING

FyreWrap Elite TM 1.5 Duct Insulation Grease Duct ASTM E2336 System

CERTIFICATE OF APPROVAL No CF 563 SIDERISE INSULATION LIMITED

Building Enclosure Concept Design Checklist

Firestop Products for Construction Joints Applications

SECTION FIRE RESISTIVE JOINT SYSTEMS

CERTIFICATE OF APPROVAL No CF 563 SIDERISE INSULATION LIMITED

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: CITADEL ARCHITECTURAL PRODUCTS, INC.

PRODUCTION SPECIFICATIONS INSULATED CONCRETE FORMS

PRODUCTION SPECIFICATIONS INSULATED CONCRETE FORMS

Ultra-High Performance Wall System Glass Fiber Reinforced Concrete

FyreWrap Elite 1.5 Duct Insulation Air Distribution System (ADS Ducts)

Engineering Analysis of NFPA 285 Tested Assemblies

REPORT HOLDER: OMEGA PRODUCTS INTERNATIONAL, INC CALIFORNIA AVENUE CORONA, CALIFORNIA EVALUATION SUBJECT:

SECTION THERMAL INSULATION

DIVISION 7 THERMAL AND MOISTURE PROTECTION SECTION PENETRATION FIRESTOPPING

CERTIFICATE OF APPROVAL No CF 563 SIDERISE INSULATION LIMITED

Exterior Wall Systems NFPA 285

Product Information Sheet. FyreWrap 1.5 Duct Insulation. Introduction. Product Components. Typical Product Parameters

Combustible Exterior Wall Cladding Systems: An ICC Perspective

UNIFIED FACILITIES GUIDE SPECIFICATIONS

ESR-1794* Reissued September 1, 2012 This report is subject to renewal November 1, 2014.

Comparison of UK Window Standards to Canadian Standards

ADVANCE METAL INDUSTRIES L.L.C.

Fire Considerations. Combustible Cladding and Components Of Exterior Walls and Curtain Walls. APEGBC/BCBEC Seminar, April

CAJ. Combos. C-AJ of 5. Through Penetrations Series. Concrete. 3Fire Protection Products

SECTION Blown Insulation THERMAL INSULATION

SPECIFICATION SECTION : FIRE RATED GLASS & FRAMING GPX Hurricane System

Common Firestop Issues in Wood Framed Commercial Construction

SEPTEMBER construction type cavity barriers. SP Firestop Systems. The purpose-made solution for cavity fire stopping

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: METL SPAN, A DIVISION OF NCI GROUP, INC.

ESR-1061 Reissued May 1, 2011 This report is subject to renewal in two years.

Building Codes and Ordinances ARC 227

Supplemental Correction Sheet Curtain Wall (2017 LABC)

TECH SOLUTIONS A Prescriptive Solution to Meet Air Barrier Energy Code Requirements in Metal Buildings

3-Dimensional Thermal Analysis of Lenmak EnvaTherm and SpandrelTherm Backpan Assemblies

CURTAINROCK and ROXUL SAFE

XHBN.HW-D Joint Systems. Design/System/Construction/Assembly Usage Disclaimer. Joint Systems. System No. HW-D-0631

Design & Testing of Fire Resistance and Smoke Resistant Barriers. Rich Walke UL Codes and Advisory Services

Gold Bond BRAND Kal-Kore Plaster Base

ROCKWOOL Board Insulation Section Master Guide Specification Page 1 Jan 2017

EcoTouch Insulation with PureFiber Technology

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: KINGSPAN INSULATED PANELS, INC.

Duct Wrap 2x2 Duct Wrap 2x2+ Commercial Kitchen Grease Duct

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: PARKLEX USA

THERMAL AND AIR BARRIER WALL SYSTEM

NFPA 285 Assemblies. Table of Contents

Pyroscat Duct Wrap XL

Transcription:

Key Points in Curtain Wall Firestopping March 27, Fouad Hajj

Today we will cover 1. What is Curtain Wall Firestopping? 2. CW Standards 3. What does the code require. 4. CW Testing 5. Failure Points and implications 6. U.L. Systems 7. Installation Issues 8. Inspections

The slot between the slab and the Curtain Wall must be PROPERLY firestopped. Curtain Wall Slot To Firestop

If the Curtain Wall firestopping is not properly installed, in case of fire, the result can be catastrophic Or else smoke and fire will spread Windsor Tower, Madrid 2005

Today we will cover 1. What is Curtain Wall Firestopping? 2. CW Standards 3. What does the code require? 4. CW Testing 5. Failure Points and implications 6. U.L. Systems 7. Installation Issues 8. Inspections

Therefore, it s crucial that CW designs be tested to the correct standards IBC NFPA Barriers Through Penetration Joints Safing Slot ASTM E-119 UL 263 ASTM E-814 UL 1479 UL 2079 ANSI 2079 ISMA ASTM E-2307 ASTM E-119 UL 263 ASTM E-814 UL 1479 UL 2079 UBC AC-30 ISMA UBC 29-6

Today we will cover 1. What is Curtain Wall Firestopping? 2. CW Standards 3. What does the code require? 4. CW Testing 5. Failure Points and implications 6. U.L. Systems 7. Installation Issues 8. Inspections

Today we will cover 1. What is Curtain Wall Firestopping? 2. CW Standards 3. What does the code require? 4. CW Testing 5. Failure Points and implications 6. U.L. Systems 7. Installation Issues 8. Inspections

Curtain Wall testing is done by using the Intermediate Scale Multi-storey Apparatus (ISMA) Pre-Burn

Interior Burner Lit Time: 0:00

Exterior Burner Lit Time: 0:05

Flames Climbing Exterior Time: 0:15

Melting of Mullions & Transoms Time: 0:45

Burner off at 2 Hours Time: 2:00

Today we will cover 1. What is Curtain Wall Firestopping? 2. CW Standards 3. What does the code require? 4. CW Testing 5. Failure Points and implications 6. U.L. Systems 7. Installation Issues 8. Inspections

Post Test Analysis indicates the failure points that need special protection Close up Detail of Mullion and Transom Damage

Today we will cover 1. What is Curtain Wall Firestopping? 2. CW Standards 3. What does the code require? 4. CW Testing 5. Failure Points and implications 6. U.L. Systems 7. Installation Issues 8. Inspections

STI has invested heavily in Curtain Wall testing: UL is the premier fire testing lab in the US STI tests mostly at UL STI designed and tested the first C.W. System with vision glass STI has more UL C.W. tests than all other competitors combined! (93 out of 123)* As a result, STI has privileged working relationships with major C.W. designers/engineers around the world *Source: UL Online Certifications Directory (www.ul.com/database) as of Oct 14, 2011

Understanding the UL Directory Numbering System

Understanding the UL Directory Numbering System CW-D-2042 First Two Alpha Characters CW Identifies the gap between a fire rated floor and a non rated exterior curtain wall Third Alpha Character is S or D S Static Joints D Dynamic Joints

Understanding the UL Directory Numbering System CW-D-2042 Number Range = Max Clearance Distance Between Curtain Wall and Perimeter of Floor 0000-0999 =Less Than or Equal to 2 1000-1999 =Greater than 2 -Less than = to 6 2000-2999 =Greater than 6 -Less than = to 12 CW-D-2042 Last Three Numeric Components = Test Number in the Series Designates 042 as the 42nd test in the 2000-2999 PFCS series

Today we will cover 1. What is Curtain Wall Firestopping? 2. CW Standards 3. What does the code require? 4. CW Testing 5. Failure Points and implications 6. U.L. Systems 7. Installation Issues 8. Inspections

Aluminum Tubular Mullion Aluminum tubular Mullion 3. Foil Faced Mineral Wool 8PCF Transom and Vision Glass 1. Perimeter Angle Spandrel Panel (Glass, aluminum, or stone) 5. Mullion Covers: Mineral Wool 8PCF 4. Slot Treatment: a. Mineral Wool (4 PCF) compressed and fitted tight in safing slot b. AS-205 Spray over MW Safing 2. Stiff-Back Angle Concrete Slab

Steel Back-Pan Spandrel Panel CW-S-0002 Stiff-Back Angle Additional Insulation ONLY BACK-PAN TESTED SYSTEM. PATENDED DESIGN!

Steel Back-Pan CW: A Word of Caution!

Reverse Back-Pan (Shadow Box) Spandrel Panel CW-D-1009 Perimeter Angles Stiff-Back Angle Shadow Box

Extending the Rated Floor to the Wall MANDATORY! In rated construction, all floors are rated. The safing slot must be sealed in a manner that extends this rating to the exterior wall surface

Traditional Designs Do not adequately protect the safing slot! Mineral Wool Installation Safing is cut slightly oversized and jam fit into the opening foil side up with the grain parallel to the floor. Z shaped steel safing clips are used to impale the safing and suspend it into the opening.

Traditional Designs Do not adequately protect the safing slot! Sealant Installation Two caulk beads are applied to seal the edges of the foil facing to the adjacent surfaces.

Traditional Designs Do not adequately protect the safing slot! In a Fire The insulation is oriented improperly It lacks resilience and will not rebound. As it burns, the edges shrink inward creating gaps.

Newer Tested Systems Take advantage of Mineral Wool s natural resilience to help keep the slot closed during a fire! Mineral wool safing is oriented with its grain running vertically

Newer Tested Systems Use Proper Orientation and Compression Providing maximum compression and extension and a tight fit against the spandrel insulation without the need for safing clips! Assuring a tighter smoke, gas, and fire seal!

Use Proper Orientation and Compression It is simple and easy to do!

Benefits of Pro-Actively Designing the Safing Slot Maintains compartmentation Prevents the migration of smoke through to floors above. Buys time for occupants to escape. Provides additional protection in the event of a sprinkler failure.

Today we will cover 1. What is Curtain Wall Firestopping? 2. CW Standards 3. What does the code require? 4. CW Testing 5. Failure Points and implications 6. U.L. Systems 7. Installation Issues 8. Inspections

Steps to Inspect Perimeter Fire Barrier Firestop Step 1 to 5 Step 1: Verify Documents and submitted Drawings reference Legitimate Perimeter Fire Barrier Systems such as UL. CW-S or CW-D Step 2: Verify the Rating of the System is Greater than or equal to the rating of the floor Step 3: Verify Firestop material to be used and listed for use in Perimeter Fire Barrier Systems. Step 4: Verify Documents reference systems that have been tested with windows or vision glass if the building has glazing close to the safing area. Step 5: verify Stiff steel reinforcement member, if required, has been placed behind exposed curtain wall panel insulation.

Steps to Inspect Perimeter Fire Barrier Firestop- Step 6 ASTM E119 Temperature Curve Step 6: verify Insulation and brand used is listed within the tested system. Rock wool is the typical insulation of choice 2080 F (5 hours) Glass Melts Mineral wool still intact Aluminum Melts Fiberglass Insulation Fails (6 Minutes) at 1050 F and IS Not To Be Used In a Fire Containment Assembly

Steps to Inspect Perimeter Fire Barrier Firestop Step 7 to 11 Step 7: Verify Insulation panels are securely fastened with mechanical fasteners per the system, instead of just friction-fitted in place. Step 8: Verify the exposed mullions, if required by the system are covered with the proper insulating barrier securely fastened with mechanical fasteners per the system design. Step 9: Verify Sealant is applied to the proper depth Step 10: Verify the Parameters indicated in the system are the same as those installed in the field.

Firestopping Inspection Manual The IFC has put out a Firestopping Inspection Manual to help field inspectors

In Conclusion Thanks شكرا Fouad Hajj Specified Technologies Inc. District Manager (Gulf Region) Tel: +974 558 58 390 fouadh@stifirestop.com