TRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION ATHENS - GREECE SPECIFICATION TR-1

Similar documents
SPECIFICATION FOR DISC INSULATORS (Standard Type)

Technical Specification for. Insulators. Part 1. Insulators for High and Extra-High Voltage Overhead Lines

General Requirements. Technical Specifications for Insulators of Transmission Lines

SPECIFICATION FOR 11 & 33kV COMPOSITE INSULATORS Part 1: Pin Type

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators (63 kv- 400 kv)

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008

MGVCL/MM/1043/13-14/11 KV Disc Insulators (Porcelain)

SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS:

Maharashtra State Electricity Distribution Co. Ltd.

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA

Maharashtra State Electricity Distribution Co. Ltd.

FIJI ELECTRICITY AUTHORITY BIDDING DOCUMENT

SPECIFICATION FOR STAY INSULATORS (PORCELAIN)

SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: -

11KV PORCELAIN INSULATORS AND FITTINGS

093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH

NATIONAL ELECTRIC POWER COMPANY (NEPCO) TENDERNO. 9/2013 FOR THE SUPPLY OF INSULATORS AND FITTINGS FOR DOUBLE AND QUADRUPLE CIRCUITS 132 kv OHTL's

TURKISH ELECTRICITY DISTRIBUTION CO. TECHNICAL SPECIFICATION FOR POST (SUPPORT) INSULATORS FOR MEDIUM VOLTAGE SYSTEMS

TECHNICAL SPECIFICATION OF 70KN & 45KNDISC INSULATOR (B & S)

Technical Specification for Outdoor Porcelain Station Post Insulators

Technical Specification for. Insulators. Part 1

6C-001 High-Voltage Pin-Type Insulator

Specification No. CSC- XXIX/DH/UH/P&D/

DESIGN TEST REPORT. GAMMA Insulators 6184R-70 ANSI Class 55-3 Pin Type Insulator..

DESIGN TEST REPORT. GAMMA Insulators 7061R-70 ANSI Class 55-5 Pin Type Insulator.

DESIGN TEST REPORT. GAMMA Insulators 6183R-70 ANSI Class 55-4 Pin Type Insulator.

APDRP SCHEME, WESCO. Technical Specification for 33KV Air Break Switch PART 1: SCOPE AND CONDITIONS

FOREWORD SCOPE NORMATIVE REFERENCES DEFINITIONS REQUIREMENTS... 4

PART-II SPECIFICATION OF 22KV PIN INSULATORS. This specification covers 22KV Pin Type Insulators for 22KV H.T. over head power lines.

SPECIFICATION: LINE TAPS FOR ALUMINIUM/ACSR AND COPPER CONDUCTORS

TECHNICAL SPECIFICATION FOR 11 POST INSULATORS, 11 KV & 33 KV PIN INSULATORS AND 11 KV, B&S TYPE 45 KN & 70 KN DISC INSULATORS.

TECHNICAL SPECIFICATION FOR 11 KV & 33 KV POST INSULATORS, 11 KV & 33 KV PIN INSULATORS AND 11 KV, B&S TYPE 45 KN & 70 KN DISC INSULATORS.

Maharashtra State Electricity Distribution Co. Ltd.

33-SDMS-02 SPECIFICATIONS FOR

High Quality Porcelain Insulators for Transmission Lines

SPECIFICATION FOR STOCKBRIDGE TYPE VIBRATION DAMPERS FOR DISTRIBUTION AND TRANSMISSION OVERHEAD LINES

Date: TECHNICAL SPECIFICATION FOR (LT,11KV, 33KV) PORCELAIN PIN INSULATORS

POST AND DISC INSULATOR

Technical Specification for Helical Fittings for Overhead Power Lines

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION

1. Filled-in Supply Record Form.

SPECIFICATION SS-20 / 4 STEEL STRUCTURES FOR SUBSTATION AND SWITCHING STATION MATERIAL

DUCTILE IRON PIPES AND FITTINGS DETAILED PRODUCTS SPECIFICATIONS

TECHNICAL SPECIFICATION OF LONG ROD PORCELAIN INSULATORS FOR TRANSMISSION LINES

9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA

37-SDMS-01 REV. 03 SPECIFICATIONS FOR

SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION The ELECTRICITY (PEDE) TENDER DOCUMENTS FOR

SECTION-II (VOLUME-II) PAGE 1

31-SDMS-03 REV. 01 SPECIFICATIONS FOR

SPECIFICATION FOR POLYMER DISC INSULATOR

660 Volts 630 & 800AMP

UNS 5kA Arrester. Certified Test Report IEC

Technical Specification for Steel Forged Fittings

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators

TABLE OF CONTENTS. FOREWORD... Error! Bookmark not defined. INTRODUCTION SCOPE NORMATIVE REFERENCES DRAWING...4

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS. Insulators & Lightening Arrestors GROUP A

ANNEXURE - ' D ' TECHNICAL SPECIFICATION FOR INSULATOR PINS ( PINS FOR 11,22 AND 33 kv INSULATORS )

TECHNICAL SPECIFICATIONS

SECTION 07 TECHNICAL SPECIFICATIONS 11KV OUTDOOR TYPE SINGLE PHASE METAL OXIDE (ZNO) GAPLESS LIGHTNING ARRESTER (LA)

TABLE OF CONTENTS. Page FOREWORD INTRODUCTION SCOPE NORMATIVE REFERENCES

~ i\~~ Oso~pl'-tvDI~,~

CARES Technical Approval Report TA

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara:

Mar11 Rev D

COMPOSITE INSULATORS

11-SDMS-01 REV. 03 ( )

8. Hydrophobicity classification guide STRI guide 1.92/1 9. Radio interference characteristics of overhead power lines and high-voltage equipment

Single Core, Copper Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

POLYMER HOUSED SURGE ARRESTORS

Necessary Check Points & Testing for Screening the Quality of Insulators

TABLE OF CONTENTS INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS... 3

INSULATORS NEW. See page J-4 for more information.

Mar11 Rev C

SPECIFICATION FOR HT-LT STAY (GUY) INSULATORS:

UHS 10kA Arrester. Certified Test Report IEC

SPECIFICATION OF HT-LT STAY (GUY) INSULATORS:

SOLARLOK BREEZE Junction Box

Guide Specifications ADP Series SECTION SHEET METAL ROOFING

HARYANA VIDYUT PRASARAN NIGAM LIMITED. TECHNICAL SPECIFICAION FOR POLYMER INSULATOR STRINGS FOR 220KV / 132KV/66KV TRANSMISSION LINES

Specification for Polymer Disc Insulator

TECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS

TEMPERED GLASS INSULATORS

12-SDMS-01 Rev.02 SPECIFICATIONS FOR

TECHNICAL SPECIFICATION OF SILICON RUBBER HOUSED COMPOSITE INSULATORS FOR TRANSMISSION LINES

BIDDING DOCUMENT FOR. Supply of Galvanized Steel Tubular Poles, 11KV Polymer Insulators and ACSR Conductors under Saubhagya Scheme

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS. Polymer Insulators

SMPM Female Cabled Connectors

MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO. Ltd. (MUMBAI) SCHEDULE 'A' TECHNICAL SPECIFICATION FOR. 11 kv, 22 kv & 33 kv HORN GAP FUSES FOR

GROUP A. Polymeric Insulators.

42-SDMS-02 SPECIFICATIONS FOR FIBERGLASS REINFORCED LOW VOLTAGE SERVICE CABINET FOR 800A BULK CUSTOMERS

TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE

SECTION 1 SCOPE, SPECIFIC TECHNICAL REQUIREMENTS AND QUANTITIES

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION

Precast concrete composite wall with point connectors

Sediver toughened glass insulators for HVAC applications. Experts & Pioneers USA

TECHNICAL SPECIFICATION OF SILICON RUBBER HOUSED COMPOSITE INSULATORS FOR TRANSMISSION LINES

CHAPTER 6 HIGH VOLTAGE ELECTRICAL TESTING RESULTS

Transcription:

I NDEPENDE N T POWER TR ANSM ISSION OP ER AT O R S.A. TRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION ATHENS - GREECE SPECIFICATION TR-1 STRING INSULATOR UNITS Revision March 2015 ATHENS - GREECE

I N D E P E N D E N T P O W E R T R AN S M I S S I O N O P E R AT O R S. A. TRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION SPECIFICATION TR-1 This specification covers the manufacturing and testing of cap and pin type insulators, made from toughened glass. The insulators have to pass successfully the tests mentioned in paragraph 3 and shall meet all the requirements mentioned in present specification. For all the standards referred below is valid their latest edition. 1. DESIGN AND FABRICATION 1.1 The insulators shall be designed and fabricated to provide mechanical ruggedness and long-service life, without thereby sacrificing requirements to meet electrical and operating characteristics herein specified. The quality of the insulators during the manufacturing process will be verified by standard EN ISO 9001. Under surfaces and ribs shall be shaped for easy cleaning. Shells shall be substantially symmetrical in shape without appreciable warping. 1.2 The toughened glass shall be sound and free from defects and blemishes, which might adversely affect the life of the insulator. All exposed glass parts shall have a smooth surface. 1.3 Insulators shall be designed to avoid excessive concentration of electrical stresses, in any section or across leakage surfaces. Design features tending to adversely affect radio reception shall be avoided as far as practicable. 1.4 The toughened glass, shall not engage directly with hard metal. When cement is used, every precaution shall be taken to ensure that such cement is suitable and that it shall not cause fracture by expansion or loosening by contraction. 1.5 The metal parts, except for the cotter pins, shall be made of a good commercial grade of malleable iron or open hearth or electric furnace steel, hot-dip galvanized. Cotter pins shall be made of phosphor-bronze or stainless steel. Stainless steel used shall have good resistance against corrosion and shall be of quality 18 Cr 8 Ni or equivalent. 1.6 Dimensions of ball and socket couplings of string insulator units shall be in accordance with Standard IEC 60120 (standard coupling / split pin). 2. MARKING Each insulator unit shall bear legible and indelible symbols identifying the manufacturer, the year of manufacture and the rated combined mechanical and electrical strength, identified by the word "M-E". 3. TESTS Insulators shall be subjected to the following tests, in accordance with International Standard IEC 60383-1, except cases that different standard is referred, and the values given in Annexes A, B, C and D, depending on the required insulator. All required tests should be preformed in proper independent laboratories accredited according to International Standard ISO/IEC 17025, except sample and routine tests which can be performed to manufacturer s laboratory, if it is certified by ISO 9001. Test reports have to be written in Greek or English language and shall be certified by laboratory where the tests have taken place. Page 2 of 8 TR 1/Rev. March 2015

3.1 TYPE TESTS: 3.1.1 Dry lightning impulse withstand voltage test, as per paragraph 13. 3.1.2 Wet power-frequency withstand voltage test (the wet flashover voltage shall also be determined), as per paragraph 14. 3.1.3 Mechanical failing load test, as per paragraph 19. 3.1.4 Thermal-mechanical performance test, as per paragraph 20. 3.1.5 Steep front-of-wave flashover voltage test, according to requirements and procedures of Standard IEC 61211/2004. Tests that have taken place according to requirements and procedures of the above standard and previous edition are also acceptable. 3.1.6 Power arc test Test shall be performed according to requirements and procedures of International Standard IEC 61467, with test circuit B (Unbalanced supply circuit / Balanced return circuit) of Table 1 and Test series X of Table 2. Each insulator unit shall withstand this test without puncture or mechanical failure. 3.1.7 Radio-Influence Voltage test, as per Standard IEC 60437. 3.1.8 Residual-Strength test, as per Standard IEC 60797. 3.2 SAMPLE TESTS: 3.2.1 Puncture test, as per paragraph 15.1 3.2.2 Steep front-of-wave flashover voltage test, according to requirements and procedures of Standard IEC 61211/2004. 3.2.3 Verification of dimensions, as per paragraph 17. 3.2.4 Mechanical failing load test, as per paragraph 19. 3.2.5 Verification of the axial, radial and angular displacements, as per paragraph 21. 3.2.6 Verification of the locking system, as per paragraph 22. 3.2.7 Thermal shock test, as per paragraph 24. 3.2.8 Galvanizing test, as per paragraph 26. 3.3 ROUTINE TESTS (shall be performed in the following order): 3.3.1 Visual examination, as per paragraph 27. 3.3.2 Mechanical routine test (to a tensile load equal to 50% of the specified electromechanical failing load), as per paragraph 28.2. 4. INSPECTION AND TESTING 4.1 The insulators shall be subjected to inspection and shall not be released for shipping without the approval of Corporation s representative. The approval for shipping shall neither relieve the from responsibility of furnishing material conforming to all requirements of Corporation nor invalidate any claim which Corporation may make because of defective or unsatisfactory material. Page 3 of 8 TR 1/Rev. March 2015

4.2 shall submit to Corporation copies of the control and test reports of the material. Corporation reserves the right to demand all the routine test reports from the manufacturer. 4.3 In each delivery quantity, sample tests shall be performed in accordance with the requirements of par.3.2 of present specification. 4.4 For type test reports that haven t been submitted or that aren t adequate according to the requirements of par.3 of present specification, IPTO SA reserves the right to request the performance of any or all type tests specified in par.3.1 of present specification on samples which shall be taken from the production of the offered items. The Corporation reserves the right to select test laboratory and witness any or all tests. 4.5 All Bidders shall have to state the manufacturers of the material, as well as all related sub-contractors, if any. They shall also have to submit along with their offer a Quality Assurance Plan (Q.A.P), for the manufacturing procedure of the stated manufacturer and all potential sub-contractors, by which it shall be evident in a detailed way the entire manufacturing procedure, the quality control equipment as well as all quality control stages, including all of the related printed material and referring to the specific international standards and regulations applied. During the Technical Evaluation procedure, IPTO SA shall reserve itself the right to monitor the production procedure so as to ascertain the application of the Q.A.P. and, in general, to conclude on the production procedure, in a way that shall deem the offer technically acceptable or not. 5. PACKING AND SHIPPING 5.1 Packing and shipping of the insulators must be in such a manner that protects them from damage in transit (by sea, plane, rail way, on road) and handling. 5.2 Containers shall conform the all standard requirements, for the class of material being packed and shall be suitable for outdoor storing. 5.3 Each container shall be legibly and durable marked with the gross weight, the number of units, the purchase order number, the characteristic mark of the manufacturer and all shipping marks. 5.4 All insulators, together with crates and methods of packing, shall be subject to final inspection and test at Seller's works. The number of insulators in each crate is specified in ANNEXES A, B and C. 6. DATA TO BE SUBMITTED WITH OFFER In the offers must be included the following in a clear and unique way. 6.1 Full description of the offered items, with a scale drawing showing in cross-section for each insulator type, all essential, dimensions and tolerances, type of material of each part and method of casting (malleable or cast, etc.) of metal parts. 6.2 A reference list of at least three (3) Electrical Companies, who have buy enough quantities of the same or similar type insulators with those that are offered which have been used with excellent operation on overhead Transmission Lines, for a period of at least five (5) years followed by the corresponding certificates. Reference list and corresponding certificate shall include the exact type of insulator, operation voltage, exact quantity and the date of selling or installation. Certificates shall be original or validated copies and distinct regarding the Electrical Company that edit and guarantee the excellent operation of corresponding insulators. Bidders that have supplied in the last decade, IPTO SA (or PPC SA) with the requested material, have no obligation of submitting the prerequisites of this paragraph, provided that it does not change the factory of manufacture. 6.3 Test reports concerning the type tests specified in par.3.1 of present specification, by independent Page 4 of 8 TR 1/Rev. March 2015

laboratory accredited according to International Standard ISO/IEC 17025. Test reports must be complete, with drawing of the tested insulator. 6.4 Confirmation of the insulators specified in ANNEXES A, B or C and to complete them in corresponding columns. 6.5 The following for a string of 10 units in case of insulators of ANNEX A and 18 units in case of insulators of ANNEX B and C: - Low-frequency flashover dry, - Low-frequency flashover wet, - Dry impulse flashover positive and negative and - Wet Switching Impulse flashover positive and negative. Page 5 of 8 TR 1/Rev. March 2015

I N D E P E N D E N T P O W E R T R A N S M I S S I O N O P E R A T O R S. A. TRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION ATHENS - GREECE SPECIFICATION TR-1 / ANNEX A INSULATOR DATA (Insulators for application on 150 kv T.L.) DESIGNATION Normal type Fog type Type 1 Fog type Type 2 Maximum Diameter mm 255 255 280 Spacing mm 146 127 146 Ball and Socket size mm 16A 16A 16A Minimum Leakage Distance mm 295 390 440 Min.Electro-Mechanical failing load / Tensile strength kn 100 100 100 Mechanical Impact strength Nm 10 10 10 Short Circuit Current of the system ka 18 18 18 Isys Duration t sec 0.5 0.5 0.5 kv 70 70 85 Dry one minute Dry one minute kv 280 244 280 kv 40 40 50 Wet one minute Wet one minute kv 195 170 195 Dry lightning Impulse Withstand voltage kv 105 110 125 Dry lightning Impulse Withstand voltage kv 430 395 430 Puncture Voltage kv 130 130 130 test Voltage to determine RIV, rms to ground kv 10 10 10 Maximum RIV at 1000 khz µv 50 50 50 Number of units per package 5 6 5 Net weight per unit kg Remarks: 1. The pin of the fog type insulators shall be equipped with a zinc sleeve fused to it without gaps. The fused area shall be more than 80% of the total area between the zinc sleeve and the pin. The zinc sleeve shall have sufficient thickness and length. The zinc shall have a minimum purity of 99.7% 2. The galvanization of the caps of the fog type insulators shall be reinforced with a thickness of 110 µm. 3. Especially the fog type insulators, type 1, shall be designed according to drawing TMΓM 1001, regarding the under ribs. 4. The value Isys shall be used to perform type test of par.3.1.6 of present specification, with test circuit B of Table 1 and Test series X of Table 2, according to International Standard IEC 61467. Page 6 of 8 TR 1/Rev. March 2015

Page 7 of 8 TR 1/Rev. March 2015

I N D E P E N D E N T P O W E R T R A N S M I S S I O N O P E R A T O R S. A. TRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION ATHENS - GREECE SPECIFICATION TR-1 / ANNEX B INSULATOR DATA (Insulators for application on 400 kv T.L.) DESIGNATION Normal type Fog type Maximum Diameter mm 280 330 Spacing mm 170 170 Ball and Socket size mm 20 20 Minimum Leakage Distance mm 370 540 Min.Electro-Mechanical failing load / Tensile strength kn 160 160 Mechanical Impact strength Nm 10 10 Short Circuit Current of the system Isys ka 31.5 31.5 Duration t sec 0.5 0.5 kv 75 90 Dry one minute Dry one minute kv 300 320 kv 45 55 Wet one minute Wet one minute kv 200 230 Dry lightning Impulse Withstand voltage kv 110 140 Dry lightning Impulse Withstand voltage kv 470 535 Puncture Voltage kv 130 130 test Voltage to determine kv 10 10 RIV, rms to ground Maximum RIV at 1000 khz µv 50 50 Number of units per package 5 6 Net weight per unit kg Remarks: 1. The pin of the fog type insulators shall be equipped with a zinc sleeve fused to it without gaps. The fused area shall be more than 80% of the total area between the zinc sleeve and the pin. The zinc sleeve shall have sufficient thickness and length. The zinc shall have a minimum purity of 99.7% 2. The galvanization of the caps of the fog type insulators shall be reinforced with a thickness of 110 µm. 3. The value Isys shall be used to perform type test of par.3.1.6 of present specification, with test circuit B of Table 1 and Test series X of Table 2, according to International Standard IEC 61467. Page 8 of 8 TR 1/Rev. March 2015