Solar cooling design: a case study

Similar documents
Energy study of a non-residential and historic building in transient conditions

SIMULATION MODEL IN TRNSYS OF A SOLAR HOUSE FROM BRAŞOV, ROMANIA

Active solar heating system with concrete plate heating analysed with dynamical thermal simulations

ANNUAL ENERGY PERFORMANCE OF SOLAR THERMAL SYSTEMS IN BRAŞOV, ROMANIA

BUILDING DESIGN AND THERMAL INERTIA: WHEN, WHY, WHERE

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models

Potentials of the new design concepts of district heating and cooling toward integration with renewable energy sources

Solar Power. Technical Aspects and Environmental Impacts. 6 th March 2011 Sustainable Energy Options (UAU212F) - University of Iceland

Energy Audit of two Apartment Buildings in Cagliari using Energy Simulation

Simulation Studies on Performance of Solar Cooling System in UAE Conditions

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

Nearly Zero Energy Building in Lecco Modern technological building compared to an ancient Villa

OPEN COMPETITION Energy Design of High Performance Buildings Organised by EC-JRC and ESRU

Energy Analysis of Using Thermal Mass in a Hot Humid climate

Effect of Building Orientation and Window Glazing on the Energy Consumption of HVAC System of an Office Building for Different Climate Zones

STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS

DESIGN AND MODELING THE Φ-F

362: Indoor climate control effect of AAC panels as determined by house model measurements and simulations

Transient Performance Analysis of a Model Building Integrated with a Trombe-Wall

Performance Modeling of a Solar Driven Absorption Cooling System for. Carnegie Mellon University s Intelligent Workplace

ENERGY SAVING INNOVATION IN CHINESE TRADITIONAL BUILDINGS. L. Zhu Nanjing University of Technology China

JOTUN Cool Shades. Impact of the TSR Value on the Users Comfort and the Energy Performance of Buildings. ai³ Werner Jager

POLYCITY- WORKSHOP BASEL SUSTAINABLE TOWN PLANNING AND ENERGY BENCHMARKING OF BUILDINGS

ENERGETIC MONITORING AND OPTIMIZATION OF A SOLAR HOUSE

Modeling and analyzing solar cooling systems in Polysun

Investigations of thermal self-sufficient Residential Buildings with Solar Energy Systems

PASSIVE HOUSE. is a building, which doesn t need an active type of heating. Dr. Ing Mihail Stancu

The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort

Passive Thermal Control for Window Insulation

MULTIDISCIPLINARY DESIGN PROCESS: URBAN, ARCHITECTURAL AND TECHNOLOGICAL ANALYSES FOR ENERGY-EFFICIENT RESIDENTIAL BUILDINGS IN NORTHERN ITALY

Lecture 3: Utilization of Passive Solar Technology

Available online at ScienceDirect. Energy Procedia 91 (2016 )

SOLAR ENGINEERING OF THERMAL PROCESSES

Simulation And Optimization of a Solar Absorption Cooling System Using Evacuated Tube Collectors

Solar gains in the glazing systems with sun-shading

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

GENERALIZED CRITERIA OF ENERGY PERFORMANCE EVALUATION IN EARLY DESIGN STAGES OF NEARLY ZERO-ENERGY BUILDINGS

Market size and energy consumption of Korean building sector

Eco-technologies for energy efficient buildings in Italy

S. LONGO. The paper shows analysis of the impact on thermal comfort of natural ventilation in a nonresidential Mediterranean case-study.

The Elithis Tower is an experimental and demonstration. Elithis Tower in Dijon, France. nzeb case studies

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Simulation of a concentrating PV/thermal collector using TRNSYS

COMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES

BASIC EUROPEAN GLAZED COLLECTORS & SOLAR DOMESTIC

Passiv Haus Institut. Certification as "Quality Approved Passive House" Criteria for Non-Residential Passive House Buildings

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE

ADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING

THERMAL AND ELECTRICAL PERFORMANCES OF A NEW KIND AIR COOLED PHOTOVOLTAIC THERMAL SYSTEM FOR BUILDING APPLICATION

ZEMedS: Implementation

Solar Cooling Technologies for Southern Climates - A System Comparison

Solar-Assisted Space Heating of a Highly Insulated Energy Efficient House

EVALUATION OF A HIGH TEMPERATURE SOLAR THERMAL SEASONAL BOREHOLE STORAGE

Identified technologies for the InfraSUN pilot plant

Thermal Performance of Retrofitted Envelopes with Internal Insulation: A Comparative Analysis

Asian Journal on Energy and Environment ISSN Available online at

SOLAR PHOTOVOLTAIC ENERGY

TREES Training for Renovated Energy Efficient Social housing. Section 1 Techniques 1.2 Replacement of glazing

Analysis of different shading strategies on energy demand and operating cost of office building

Catalogue of Learning Targets. Certified PHPP Expert

Green Star Design & As Built Submission Template

carbon-neutral architectural design Pablo La Roche CRC Press Taylor & Francis Croup Boca Raton London NewYork CRC Press is an imprint of the

The lotus flower: biomimicry solutions in the built environment

House Pillon Year of construction (2008), Caldaro (IT)

Performance evaluation of hybrid solar parabolic trough concentrator systems in Hong Kong

ANALYSIS OF ENVELOPE THERMAL BEHAVIOUR THROUGH PARAMETRIC STUDIES. Civil Engineer, PhD, Assistant Professor, Civil Engineering Department (3)

Sustainable Building Design and Renewable Applications

SKYLIGHT DESIGN PERFORMANCE EVALUATION METHOD DEVELOPMENT WITH THERMAL AND DAYLIGHT SIMULATION

Passive house optimization for Southern Italy based on the New Passivhaus Standard

Solar Energy Technologies

An Investigation of Energy Efficient and Sustainable Heating Systems for Buildings: Combining Photovoltaics with Heat Pump

Portuguese Thermal Building Legislation and Strategies for the Future

RESEARCH OF SOLAR WATER HEATERS MODEL

Experimental Study to Evaluate the Performance of Iraqi Passive House in Summer Season

Project Description. Projected build start date 02 Aug 2010 Projected date of occupation 03 Dec Existing external wall construction

Residential buildings retrofit: the role of solar technologies

Imp ementation Case:

Chapter 7. Passive Solar Contents

A STUDY ON DESIGN OPTIMIZATION OF A NEAR NET-ZERO ENERGY HOUSE

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France

Performance Analysis of a Solar Powered Adsorption Cooling System

In office buildings, often large windows have been. Total economy of windows and facades in low energy office buildings. Articles

Comparative Study On Simulation Tools Of Annual Heat Load For Energy Management Y. Takahashi 1 *, G. Yoon 1, M. Yoshinaga 2, and R. Chiba 3 1 Graduate

Single family house in Herselt BE

Thermal Control in Buildings by John Straube (updated )

BUILDING INTEGRATION OF RENEWABLE ENERGY SYSTEMS TOWARDS ZERO OR NEARLY ZERO ENERGY BUILDINGS

Figure 1: Uncovered and covered PVT collectors

DEVELOPMENT OF A DESIGN TOOL TO SIMULATE THE THERMAL PERFORMANCE OF DIRECT GAIN PASSIVE SOLAR SYSTEMS USING TMY3 DATA

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

Control strategies study of a complete solar assisted air conditioning system in an office building using TRNSYS.

SOLAR XXI: A Portuguese Office Building towards Net Zero-Energy Building

546: High Altitude Design, Optimising Residential Architecture in the Alborz Mountains, Iran

Simulation and economic analysis of solar cooling for building in tropical climate of Surabaya, Indonesia

Simulation and Energy Analysis of Thermal Environment of Unassisted Passive Solar House

EE2E045 A Calculation Method on the Energy Demand of Urban Districts

Study of the energy performance of a retrofitting office

Solar Cooling for Southern Climates, Double Effect Absorption Chillers with High Concentrating Collectors Versus Standard Single Effect Systems

SOLAR COOLING: STATE OF THE ART, TECHNICAL ANALYSIS AND FIRSTS APPLICATIONS

Thermal insulation of buildings and cooling demand

Transcription:

Eco-Architecture IV 399 Solar cooling design: a case study S. Grignaffini & M. Romagna Department of Astronautic, Electric and Energetic Engineering, Sapienza, University of Rome, Italy Abstract Throughout the years various methods have been used for heat prevention and indoor temperature control in the summer in Mediterranean, tropical and subtropical countries. The alternative cooling strategies are based on various passive and low energy cooling technologies for protection of the buildings via design measures or special components to moderate the thermal gains, or to reject the excess heat to the ambient environment. All these techniques aim to reduce summer cooling loads and electricity demand for air conditioning. During the summer, in Mediterranean, tropical and subtropical countries, the demand for electricity increases because of the extensive use of heating ventilation air conditioning (HVAC) systems, which increase the peak electrical load, causing several problems in the electricity supply. The cooling of buildings can be efficiently addressed by referring to the concepts of energy efficiency and use of renewable sources. A particular method is the use of absorption chillers capable of using the thermal energy for producing chilled water. So, an integration of the system with renewable energy is possible: the absorption chiller can be supplied with thermal energy captured by solar collectors. This last mode of operation leads to the solar cooling systems. The use of solar energy to drive cooling cycles for space conditioning of most buildings is an attractive concept, since the cooling load coincides generally with solar energy availability and therefore the cooling requirements of a building are roughly in phase with the solar radiation. Moreover, they are energy efficient and environmentally safe. The purpose of this paper is to describe a solar cooling system to be installed on the roof of a building in Rome, the headquarters of the State Monopoly of Italy. WIT Transactions on Ecology and The Environment, Vol 165, 201 2 doi:10.2495/arc120351

400 Eco-Architecture IV The medium sized power plant is composed of the following components: solar collectors; thermal storage; absorption chiller; cooling tower; auxiliary system backup. Solar cooling design will be based on a dynamic simulation in TRNsys. Keywords: solar cooling, transient state calculation, TRNsys. 1 Introduction Buildings with a life of over 15 20 years are characterized mostly by poor energy performance. The greater the length of the buildings, the lower their thermal-energy performance, in most cases. The study of their rehabilitation is now an issue technically and scientifically more than ever. Computing systems used today are usually full of uncertainties relying on overly simplified and analytically weak models. The most advanced computing systems in transition, however, are closest to reality and allow for modelling the behaviour of buildings in more detail with step by step analysis and also non-linear correlations. 1.1 Case study description The research work carried out by the authors has as the subject building, the site of the Directorate General of AAMS (Monopoly Administration State) who are charged at the national level to regulate the public gaming sector and control the production, distribution, sale and duties of tobacco products. The building is located in the Centre of Rome and is composed of two connected bodies. The smaller building overlooks the square and has a significant historical value, dating back to the second half of the 1800s. The other part, the larger one is the administrative headquarters of AAMS a newer building built in the 1960s. So, we will call the two buildings, for convenience, a historic building and modern building, respectively. The historic building is divided into a basement at an altitude of about -5 m from the ground and 4 floors above ground to a height of about 22 m. Architecturally, the building consists of offices overlooking the square and a long corridor, with a substantially rectangular plan of maximum size 17.1 x 74.1 m and extension plan of approximately 1030 m 2. This building has a volume of 20000 m 3 and an S/V ratio (Surface/Volume [m 2 /m 3 ]) equal to 0.29 m 2 /m 3 with different floor heights, and then different floor volumes. The modern building is divided into two underground floors and 7 floors above ground to a total height of about 24 m. The area of the part used for offices (i.e. excluding stores and technical rooms) is about 3040 m 2. This second volume of 70,300 m 3 has an S/V ratio equal to 0.28 m 2 /m 3. The entire building complex is served from the same thermal power plant and has a total area of 30,000 m 2. The two buildings were built at different times so the thermal performance

Eco-Architecture IV 401 characteristics are significantly different. The historic building has small openings made in the main walls (bearing masonry): the wall thickness is about 1.5 m in the basement up to 0.80 m on the top floor. The modern building is characterized by large glass surfaces and walls with no insulation layer. This characteristic is the fundamental cause of its natural tendency to overheating in summer. The buildings have a north-west orientation and the angle between the line orthogonal to the main facade of the historic building and direction of the north is 66 (Figure 1). A precise evaluation of the contributions from solar radiation through the glass surfaces is not easy because the building is located in a densely urbanized district where neighbouring buildings with their shadows affect the exposure. Figure 1: Case study: building orientation and its position in urban surroundings of Rome. 2 Calculation methodology and transient state modelling The main purpose is to verify analytically the possibility of installing a solar thermal system that integrates the current internal temperature control systems. The project idea is to install a field of solar panels directly to the integration of the winter heating with an absorption machine for the construction of a solar cooling system for summer cooling. The calculation will be strictly made by using the most advanced methods for transient state calculation through the use of TRNsys code.

402 Eco-Architecture IV The study begins by collecting data on building energetic consumption, in order to know, through energy audit, the heating energy required (i.e. by a thermographic survey (Figure 2.)) Figure 2: Thermographic survey: building main facade. A TRNsys model of the building will be created and it will be calibrated through the undetermined parameters in the calculation data of the diagnosis previously carried out. The output of thermal energy obtained, representing the energy demands at the time, will be the starting point for the operations of building energy upgrading. The model is based on statistical data appropriately averaged for the characterization and sunny weather for the site of the building complex studied. 2.1 Energy audit Starting from the data supply of the main sources of energy is recovered through a reverse process of calculating the determination of energy needs done and not supposed to reach stable thermal conditions required for the entire calendar year. Where possible, values were averaged over several years before being processed, in order to obtain statistically acceptable values and lack of physiological fluctuations related to climate and other occasional events. By studying these systems, heating demand was related to the consumption of natural gas marked on the meter installed before the thermal system. The regression was obtained by the following formula: Q = C Pc η t (1) with Q being the heat energy required in a given period of time when C [m 3 ] of natural gas with calorific value (Pc) of gas equal to 34,541 kj/m 3 are burned. The processing yield η t is shown on the manufacturer s data sheets of the various thermal machines unless an empirical reduction factor to take into account other losses in yield of system. In Tables 1 and 2, the results of the regression and the values of the energy needs of the volume index are reported.

Eco-Architecture IV 403 A process conceptually similar was followed for cooling demand, but by analyzing the data of electricity consumption. In this case the values are given as the sum total consumption and hence we must extrapolate from other links the consumption of installed chillers. The correlations proposed and exploited are those with average maximum and minimum temperatures and the brightness values of the ground. Figure 3 shows the comparison with the temperatures, where it shows a clear correlation with consumption during the summer. Table 1: Building heating demand. Use Gas Use[m 3 /year] Energy [kwh/year] Index [kwh/m 3 year] Heating 167.557 1.543.361 1,35 Hot Water 3.952 36.781 18,1 Table 2: Building cooling demand. Use Electricity Thermal Index [kwh/m 3 [kwh/year] Energy[kWh/year] year] Cooling 295.887 887.725 10,1 Figure 3: Electricity consumption and temperature correlation. During the months of no operation of the temperature control system, it is assumed that consumption is linked exclusively to other uses. As for gas, Table 2 shows the annual data analysis for the electricity used for the cooling system. 2.2 TRNsys model TRNsys building model is realized by connecting types identified by a number: 89, 16, 69, 34, 65, 25, 24 and Type 56 Multi-Zone Building. More types will be added for the specific project along with various calculator forms (Figure 4).

404 Eco-Architecture IV The base model is realized through improved calibration data obtained from the energy audit, in order to determine infiltrations and thermal bridges and to verify the effects of shade from surrounding buildings and the temperature of basements that are not temperature controlled and the effects of shielding on the windows fixed on the top floor. Once models were built and calibrated, we can analyze the output results of the TRNsys solver. Among the many outputs of the calculation, the most interesting for the planning phase and the interpretation of the thermal behaviour of the building are the temperatures and thermal inputs delivered every hour. Figure 5 represents the output of the two buildings of the Figure 4: TRNsys model of case study building. Figure 5: Annual building energy rate: TRNsys model outputs.

Eco-Architecture IV 405 thermal-generated model implemented for the pre-intervention situation. The heating rates have developed quite differently from these and there is a heating requirement proportionately higher in winter than in summer, a sign in a temperate climate (such as Rome climate), of a poor energetic quality of the building. The peak intensities obtained from the calculation is about 4 MW and 2 MW for heating and cooling while the medium ones are, respectively, 916 kw and 616 kw. Detailed analysis shows a more constant demand for the historic building with greater thermal inertia and lower glass surfaces. 3 Energy improvement and energy audit in transient state Once the model of the building developed, the possible energy improvement has been proposed and verified. By the use of a TRNsys model it was possible to evaluate, in a more complex way, every single intervention verifying peak hours and seasonal averages of the thermal powers and obtaining objective data on the summer behaviour of the system for the design of solar cooling. Interactions between the various interventions and the non-linearity of their combination were studied too. Each intervention highlighted specific effects on the heating requirements of the building by changing the proportionality between energy demand and the demand for heating and cooling. There are some traditional interventions such as lowering the transmittance of the dispersants opaque walls (through the provision of insulation) and the replacement of windows with greater efficiency which lead to a reduction of heating requirements only during wintertime. During summertime, however, the demand remains constant, since, as expressed numerically by calculating the ratio of solar gains and losses through the envelope remains constant. In other words, the building naturally stores energy in the absence of cooling systems. Without dwelling too much on this part, Table 3 shows (text indexes derived from a weighted average on volumes) the results obtained with the redevelopment of the dispersant structures chosen: 3.1 Modern building provision of an insulating layer of about 4 cm for external walls and of about 6 cm for the floors. (heat capacity of 700 J/kg K, thermal conductivity of 0.18 kj/h m K, density 80 kg/m 3 ) replacement of single glazed (thickness 4 mm, U-value 5.68, G-value of 0.855, 0.83 T-sol, sol-rf 0.075) of all windows with double glazing (4-16-4 mm thickness, U -value 2.83, G-value of 0.755, 0.693 T-sol, sol-rf 0.126. 3.2 Historic building provision of an insulating layer of about 4 cm for external walls and of about 6 cm for the floors.

406 Eco-Architecture IV Table 3: Performance indexes after structural interventions of energy improvement [kwh/m 3 year]. Index Historic Building Modern Building Total Heating Index 12,8 9,5 10,3 Cooling Index 4,0 8,6 7,5 In order to reduce the summer demand in the modern building an innovative intervention is proposed: a building night cooling with 3 air changes per hour from 1 to 6 o clock AM. With this intervention, the cooling index decreases from 8.6 to 6.1 kwh/m 3 year. Overall, the redevelopment leads to a lowering of the thermal energy needs both in summer and wintertime. The energy for heating is equal to 849,300 kwh/year while for cooling one is 465,450 kwh/year. Please note that the choice of the redevelopment was also made in anticipation of the installation of a solar cooling system. The modulation and the proportionality of the application in heating and cooling are essential for the success of the intervention of integration with solar system. 4 Integration with solar heating system: transient state calculation Once the values of the thermal demand of the building have been obtained it is possible to design the system integration of solar energy. The system has the space to install the roof level (about 3000 m 2 ) of the modern building where collectors for the capture of solar energy can be installed. The system involves the coupling of an absorption chiller to provide integration with the system even during the summertime. Installations can be integrated in both heating and cooling system, reducing the depreciation costs for equipment and collectors. Making use of the TRNsys code we can get a track time of supply thermal energy depending on the design parameters. The calculation of the solar system was held in parallel to the building. The parameters used in the calculation affects the solution but do not alter the development. 4.1 Solar system model The design of the system is so integrated with respect to the transient calculation. The main parameters to determine the type of collectors is to be installed, orientation, tilt angle and their extension. For the installation of solar-cooling the main parameter is the cooling capacity of the absorption chiller. Please note we are still in pre-dimensioning, the final calculation will be done as a test, once all the parameters of the system components are known and entered. The proposed plant collectors have arranged coverage with azimuth angle equal to 24 south and 35 tilt angle. The following statement, even if not energetically optimal, was chosen for optimal energy efficiency issues of installation. Each collector has an absorber

Eco-Architecture IV 407 area of 2.257 m 2 and the efficiency curve with parameters a 0 = 0.8, a 1 = 2.02 W/m 2 K, a 2 = 0.0046 W/m 2 K 2. The system consists of rows of collectors connected in parallel and in series to ensure that the design conditions imposed by the manufacturer for maximum temperatures of the heat transfer fluid circulating in the solar and flow into the circulation. The exchange occurs in a thermal storage tank. As a first approximation, without knowing the specifics of the absorption chiller to install itself as a constant average performance standard which could facilitate the predimensioning and choice of range of collectors to be installed. This determines the ratio between the total heat demand and the amount of energy obtained from solar energy. Figure 6 shows the revised output in Excel for the amount of solar collectors to pre-dimensioning of 400 collectors for a total extension of 900 m 2.This choice is not direct and must take into account various aspects. We must consider not only the integral values of energy exchanged but also the contemporary and the respective proportionality between energy supply and demand. Solar energy expressing as heat cannot be stored temporarily for periods of time to allow 100 % coverage without oversizing plant consistently enough to make the management too difficult as well as uneconomic during periods of inactivity. In Figure 6, the jump between about 3000 and 7000 hours is due to the transition between heating and cooling, and then the intervention of the absorption chiller, which reduces the efficiency of the energy process. Availability of solar system Figure 6: Solar system: TRNsys model outputs. 4.2 Transient state sizing Through the calculation carried out with TRNsys transient it was possible to determine the incident solar radiation to the panel that was equal to 4021 kwh/year. This energy is converted into heat by the collectors with an average of 3024 kwh/year with an average efficiency of about 75%. It should be emphasized again that the choice of interventions to achieve redevelopment is key to achieving energy proportionality in the application for you to have a

408 Eco-Architecture IV balanced sizing of the system. The energy required for cooling should be a little lower (about -20%) than that required for heating. The state before the redevelopment of this building leaves no room for action in the absence of balanced choices of action structures. Figures 7 show, respectively, the behaviour of interaction for a typical week in winter and summer. The main evidence of the work is that a good sizing of the solar cooling in winter should be characterized by values of coverage throughout the day not far in excess of the minimum demand to prevent excessive heat storage. In summer, however, as can be appreciated from the figure, the system transient calculation takes a clear step in the evolution of supply and demand being the second curve almost proportionally contained in the first. Table 4: Energy improvement: summary table. Initial Value Solar System Final Value Reduction % Contribution Heating [kwh/ year] 1.529.230 276.805 574.295-62,5 Cooling [kwh/ year] 655.650 187.407 483.593-26,5 Heating Index[kWh/m 3 year] 18,4 6,9 Cooling Index [kwh/m 3 year] 8,2 5,8 Availability of solar system Figure 7: Solar system: TRNsys model outputs on a typical winter day.

Eco-Architecture IV 409 Availability of solar system Figure 8: Solar system: TRNsys model outputs on a typical summer day. Availability of these data also reflect the fact that while in winter the heat engines at maximum power demand are reduced by the presence of the installation of solar cooling in summer with a correspondence between peak demand and power available, they have an interesting decline from 1.4 MW to 1 MW with a reduction of about 25%. Among the outputs of TRNsys and the revision in Excel extracts, the peak value of energy absorption chiller for the collector array adopted in our case is about 360 kw. The system allows the total elimination of a domestic hot water system, the heat being abundantly available in excess in relation to energy needs for this use. 5 Conclusions The modelling phase is the only one that allows a calculation of real variables and the integration of thermal energy plants and facilities. An analysis of data obtained from the dynamic calculation can determine, in fact, the energy actually absorbed by the system to supplement the application. Table 5 shows the global indexes for the building following the intervention of integration through renewable sources. The energy derived from the table is considered as deductible contribution to the energetic needs being free gains for the building. References [1] Henning, H.-M. (2004) Solar-Assisted Air-Conditioning in Building A Handbook for Planners. Springer-Verlag/Wien.

410 Eco-Architecture IV [2] University of Wisconsin-Madison (2004) TRNSYS 16: A TRaNsient SYstem Simulation program Volume 5 Mathematical reference, University of Wisconsin-Madison. [3] Hellmann, H.-M. and Ziegler, F. (1999) Simple absorption heat pump modules for system simulation programs, ASHRAE Transactions 105. [4] Duffie, J. A. and Beckman, W. (2006), Solar Engineering of Thermal Processes, Wiley-Interscience.