CJ Buma. To: Steelform Building Products Inc. Wednesday, 2007 May Avenue Edmonton, AB, T6B 2V2. Attn: Mr.

Size: px
Start display at page:

Download "CJ Buma. To: Steelform Building Products Inc. Wednesday, 2007 May Avenue Edmonton, AB, T6B 2V2. Attn: Mr."

Transcription

1 To: Steelform Building Products Inc. Wednesday, 2007 May Avenue Edmonton, AB, T6B 2V2 Attn: Mr. Marty MacDonald aci Acoustical Consultants Inc. Suite 107, Ave Edmonton, Alberta, Canada T6E 0G9 Phone: (780) , Fax: (780) re: Acoustical Testing Results of Steelform Products Dear Marty, Thank you for retaining aci to conduct STC field testing at the Park One Condominium Building. The results and discussion of the testing are attached. We trust the information provided is sufficient. Please contact us if you have any questions. Yours very truly, aci Acoustical Consultants Inc., CJ Buma Corjan Buma, M.Sc., P.Eng. Associate Consultant APEGGA Permit to Practice # P7735 1

2 INTRODUCTION aci Acoustical Consultants Inc. of Edmonton was retained by Steelform Building Products Inc. to conduct standarized acoustical measurements of some of its stud and joist products as installed at the Park One condominium located at 111 Street and 68 Avenue in Edmonton, AB. The purpose of this study was to determine the STC (sound transmission class) performance across a party wall and one floor/ceiling assembly within the building. Site work was conducted for aci by Corjan Buma, M.Sc., P.Eng., on Friday, 2007 Febr. 2. MEASUREMENT METHODS STC TEST The STC testing was done using the ASTM E336 standard Standard test method for measurement of airborne sound insulation in buildings as a guideline. The general procedure involves producing a loud source of sound on one side of the measured partition with a loudspeaker, as shown in Figure 1, producing pink noise. Sound level measurements are conducted on the source side at several locations (to be averaged in post-processing) and on the receiver side at several locations. The difference in sound levels between the two locations is known as the Transmission Loss (TL). Finally, a measurement of the reverberation time within the receiver space is conducted to allow for adjustment of the receiver sound pressure levels in accordance with the ASTM standard. The results are used, along with the area of the tested partition and the volume of the receiver room to calculate the adjusted TL values in each of the measured 1/3 octave band frequencies. Finally, a standardized STC curve is fitted to the adjusted TL curve according to the fitting criteria outlined in the ASTM standard. The resultant value of the standard curve at 500 Hz is known as the STC value. This value, being measured in a constructed building, is known as the Apparent STC (ASTC). The ASTC value is generally lower than the laboratory achievable STC value (known as the rated STC ) because there are typically (1) additional noise flanking paths around the partition and (2) mechanical and/or electrical components that allow noise transfer through the partition; both of these are intentionally minimized or prevented in laboratory testing. As such, the reported ASTC value is a measure of the overall construction performance. Table 1 shows a range of STC and ASTC values and typical subjective response. 2

3 Table 1. Subjective Performance of Various STC Values STC Lab Apparent STC Subjective description of effectiveness Most sentences clearly understood Many phrases and some sentences understood without straining to hear Individual words and occasional phrases clearly heard and understood Medium loud speech clearly audible, occasional words understood Normal speech audible by straining to hear. Loud speech audible, music easily heard Normal speech unintelligible, Loud speech audible by straining to hear; music normally can be heard and may be disturbing Loud speech essentially inaudible; music can be heard faintly but bass notes disturbing Music heard faintly, bass notes "thump"; power woodworking equipment clearly audible Music still heard very faintly if played loud Effectively blocks most air-borne noise sources The measurement equipment for the STC testing consisted of a Brüel and Kjær Type 2250 Precision Integrating Sound Level Meter, collecting data in 15-second L eq samples measuring the broadband A-weighted and 1/3 octave band frequency sound levels. The sound level meter was calibrated at the start of the measurements to ensure accurate results. The sound source consisted of a NTI Minirator MR1 generating pink noise and a JBL EON-G15 loudspeaker. Reverberation time measurements were conducted with the loudspeaker (used for room excitation) and the Sound Level Meter as both the source and measurement system. Refer to the Appendix for calibration certificates for the Sound Level Meter. 3

4 BACKGROUND SOUND LEVEL CONSIDERATIONS Note that during all tests the sound level in each of the pertinent 1/3 octave bands is required to be at least 10 db above the ambient sound level (with the source signal turned off). This ensures that the measured sound is loud enough to not have interference from the other constant sources such as ventilation and other equipment. As such, measurements in the receiver room are conducted with the source sound both on and off and then compared after the test. Some of the STC tests occurred with receiver room levels less than 10 db above ambient in several of the 1/3 octave bands; this was due to either low-level sound due to Contractors still at work in the building or the in-suite air-handling equipment being on. In general, the deficient 1/3 octave values were not responsible for determining the resultant ASTC value. However, where the ASTC value did appear to be affected by higher-thandesirable background sound level, the results are reported with the ASTC value followed by a + sign, indicating that the actual ASTC would have been slightly higher had background noise not interfered with the result. TEST LOCATIONS An up-down assessment of a floor/ceiling assembly was conducted from Unit 203 to Unit 103 and a side-to-side assessment of a party wall was conducted from Unit 405 to Unit 404. The suites tested were all unoccupied, having been finished to the degree of painting, baseboards, millwork and most doors in place. Some of the bedrooms had been equipped with finish flooring (in the form of carpet or lino or laminate). There were no obvious holes/leaks between any of the units though typically party-walls did have an electrical box into the room on either side. Some doors had not yet been equipped with handles (resulting in a 50-mm open hole) and none were equipped with perimeter seals. Subjective listening/assessment during side-to-side STC testing (Unit 405 to Unit 404) verified that the lack of perimeter seals and lack of some doorhandles was not the determining factor in STC results. Unit 203 to Unit 103 The STC assessment from Unit 203 to Unit 103 was done in the living room area and assessed the performance of Steelform joists in a floor/ceiling construction. 4

5 The floor/ceiling assembly consisted of 22-gauge metal deck, filled with concrete topping (minimum thickness 38 mm), on 150-mm Delta joist, 50-mm Spider insulation applied to underside of deck, furring bar ( hat channel ) below Delta joist and one layer 16-mm Type X drywall attached below furring bar. Unit 405 to Unit 404 The side-to-side STC test was done from Unit 405 Bedroom and Unit 404 Bedroom. The composition of this party wall was Delta stud on both sides of 25-mm gap (no board material within 25-mm gap), common batt insulation in stud-cavities on both sides of gap and one layer of 16-mm Type X drywall on one side and two layers of 16-mm Type X drywall on the other. (Note that there is acoustically no difference whether the sound source is on the 2-layer or the 1- layer side of the party wall.) RESULTS OF STC TESTS The results of the STC tests are shown in Table 2 and Figures 2 & 3. The value of ASTC 58 is considered very good (an ASTC value of 55 or more would qualify as superior sound isolation ). The value of ASTC 53 is considered good. Table 2. Derived ASTC Values Source Receiver ASTC Unit 203 Unit Unit 405 Unit For reference, the Alberta Building Code states (in Section 9.11): every dwelling unit shall be separated from every other space in a building in which noise may be generated by a construction providing a sound transmission class rating of at least 50, measured in accordance with Subsection or as listed in A in Appendix A 5

6 The test method discussed in Subsection refers directly to ASTM E 336 (which was followed as part of this test). Thus, the tested value of ASTC 58 appreciably exceeds the requirement of the Alberta Building Code. For the fourth floor result, had Spider insulation been used on fourth floor, the ASTC may well have gone above 53 (assumes Spider insulation is more dense than common batt insulation). CONCLUSION The results of the ASTC in-situ testing of the Steelform products indicate that building code requirements can be met, and even exceeded, with the use of the Steelform products. 6

7 Figure 1. Sound Source Used for STC Testing (Unit 203) 7

8 Sound Transmission Loss (db) STC Frequency (Hz) Figure 2 ASTC Result For Floor/Ceiling Between Living Rooms of Units 203 & Sound Transmission Loss (db) STC Frequency (Hz) Figure 3 ASTC Result For Party-Wall Between Bedrooms of Units 405 & 404 8

9 APPENDIX 9

10 B&K 2250 Calibration Certificate(s) 10

11 B&K 4231 Calibrator Calibration Certificate 11

KINETICS NOISE CONTROL TEST REPORT #AT001110

KINETICS NOISE CONTROL TEST REPORT #AT001110 KINETICS NOISE CONTROL TEST REPORT #AT001110 KINETICS NOISE CONTROL PRODUCTS: o NONE ACOUSTICAL RATINGS: o STC 53 o IIC 29 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o REPORT NO. A1-010601.1 o DATED:

More information

KINETICS NOISE CONTROL TEST REPORT # AT001084

KINETICS NOISE CONTROL TEST REPORT # AT001084 KINETICS NOISE CONTROL TEST REPORT # AT001084 KINETICS NOISE CONTROL PRODUCTS: o MODEL ISOGRID ACOUSTICAL RATINGS: o STC 63 o IIC 50 TESTING AGENCY & REPORT NUMBER: o NRC-CNRC o B-3463.6 KINETICS DRAWING

More information

KINETICS NOISE CONTROL TEST REPORT #AT001049

KINETICS NOISE CONTROL TEST REPORT #AT001049 KINETICS NOISE CONTROL TEST REPORT #AT001049 KINETICS NOISE CONTROL PRODUCTS: o NONE ACOUSTICAL RATINGS: o STC 53 o IIC 27 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA o B-3463.1

More information

KINETICS NOISE CONTROL TEST REPORT #AT001108

KINETICS NOISE CONTROL TEST REPORT #AT001108 KINETICS NOISE CONTROL TEST REPORT #AT001108 KINETICS NOISE CONTROL PRODUCTS: o 1 RIM ACOUSTICAL RATINGS: o ATSC 49 o FIIC 48 TESTING AGENCY & REPORT NUMBER: o ACENTECH, INC. o PROJECT NO. 619530 o DATED:

More information

INTRODUCTION SPECIMEN DESCRIPTION

INTRODUCTION SPECIMEN DESCRIPTION INTRODUCTION SPECIMEN DESCRIPTION Airborne sound transmission measurements were performed on a wall assembly with a single layer of the product identified by the client as QuietRock QR-530 Serenity on

More information

KINETICS NOISE CONTROL TEST REPORT #AT001052

KINETICS NOISE CONTROL TEST REPORT #AT001052 KINETICS NOISE CONTROL TEST REPORT #AT001052 KINETICS NOISE CONTROL PRODUCTS: o ISOMAX CLIPS ACOUSTICAL RATINGS: o STC 66 o IIC 44 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA

More information

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure

More information

KINETICS NOISE CONTROL TEST REPORT #AT001021B

KINETICS NOISE CONTROL TEST REPORT #AT001021B KINETICS NOISE CONTROL TEST REPORT #AT001021B KINETICS NOISE CONTROL PRODUCTS: o ICW ACOUSTICAL RATINGS: o STC 76 o IIC 62 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B3463.13 KINETICS DRAWING NUMBER:

More information

Signatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.

Signatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only. ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 492: Laboratory Measurement of Impact Sound Transmission through Floor- Ceiling Assemblies Using

More information

ICF/Building System FSTC Test Report

ICF/Building System FSTC Test Report REP ICF STC test.doc 1of5 2003 03 12 C/o Michel Philippe IntegraSpec Insulating Concrete Forms (ICF) Building System By: Phil-Insul Corporation 735 Arlington Park Place, 11U Kingston, ON, K7M 8M8 TEL:

More information

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure

More information

ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements

ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements 1 of 7 TEST : Acoustical Surfaces, Inc. Report Date: May 25, 2011 Test Date: September 28, 2010 Test

More information

ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements

ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements 1 of 7 TEST : Acoustical Surfaces, Inc. Report Date: May 25, 2011 Test Date: September 28, 2010 Test

More information

Results of FIIC and FSTC Measurements at Harvard Estates

Results of FIIC and FSTC Measurements at Harvard Estates Harvard Estates FIIC and FSTC Tests STEWART AIT ALLAOUA PERKINS 6042 Seaview Ave. NW, Suite 102 Seattle, WA 98107 Phone: (206) 839-0819 Fax: (206) 839-0824 January 21, 2005 Charles Strazzara, AIA Studio

More information

Acoustical Engineering Solutions.

Acoustical Engineering Solutions. Acoustical Engineering Solutions. Meeting IBC Acoustical Requirements for Multifamily Construction By Scott Harvey, PE, INCE Bd. Cert. Phoenix Noise & Vibration Frederick, Maryland Copyright Materials

More information

FIELD FLOOR IMPACT SOUND ISOLATION

FIELD FLOOR IMPACT SOUND ISOLATION FIELD FLOOR IMPACT SOUND ISOLATION 46 OAKDENE DRIVE 15 th September 2015 For BUILD IT ECO Unit 8 / 49 Prindiville Drive WANGARA WA 6065 UNIT 3 / 2 HARDY STREET, SOUTH PERTH 6151 TEL: 9474 5966 EMAIL: reception@gabriels.net.au

More information

B Page 1 of 21-

B Page 1 of 21- Airborne and impact sound transmission measurements were performed on three floor assemblies which comprised the NRC 150 mm reference concrete slab and a 102 mm floating concrete slab. For report purposes,

More information

KINETICS NOISE CONTROL TEST REPORT #AT001067

KINETICS NOISE CONTROL TEST REPORT #AT001067 KINETICS NOISE CONTROL TEST REPORT #AT001067 KINETICS NOISE CONTROL PRODUCTS: o FLM- NEOPRENE PAD ACOUSTICAL RATINGS: o STC 69 o IIC 61 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA

More information

RC CHANNEL ACOUSTIC ASSEMBLY

RC CHANNEL ACOUSTIC ASSEMBLY RC CHANNEL ACOUSTIC ASSEMBLY FLOOR/CEILING ASSEMBLY DIRECT FIX TO TJI DSA TJI rc channel FSTC 53 FIIC 44 PAC INTERNATIONAL CONSTRUCTION * Hardwood Flooring * 1/2" Plywood Fire resistance ratings * 1-1/2"

More information

21 ST CENTURY LEARNING ACOUSTICS. Steve Meszaros, M.Sc., P.Eng Acoustical Technical Director / Associate

21 ST CENTURY LEARNING ACOUSTICS. Steve Meszaros, M.Sc., P.Eng Acoustical Technical Director / Associate 21 ST CENTURY LEARNING ACOUSTICS Steve Meszaros, M.Sc., P.Eng Acoustical Technical Director / Associate Introduction Steve Meszaros B.Sc. (Mechanical Engineering) University of Manitoba M.Sc. (Biosystems

More information

June 28, VIA Kristina Damschen Indow Windows 2267 N. Interstate Avenue Portland, OR, United States, 97227

June 28, VIA   Kristina Damschen Indow Windows 2267 N. Interstate Avenue Portland, OR, United States, 97227 BCIT Centre for Architectural Ecology NE3 3700 Willingdon Ave Burnaby, British Columbia, Canada V5G 3H2 T: 604.456.8045 June 28, 2016 VIA EMAIL: kristina@indowwindows.com Kristina Damschen Indow Windows

More information

KINETICS NOISE CONTROL TEST REPORT #AT001032

KINETICS NOISE CONTROL TEST REPORT #AT001032 KINETICS NOISE CONTROL TEST REPORT #AT001032 KINETICS NOISE CONTROL PRODUCTS: o ICC ACOUSTICAL RATINGS: o STC 84 o IIC 70 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B-3448.12 KINETICS DRAWING NUMBER:

More information

Intertek Testing Services

Intertek Testing Services Acoustical 3933 U.S. Rt. Cortland, NY 13045 Phone: 607-753-6711 Fax: 607-756-9891 Order No. J99031102-003 December 10, 1999 REPORT NO. J99031102-003 SOUND TRANSMISSION LOSS TEST AND CLASSIFICATION OF A

More information

1.0 INTRODUCTION BUILDING REGULATIONS SOUND INSULATION REQUIREMENTS TEST PROCEDURE AND ANALYSIS...3

1.0 INTRODUCTION BUILDING REGULATIONS SOUND INSULATION REQUIREMENTS TEST PROCEDURE AND ANALYSIS...3 Concrete Centre Limited Bron Derw Residential Development, Colwyn Bay Sound Insulation Test Report 25 July 2005 PROJECT: CLIENT: Bron Derw Residential Development, Colwyn Bay Concrete Centre Limited Riverside

More information

Presented By: Jim O Neill. Acoustics

Presented By: Jim O Neill. Acoustics Presented By: Jim O Neill Acoustics Topics STC and IIC 101 Sound in floors Sound in walls Noise In Multifamily Measurements of Noise Two ASTM Standards STC Sound Transmission Classification Measurement

More information

REPORT 3933 US ROUTE 11, CORTLAND, NEW YORK, 13045

REPORT 3933 US ROUTE 11, CORTLAND, NEW YORK, 13045 REPORT 3933 US ROUTE 11, CORTLAND, NEW YORK, 13045 FOR THE SCOPE OF LAB CODE 100402-0. Order No. 100667931 Date: May 23, 2012 REPORT NO. 100667931CRT-001a SOUND TRANSMISSION LOSS TEST AND CLASSIFICATION

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Classic-Craft, Fiber Classic, and Smooth Star

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Classic-Craft, Fiber Classic, and Smooth Star ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Classic-Craft, Fiber Classic, and Smooth Star TYPE: 3/8 Impact Rated Side Hinged Door ATI Data File No. 74385.01A*

More information

This page was. intentionally. left blank

This page was. intentionally. left blank CONSTRUCTION Measurement of Airborne Sound Insulation of 8 Wall Assemblies Measurement of Airborne and Impact Sound Insulation of 29 Floor Assemblies Nordic Engineered Wood Report No. A1-006070.10 July

More information

acoustics 101 The following is a brief tutorial that describes the use of a flooring underlayment as an acoustic barrier.

acoustics 101 The following is a brief tutorial that describes the use of a flooring underlayment as an acoustic barrier. acoustics 101 The following is a brief tutorial that describes the use of a flooring underlayment as an acoustic barrier. 1 why use a floor underlayment? IT S WHAT S UNDERNEATH THAT COUNTS - BENEFITS OF

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door with Impact Glass

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door with Impact Glass ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 8/0 Sliding Patio Door with Impact Glass ATI Data File No. 74391.01 74391.01A* Summary of Test Results

More information

RR-337 Apparent Sound Insulation in Cold-Formed Steel-Framed Buildings. Christoph Hoeller, David Quirt, Berndt Zeitler, Ivan Sabourin.

RR-337 Apparent Sound Insulation in Cold-Formed Steel-Framed Buildings. Christoph Hoeller, David Quirt, Berndt Zeitler, Ivan Sabourin. Construction RR-337 Apparent Sound Insulation in Cold-Formed Steel-Framed Buildings Christoph Hoeller, David Quirt, Berndt Zeitler, Ivan Sabourin 07 April 2017 Page 1 of 108 DRAFT 1 st edition October

More information

CASE STUDY OF THE SOUND REDUCTION OF VARIOUS RESIDENTIAL GLAZING TREATMENTS

CASE STUDY OF THE SOUND REDUCTION OF VARIOUS RESIDENTIAL GLAZING TREATMENTS Abstract CASE STUDY OF THE SOUND REDUCTION OF VARIOUS RESIDENTIAL GLAZING TREATMENTS Greg Barry 1, Darren Jurevicius 2 and Matthew Stead 3 1 Resonate Acoustics, Adelaide SA 5082, Australia Email: greg.barry@resonateacoustics.com

More information

A few amazing facts about Acoustiblok

A few amazing facts about Acoustiblok A few amazing facts about Acoustiblok A standard metal stud 5/8" gypsum board wall with only 1 layer of 16 oz. Acoustiblok has better sound reduction, (STC 53*, Riverbank Laboratories), than a solid 12"

More information

RSIC ACOUSTIC ASSEMBLY

RSIC ACOUSTIC ASSEMBLY RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO SOLID WOOD JOIST FCWT RAL IN08-016 CONSTRUCTION Sheet Vinyl 1/2 Wood Underlayment 5/8 Plywood Subfloor (*L513 3/4 Ply) 2" X 10" Solid Wood Joist

More information

APPARENT SOUND INSULATION IN COLD-FORMED STEEL-FRAMED BUILDINGS

APPARENT SOUND INSULATION IN COLD-FORMED STEEL-FRAMED BUILDINGS APPARENT SOUND INSULATION IN COLD-FORMED STEEL-FRAMED BUILDINGS Christoph Höller National Research Council Canada, Ottawa, Ontario, Canada email: christoph.hoeller@nrc.ca David Quirt JDQ Acoustics, Ottawa,

More information

Identifying impacts of amplified sound in commercial spaces below residences in mixed-use buildings

Identifying impacts of amplified sound in commercial spaces below residences in mixed-use buildings Identifying impacts of amplified sound in commercial spaces below residences in mixed-use buildings Tyler Adams a) Mei Wu b) Mei Wu Acoustics 3 Twin Dolphin Drive, Suite 190, Redwood City, CA 94065-1516

More information

Measurement of Airborne & Impact Sound Insulation. University of Durham, Pavilion H, Howlands Farm, Durham.

Measurement of Airborne & Impact Sound Insulation. University of Durham, Pavilion H, Howlands Farm, Durham. FAO: CARL SUTCLIFFE noise.co.uk noise.co.uk Ltd Report No U20 Measurement of Airborne & Impact Sound Insulation University of Durham, Pavilion H, Howlands Farm, Durham. For: The Concrete Centre 9/9/2005

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 8/0 Sliding Patio Door Summary of Test Results ATI Data File No. Glazing (Nominal Dimensions) STC

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ACOUSTIBLOK, INC. WALL ASSEMBLY: #1

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ACOUSTIBLOK, INC. WALL ASSEMBLY: #1 ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: ACOUSTIBLOK, INC. WALL ASSEMBLY: #1 TYPE: Standard 8" Hollow Block Wall With Single Stud Wall Construction SOUND ISOLATION MATERIAL: Acoustiblok

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 900 Series. TYPE: Out-swing Double Terrace Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 900 Series. TYPE: Out-swing Double Terrace Door ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: UNITED STATES ALUMINUM SERIES/MODEL: 900 Series TYPE: Out-swing Double Terrace Door ATI Data File No. 63136.01 Summary of Test Results Glazing

More information

KINETICS NOISE CONTROL TEST REPORT #AT001035

KINETICS NOISE CONTROL TEST REPORT #AT001035 KINETICS NOISE CONTROL TEST REPORT #AT001035 KINETICS NOISE CONTROL PRODUCTS: o RIM I-2-16 ACOUSTICAL RATINGS: o STC 66 o IIC 63 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B-3140.1 KINETICS DRAWING

More information

THE FRAME RESIDENTIAL DEVELOPMENT, SPORTCITY, MANCHESTER THE CONCRETE CENTRE LTD 1.0 INTRODUCTION...2

THE FRAME RESIDENTIAL DEVELOPMENT, SPORTCITY, MANCHESTER THE CONCRETE CENTRE LTD 1.0 INTRODUCTION...2 Concrete Centre Limited The Frame Residential Development, Sport City, Manchester Sound Insulation Test Report 2 August 2005 PROJECT: CLIENT: The Frame Residential Development, Sportcity, Manchester Concrete

More information

Signatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.

Signatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only. ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 492: Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using

More information

Acoustical Engineering Solutions

Acoustical Engineering Solutions Acoustical Engineering Solutions Noise & Vibration Control in Wood Framed, Residential Structures By Scott Harvey, PE, INCE Bd. Cert. Phoenix Noise & Vibration Frederick, Maryland Copyright Materials This

More information

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK Order No Date: May 24, 2008 REPORT NO CRT-001

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK Order No Date: May 24, 2008 REPORT NO CRT-001 REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK 13045 Order No. 3151742 Date: May 24, 2008 REPORT NO 3151742CRT-001 IMPACT SOUND TRANSMISSION TEST AND CLASSIFICATION OF LM FLOORING ½ INCH ENGINEERED HARDWOOD

More information

The simplified method versus the detailed method of calculating flanking sound transmission through walls with linings

The simplified method versus the detailed method of calculating flanking sound transmission through walls with linings PROCEEDINGS of the 22 nd International Congress on Acoustics Challenges and Solutions in Acoustical Measurements and Design: Paper ICA2016-50 The simplified method versus the detailed method of calculating

More information

Introduction to Acoustics:

Introduction to Acoustics: Introduction to Acoustics: How I Learned to Stop Worrying and Love the Sound Level Meter Samantha Rawlings, LEED AP BD+C For IFMA New Mexico 07.14.2015 Veneklasen Associates INTRODUCTION Consultants in

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ALL SEASONS DOOR & WINDOW, MFG SERIES/MODEL: A500. TYPE: Double Hung Window

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ALL SEASONS DOOR & WINDOW, MFG SERIES/MODEL: A500. TYPE: Double Hung Window ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: ALL SEASONS DOOR & WINDOW, MFG SERIES/MODEL: A500 TYPE: Double Hung Window Data File No. 97455.01 Summary of Test Results Glazing (Nominal Dimensions)

More information

KINETICS NOISE CONTROL TEST REPORT #AT001087

KINETICS NOISE CONTROL TEST REPORT #AT001087 KINETICS NOISE CONTROL TEST REPORT #AT001087 KINETICS NOISE CONTROL PRODUCTS: o NONE ACOUSTICAL RATINGS: o FSTC 31 o FIIC 27 REMEDIAL ACTION REQUIRED KINETICS DRAWING NUMBER: AT001087A 6300 IRELAN PLACE,

More information

KINETICS NOISE CONTROL TEST REPORT #AT001073

KINETICS NOISE CONTROL TEST REPORT #AT001073 KINETICS NOISE CONTROL TEST REPORT #AT001073 KINETICS NOISE CONTROL PRODUCTS: o ISOMAX CLIPS ACOUSTICAL RATINGS: o STC 63 TESTING AGENCY & REPORT NUMBER: o RIVERBANK ACOUSTICAL LABORATORIES o RAL TL06-048

More information

Acoustical Characteristics of Carpet

Acoustical Characteristics of Carpet CRI TECHNICAL BULLETIN Acoustical Characteristics of Carpet Carpet is an outstanding sound absorptive material. When properly selected, carpet absorbs airborne noise as efficiently as many specialized

More information

SOUND INSULATION TESTING IN DWELLINGS

SOUND INSULATION TESTING IN DWELLINGS SOUND INSULATION TESTING IN DWELLINGS Chris Dilworth, AWN Consulting This Presentation Discusses the standards by which we judge sound insulation performance. Presents the results of sound insulation tests

More information

LOXO CLADDING SOUND INSULATION PERFORMANCE. Opinion on Acoustic Performance of. Loxo Cladding Systems Utilising Aerated Concrete.

LOXO CLADDING SOUND INSULATION PERFORMANCE. Opinion on Acoustic Performance of. Loxo Cladding Systems Utilising Aerated Concrete. LOXO CLADDING SOUND INSULATION PERFORMANCE Opinion on Acoustic Performance of Loxo Cladding Systems Utilising Aerated Concrete Rp001 2012195C 08 May 2012 Level 369 Cambridge Terrace PO Box 4071 Christchurch

More information

TECHNICAL DOCUMENT - SOUND INSULATION R9 SYSTEM. Dated: 30 August 2013

TECHNICAL DOCUMENT - SOUND INSULATION R9 SYSTEM. Dated: 30 August 2013 Level 2, 6 Kings Park Road West Perth, Western Australia, 6000 Phone: +61 8 9488 0848 ABN: 54 160 488 175 ACN: 160 488 175 FBM Licence Limited E-Mail: info@fbmlicence.com.au Web: www.fbmlicence.com.au

More information

Canadian Wood Council G063. Acoustic Considerations for Wood Frame Construction

Canadian Wood Council G063. Acoustic Considerations for Wood Frame Construction Canadian Wood Council G063 Acoustic Considerations for Wood Frame Construction Russ Lewis, M.Eng., P.Eng. Senior Consultant / Principal Rowan Williams Davies & Irwin Inc. February 4, 2016 Credit(s) earned

More information

Intertek Testing Services

Intertek Testing Services Intertek Testing Services 3933 U.S. Rt. 11 Cortland, NY 13045-0950 Phone: 607-75~-6711 Fax: 607-758-6506 Intertek Testing Services For The Scope of Accreditation Job No. 3034879 January 15, 2003 REPORT

More information

Noise Control Of Building

Noise Control Of Building International Conference on Electrical, Electronics, and Optimization Techniques (ICEEOT) - 2016 Noise Control Of Building Sandesh G. Jharbade Civil Department P.R.M.I.T & R, Badnera Badnera, India Mayur

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 6/8 Sliding Patio Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 6/8 Sliding Patio Door ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 6/8 Sliding Patio Door ATI Data File No. 74387.01 74387.01A* Summary of Test Results Glazing (Nominal

More information

RSIC ACOUSTIC ASSEMBLY

RSIC ACOUSTIC ASSEMBLY RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO WOOD OPEN WEB TRUSS TFCSW RAL IN09-045 STC 56 IIC 73 CONSTRUCTION Carpet and Pad 3/4 T&G OSB Subfloor 11-1/4" Deep Open Web Truss @ 24" OC R-11

More information

Soundproofing of Wood-frame buildings

Soundproofing of Wood-frame buildings Soundproofing of Wood-frame buildings Learning objectives Basic Acoustic Principles and Definitions Impact and Airborne sounds in light wood-frame buildings Means of soundproofing light wood-frame buildings

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 390. TYPE: Sliding Glass Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 390. TYPE: Sliding Glass Door ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 390 TYPE: Sliding Glass Door Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC

More information

FLOOR CEILING ASSEMBLY

FLOOR CEILING ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO SOLID WOOD JOIST FCWT RAL IN09-012 Toll Free (866) 774-2100 WWW.PAC-INTL.COM Fire Resistance Ratings CONSTRUCTION 3/8" HARDWOOD FLOORING VAPOR BARRIER 3/4 LT WT CONCRETE

More information

RSIC-1 ACOUSTIC ASSEMBLY

RSIC-1 ACOUSTIC ASSEMBLY RSIC-1 ACOUSTIC ASSEMBLY FLOOR/CEILING ASSEMBLY DIRECT FIX TO CONCRETE SLAB FCS5 DSWA FIIC 72 CONSTRUCTION * 3/8" Hard Wood flooring * 8" PT concrete slab Fire resistance ratings * R-8 insulation ANS/UL

More information

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP. TYPE: Picture Window

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP. TYPE: Picture Window AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP TYPE: Picture Window ATI Data File No. 71965.01A 71965.01B Summary of Test Results Glazing

More information

The specimen B W was identified by the client as a Skyfold Classic operable partition, with panels, seals, and clearances in configuration 4E.

The specimen B W was identified by the client as a Skyfold Classic operable partition, with panels, seals, and clearances in configuration 4E. TestingLaboratory: Client: Specimen: SpecimenID: Manufacturer: ConstructionDates: Testspecimenmountedby: NationalResearchCouncilCanada InstituteforResearchinConstruction 1200MontrealRoad Ottawa,OntarioK1A0R6

More information

RSIC-1 ACOUSTIC ASSEMBLY

RSIC-1 ACOUSTIC ASSEMBLY RSIC-1 ACOUSTIC ASSEMBLY FLOOR/CEILING ASSEMBLY DIRECT FIX TO CONCRETE SLAB FCS3 DSWA FIIC 69 PAC INTERNATIONAL Inc. Toll Free 866-774-2100 Telephone 503-649-7700 CONSTRUCTION * Ceramic Tile * 1/4" James

More information

4-Acoustics: Background

4-Acoustics: Background 4-Acoustics: Background In the past acoustics for buildings especially concert halls was done by luck. A design would be done that worked well and then it would be mimicked. Other times awful designs emerged

More information

KINETICS NOISE CONTROL TEST REPORT #AT001109

KINETICS NOISE CONTROL TEST REPORT #AT001109 KINETICS NOISE CONTROL TEST REPORT #AT001109 KINETICS NOISE CONTROL PRODUCTS: o NONE ACOUSTICAL RATINGS: o ASTC 53* (*USING INSUL) o AIIC 29 TESTING AGENCY & REPORT NUMBER: o COLLECTIVE TECH / HENDERSON

More information

Knock on Wood: Acoustical Design in Mass Timber Structures

Knock on Wood: Acoustical Design in Mass Timber Structures Knock on Wood: Acoustical Design in Mass Timber Structures Denis Blount Associate Arup Acoustics, AV, Theatre (Seattle) Disclaimer: This presentation was developed by a third party and is not funded by

More information

A L I O N Technical Center. Test Report

A L I O N Technical Center. Test Report FOR: Dublin, OH Sound Transmission Loss CONDUCTED: 2018-03-30 Page 1 of 8 ON: KNM-100B Limp Mass Vinyl TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce, National

More information

Copyright 2018 American Wood Council 1

Copyright 2018 American Wood Council 1 for Wood Frame Assemblies BCD800 Jason Smart, P.E. Manager, Engineering Technology American Wood Council The American Wood Council is a Registered Provider with The American Institute of Architects Continuing

More information

RSIC ACOUSTIC ASSEMBLY

RSIC ACOUSTIC ASSEMBLY RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO WOOD OPEN WEB TRUSS TFCSW RAL IN09-044 STC 54 IIC 52 CONSTRUCTION Hardwood Flooring 1/16" Foam Underlayment 3/4 T&G OSB Subfloor 11-1/4" Deep

More information

600 Series 56 STC. Results Apply to 600 Series; Individual and Pairs. Quentin J. Schrader. Lab Code: /17/2014

600 Series 56 STC. Results Apply to 600 Series; Individual and Pairs. Quentin J. Schrader. Lab Code: /17/2014 UNCLASSIFIED HUFCOR TEST NO.: A1406663 Hufcor Testing Facilities P.O. Box 591 2101 Kennedy Rd. Janesville, WI 53547 USA 600 Series 56 STC Results Apply to 600 Series; Individual and Pairs Quentin J. Schrader

More information

OLIVE VILLAS, SANDOWN LANE, LIVERPOOL, L15 4HU

OLIVE VILLAS, SANDOWN LANE, LIVERPOOL, L15 4HU MEASUREMENT OF THE SOUND INSULATION OF SEPARATING FLOORS on behalf of URBAN BUBBLE LTD for the development at OLIVE VILLAS, 38-40 SANDOWN LANE, LIVERPOOL, L15 4HU REPORT DATE: 14 OCTOBER 2015 REPORT NUMBER:

More information

Noise and Vibration Control in Wood-Framed, Multi-Family Buildings

Noise and Vibration Control in Wood-Framed, Multi-Family Buildings Noise and Vibration Control in Wood-Framed, Multi-Family Buildings Presented by Scott Harvey, PE, INCE Bd. Cert. Disclaimer: This presentation was developed by a third party and is not funded by WoodWorks

More information

LABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF STEEL CLAD PIR WALL PANELS (According to ISO )

LABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF STEEL CLAD PIR WALL PANELS (According to ISO ) Ref no: LABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF STEEL CLAD PIR WALL PANELS (According to ISO 10140 2) AUCKLAND UNISERVICES LIMITED a wholly owned company of THE UNIVERSITY OF AUCKLAND Report

More information

BAY MEADOWS PHASE II SPAR 2 SAN MATEO, CALIFORNIA

BAY MEADOWS PHASE II SPAR 2 SAN MATEO, CALIFORNIA Charles M Salter Associates Inc BAY MEADOWS PHASE II SPAR 2 SAN MATEO, CALIFORNIA RESIDENTIAL INTERIOR NOISE ANALYSIS Prepared for: Kim Havens Wilson Meany Sullivan Four Embarcadero Center, Suite 3330

More information

How to modify a tested fire-rated wall to improve its STC sound rating, while maintaining its official fire-rated qualification

How to modify a tested fire-rated wall to improve its STC sound rating, while maintaining its official fire-rated qualification How to modify a tested fire-rated wall to improve its STC sound rating, while maintaining its official fire-rated qualification Harold FORESTER, Eng. 1 Forester Controls Canada ABSTRACT Local regulatory

More information

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK Order No October 15, REPORT NO CRT-002d3

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK Order No October 15, REPORT NO CRT-002d3 REPORT ACCREDITATION UNDER NVLAP 3933 US ROUTE 11 CORTLAND, NEW YORK 13045 Order No. 3166866 October 15, 2013 REPORT NO. 3166866CRT-002d3 IMPACT SOUND TRANSMISSION TEST AND CLASSIFICATION OF LAMINATE FLOORING

More information

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure

More information

GenieClip. Sound Isolation Clips. It s not magic, it s engineering. Impact and Airborne Sound Control

GenieClip. Sound Isolation Clips. It s not magic, it s engineering. Impact and Airborne Sound Control It s not magic, it s engineering. Impact and Airborne Sound Control GenieClip Sound Isolation Clips Patents: US 7895803, US 9121469, CA 2552516, AU 2007276677, CN 1011919, EPO Patent Pending GenieClip

More information

Sound Attenuation. Slide 1 of 48. PAC International Inc START

Sound Attenuation.   Slide 1 of 48. PAC International Inc START Sound Attenuation START www.pac-intl.com Slide 1 of 48 Sound Attenuation PAC International 7310 Smoke Ranch Rd Suite "E" Las Vegas, NV. 89128 Course Number: XXXXXX Learning Units: 1.00 PAC International

More information

Flanking Transmission at Joints in Multi-Family Dwellings. Phase 1: Effects of Fire Stops at Floor/Wall Intersections

Flanking Transmission at Joints in Multi-Family Dwellings. Phase 1: Effects of Fire Stops at Floor/Wall Intersections Flanking Transmission at Joints in Multi-Family Dwellings. Phase 1: Effects of Fire Stops at Floor/Wall Intersections Nightingale, T.R.T. and Halliwell, R.E. IRC-IR-754 www.nrc.ca/irc/ircpubs Flanking

More information

A L I O N Technical Center. Test Report

A L I O N Technical Center. Test Report FOR: Dublin, OH Sound Transmission Loss CONDUCTED: 2018-03-30 Page 1 of 9 ON: KNM-100AL Limp Mass Vinyl with Reinforced Aluminum Foil Face TEST METHOD Riverbank Acoustical Laboratories is accredited by

More information

Architectural Acoustics

Architectural Acoustics Architectural Acoustics SUSPENDED CEILING SYSTEMS A Sustainable Integrated Ceiling Platform Presented by: United States Gypsum Company AIA Provider #: K011 Credit(s) earned on completion of this course

More information

LABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF PIR ROOF PANELS (According to ISO )

LABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF PIR ROOF PANELS (According to ISO ) Ref no: LABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF PIR ROOF PANELS (According to ISO 10140 2) AUCKLAND UNISERVICES LIMITED a wholly owned company of THE UNIVERSITY OF AUCKLAND Report prepared

More information

Exton, PA FUTURE C.1 C.2. as followed: C.2.1 C.2.2 C.2.3. Page 68. Solution. Proposed. Page 69. Sean. of 147. Page 67

Exton, PA FUTURE C.1 C.2. as followed: C.2.1 C.2.2 C.2.3. Page 68. Solution. Proposed. Page 69. Sean. of 147. Page 67 C. Core Investigation Areas C.1 Introduction Detailed analysess of technical building systems and construction methods have been selected and investigated. The three main challengingg areas on the Wellington

More information

AND ACCESSORIES FOR DRYWALL CONSTRUCTION

AND ACCESSORIES FOR DRYWALL CONSTRUCTION STEEL TRIMS AND ACCESSORIES FOR DRYWALL CONSTRUCTION Quality in your corner. THE STRENGTH WITHIN MONTREAL TORONTO CALGARY EDMONTON VANCOUVER STEEL TRIMS AND ACCESSORIES for Construction BAILEY HAS YOUR

More information

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to SENECA RADIANT TECHNOLOGIES

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to SENECA RADIANT TECHNOLOGIES ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to SENECA RADIANT TECHNOLOGIES Series/Model: Floor/Ceiling Assembly Specimen Type: Dimensional Lumber - 2x10 Overall Size: 3023 mm by

More information

D R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to PROTECTO WRAP COMPANY. Series/Model: Whisper Mat CS

D R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to PROTECTO WRAP COMPANY. Series/Model: Whisper Mat CS ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to PROTECTO WRAP COMPANY Series/Model: Whisper Mat CS Specimen Type: Sound Control & Crack Suppression Membrane Overall Size: 3023 mm

More information

Technical Features Sound Construction Design Aid For Office Acoustics

Technical Features Sound Construction Design Aid For Office Acoustics Technical Features Sound Construction Design Aid For Office Acoustics HOW TO DETERMINE COMPOSITE SOUND ISOLATION RATINGS FOR OFFICES BY COMBINING PERFORMANCE OF WALLS, CEILINGS AND FLOORS by Vincent M.

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Liberty, MO. Sound Transmission Loss CONDUCTED: 2016-02-09 Page 1 of 8 ON: 3/4" Insulated Glazed Unit TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce,

More information

Laboratory Data Examining Impact and Airborne Sound Attenuation in Cross- Laminated Timber Panel Construction - Part 2

Laboratory Data Examining Impact and Airborne Sound Attenuation in Cross- Laminated Timber Panel Construction - Part 2 Laboratory Data Examining Impact and Airborne Sound Attenuation in Cross- Laminated Timber Panel Construction - Part 2 Matthew GOLDEN 1 ; Wilson BYRICK 2 1,2 Pliteq Inc., Canada ABSTRACT At INTER-NOISE

More information

NYU Core: Post-EIS Façade Improvement Acoustical Assessment

NYU Core: Post-EIS Façade Improvement Acoustical Assessment NYU Core: Post-EIS Façade Improvement Acoustical Assessment Revised Version: September 24, 2012 Prepared by: AKRF, Inc. for New York University DRAFT FOR CLIENT REVIEW Table of Contents Introduction...

More information

The purpose of the testing on the mock up specimen was to document the acoustical performance of four underlayments installed under ¾ thick marble.

The purpose of the testing on the mock up specimen was to document the acoustical performance of four underlayments installed under ¾ thick marble. February 24, 12 Daniel Tormo Green Sound Control 6956 SW 47 th Street Miami, FL 33155 Re: Field Impact Insulation Class Testing Report Paramount Bay, Miami Florida Dear Daniel, This letter presents the

More information

Analysis 4 Acoustical Analysis of Interior Partitions- Breadth

Analysis 4 Acoustical Analysis of Interior Partitions- Breadth Analysis 4 - Breadth Background Good classroom acoustics are vital when the teaching and learning process relies strongly on verbal communication. Transmission of noise from one learning environment to

More information

Freedomd From Distraction

Freedomd From Distraction A C O U S T I C S Freedomd From Distraction n I UNDERSTANDING THE ACOUSTICS OF OPERABLE WALLS SOUND IS... 1. Generated In specifying operable partitions or planning multi-use space for your facility, no

More information

D R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA

D R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to REGUPOL AMERICA Regupol Sonus HS300 3 mm Underlayment Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632

More information

Acoustics and Classrooms BARD MANUFACTURING COMPANY REGISTERED AIA PRESENTER VAUGHAN SMITH

Acoustics and Classrooms BARD MANUFACTURING COMPANY REGISTERED AIA PRESENTER VAUGHAN SMITH Acoustics and Classrooms BARD MANUFACTURING COMPANY REGISTERED AIA PRESENTER VAUGHAN SMITH Acoustics and Classrooms SOURCES OF NOISE ACOUSTICAL TERMS AND DEFINITIONS ANSI STANDARD OCCUPIED AND UNOCCUPIED

More information

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure

More information