SIGNIFICANCE OF ACCELERATION IN THE DESIGN OF DAMPERS FOR LIFELINE BUILDINGS IN SEISMIC GROUND MOTIONS

Similar documents
EFFECT OF FLUID VISCOUS DAMPERS IN MULTI-STOREYED BUILDINGS

Choice of in-structure Damping Model: Do we have an answer? Answer?

Evaluation Of Response Modification Factor For Moment Resisting Frames

SEISMIC ANALYSIS OF BUILDING USING TWO TYPES OF PASSIVE ENERGY DISSIPATION DEVICES

EARTHQUAKE RESPONSE ANALYSIS OF MID-STORY BUILDINGS ISOLATED WITH VARIOUS SEISMIC ISOLATION TECHNIQUES

International Journal of Intellectual Advancements and Research in Engineering Computations

Assistant Professor, Applied Mechanics Department, Government College of Engineering, Amravati, India 2

Study of seismic effect on buildings modified with shear wall

IMPROVING SEISMIC PERFORMANCE: ADD STIFFNESS OR DAMPING? Trevor E. Kelly 1

COMPARITIVE STUDY OF BASE ISOLATORS AND VISCOUS FLUID DAMPERS ON SEISMIC RESPONSE OF RC STRUCTURES

SEISMIC VULNERABILITY OF EXISTING RC BUILDINGS IN INDIA

SSRG International Journal of Civil Engineering ( SSRG IJCE ) Volume 4 Issue 6 June 2017

Kiran K. Shetty & Krishnamoorthy Department of Civil Engineering, Manipal Institute of Technology, Manipal , Karnataka, India

Application of Isolation Technology in High-voltage Electrical Equipments

Parametric Study of Dual Structural System using NLTH Analysis Ismaeel Mohammed 1 S. M. Hashmi 2

Performance-based plastic design of a high rise moment resisting frame with friction dampers

SEISMIC DAMAGE CONTROL WITH PASSIVE ENERGY DEVICES: A CASE STUDY

ANALYSIS PROCEDURES FOR PERFORMANCED BASED DESIGN

EFFICIENCY OF USING VISCOUS DAMPERS FOR MULTI-STOREY STEEL STRUCTURES SUBJECTED TO SEISMIC ACTIONS


Earthquake Resistant Design for Low Rise Open Ground Storey Famed Building

Seismic Behaviour Of A Soft Storey Building With & Without Viscous Dampers

SEISMIC RESPONSE OF UNSYMMETRIC BUILDING WITH OPTIMALLY PLACED FRICTION DAMPERS

Seismic performance assessment of reinforced concrete buildings using pushover analysis

Seismic behavior of concrete structures equipped with ADAS devices

Seismic Behavior Of Reinforced Concrete Buildings Under Varying Frequency Contents

COMPARATIVE ANALYSIS OF SEISMIC ISOLATED SYSTEMS IN BRIDGES

METHODOLOGY OF THE VULNERABILITY STUDY OF THE STRATEGIC BUILDINGS IN ALGERIA

Non Linear Static Analysis of Multi-storeyed Special Moment Resisting Frames

Linear and Nonlinear Seismic Analysis of a Tall Air Traffic Control (ATC) Tower

EARTHQUAKE LOADS ON MULTISTOREY BUILDINGS AS PER IS: AND IS: : A COMPARATIVE STUDY

Seismic Assessment of an RC Building Using Pushover Analysis

Supplemental damping for seismic strengthening: a case study

Seismic Evaluation of the Historic East-Memorial Building Retrofitted with Friction Dampers, Ottawa, Canada

Seismic Performance of Multistorey Building with Soft Storey at Different Level with RC Shear Wall

Dynamic Time History Analysis of Plane Frame with Tuned Mass Considering Soil-Structure Interaction

SEISMIC RESPONSE OF MULTISTOREYED STEEL FRAME WITH VISCOUS FLUID SCISSOR JACK DAMPERS

Comparison between Seismic Behavior of Suspended Zipper Braced Frames and Various EBF Systems

Performance Improvement of Tall Reinforced Concrete Structures with Multiple Tuned Mass Dampers (MTMD)

PERFORMANCE BASED ANALYSIS OF R.C.C. FRAMES

NON-LINEAR STATIC PUSHOVER ANALYSIS FOR MULTI-STORED BUILDING BY USING ETABS

Evaluation of Seismic Response Modification Factors for RCC Frames by Non Linear Analysis

DYNAMIC ANALYSIS OF 25 STOREY RCC BUILDING WITH AND WITHOUT VISCOUS DAMPERS. Naziya Ghanchi1, Shilpa Kewate2

Department of Civil Engineering, SKP Engg. College, Tiruvanamalai, TN, India

Pushover Analysis of RC Bare Frame: Performance Comparison between Ductile and Non-ductile detailing

SEISMIC ASSESEMENT OF RC FRAME BUILDINGS WITH BRICK MASONRY INFILLS

EQUIVALENT UNIFORM DAMPING RATIOS for Irregular in Height Concrete / Steel Structural systems

Seismic Response of Soft Storey Buildings with Viscoelastic Dampers

International Journal of Engineering Research & Science (IJOER) ISSN: [ ] [Vol-3, Issue-3, March- 2017]

MAXIMUM FLOOR DISPLACEMENT PROFILES FOR THE DISPLACEMENT-BASED SEISMIC DESIGN OF REINFORCED CONCRETE FRAMES

COMPARATIVE STUDY OF REINFORCED CONCRETE SHEAR WALL ANALYSIS IN MULTI- STOREYED BUILDING WITH OPENINGS BY NONLINEAR METHODS

PERFORMANCE BASED SEISMIC EVALUATION OF MULTI-STOREYED REINFORCED CONCRETE BUILDINGS USING PUSHOVER ANALYSIS

Aluminium Shear Yielding Damper (Al-SYD) as an Energy Dissipation Device in Truss Moment Frames (TMFs)

Torsional and Seismic Behavior of Shear Wall Dominant Flat Plate Buildings

International Journal of Engineering and Techniques - Volume 4 Issue 2, Mar Apr 2018

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Control of Earthquake Resistant High Rise Steel Frame Structures

Comparative Study and Seismic Analysis of a Multistorey Steel Building

Proceedings of the 3rd International Conference on Environmental and Geological Science and Engineering

Seismic Analysis and Design of Vertically Irregular RC Building Frames

Seismic Performance of Residential Buildings with Staggered Walls

Dynamic Analysis of High Rise Flat Plate Building with Different Retrofitting Systems

PUSHOVER ANALYSIS (NON-LINEAR STATIC ANALYSIS) OF RC BUILDINGS USING SAP SOFTWARE

A Performance Based Evaluation of a Wall- Frame Structure Employing the Pushover Analysis Tool

Damage-control Seismic Design of Moment-resisting RC Frame Buildings

Seismic Damage Prediction of Reinforced Concrete Buildings Using Pushover Analysis

Dynamic Response of Ground Supported Rectangular Water Tanks to Earthquake Excitation

EFFECTS OF STRONG-MOTION DURATION ON THE RESPONSE OF REINFORCED CONCRETE FRAME BUILDINGS ABSTRACT

DYNAMIC TESTING OF FULL-SCALE 11-STORY RC BUILDING AND ITS 3-STORY STRUCTURAL PART: COMPARISON OF THE RESULTS AND SEISMIC RESISTANCE ESTIMATION

COMPARISON BETWEEN TWO OPTIMIZATION PROCEDURES FOR DAMPER LOCATION IN STEEL FRAME STRUCTURES

SEISMIC DESIGN OF STRUCTURE

SEISMIC PERFORMANCE OF FLAT SLAB WITH DROP AND CONVENTIONAL SLAB STRUCTURE

Effective Viscous Damping Ratio in Seismic Response of Reinforced Concrete Structures

ANALYSIS OF A SQUAT CONCRETE WALL, DIFFERENCE IN TRANSLATION DURING SEISMIC EXCITATION DUE TO FOUNDATION SUPPORT. ABSTRACT

Optimum Dimensions of Suspension Bridges Considering Natural Period

Improved Seismic Response of RC Frame Structures by Using Fluid Viscous Dampers

Seismic Performance Of R C Flat-Slab Building Structural Systems

Evaluation of Response Reduction Factor and Ductility Factor of RC Braced Frame

Seismic assessment of an existing hospital

Keywords: Discrete Staggered Shear Wall, High-Rise Building, Response Spectrum Analysis, Storey Drift.

Initial cost and seismic vulnerability functions for buildings with energy-dissipating devices

NONLINEAR PERFORMANCE OF A TEN-STORY REINFORCED CONCRETE SPECIAL MOMENT RESISTING FRAME (SMRF)

MCEER Hospital Demonstration Project

Investigating the Effect of Pounding on Seismic Response of Isolated Structures

Performance Based Placement Of Visco-Elastic Dampers In An R.C.C Building

Behavior and Performance of Structures Equipped With ADAS & TADAS Dampers (a Comparison with Conventional Structures)

S. Gandhi *1, Syed Rizwan 2

Pushover Analysis Of RCC Building With Soft Storey At Different Levels.

Static Analysis of Multistoreyed RC Buildings By Using Pushover Methodology

Analytical Study on Seismic Performance of Hybrid (DUAL) Structural System Subjected To Earthquake

SEISMIC RESPONSE ANALYSIS OF VERTICALLY IRREGULAR RC BUILDINGS USING LAMINATED RUBBER BEARING

Chapter 13 SEISMICALLY ISOLATED STRUCTURE DESIGN REQUIREMENTS

OPTIMUM POSITION OF OUTRIGGER SYSTEM FOR HIGH RAISED RC BUILDINGS USING ETABS (PUSH OVER ANALYSIS)

N.Nageswarao Department of Civil Engineering, Amara Institute of Engineering and Technology.

Comparison of Seismic Behavior of Multi-Storey R/C Buildings With and Without Internal Beams

Effects of Building Configuration on Seismic Performance of RC Buildings by Pushover Analysis

Performance-Based Seismic Evaluation of Wind-Impacted Tall Buildings

Modeling of Reinforced Concrete Folded Plate Structures for Seismic Evaluation Swatilekha Guha Bodh

PERFORMANCE ASSESSMENT OF COMPOSITE MOMENT-RESISTING FRAMES

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Transcription:

SIGNIFICANCE OF ACCELERATION IN THE DESIGN OF DAMPERS FOR LIFELINE BUILDINGS IN SEISMIC GROUND MOTIONS ABSTRACT: Arun M Puthanpurayil 1 and Dr. Paul Reynolds 2 1 Structural Engineer, Gifford, UK 2 Senior Lecturer, Dept. of Civil and Structural Engineering, University of Sheffield, UK Email: Arun.Mankavu@gifford.uk.com, p.reynolds@sheffield.ac.uk This paper describes an analytical study carried out to investigate the significance of the floor acceleration parameter in the design of viscous dampers aimed at reducing nonstructural damage in lifeline buildings (those buildings that need to be functional after the earthquake, e.g. Hospitals) during a seismic ground motion. A comparative quantitative assessment is carried out between the minimum drift criterion and minimum acceleration criterion for both near field and far field ground motions. The study reveals that significant anomalies are observed if the proportioning of the damper is carried out solely using the minimum drift based criterion, which is more common in practice. Both linear dampers and nonlinear dampers are used for the study; linear dampers for low rise structures and nonlinear dampers for medium and high rise structures. Linear time history analyses were performed for low rise structures equipped with linear dampers and nonlinear modal time history analyses were employed for medium and high rise structures with nonlinear dampers. Both far field and near field ground motions are used for the study. KEYWORDS: Linear Dampers, Nonlinear dampers, Linear Time History analysis, nonlinear modal Time History Analysis 1. INTRODUCTION Lifeline buildings in a broader sense can be described as those buildings which need to be fully functional after an earthquake. These include hospitals, fire stations, electrical control substations etc. which need to be functional in order to carry out a successful rescue operation. Hospitals for example equipped with a lot of highly sensitive equipment need to care for a large number of injured people immediately after the earthquake. So the seismic designs of such buildings need to cater for not only the parent structure, but also the contents of the building, so as to render it fully functional. This means seismic design of such structures should reduce both structural and nonstructural damage to the minimum possible extent. Based on the type of possible damage, nonstructural components can be classified as deformation sensitive or acceleration sensitive. Deformation sensitive nonstructural elements would include the architectural claddings, partitions etc. and acceleration sensitive equipments would include generators, heavy machines rigidly fixed to the floor, archives and normal building contents such as computing devices and shelving. For a lifeline building to be fully operational in emergency situations all these components should be fully functional and intact. At present this is achieved by the innovative application of mechanical devices in the primary structural system which tend to reduce the detrimental response of the system during a seismic motion. A recent study shows that there is considerable reduction in the seismic responses characterizing nonstructural damage of RC frames when viscous dampers are added to the system (Arun, 27). A comparative study carried out for the low, medium and high rise structures showed that; linear dampers resulted in considerable reduction in seismic response of low rise structure while nonlinear dampers were required for medium and high rise categories (Arun, 27). Currently in the design process of viscous dampers for nonstructural damage mitigation, it is a common practice to give more significance to displacement sensitivity than to acceleration sensitivity. This approach can be justified on the

basis that most of the costly nonstructural components of the buildings are displacement/deformation-sensitive (Whittaker & Soong, 23). However this approach would not suffice for lifeline buildings such as hospitals which houses a lot of highly acceleration sensitive contents. This paper emphasizes the significance of acceleration in the design of dampers for lifeline buildings. A set of response curves are presented based on control quantities (drift and acceleration) and a comparative study is carried out on the effect of the damper sizing parameters on these control quantities. The study is carried out for all the three categories of structures i.e. low rise, medium rise and high rise buildings subjected to both near field and far field ground motions. 2. GROUND MOTIONS USED IN THIS STUDY A set of real earthquake time histories were generated using the software Seismosignal developed by Seismosoft. The time histories were classified as Near Field Earthquake (NFE) and Far Field Earthquake (FFE) based on their frequency content. The details of the time histories are given in table 2.1. Table 2.1 Frequency content and Peak ground acceleration of the earthquakes used Earthquakes Predominant Frequency Peak Ground acceleration (g) Content (Hz) Sakaria.3-9..556 (NFE) Loma Priea Corrailitos 2.-3.5.689 (NFE) Chi-Chi Longitudinal 1.6-1.7.776 (FFE) Loma Prieta Emeriville (FFE).6-1..2498 3. METHODS OF ANALYSIS USED IN THE STUDY Linear viscous dampers are analyzed using linear time history analysis and frames with nonlinear viscous dampers are analyzed using nonlinear modal time history analysis (Fast Nonlinear Analysis method). 3.1 Linear Time History Analysis Linear time history analysis is an incremental time stepping procedure for evaluating the dynamic response of a structure subjected to an arbitrary loading that may vary with time (Hart & Wong, 2). The method involves a solution of the complete set of equilibrium equations at each time increment t. The dynamic equilibrium equation for a system is given by Eqn.3.1. M &&+ x Cx& + Kx = f (t) (3.1) Where M is the mass matrix, K is the stiffness matrix, C is the damping matrix. & x&, x& and x are acceleration, velocity and displacement respectively of the structural system and f (t) is the external load vector. Qualitatively, equation (3.1) can be looked upon as derived from static equilibrium considerations at time t. Therefore in short dynamic analysis can be viewed as a static analysis at time t with inertia and damping force included (Bathe & Wilson, 1976). Here in order to solve the equation (3.1), direct integration technique is used. Direct numerical integration attempts to satisfy dynamic equilibrium in specific discrete points in time. The numerical integration is carried out by Hilbur, Hughes and Taylorα method which is a modification of the classic Newmark time integration scheme.

3.2 Nonlinear Modal Time History Analysis (FNA Method) Nonlinear modal time history analysis is carried out using SAP 2. This method is especially suitable for analysis of structures which are primarily elastic, but have some nonlinear elements intended for undergoing large localized strains (Wilson, 22). The force equilibrium of a computer model at a time t with diagonal non-linear elements incorporated is given by Eqn. 3.2(Wilson, 22). M & x& (t) + C x& (t)+ K x (t)+f NL (t) = -f (t) (3.2) Where M is the diagonal mass matrix, K is the stiffness matrix, C is the proportional damping matrix. & x& (t), x& (t) and x (t) are acceleration, velocity and displacement respectively of the structural system and f (t) is the external load vector. The f NL (t) is the global node force vector for the sum of the forces in the nonlinear elements. Here the elastic stiffness matrix K neglects the stiffness of the diagonal nonlinear elements. The mode shapes are determined by Ritz-Vector analysis. Modal analysis by Ritz-vector method spans in the spatial distribution of loading but approximates its frequency content. Ritz vectors are basically constructed from the loading applied (SAP Manual, 22). 4. DESCRIPTION OF SUPPLEMENTALLY DAMPED STRUCTURAL SYSTEM The structures analyzed are three reinforced concrete frames; a two storey frame representing the low rise structure, a ten storey frame representing the medium rise structure and a twenty storey frame representing the high rise structure. The frames are designed as OMRF (ordinary moment resisting frame) with no special requirement for ductility. The cross sections are proportioned by considering only the gravity load effects. This is done in order to assess the maximum possible drift and peak acceleration that can happen in the structure. The frames are designed to take a live load of 4kN/m 2. The frames are assumed to be part of a building with a typical grid spacing of 7.5 m x 7.5 m. The dead loads include the weights of all services, a 25 mm thick slab throughout the plan area in each floor and down stand beams of size 3mm x 7mm. The dampers are arranged such that one damper runs diagonally in each bay in every floor. The damper is assumed to be connected to the centre line of the frames. The damper is assumed to be fitted to the structure in such a way that it does not add additional stiffness to the structure but only provides the damping. The analytical models of the frames are shown in figure 1. (a) (b) (c) Figure 1 (a) Arrangement of dampers in two storey frame (b) Arrangement of dampers in ten storey frame ( c ) Arrangement of dampers in twenty storey frame

5. OBSERVATIONS AND DISCUSSIONS: This section outlines the observations made in the study and also critically draws a qualitative outlook on the effect of acceleration on the damper sizing process. The results are presented in the form of response curves illustrating the effect of the sizing parameters on the control quantities (drift and acceleration) and a comparative study is carried out. As stated earlier linear dampers are used for low rise structure whereas nonlinear dampers are used for medium and high rise structures. The curves for the low rise structure depict the variation of control parameters with respect to damping coefficient c. In the case of medium and high rise structures each curve illustrates the effect of the velocity exponent η on control parameters for a constant damping coefficient c. The c value studied for linear dampers range from 5-2 kn-sec/m and for nonlinear dampers it ranges from 5-8 kn-sec/m. Though higher c values are available in practice, the limits have been chosen by taking a judicious view considering the economic aspect. An increase in the c value always increases the size and cost of the damper (Taylor, 1999). The η value for linear dampers is unity and for the nonlinear dampers, it ranged from.3-1. (Kelly, 21). 5.1 Observations for Near Field ground motions: A total of 64 time history analyses using near field ground motions are carried out for the development of the response curves presented in figures 2-4. Top most Drift vs Damping Coefficient c Acceleration vs Damping Coefficient c 6 Topmost Drift (m).5.4.3.2.1 5 1 15 2 Damping Coefficient c (kn-sec/m) Acceleration (m/s 2 ) 4 2 5 1 15 2 Damping Coefficient c(kn-sec/m) Figure 2 Low Rise Structure (Two Storey Frame) Figure 2 above depicts the variation of drift and floor accelerations with respect to damper sizing parameters. For low rise structures employing linear dampers, a similar trend is followed for both drift and acceleration; Results suggest that, although there are variations in the optimum sizing parameter to be used, in practical terms there is no significant difference between using either the minimum drift or minimum acceleration as the basis for selection. In short for the given range of c under consideration it is easy to qualitatively arrive at optimum sizing parameters by giving due consideration for both the control criterions i.e. drift and acceleration..8 Drift vs Damping Exponent for Ten Storey Structure Acceleration vs Damping Exponent (Ten Storey Structure) Drift (m).7.6.5.4.3.2.1.1.2.3.4.5.6.7.8.9 1 Damping Exponent c=5 c=6 c=7 c=8 Acceleration (m/s 2 ) 12 1 8 6 4 2.1.2.3.4.5.6.7.8.9 1 Damping Exponent c=5 c=6 c=7 c=8 Figure 3 Medium Rise Structure (Ten Storey Frame)

Figure 3 illustrates the variation of control quantities (drift and acceleration) with respect to damper sizing parameters for medium rise structures. Whilst the drift curve obtained is very random in nature with alternating crusts and troughs; On the contrary acceleration curve tends to follow a uniform pattern. It should be noted that if drift alone is taken as the control parameter for damper proportioning, it tends to increase the acceleration. To exemplify this, the value of damping coefficient and velocity exponent for minimum drift is c 5 forη. 4 ; but looking at the acceleration response curves we find that this range is very detrimental for the acceleration criterion as we find the system experiencing peak values and the minimum value for floor acceleration occurs at c 5 and η. 8. So this might prove very critical for buildings hosting acceleration sensitive equipments. Drift vs Damping Exponent for Twenty Storey Structure Acceleration vs Damping Exponent (Twenty Storey Structure).25 5 D rift (m).2.15.1.5 c=5 c=6 c=7 c=8 Acceleration m/s 2 4 3 2 1 c=5 c=6 c=7 c=8.1.2.3.4.5.6.7.8.9 1.1.2.3.4.5.6.7.8.9 1 Damping Exponent Damping Exponent Figure 4 High Rise Structure (Twenty Storey Frame) Figure 4 presents the relationship of control parameters with respect to damper sizing parameters for high rise structures. The drift curves obtained in general have positive slope, whereas the acceleration curves exhibit a negative slope giving an absolute minimum zone forη in the range of.75-.8 after which it changes the slope. Here also the trend exhibited in the medium rise structure is replicated but with a higher intensity. For example, the optimum range of damping coefficient and velocity exponent for minimum drift design is c 6 8 forη.35. 55 ; this range is very detrimental for minimum acceleration criterion as we find the system experiencing peak values. So this might prove very critical for buildings hosting acceleration sensitive equipments. 5.2 Observations for Far Field ground motions: A total of 64 time history analyses using far field ground motions are carried out for the development of the response curves presented in figures 5-7.. Figure 5 Low Rise Structure (Two Storey Frame)

Figure 5 above depicts the variation of drift and floor accelerations with respect to damper sizing parameters for low rise structures subjected to far field ground motions. Here again the trend exhibited as in the case of near field vibration is repeated, but with a reduced intensity. Both the curves have the same nature of slope qualitatively; though a strict quantification of the parameters would suggest a slight variation in the optimum selection of the sizing parameters based on either of the above two described design criterions. As with the low rise study for near field ground motions, the results suggest that, although there are variations in the optimum sizing parameter to be used, in practical terms there is no significant difference between using either drift or acceleration as the basis for selection. In short the response curves indicate that it is easy to qualitatively arrive at optimum sizing parameters by giving due consideration for both the control criterions. Figure 6 Medium Rise Structure (Ten Storey Frame) Figure 6 illustrates the variation of control parameters (drift and acceleration) with respect to damper sizing parameters for medium rise structures. The drift curves obtained are very random in nature with prominent alternating troughs and crests; this is in contrast to the acceleration curves which tend to follow a uniform pattern with a negative slope giving an absolute minimum atη.8. 85 and after which the slope changes the nature showing an ascending trend. But evidently here also it is very explicit that if minimum drift solely is taken as the control parameter, it tends to increase the acceleration. For example, the optimum range of damping coefficient and velocity exponent for minimum drift base criterion is c 7 8 forη.4. 6 ; but this is very critical for the acceleration criterion as we can find that the system experiencing peak values at.4 and then decreases slowly when it proceeds to.6. So this range might prove very critical for buildings hosting acceleration sensitive equipments. Figure 7 High Rise Structure (Twenty Storey Frame)

Figure 7 illustrates the variation of control quantities with respect to damper sizing parameters for high rise structures. The drift curves obtained in general have positive steep slope up to a specific point at which they drop down, whereas the acceleration curves exhibit a general negative slope. Here also the trend exhibited in the medium rise structure is repeated but with a higher intensity. For example, the optimum range of damping coefficient and velocity exponent for drift base design is c 6 8 for η.3. 4 ; but for acceleration consideration this range of sizing parameters exhibits peak values. 5.3 Discussions: The observations made in both near field and far field ground motions emphasizes the significance of floor acceleration as an important control parameter in the design of dampers for lifeline buildings. The effect of floor acceleration is found to be more prominent for medium and high rise structures employing nonlinear dampers as compared to low rise structures employing linear dampers. This can be attributed to the fact that the force in the viscous damper is out of phase with the displacement of the frame and maximum acceleration would occur when the force response reaches a maximum. Medium and High rise structures experience larger drift due to the inherent flexibility of the frame. So if minimum drift criterion is given more significance as compared to minimum acceleration in damper sizing process, then it would call for larger force in the damper. This force would induce higher acceleration in the parent structure. So if drift is considered as the sole control parameter there is a high chance that the system might be vulnerable to the initiation of large accelerations. Although quantitatively the results presented in the study are specific to the analyzed structural system, they pose no limitation to qualitatively understanding the significance of floor accelerations in damper design process. 6. CONCLUSION The effect of acceleration sensitivity in the damper design process is investigated in detail and the results are presented in the form of response curves. A comparative assessment of the effect of the damper sizing parameters on drift and acceleration are presented. The presented results qualitatively illustrate the significance of acceleration in the damper design process for lifeline buildings. Discussions on the observations are also included. REFERENCE Arun, M.P. (27), Optimal Viscous Dampers for Reduction of Non-structural Damage in Seismic Loading, MSc. Thesis, Sheffield University, U.K. Whittaker, A.S and Soong, T.T. ( 23). An overview of nonstructural components research at three US earthquake engineering research centers. seismic design, Performance and Retrofit of Non-Structural components in Critical facilities ATC: 29-2 proceedings, 271-28. Hart, C.G. and Wong, K. (2), Structural Dynamics for Structural Engineers, John Wiley & Sons. Inc, New York. Bathe, K. J. and Wilson, E. L. (1976), Numerical Methods in Finite Element Analysis, Prentice-Hall, Inc., New Jersey. Wilson, E.L. (22), Three-Dimensional Static and Dynamic Analysis of Structures, Computers and Structures Inc., Berkeley, U.S.A. SAP 2 Analysis Reference Manual.(22), Computers and Structures Inc., Berkeley, U.S.A.

Taylor, D.P. (1999), Buildings: Design for Damping, Taylor Devices Inc., U.S.A Kelly, E.T. (21), In-structure Damping and Energy Dissipation: Design Guidelines, Holmes Consulting Group Ltd., Wellington, New Zealand.