Electro-Chemical UET Water Treatment System Achieves Sustainability Objectives for Scottsdale Fashion Square Mall.

Similar documents
IWC ZLD: New Silica Based Inhibitor Chemistry Permits Cost Effective Water Conservation for HVAC and Industrial Cooling Towers

NACE Paper No

Water Conservation Technology for Recirculating Cooling Systems

Cooling Tower Water Management Plan. 901 Fifth Avenue

Zero Liquid Discharge Cooling Tower Treatment at CSI

4709 Hwy 36 South, Suite 10 Rosenberg, TX Phone:

Saturation Index -100 F

Puckorius & Associates, Inc.

NACE CORROSION 2008 TEG 096X Symposia - Paper 1421

Real World Experiences with a Plant- Based Alternative to Chemical Treatment in Cooling Water Systems

SRS WATER TREATMENT SYSTEMS

WATER BASICS ENGR. ALBERT SAMUELA KHUN UNNOP TONGYA

1. Introduction. Figure 1: Open Recirculation Cooling Water Tower (image courtesy of Solenis) Page 3

Case Study 3M Corporate Headquarters 2014 Distributed by:

EXHIBIT A UNIVERSITY OF NEVADA - LAS VEGAS WATER TREATMENT BEST PRACTICES

Sulfuric Acid Plant Cooling Tower Improvements

Cooling Tower Water Conservation: Simple Strategies & Advanced Treatment Eric Elam Water Savers LLC, RTS Water August 15 th, 2017

Operation and Maintenance of Electrochlorination Plant

BRINGING WATER TREATMENT IN HOUSE - MONITORING AND CONTROL STRATEGIES AND IMPROVED RESULTS AT NRG PHOENIX

Cooling tower efficiency U2 Eco-efficiency resources for the food processing industry

Zero Discharge Treatment Method for Cooling Towers and Heat Exchangers with SP3, I-SOFT-OB, OXYDES & KATALOX LIGHT

Green Technologies to Minimize Cooling Tower Water Use

GRUNDFOS WHITE PAPER. Chlorine dioxide offers increased efficiency and

COOLING TECHNOLOGY INSTITUTE

Boiler Water Treatment

Cleaning Techniques for Cooling Systems and Boilers

On-Site Generation Of Disinfectants

Case Study - Office Building Cooling Tower - Bio and Scale. (10 week evaluation)

Distribution Review. Corrosion Control. Corrosion Control Vocabulary. American Water College 1. Corrosion Control Training Objectives

WATER SAVING REDUCES TREATMENT OPERATING COSTS ENERGY-EFFICIENT COOLING TOWER

Evaluation of the Performance of Scalesweeper, an Electromagnetic Unit, to Prevent Scale Formation in Water and Heating Systems February 2017

high cycles cooling tower operation using a revolutionary alkaline treatment program Continuum* AEC (Alkyl Epoxy Carboxylate)

DeCaIon. A badly scaled/fouled heat exchanger. A well maintained heat exchanger SGBP

Metropolitan Washington Airports Authority PROCUREMENT AND CONTRACTS DEPT. AMENDMENT OF SOLICITATION

White Paper. A Reliable Alternative to Chemicals for Cooling Water Treatment. GWS-1107-D 10/31/11 Copyright 2011 All Rights Reserved

Only a small concentration of this Sodium Hypochlorite is required to combat marine fouling, 0.1 to 0.3 ppm.

Cooling Tower Water Management

Evaluation of the Performance of Scalesweeper, an Electromagnetic Unit, to Prevent Scale Formation in Water and Heating Systems

Boiler/Cooling Water Processes and Parameters

Cooling Tower Water Treatment. 30A avenue du Pacifique Laval Qc.H7N 3X5 Téléphone

Evaluation of the Performance of Scalesweeper, an Electromagnetic Unit, to Prevent Scale Formation in Water and Heating Systems

OPERATIONAL UPDATE ON INNOVATIVE COOLING TOWER PRETREATMENT TECHNOLOGY

Evaporative Condenser Passivation. Cameron Klein Strand Associates, Inc.

The Cooling Water Handbook A basic guide to understanding industrial cooling water systems and their treatment

Water supplied by Marafiq does not meet the process requirements.

On Site Disinfectant & Anti Fouling Generation Systems. By Aeolus Sustainable Bio-Energy Pvt Ltd Surat

About EVAPCO. EVAPCO for LIFE OUR COMMITMENT PROTECTING THE ENVIRONMENT

Zero Blowdown Technology - ZBT Arizona Transportation Center

Optimizing Steam and Cooling Systems for Reliability and Sustainability. Presented By: Kevin Emery

ENEREF INSTITUTE EXAMINES FILTRATION SYSTEMS FOR BUILDING COOLING TOWERS.

ELECTROLYTIC RECOVERY FROM RINSE WATERS. C.A.Swank. ERC/LANCY Division of Dart & Kraft, Inc. 525 West New Castle Street Zelienople, PA 16063

A. Submit manufacturer s data, qualifying documents, and shop drawings on the proposed water treatment system before starting any work.

Tech Byte 11: Benefits of Filtration for Open Cooling Tower Systems

M. Ghazi Mirsaeed 1, A.Ataei 1, A. Torabian 2, A.H. Hassani 1, J.Hashmiyan 3

LOCALIZED AND GENERAL CORROSION OF COPPER IN AZOLES AND SILICA INHIBITED ZERO BLOWDOWN COOLING WATER IN AN AUTOMOTIVE PLANT

Engineering for Legionella Control at Cooling Towers. Clive Broadbent AM, FIE Aust.

PRODUCTION OF PW/HPW/WFI AND USP/EP REQUIREMENTS. Erez Eilam F&U Area Lead Novartis Singapore Bio production Operations

A new application of an old idea

Water Treatment System

WHITE PAPER. Water Quality. Management for the Plastics Industry. Benefit from Improved. Water Quality. Management.

Case Study Whistler Water Distribution System Corrosion Study

Making feed water for you! Advantage. Protecting any Water Treatment System against. Scaling. a Water Company WAT C H WAT E R

Joel E. Bowdan III, P.E WateReuse California CII Pre-Conference Workshop

On-Site Sodium Hypochlorite Generation Equipment

Scale and Deposition are Often the First Problem Associated With Tower and Refrigeration Systems

COOLING TOWER WATER TREATMENT

EFFECTIVE USE OF RECYCLED WATER IN COOLING TOWERS WITH NEW GREEN TECHNOLOGY. Abstract

Status of Chlorate Regulations & Impact at Water Treatment Plants

Japanese Car Manufacturer. Cooling Towers

Purification of Brackish Water using Hybrid CDI-EDI Technology

TRUSTEES OF THE CALIFORNIA STATE UNIVERSITY CALIFORNIA STATE UNIVERSITY, FULLERTON REQUEST FOR PROPOSAL NO ADDENDUM NO. 1

TITLE: WATER TREATMENT PROGRAM FOR CHILLED WATER PLANTS THIS ADDENDUM IS FOR THE PURPOSE OF MAKING THE FOLLOWING CHANGES OR CLARIFICATIONS IN RED:

Electro-Pure Technology. Advanced Water Treatment Technology. Ability to treat a wide range of contaminants simultaneously

Cooling Tower Treatment Chemicals

Chemical Free Water Treatment System

EVAPCO ENGINEERING. Commercial HVAC. District Energy. Industrial Process. Power. Industrial Refrigeration

# 524 Compare Drinking and Bottle Water Sciencefaircenter.com Study Kit

Corrosion Monitoring in Cooling Water Systems

Rural & Urban Drinking Water Disinfection Systems. By Aeolus Sustainable Bio-Energy Pvt Ltd Surat

13 th Annual GC&EC Green Corrosion Inhibition and Water Treatment Session

Writing Service Reports

The Application of Non-phosphorous AEC Program in Cooling Water Systems of Petrochemical Industry

In Depth Feasibility Studies Aquifer Thermal Energy Storage (ATES) VAMC Chillicothe and Columbus, OH

Schematic diagram of a cooling water system

Types of corrosion. 1)Uniform or General Corrosion

HIGH EFFICIENCY 0.5 & 0.25 MICRON COOLING WATER FILTRATION SYSTEM

BIOBAN CWT Brand of 25% Aqueous TRIS(HYDROXYMETHYL)NITROMETHANE Cooling Water Treatment Microbicide EPA Reg. No

Addendum #4. Addendum No. 4

COC = ,000/ (CaH x TA) This discovery is the basis of our unique, patented HighCycle water management products.

Chlorine dioxide. Chlorine dioxide

POTENTIAL ENERGY AND COST SAVINGS THROUGH PROPER TREATMENT OF HEATING AND COOLING SYSTEMS

What We ve Learned About Biofilms

OC30 Conduct a qualitative experiment to detect the presence of dissolved solids in water samples, and test water for hardness (soap test)

COMMERCIAL AND INDUSTRIAL PROCESS COOLING AND CONDENSER WATER SYSTEMS

Electrocoagulation. Achieving clean, clear, treated and reusable water: The process, technology and benefits. CALL US (631)

Lecture 1: Introduction

Higher COC and ph Independent Operation of Cooling Water Systems

EVAPCO ENGINEERING. Commercial HVAC. District Energy. Industrial Process. Industrial Refrigeration. Power

IWC REPORT ZLD: New Silica Based Inhibitor Chemistry Permits Cost Effective Water Conservation for HVAC and Industrial Cooling Towers

Bringing new ground in

Transcription:

Electro-Chemical UET Water Treatment System Achieves Sustainability Objectives for Scottsdale Fashion Square Mall. By George Chac, Melvin Mathew and Terry Waldo May, 28 Owned by Macerich (NYSE:MAC), Scottsdale Fashion Square is the largest and most upscale shopping center in Arizona. It s also recognized as one of the most-visited destinations in the state. Scottsdale Fashion Square is sharply focused on integrating sustainability in its operations as part of its long-term, fully-integrated business model., as are all of the fiftyfive Macerich malls located in fifteen states, coast to coast. The Macerich commitment to Saving water The Macerich commitment to saving water led them to search for an innovative but proven technology that not only reduces water use, but also, eliminates chemical use and decreases costs. The cooling towers utilized in the mall s HVAC systems were the single largest user of water, so they were scrutinized in great detail, thus, prompting the discovery of a new system.

The new system utilizes Dynamic Water s UET electro-chemical reactors to speed the process of scaling within the controlled environment of tubular reactors on a basin side loop, rather than in their process piping. The controller continuously adjusts the electrolysis by examining 42 parameters every 6 milliseconds. It then sends an electric current from an anode to the cathode using the water as a medium. The DC process spurs electrolysis in the water, separating H+ and OH+ ions from their counterparts, achieving equilibrium while retaining the minerals required to maintain proper PH balance. The rapidly formed scale is soft and easy to clean out of the reactor chamber. The water leaving the reactors is in balance and no longer seeks to deposit scale in the tower or process piping and chiller. SCOPE: The purpose of this report is to show Dynamic Water s UET Reactor s efficacy as a water treatment alternative to traditional chemical treatment in Scottsdale Fashion Square. The study will take the existing site using the UET system and quantify efficacy using the following: - Before and After Photos showing progress - Water usage before and after UET treatment - Corrosion control during UET treatment - Approach Temperature during UET treatment Scottsdale Fashion Square Results Cooling System: UET System: 4x BAC 3985C-2 Cooling Towers @ 985 nominal tons each 3,94 total tons of refrigeration (4) 4x4 UET Reactor Systems UET Service Start : August 2 st, 27 Results Water Savings Metrics: Before UET After UET Cycles 3.5 6.5 Conductivity Bleed/Setpoint (µs/cm) 3,5 6,5 Annual Water Usage (gallons) 9,976, 7,854, (2% savings) Annual Blowdown (gallons) - ESTIMATE 2,85, (estimate),28, (57% savings) Makeup conductivity is roughly, µs/cm How UET Achieved the Macerich Goals The UET process is a well-established technology which works with any water composition to restore water to its natural balance without adding chemicals by applying continuous partial electrolysis.

Cooling System Efficiency: No appreciable change in approach temperatures. All approach temperatures are trending down over time, pointing to signs of scale removal within the chiller. 2 Chiller Approach Temperatures.5.5 8/3/27 9/22/27 //27 2/3/27 2/9/28 4//28 5/3/28 condenser # Approach Linear (condenser# Approach) 2 Chiller 2 Approach Temperatures.5.5 8/3/27 9/22/27 //27 2/3/27 2/9/28 4//28 5/3/28 condenser #2 Approach Linear (condenser#2 Approach)

2 Chiller 3 Approach Temperatures.5.5 8/3/27 9/22/27 //27 2/3/27 2/9/28 4//28 5/3/28 condenser #3 Approach Linear (condenser#3 Approach) AFTER UET (November 27):

CORRATOR RESULTS: Corrator results show copper and mild steel corrosion well within acceptable range.

The Science behind UET UET uses Partial Electrolysis to create ph gradient H2O H+ + OH- Anode has a ph of, Cathode has ph of 4 Due to ph gradient, ions begin aggregating in order to balance the water. Cathode has aggregation of positive ions (calcium, magnesium). Anode has aggregation of negative ions (chlorides).

Excess calcium, silica and magnesium precipitate with carbonate and forms onto the cathode wall (scale control). Chlorides in water become activated to form HOCl and Chlorine (biocide). Water has saturated, stable Ca2+ and Mg2+ which acts as a corrosion inhibitor. ph of 9 is far from corrosive index (corrosion control) Scale, Corrosion and Bio-Contamination Scale, corrosion, and bio-contamination are the cause of major problems with commercial and industrial process water systems. Inefficient heat transfer, plugging, and outright failure happen all the time. Treatment of all three must be simultaneous to achieve and maintain effective water treatment. UET simultaneously controls all three problems: SCALE: The unstable minerals are precipitated within the wall of the reactor, keeping it out of the system. CORROSION: Stable calcium and magnesium ions are left in an aqueous state while the ph is balanced around 9. The water is well within the scale forming region, thus preventing corrosion. BIO-CONTAMINATION: The UET provides continuous halogenation and is able to raise or lower chlorine level. Why Traditional Treatment Fails Chemical treatment does not have an answer for changes in makeup water composition. Many chemical treatments can go awry, oscillating between scale forming and corrosion while blooming dangerous amounts of bio-contamination. Chemical treatment does not have an answer for silica. Typically chemical treatment programs will not go above 5 ppm silica. Why Dynamic Water Technology Succeeded UET is a patented technology that utilizes controlled electrolysis to manage scaling, corrosion and biocontamination instead of chemicals. The system speeds the process of scaling within the controlled environment of tubular reactors on a basin side loop, rather than in the process piping.

The controller continuously adjusts the electrolysis. It then sends an electric current from an anode to the cathode using the water as a medium. The DC process spurs partial electrolysis in the water, splitting H+ and OH+ ions. The rapidly formed scale is soft and easy to clean out of the reactor chamber. The water leaving the reactors is in balance and no longer seeks to deposit scale in the tower or process piping and chiller. The reactor also generates measurable chlorine, despite not adding any chemicals. The biocide level is adjustable and disinfects the process water, killing algae and bacteria, including the pathogenic legionella. Cooling System Efficiency: No appreciable change in approach temperatures. All approach temperatures are trending down over time, pointing to signs of scale removal within the chiller. 2 Chiller Approach Temperatures.5.5 8/3/27 9/22/27 //27 2/3/27 2/9/28 4//28 5/3/28 condenser # Approach Linear (condenser# Approach) 2 Chiller 2 Approach Temperatures.5.5 8/3/27 9/22/27 //27 2/3/27 2/9/28 4//28 5/3/28 condenser #2 Approach Linear (condenser#2 Approach)

2 Chiller 3 Approach Temperatures.5.5 8/3/27 9/22/27 //27 2/3/27 2/9/28 4//28 5/3/28 condenser #3 Approach Linear (condenser#3 Approach) AFTER UET (November 27):