SPECIFIER: Select mounting style in first subparagraph below.

Size: px
Start display at page:

Download "SPECIFIER: Select mounting style in first subparagraph below."

Transcription

1 SECTION SUMMARY A. Section Includes: SPECIFIER: Select mounting style in first subparagraph below. 1. Prefabricated, [casework-mounted] [bench-mounted], chemical fume hood unit. 2. Related accessories. a. Junction boxes, switches, receptacles, and other controls. b. Fixtures, shipped loose for field installation. 3. Demonstration and training in the use and maintenance of the fume hoods RELATED REQUIREMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. SPECIFIER: Select applicable Section in paragraph below for correct location of related casework. B. Section [ Architectural Wood Casework] [ Manufactured Metal Casework] [ Manufactured Wood Casework] [ Manufactured Plastic Casework] SPECIFIER: Indicate specific Sections in the 3 Divisions of Work below, or keep as is. C. Division 22 - Plumbing: Furnishing and installation of plumbing utilities and final connections. D. Division 23 - Heating, Ventilating, and Air Conditioning (HVAC): Furnishing and installation of exhaust duct work and equipment and final connections to fume hoods. E. Division 26 - Electrical: Furnishing and installation of electrical utilities and final connections REFERENCES SPECIFIER: Use care when indicating the edition date of the referenced standards; these standards are subject to regular review, and updated accordingly. 06/01/

2 A. American National Standards Institute/American Industrial Hygiene Association (ANSI/AIHA) 1. ANSI/AIHA Z , Laboratory Ventilation B. American National Standards Institute/American Society of Heating, Refrigerating, and Air Conditioning Engineers (ANSI/ASHRAE) 1. ANSI/ASHRAE Standard , Method of Testing Performance of Laboratory Fume Hoods C. American National Standards Institute/International Organization for Standardization/American Society for Quality Control (ANSI/ISO/ASQC) 1. ANSI/ISO/ASQC Q , Quality Management Systems Requirements Standard D. ASTM International (ASTM) 1. ASTM C , Standard Specification for Heat-Treated Flat Glass--Kind HS, Kind FT Coated and Uncoated Glass. 2. ASTM C e1, Standard Specification for Laminated Architectural Flat Glass 3. ASTM D570-98(2010)e1, Standard Test Method for Water Absorption of Plastics 4. ASTM D638-10, Standard Test Method for Tensile properties of Plastics 5. ASTM D695-10, Standard Test Method for Compressive Properties of Rigid Plastics 6. ASTM D790-10, Standard Test Methods for Flexural Properties of Unreinforced and Reinforced Plastics and Electrical Insulating Materials 7. ASTM D a, Standard Specification for Polypropylene Injection and Extrusion Materials 8. ASTM E84-10b, Standard Test Method for Surface Burning Characteristics of Building Materials 9. ASTM E162-09, Standard Test Method for Surface Flammability of Materials Using a Radiant Heat Energy Source E. The Scientific Equipment and Furniture Association (SEFA) 1. SEFA , Recommended Practices for Laboratory Fume Hoods F. Underwriters Laboratories, Inc. (UL) G. US Consumer Product Safety Commission (CPSC) CFR Part 1201 ( Edition) Safety Standards for Architectural Glazing Materials 1.04 ACTION AND INFORMATIONAL SUBMITTALS SPECIFIER: Revise Section number in the paragraph below to match that used in the Project Manual. A. Submit in accordance with Section [ ] [Other]: 1. Product Data: For each product indicated, submit technical data. Include the following: a. Manufacturer's model number /01/2011

3 b. Detailed specifications of construction. c. Accessories and components that will be included for Project. 2. Shop Drawings: Include plans, elevations, and sections with dimensions, description of materials and finishes, general construction roughing-in dimensions, component connections, anchorage methods, hardware, utility service requirements, and attachments to other work. a. Include layout of units with relation to surrounding walls, doors, windows, lighting and air-conditioning fixtures, connections of hood to hood exhaust system, location of access doors, and junction boxes. b. Indicate clearance requirements for access and maintenance. c. Indicate utility service connections for water, drainage, and power; include roughing-in dimensions. d. Coordinate shop drawings with other trades whose work affects installation or performance of fume hoods. 3. Samples: a. Not less than 4" square piece of polypropylene stock used in the general construction of the fume hood, in thickness and finish specified, if requested by the Architect. b. Not less than 4" square piece of work surface material, in thickness, color, and finish specified. 4. Test and Evaluation Reports: Submit results of testing required under Articles 2.09 SOURCE QUALITY CONTROL, and 3.03 FIELD QUALITY CONTROL. 5. Qualification Statements: Written statement from fume hood manufacturer, that installer meets the requirements specified in Article 1.06 QUALITY ASSURANCE CLOSEOUT SUBMITTALS SPECIFIER: Revise Section number in the paragraph below to match that used in the Project Manual. A. Submit in accordance with Section [ ] [Other]: 1. Operation and Maintenance Data: Include detailed instructions for use and maintenance of fume hoods. 2. Warranty: Submit 2 copies for inclusion in the Owner's systems and equipment maintenance manual QUALITY ASSURANCE A. Compliance: 1. Comply with the provisions of the Building Code, these specifications, and standards referenced in Article 1.03 REFERENCES, except where more stringent requirements are shown on the Drawings or specified herein. 2. Fume hoods and their installation shall comply with laws, ordinances, rules, regulations and orders of governing authorities having jurisdiction over this portion of the Work. 06/01/

4 B. Manufacturer: A firm with undivided responsibility for the fabrication of fume hoods, performed at a single location, and with minimal exposure to outside contaminants. C. Installer: The manufacturer or an installer authorized by the manufacturer to install laboratory equipment, with at least 10 years of successful experience in installing fume hoods similar to those specified DELIVERY, STORAGE, AND HANDLING A. Deliver, store, and handle fume hoods using means and methods that will prevent damage, deterioration, and loss, including theft and vandalism. Comply with manufacturer's written instructions. 1. Deliver fume hoods to Project site in an undamaged condition in manufacturer's original sealed containers or other packaging system, complete with labels and instructions for handling, storing, unpacking, protecting, and installing. 2. Inspect fume hoods on delivery to determine compliance with the Contract Documents and to determine that products are undamaged and properly protected. SPECIFIER: Select Contractor or Construction Manager in subparagraph below as applicable. 3. The [Contractor] [Construction Manager] will provide a secure location and enclosure at Project site for storage of fume hoods until time of installation FIELD CONDITIONS A. Environmental Requirements: 1. Do not install fume hoods until building is enclosed, and surrounding construction is completed and will not affect the final positioning of the product, including overhead work associated with the fume hoods, floor, wall and ceiling finishes, mechanical, electrical, plumbing, and fire protection work performed by others WARRANTY SPECIFIER: When warranties are required, verify with Owner's counsel that warranties stated in this Article are not less than remedies available to Owner under prevailing local laws. A. Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace fume hoods that fail in materials or workmanship within specified warranty period. 1. Failures include, but are not limited to: a. Manufacturer defects; b. structural failure; /01/2011

5 c. warping, and; d. finish. 2. Failures do not include: a. Damages caused by misuse, abuse, or modifications made by the Owner. 3. Warranty Period: One [Other] year [s] from the [date of Substantial Completion] [date of customer acceptance of completed unit]. PART 2 - PRODUCTS 2.01 MANUFACTURER A. Acceptable Manufacturers: LabAire Systems, a Division of Activar Plastics Products Group 9650 Newton Avenue South Bloomington, Minnesota B. Substitutions: Manufacturers seeking approval of their products are required to comply with the Owner's Instructions to Bidders MANUFACTURED UNITS A. Fume Hood: Model LAS-1000 "DynamicFLO Fume Hood", VAV or constant volume chemical fume hood. SPECIFIER: Select sizes listed below based on Project conditions and Owner's recommendations. B. Sizes: 1. Width: [4] [5] [6] [7] [8] [other] feet. 2. Depth: [30] [36] [other] inches. 3. Height: [55-1/2] [other] inches PERFORMANCE CRITERIA A. General Performance Requirements: Properly installed and operating fume hoods serve as ventilated workspaces, with the purpose of capturing, containing, and evacuating fumes, vapors and airborne particulates associated with the activity within the enclosure. B. Illumination Within the Work Area: 1. Definition of Work Area: The area from the work surface to the maximum opening height of the front sash (typically 30 inches); the width from inner side wall to inner side wall, and; the depth from the inner face 06/01/

6 of the front sash to the front face of the baffles. 2. The average illumination level within the work area shall be 90 to 120 foot candles. 3. Average illumination is determined by measuring light in 6 inch intervals within the work area. C. Air Flow: Proper design shall allow for safe and consistent air flow inside the hood and around the hood face. 1. The fume hood is designed to work within a Variable Air Volume System. a. The system shall maintain a safe face velocity based on the recommendations of the manufacturer. 2. Variations in air flow shall not exceed manufacturer's in-house test results when tested in accordance with ANSI/ASHRAE 110. D. Static Air Pressure Loss: 1. The design of the fume hood shall allow for minimal static pressure loss. 2. The maximum average static pressure loss reading shall be taken 3 diameters above the hood outlet from 4 points, 90 degrees apart, and shall not exceed the following guidelines in full open position: Face Velocity (FPM) Measured Static Pressure Loss (WG) 60 FPM 0.15 inches 80 FPM 0.22 inches 100 FPM 0.30 inches 2.04 MATERIALS A. Materials: 1. Hood: Polypropylene "Protec TM PP" (Vycom Corporation). a. Physical Characteristics: Refer to manufacturer's chart at end of this Specification. SPECIFIER: Specify desired work surface material and its physical characteristics, including product name, manufacturer, style, size, color, finish, etc.; polypropylene is the standard; examples of other acceptable work surfaces are indicated below. 2. Work Surfaces: a. [Polypropylene as specified above] [High pressure laminate] [Phenolic resin] [Slate] [Stainless steel] [Trespa ]: 3. Sash Glazing: a. Laminated Safety Glass: Clear laminated glass complying with ASTM C1172 and with testing requirements in 16 CFR 1201 for Category II materials. 1) Construction: Two plies of 1/8-inch thick tempered float glass, each complying with ASTM /01/2011

7 C1048; Type I; Quality-Q3; Class I, and; separated by a clear inch polyvinyl butyral interlayer. 2) Overall Glass Thickness: 1/4-inch (nominal). 3) Provide safety glazing labeling. 4. Sash Counterweight Connection: Kevlar-reinforced polyurethane belt. 5. Adhesives/Sealants: 100 percent silicone. 6. Fasteners: Manufacturer's standard recommended fasteners. a. Polypropylene screws. b. Steel shoulder bolts (used outside work zone, pulleys). 7. Lighting: SPECIFIER: Select preferred lighting in subparagraph below. a. [Two-tube LED light] [Two-tube fluorescent light] 2.05 CONTROLS A. Standard Operation Controls: 1. Sash Control: Manual raising and lowering. 2. Lighting: Electrical switch with on-off positions. 3. Rear Baffles: Stationary. SPECIFIER: Review optional control choices below with the Owner and manufacturer, then select desired controls. B. Optional Operation Controls: 1. Optional Sash Control: Encoded motor-driven sash, with adjustable settings, including speed, location, and presets. a. Programmable Logic Controller (PLC) with Human Machine Interface (HMI) and touch screen control. 2. Optional Lighting Control: a. Programmable Logic Controller (PLC) with Human Machine Interface (HMI). 3. Optional Adjustable Rear Baffle Control: Motor-driven valves. a. Programmable Logic Controller (PLC) with Human Machine Interface (HMI). 4. Optional Air Flow Monitor and Control: 06/01/

8 SPECIFIER: Select one or all of the features in subparagraph below. a. Face velocity monitor control b. Auto motion sensor control c. Sash positioning sensor 2.06 FIXTURES SPECIFIER: Review optional fixtures below with the Owner and manufacturer; fume hoods do not come equipped with these unless specified. 9. Fixtures: a. Sinks: 1) Cup sinks 2) Fabricated sinks 3) Custom sized sinks b. Faucets: 1) Premanufactured faucets 2) Fabricated or custom faucets c. Gas: 1) Air 2) Gas 3) Vacuum 4) Other d. Handles 1) Premanufactured handles 2) Fabricated handles 2.07 ACCESSORIES SPECIFIER: Additional accessories are available from the manufacturer; review available optional accessories with manufacturer and Owner prior to specifiying. A. Accessories: Available upon request FABRICATION /01/2011

9 A. General: The main assembly is constructed of 1/2-inch thick, white polypropylene. Seams are fully-welded forming the rigid internal structure, with removable, white polypropylene panels to enclose utilities and inner components. Panels are sized differently to accommodate ease of use and function. Standard overall dimensional tolerances are plus-or-minus1/8-inch. B. Joints: Joints are formed with 5/32-inch white polypropylene welding rod. 1. Joints are water tight. 2. Exterior welds are shaved flush with construction material to create a uniform surface. C. Structure: The unit is constructed with the inner walls as the main support structure. Walls contain access ports to the utility areas, which are secured with 1/4-20 white polypropylene Philips head screws. Ports are flush with the surrounding walls with lipped construction to reduce the potential of leakage. External walls are removable and secured with 1/4-20 white polypropylene Philips head screws. 1. The lining is 1/8-inch virgin sheet stock material and overlays the polypropylene surface such that the interior dimensions are identical. The liner is heat-welded together to form a ridged structure, and fastened to the polypropylene by 1/4-20 flathead screws of like material. D. Airfoil: The airfoil is constructed from 3/8-inch white polypropylene with additional bracing and mounting brackets spaced along the length of it. The airfoil rests on the lip of the spill retention trough. The airfoil is removable for easy cleanup. SPECIFIER: Select preferred work surface profile in paragraph below. E. Work Surface: The work surface is [flat] [dished to accommodate additional spill retention]. The surface has a ribbed structure on the underside to add structural rigidity. SPECIFIER: Add subparagraph below when a nonstandard work surface material is selected; coordinate with Article 2.03 MATERIALS. 1. Provide polypropylene liner to enclose and maintain sealed work environment. SPECIFIER: Identify glazing material in paragraph below based on selection made in Article 2.03 MATERIALS. F. Viewing Panel and Sash: The front viewing panel is glazed with [safety glass] [other]. The frame supporting the glass is made of white polypropylene. The front sash is suspended with a counterweight that is encapsulated with white polypropylene and contains a ballast area. The sash will be attached with a Kevlar-reinforced polyurethane belt. The pulleys are made from polypropylene or aluminum (with locating system). The handle is constructed of white polypropylene and fastened with a clear double-sided tape. G. Baffles: The baffles are rectangular-shaped. Four layers of evenly spaced slots pulls the workspace air into the rear exhaust plenum. H. Electrical features are contained in UL-listed PVC junction boxes connected by PVC pipe. Junction boxes are 06/01/

10 sealed using gaskets. SPECIFIER: Closure panels are optional; select the paragraph below and desired area of enclosure if these are required. I. Closure Panels: 1. Provide additional panels to enclose [the upper sections of the hood to the ceiling above] [and] [the plumbing chase] SOURCE QUALITY CONTROL A. Tests: Fume hoods are tested at the manufacturer's assembly facility in compliance with ANSI/ASHRAE 110 (Manufacturer's Test), by independent third party testing prior to shipping; results are available to the Owner, if requested. 1. These tests generally include: a. Tracer Gas Test b. Face Velocity Test c. Smoke Pattern Test d. Saturation Smoke Test PART 3 - EXECUTION 3.01 EXAMINATION SPECIFIER: Select Contractor or Construction Manager in paragraph below as applicable. A. Examine substrates, areas, and conditions, with installer present where indicated, for compliance with requirements for installation tolerances and other conditions affecting performance. Notify the [Contractor] [Construction Manager] of conditions detrimental to performance of the Work and recommended corrections. Where the installation and its completion will be delayed due to existing conditions, follow notification immediately with a written report. Proceed with installation only after unsatisfactory conditions have been corrected INSTALLATION A. General: Install fume hoods in strict accordance with the manufacturer's instructions, plumb, level, aligned, rigid, and securely anchored to supporting casework, in proper location, and in accordance with final shop drawings. B. Coordinate sequence of work with mechanical, plumbing, and electrical trades and with installation of related casework /01/2011

11 SPECIFIER: "Acceptance Testing" specified in Article 3.03 FIELD QUALITY CONTROL below, is recommended but not required; determine costs associated with testing prior to specifying FIELD QUALITY CONTROL A. Acceptance Testing: On completion of fume hood installation and before permitting regular use, perform acceptance tests in accordance with ANSI/ASHRAE 110, for face velocity and airflow smoke patterns. 1. Advise Owner and Architect in advance of dates and times that tests are to be performed on fume hoods. 2. Fume hoods are determined to have passed testing if test results meet performance criteria specified. 3. Fume hoods which fail to comply with scheduled tests shall be adjusted in the field by the appropriate mechanical trades, and retested until compliance with specified limits of operation are obtained CLEANING AND PROTECTION A. Clean fume hoods following installation in accordance with manufacturer's instructions and recommendations using liquids that will not harm finishes and glazing. 1. Clean exposed surfaces of the fume hood including surfaces exposed to view, those within the work area, and glazing. SPECIFIER: Select Contractor or Construction Manager in paragraph below as applicable. B. Advise [Contractor] [Construction Manager] of methods to protect fume hoods until acceptance by the Owner. Protect fume hoods from damage due to other construction activity, during installation and after acceptance CLOSEOUT ACTIVITIES A. Demonstration and Training: Engage a factory-authorized service representative to train Owner's personnel to adjust, operate, and maintain fume hoods. 1. Perform training only after equipment has been installed, tested, and is operating correctly. END OF SECTION /01/

E. Fume hood to have set baffling system. No adjustable baffles allowed.

E. Fume hood to have set baffling system. No adjustable baffles allowed. 1.01 SUMMARY A. Section Includes: 1. Laboratory fume hoods. B. Related Sections: 1. Section 6500 Laboratory casework 2. Section 15 Mechanical: Furnishing and installation of plumbing utilities and final

More information

SECTION G3 FUME HOODS

SECTION G3 FUME HOODS G3 FUME HOODS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Laboratory fume hoods that shall meet the definition of a Laboratory Fume Hood as stated in the SEFA 1 2002 Recommended Practice. (Scientific

More information

SECTION CRL70 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

SECTION CRL70 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS Page 1 of 6 SECTION 08 32 20 CRL70 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS [OR WOOD] PANEL PARTITIONS. SECTION INCLUDES OVERHEAD TRACK ASSEMBLY,

More information

SECTION EZ-SLIDE 80 AND 180 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

SECTION EZ-SLIDE 80 AND 180 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS Page 1 of 6 SECTION 08 32 20 EZ-SLIDE 80 AND 180 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS PANEL PARTITIONS. SECTION INCLUDES OVERHEAD TRACK ASSEMBLY,

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 102239 - FOLDING PANEL PARTITIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM

SECTION LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM Page 1 of 6 SECTION 08 32 20 LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS SLIDING DOORS. SECTION INCLUDES OVERHEAD SLIDING TUBE ASSEMBLY, MOUNTING

More information

SECTION SAFEGUARD LABORATORY FUME HOODS

SECTION SAFEGUARD LABORATORY FUME HOODS SECTION 11 53 13 SAFEGUARD LABORATORY FUME HOODS PART 1 GENERAL Summary: This Specification identifies the minimum material and construction standards that are required to deliver a quality installation

More information

SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS SECTION 08 32 20 CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS Page 1 of 6 USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS PANEL PARTITIONS. SECTION INCLUDES OVERHEAD TRACK ASSEMBLY,

More information

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection SECTION 13090 RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13090-1 LOW INTENSITY RADIATION PROTECTION

More information

DIVISION VIII - DOORS AND WINDOWS

DIVISION VIII - DOORS AND WINDOWS DIVISION VIII - DOORS AND WINDOWS SECTION 08121 INTERIOR ALUMINUM DOORS, DOOR FRAMES, AND OFFICE FRONT FRAMING (SOLUTIONS II SYSTEM) PART 1 - GENERAL 1.01 SUMMARY A. Related Documents: Provisions established

More information

DIVISION 11 - EQUIPMENT FOOD SERVICE EQUIPMENT LABORATORY FUME HOODS. A. Design Considerations

DIVISION 11 - EQUIPMENT FOOD SERVICE EQUIPMENT LABORATORY FUME HOODS. A. Design Considerations DIVISION 11 - EQUIPMENT 11400 FOOD SERVICE EQUIPMENT A. Design Considerations 1. The A/E shall use the services of a food service equipment specialist in preparation of kitchen areas and other food preparation

More information

SECTION (FORMERLY 11610)

SECTION (FORMERLY 11610) PART 1 GENERAL SECTION 11 53 13 (FORMERLY 11610) OBSERVATION2 STYLE GLASS WALLED FUME HOODS Display hidden notes to specifier by using "Tools/Options/View/Hidden Text Summary: This Specification identifies

More information

SECTION TRESPA ATHLON SOLID COMPOSITE PHENOLIC TOILET PARTITIONS. A. Solid composite phenolic toilet compartments and urinal screens.

SECTION TRESPA ATHLON SOLID COMPOSITE PHENOLIC TOILET PARTITIONS. A. Solid composite phenolic toilet compartments and urinal screens. SECTION 102113 TRESPA ATHLON SOLID COMPOSITE PHENOLIC TOILET PARTITIONS PART 1 - GENERAL 1.01 SECTION INCLUDES A. Solid composite phenolic toilet compartments and urinal screens. 1.02 RELATED SECTIONS

More information

SECTION METAL FRAMED SKYLIGHT. A. Engineering, preparation of fabrication drawings and structural calculations for the entire skylight system.

SECTION METAL FRAMED SKYLIGHT. A. Engineering, preparation of fabrication drawings and structural calculations for the entire skylight system. SECTION 08625 METAL FRAMED SKYLIGHT PART 1 GENERAL 1.01 SECTION INCLUDES: A. Engineering, preparation of fabrication drawings and structural calculations for the entire skylight system. B. Fabrication

More information

SECTION MEDICATION CABINET. 1.1 SUMMARY A. Section Includes: 1. Medication cabinets with self-contained refrigerator and fixtures.

SECTION MEDICATION CABINET. 1.1 SUMMARY A. Section Includes: 1. Medication cabinets with self-contained refrigerator and fixtures. SECTION 12 35 70.21 MEDICATION CABINET SPEC WRITER NOTE: Delete text between // // not applicable to project. Edit remaining text to suit project. PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Medication

More information

Construction Standards PAGE

Construction Standards PAGE Construction Standards PAGE 115313-1 SECTION 115313 - PART 1 - GENERAL 1.1 M.S.U. ISSUES A. Ductless or auxiliary air hoods are not acceptable. B. Perchloric Acid hoods are not acceptable. 1.2 SUMMARY

More information

Phenolic Exterior Wall Cladding

Phenolic Exterior Wall Cladding Phenolic Exterior Wall Cladding SECTION 07 42 43 COMPOSITE WALL PANELS This specification includes hidden text for editing for a project. PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Phenolic wall

More information

SECTION SECURITY PROTECTION PART 1 GENERAL

SECTION SECURITY PROTECTION PART 1 GENERAL SECTION 13 1010 - PART 1 GENERAL 1.01 SECTION INCLUDES A. Bullet Resistant Aluminum Windows. B. Bullet Resistant Transaction Equipment. C. Bullet Resistant Speakers. D. Bullet Resistant Glazing. E. Bullet

More information

SECTION DEMOUNTABLE WALLS SKY WALLS - STRATUS SYSTEM

SECTION DEMOUNTABLE WALLS SKY WALLS - STRATUS SYSTEM 1 SECTION 10.22.19 DEMOUNTABLE WALLS SKY WALLS - STRATUS SYSTEM PART 1 - GENERAL 1.01 SUMMARY A. This section includes: 1. Full height center-glazed, butt-jointed partition system. 2. Full height doors.

More information

SECTION AWNINGS

SECTION AWNINGS SECTION 10 73 13 AWNINGS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Fixed metal awnings. 1.2 DEFINITIONS A. Awning: An architectural projection that provides weather protection,

More information

SECTION ORCHESTRA PIT FILLER

SECTION ORCHESTRA PIT FILLER PART 1 - GENERAL 1.1 SECTION INCLUDES A. Orchestra pit filler. 1.2 REFERENCES SECTION 11 61 00 ORCHESTRA PIT FILLER A. American Hardboard Association (AHA): 1. AHA A135.4-95: Basic Hardboard. B. American

More information

SECTION / METAL FRAMED SKYLIGHTS

SECTION / METAL FRAMED SKYLIGHTS Specifier Notes: This product guide specification is written according to the Construction Specifications Institute (CSI) Format, including MasterFormat, SectionFormat, and PageFormat, contained in the

More information

SECTION HANDRAILS AND RAILINGS. A. Section Cast-In-Place Concrete; coordination with substrate.

SECTION HANDRAILS AND RAILINGS. A. Section Cast-In-Place Concrete; coordination with substrate. SECTION 05520 HANDRAILS AND RAILINGS PART 1 GENERAL 1.1 SECTION INCLUDES A. Welded stainless steel railing systems. 1.2 RELATED SECTIONS A. Section 03300 - Cast-In-Place Concrete; coordination with substrate.

More information

SECTION Motor Operated Horizontal Sliding Sound Control Door

SECTION Motor Operated Horizontal Sliding Sound Control Door SECTION 08 34 73 Motor Operated Horizontal Sliding Sound Control Door PART 1 GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of the Contract, including general and Supplementary Conditions

More information

SECTION WALL AND DOOR PROTECTION

SECTION WALL AND DOOR PROTECTION PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 10 26 00 WALL AND DOOR PROTECTION SPEC WRITER NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable to

More information

Expansion Joint Covers (079513)

Expansion Joint Covers (079513) Expansion Joint Covers 07 95 00 (079513) PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General Conditions, Supplementary Conditions and Division-1

More information

SECTION LABORATORY FUME HOODS

SECTION LABORATORY FUME HOODS PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 11 53 13 LABORATORY FUME HOODS SPEC WRITER NOTE: Delete between // // if not applicable to project. Delete other items or paragraphs in the section that are not

More information

SECTION FIBERGLASS REINFORCED PLASTIC (FRP) DOORS AND FIBERGLASS RESIN TRANSFER MOLDED DOOR FRAMES

SECTION FIBERGLASS REINFORCED PLASTIC (FRP) DOORS AND FIBERGLASS RESIN TRANSFER MOLDED DOOR FRAMES SECTION 08220 FIBERGLASS REINFORCED PLASTIC (FRP) DOORS AND FIBERGLASS RESIN TRANSFER MOLDED DOOR FRAMES FIB-R-MAX SINGLE 3070 DOOR FIRE RATED SERIES MEETING UL 10(C) POSITIVE PRESSURE AND UL 10(B) NEGATIVE

More information

SECTION DOOR HARDWARE

SECTION DOOR HARDWARE SECTION 087100 -DOOR HARDWARE PART 1- GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION AIR TERMINAL UNITS

SECTION AIR TERMINAL UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

SECTION SECTIONAL OVERHEAD DOORS 424 SERIES SECTIONAL STEEL DOORS

SECTION SECTIONAL OVERHEAD DOORS 424 SERIES SECTIONAL STEEL DOORS SECTION 08 36 00 SECTIONAL OVERHEAD DOORS 424 SERIES SECTIONAL STEEL DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word click on

More information

Expansion Joint Covers

Expansion Joint Covers Expansion Joint Covers 07 95 00 (079513) PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General Conditions, Supplementary Conditions and Division-1

More information

SECTIONAL OVERHEAD DOORS SECTION SECTIONAL OVERHEAD DOORS PART 1 GENERAL

SECTIONAL OVERHEAD DOORS SECTION SECTIONAL OVERHEAD DOORS PART 1 GENERAL 13686.00 SECTIONAL OVERHEAD DOORS 083613-1 1.1 RELATED DOCUMENTS SECTION 083613 - SECTIONAL OVERHEAD DOORS PART 1 GENERAL A. Drawings and general provisions of Contract, including General and Supplementary

More information

SECTION SECTIONAL OVERHEAD DOORS 422 SERIES INSULATED STEEL DOORS

SECTION SECTIONAL OVERHEAD DOORS 422 SERIES INSULATED STEEL DOORS SECTION 08 36 00 SECTIONAL OVERHEAD DOORS 422 SERIES INSULATED STEEL DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word click on

More information

SECTION SECTIONAL OVERHEAD DOORS 432 SERIES INSULATED STEEL DOORS

SECTION SECTIONAL OVERHEAD DOORS 432 SERIES INSULATED STEEL DOORS SECTION 08 36 00 SECTIONAL OVERHEAD DOORS 432 SERIES INSULATED STEEL DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word click on

More information

SECTION [ ] COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION [ ] COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here) SECTION 08332 [08 33 13] COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Metal Counter

More information

SECTION PHENOLIC LOCKERS AND BENCHES. B. Section Gypsum Board Area Separation Wall Assemblies.

SECTION PHENOLIC LOCKERS AND BENCHES. B. Section Gypsum Board Area Separation Wall Assemblies. SECTION 10 51 29 PHENOLIC LOCKERS AND BENCHES PART 1 GENERAL 1.1 SECTION INCLUDES A. Phenolic lockers, hardware and accessories. B. Phenolic pedestal benches. C. Phenolic cubbies. 1.2 RELATED SECTIONS

More information

SECTION ACCORDION FOLDING PARTITIONS

SECTION ACCORDION FOLDING PARTITIONS PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 10 22 26.13 ACCORDION FOLDING PARTITIONS SPEC WRITER NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable

More information

SECTION STILE AND RAIL WOOD DOORS

SECTION STILE AND RAIL WOOD DOORS SECTION 08 1433 NOTE: THIS SECTION USES THE TERM "ARCHITECT." CHANGE THIS TERM TO IDENTIFY THE DESIGN PROFESSIONAL AS DEFINED IN THE AGREEMENT OR GENERAL CONDITIONS OF THE CONTRACT. PART 1 GENERAL 1.01

More information

SPECIFICATION - SECTION (10650) OPERABLE PARTITIONS

SPECIFICATION - SECTION (10650) OPERABLE PARTITIONS Acousti-Clear Automatic Seal Paired Panel 10 22 26 (10650) Operable Partitions SPECIFICATION - SECTION 10 22 26 (10650) OPERABLE PARTITIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general

More information

DIVISION 10 SPECIALTIES SECTION OPERABLE PARTITIONS

DIVISION 10 SPECIALTIES SECTION OPERABLE PARTITIONS DIVISION 10 SPECIALTIES SECTION 10 22 26 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

DIMENSIONAL LETTER SIGNAGE

DIMENSIONAL LETTER SIGNAGE SECTION - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this

More information

SECTION SECTIONAL OVERHEAD DOORS 416 SERIES SECTIONAL STEEL DOORS

SECTION SECTIONAL OVERHEAD DOORS 416 SERIES SECTIONAL STEEL DOORS SECTION 08 36 00 SECTIONAL OVERHEAD DOORS 416 SERIES SECTIONAL STEEL DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word click on

More information

2004 MASTER FORMAT SECTION Façade Panels

2004 MASTER FORMAT SECTION Façade Panels 2004 MASTER FORMAT SECTION 07 44 00 Façade Panels Hunter Douglas Façades Aluminum Façade Systems PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General

More information

SECTION TRESPA ATHLON SOLID COMPOSITE CASEWORK

SECTION TRESPA ATHLON SOLID COMPOSITE CASEWORK SECTION 064115 TRESPA ATHLON SOLID COMPOSITE CASEWORK PART 1 GENERAL 1.01 SECTION INCLUDES A. Solid composite casework. 1.02 RELATED SECTIONS A. Documents affecting work in this section includes but is

More information

SECTION STAINLESS STEEL WALL PANELS

SECTION STAINLESS STEEL WALL PANELS SECTION 07400 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Dry joint, Rainscreen stainless steel wall panel system. 2. Accessories including attachments, clips, sub girts, shims, and fasteners 3.

More information

SECTION SECTIONAL OVERHEAD DOORS 418 SERIES INSULATED STEEL DOORS

SECTION SECTIONAL OVERHEAD DOORS 418 SERIES INSULATED STEEL DOORS SECTION 08 36 00 SECTIONAL OVERHEAD DOORS 418 SERIES INSULATED STEEL DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word click on

More information

SECTION (FORMERLY 11610)

SECTION (FORMERLY 11610) SECTION 11 53 13 (FORMERLY 11610) LABORATORY FUME HOODS PART 1 GENERAL Summary: This Specification identifies the minimum material and construction standards that are required to deliver a quality installation

More information

JE Berkowitz, L.P. (updated ) B. The basis of design is the JEB Invisiwall Wall (Point Supported) by JE Berkowitz, LP. C.

JE Berkowitz, L.P. (updated ) B. The basis of design is the JEB Invisiwall Wall (Point Supported) by JE Berkowitz, LP. C. JE Berkowitz, L.P. (updated 10.19.17) JEB Invisiwall Glass Wall (Point Support) General Specification Guide Section 08 44 26.19 GLAZED ASSEMBLIES This general specification is to be used as a guide. It

More information

B. Shop Drawings: For metal lockers. Include plans, elevations, sections, details, and attachments to other work.

B. Shop Drawings: For metal lockers. Include plans, elevations, sections, details, and attachments to other work. SECTION 10 5113 - METAL LOCKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

SECTION FIBERGLASS REINFORCED POLYESTER (FRP) DOORS AND ALUMINUM FRAMES

SECTION FIBERGLASS REINFORCED POLYESTER (FRP) DOORS AND ALUMINUM FRAMES SECTION 081613 FIBERGLASS REINFORCED POLYESTER (FRP) DOORS AND ALUMINUM FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

SECTION Manufactured Metal Casework FLEXIBLE LABORATORY FURNITURE SYSTEM (OPTIMA) USA VERSION

SECTION Manufactured Metal Casework FLEXIBLE LABORATORY FURNITURE SYSTEM (OPTIMA) USA VERSION SECTION 12 31 00.4 Manufactured Metal Casework FLEXIBLE LABORATORY FURNITURE SYSTEM (OPTIMA) USA VERSION PART 1 GENERAL Summary: This Specification identifies the minimum material and construction standards

More information

SECTION METAL WALL PANELS

SECTION METAL WALL PANELS Unience USA, Inc. 2115 Linwood Avenue, Suite 500 Fort Lee, NJ 07024 Phone: 201-676-2467 Fax: 201-944-3660 Email: alfrex@alfrexusa.com Web: www.alfrexusa.com SECTION 07 42 13 METAL WALL PANELS PART 1 GENERAL

More information

SECTION The specification section is organized by placing information in three standard parts:

SECTION The specification section is organized by placing information in three standard parts: SECTION 14244 LIMITED USE HYDRAULIC ELEVATOR ***** Since 1982 Liftavator, Inc. has provided limited use/limited application (LU/LA) elevators, residential elevators, hydraulic vertical platform wheelchair

More information

SECTION SERIES ALL GLASS ENTRANCES

SECTION SERIES ALL GLASS ENTRANCES 1 SECTION 08 4210 1200 SERIES ALL GLASS ENTRANCES PART 1 - GENERAL 1.01 SUMMARY A. This section includes: 1. Vestibule doors matching entrance doors. 2. Sidelites. B. Related work in other sections: 1.

More information

SECTION SECTIONAL OVERHEAD DOORS 511 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS

SECTION SECTIONAL OVERHEAD DOORS 511 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS SECTION 08 36 00 SECTIONAL OVERHEAD DOORS 511 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word

More information

PART 1 / GENERAL SECTION ALUMINUM PLATE PANEL SYSTEM. ALPLY Insulated Panels. Alply TECH WALL Aluminum Plate System 2002

PART 1 / GENERAL SECTION ALUMINUM PLATE PANEL SYSTEM. ALPLY Insulated Panels. Alply TECH WALL Aluminum Plate System 2002 SECTION 07 42 13 ALUMINUM PLATE PANEL SYSTEM ALPLY Insulated Panels Alply TECH WALL Aluminum Plate System 2002 PART 1 / GENERAL 1.1 SYSTEM DESCRIPTION A. Preformed Aluminum Plate System for Screen wall

More information

UBC Technical Guidelines Section Edition Fume Hoods Page 1 of 5

UBC Technical Guidelines Section Edition Fume Hoods Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 12 35 53 Laboratory Casework.2 Section 23 38 16 Fume Hood Exhaust Systems.3 Section 20 00 08 Mechanical Identification for the details for fume

More information

SECTION ALUMINUM WINDOWS

SECTION ALUMINUM WINDOWS SECTION 08520 ALUMINUM WINDOWS PART 1 - GENERAL 1.01 SUMMARY A. Section includes: 1. Storefront systems and aluminum framed glass doors. 2. Hardware, fasteners, accessories, filler pieces, etc., required

More information

SECTION ALUMINUM WINDOWS

SECTION ALUMINUM WINDOWS SECTION 08520 ALUMINUM WINDOWS 1. PART 1 GENERAL 1.1 WORK INCLUDED: 1. Provide labor, material, equipment and services to furnish and install aluminum windows shown on drawings and specified herein. Window

More information

SECTION ORNAMENTAL ALUMINUM RAILING

SECTION ORNAMENTAL ALUMINUM RAILING SECTION 05730 ORNAMENTAL ALUMINUM RAILING PART 1 GENERAL 1.1 SECTION INCLUDES A. Decorative Wire Rope Railing 1.2 RELATED SECTIONS A. Section 03300 Cast-In-Place Concrete: Placement of sleeves cast in

More information

SECTION HEAVY GLASS TOP HUNG SLIDING BI-FOLD DOOR SYSTEMS

SECTION HEAVY GLASS TOP HUNG SLIDING BI-FOLD DOOR SYSTEMS Page 1 of 6 SECTION 08 32 20 HEAVY GLASS TOP HUNG SLIDING BI-FOLD DOOR SYSTEMS USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED BI-FOLD GLASS PANEL PARTITIONS. SECTION INCLUDES OVERHEAD TRACK ASSEMBLY,

More information

SECTION COMMERCIAL CURB-MOUNT ACRYLIC DOUBLE DOME SKYLIGHTS

SECTION COMMERCIAL CURB-MOUNT ACRYLIC DOUBLE DOME SKYLIGHTS SECTION 08620 COMMERCIAL CURB-MOUNT ACRYLIC DOUBLE DOME SKYLIGHTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION (FORMERLY 11610)

SECTION (FORMERLY 11610) SECTION 11 53 13 (FORMERLY 11610) LABORATORY FUME HOODS PART 1 GENERAL Summary: This Specification identifies the minimum material and construction standards that are required to deliver a quality installation

More information

SoCal Dynamic Dome Skylight SECTION UNIT SKYLIGHTS

SoCal Dynamic Dome Skylight SECTION UNIT SKYLIGHTS VELUX SECTION 08 62 00 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Dynamic dome unit skylight with formed curb counterflashing for mounting on site-built or prefabricated roof curbs, for flat, low-slope and

More information

FYPON, LLC. February 2014

FYPON, LLC. February 2014 Section 06 66 30 EXTERIOR PVC RAILINGS AND GUARDS PART 1 - GENERAL 1.1 RELATED SECTIONS: A. All contract documents apply to work of this section; this includes but is not limited to: Agreement; Drawings;

More information

SECTION SOUND-ABSORPTIVE PANELS

SECTION SOUND-ABSORPTIVE PANELS SECTION 09 77 23 SOUND-ABSORPTIVE PANELS PART 1 - GENERAL 1.1 CONDITIONS AND REQUIREMENTS A. The General Conditions, Supplementary Conditions, and Division 01 General Requirements apply. 1.2 SECTION INCLUDES

More information

SECTION FIBERGLASS REINFORCED POLYMER (FRP) PANELS

SECTION FIBERGLASS REINFORCED POLYMER (FRP) PANELS SECTION 07 44 50 FIBERGLASS REINFORCED POLYMER (FRP) PANELS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Design, Engineering, manufacturing and erection of fiberglass reinforced panels. Delegated Design of

More information

Trex Commercial Products page Metal Railing

Trex Commercial Products page Metal Railing SECTION 05520 HANDRAILS AND RAILINGS PART 1 GENERAL 1.1 SECTION INCLUDES A. Classic Railings (Picket). B. GridGuard Railings (Mesh). C. Post Rail (Glass). D. Tensiline Railings (Cable). E. Track Rail (Glass).

More information

University of Lethbridge Destination Project Jun 2017 Issued for Construction - Architectural Page 1

University of Lethbridge Destination Project Jun 2017 Issued for Construction - Architectural Page 1 09 Jun 2017 Issued for Construction - Architectural Page 1 1 General 1.1 SUMMARY.1 General Requirements: Conform with requirements of Sections of Division 01, General Requirements, as it applies to the

More information

SECTION EXTERIOR SOLID PHENOLIC RAINSCREEN PANELS

SECTION EXTERIOR SOLID PHENOLIC RAINSCREEN PANELS SECTION 074233 EXTERIOR SOLID PHENOLIC RAINSCREEN PANELS PART 1 - GENERAL 1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION ALL GLASS ENTRANCES. 1. Lock cylinders for tempered glass entrance doors are specified in Division 8 section Finished Hardware.

SECTION ALL GLASS ENTRANCES. 1. Lock cylinders for tempered glass entrance doors are specified in Division 8 section Finished Hardware. 1 SECTION 08 4210 ALL GLASS ENTRANCES PART 1 - GENERAL 1.01 SUMMARY A. This section includes: 1. Vestibule doors matching entrance doors. 2. Sidelites. B. Related work in other sections: 1. Lock cylinders

More information

SECTION METAL WALL PANELS

SECTION METAL WALL PANELS Mitsubishi Plastics Composites America, Inc. 401 Volvo Parkway Chesapeake, VA 23320 Phone: (800) 422-7270 Fax: (757) 436-1896 E-mail: info@alpolic.com www.alpolic-northamerica.com This MANU-SPEC utilizes

More information

1. Include construction details, materials, individual components and profiles, and finishes.

1. Include construction details, materials, individual components and profiles, and finishes. SECTION 08 31 13 - ACCESS DOORS AND FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings,and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Fixed equipment shall generally be furnished and installed by the General Contractor as part of the construction contract.

Fixed equipment shall generally be furnished and installed by the General Contractor as part of the construction contract. SECTION 11 00 00 - EQUIPMENT GENERAL INFORMATION Fixed equipment shall generally be furnished and installed by the General Contractor as part of the construction contract. Movable equipment shall, as a

More information

SECTION EXPANSION CONTROL

SECTION EXPANSION CONTROL SECTION 07 95 00 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1 Louis Armstrong New Orleans International Airport NOAB Project # 8910-01233 PART 1 - GENERAL SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS 1.1 RELATED DOCUMENTS A. Drawings and general provisions

More information

SECTION ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS

SECTION ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS SECTION 08 4113 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Aluminum entrance doors and frames. 2. Glass infill panels. 3. Door hardware. B. Related Sections:

More information

SECTION EXPANSION CONTROL

SECTION EXPANSION CONTROL SECTION 07 95 00 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

PRODUCTION SPECIFICATIONS INSULATED CONCRETE FORMS

PRODUCTION SPECIFICATIONS INSULATED CONCRETE FORMS PRODUCTION SPECIFICATIONS SECTION 03135 INSULATED CONCRETE FORMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Insulated panel permanent concrete form system for: 1. Exterior structural wall panels. 2. Interior

More information

PRODUCTION SPECIFICATIONS INSULATED CONCRETE FORMS

PRODUCTION SPECIFICATIONS INSULATED CONCRETE FORMS PRODUCTION SPECIFICATIONS SECTION 03135 INSULATED CONCRETE FORMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Insulated panel permanent concrete form system for: 1. Exterior structural wall panels. 2. Interior

More information

ACOUSTI-CLEAR AUTOMATIC SERIES TECHNICAL DATA

ACOUSTI-CLEAR AUTOMATIC SERIES TECHNICAL DATA Paired panel system Acoustically rated glass wall system Automatic seal system Hinged together in groups of two, facilitating quick, easy setup Each panel is supported by a single carrier Ideal for straight-line

More information

DiSorb Diffuser Product Specifications Section Sound Diffuser-Absorber for Ceilings and Walls (DiSorb Diffuser-Absorber)

DiSorb Diffuser Product Specifications Section Sound Diffuser-Absorber for Ceilings and Walls (DiSorb Diffuser-Absorber) DiSorb Diffuser Product Specifications PART 1 - GENERAL 1.01 SUMMARY A. This section includes Sound Diffuser-Absorbers for Ceilings and/or Walls. Types include: 1.02 RELATED SECTIONS 1. DiSorb Diffuser-Absorber,

More information

SECTION TOILET COMPARTMENTS. A. Section Metal Fabrications: Concealed steel support members.

SECTION TOILET COMPARTMENTS. A. Section Metal Fabrications: Concealed steel support members. SECTION 10155 TOILET COMPARTMENTS PART 1 GENERAL 1.1 SECTION INCLUDES A. Plastic laminate partitions. 1.2 RELATED SECTIONS A. Section 05500 - Metal Fabrications: Concealed steel support members. B. Section

More information

Cardinal Commercial Products ALUMINUM STOREFRONT SYSTEM SERIES CF450 GUIDE SPECIFICATIONS SECTION ALUMINUM ENTRANCES AND STOREFRONT SYSTEMS

Cardinal Commercial Products ALUMINUM STOREFRONT SYSTEM SERIES CF450 GUIDE SPECIFICATIONS SECTION ALUMINUM ENTRANCES AND STOREFRONT SYSTEMS Cardinal Commercial Products ALUMINUM STOREFRONT SYSTEM SERIES CF450 GUIDE SPECIFICATIONS SECTION 08410 ALUMINUM ENTRANCES AND STOREFRONT SYSTEMS This suggested guide specification has been developed using

More information

ALL-ALUMINUM DOOR & WINDOW FRAMING

ALL-ALUMINUM DOOR & WINDOW FRAMING ALL-ALUMINUM DOOR & WINDOW FRAMING WITH INTEGRATED ALUMINUM DOOR STOP SECTION 08 41 13 ALUMINUM FRAMED ENTRANCES AND STOREFRONTS SPECIFICATION PART 1 GENERAL 1.1 SECTION INCLUDES: A. Prefinished aluminum

More information

SECTION STEEL HEALTHCARE CASEWORK

SECTION STEEL HEALTHCARE CASEWORK SECTION 12 35 70.01 STEEL HEALTHCARE CASEWORK This guide specification has been prepared by InnerSpace Corporation to assist design professionals in the preparation of a specification section covering

More information

SECTION METAL EQUIPMENT LOCKERS

SECTION METAL EQUIPMENT LOCKERS SECTION 10 51 13 - METAL EQUIPMENT LOCKERS PART 1 GENERAL 1.1 SECTION INCLUDES A. DESCRIPTION: Furnish and install factory-assembled Heavy-Duty MIG-Welded Metal Lockers, complete, as shown and specified

More information

SECTION PANEL AND POST AND PYLON SIGNAGE. 1. Non-illuminated Panel and Post signs. 2. Internal illumination Pylon (Cabinet and Post) signs.

SECTION PANEL AND POST AND PYLON SIGNAGE. 1. Non-illuminated Panel and Post signs. 2. Internal illumination Pylon (Cabinet and Post) signs. PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Non-illuminated Panel and Post signs. 2. Internal illumination Pylon (Cabinet and Post) signs. 1.2 PERFORMANCE REQUIREMENTS A. Structural

More information

B. Samples for Initial Selection: For each type of impact-resistant wall protection unit indicated.

B. Samples for Initial Selection: For each type of impact-resistant wall protection unit indicated. SECTION 102600 - WALL AND DOOR PROTECTION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION EXPANSION CONTROL

SECTION EXPANSION CONTROL SECTION 07 95 00 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

A. Access doors and frames are part of an access door and frame allowance.

A. Access doors and frames are part of an access door and frame allowance. SECTION 08 31 13 ACCESS DOORS AND FRAMES PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION COMPOSITE WALL PANELS PART 1 GENERAL 1.01 SECTION INCLUDES

SECTION COMPOSITE WALL PANELS PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 07 4243 - PART 1 GENERAL 1.01 SECTION INCLUDES A. Composite wall panel system consisting of aluminum-faced composite panels in a rainscreen application as part of the assembly described below.

More information

Section PANEL SIGNAGE

Section PANEL SIGNAGE Section 10 14 23 PANEL SIGNAGE PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including FDOT DIVISION I GENERAL REQUIREMENTS & COVENANTS Specification Sections,

More information

K. ASTM F436- Standard Specification for Hardened Steel Washers; 2011.

K. ASTM F436- Standard Specification for Hardened Steel Washers; 2011. DIVISION 05 METALS 05 12 00 STRUCTURAL STEEL FRAMING PART 1 GENERAL 1.1 SECTION INCLUDES A. Structural steel framing members, support members. 1.2 RELATED REQUIREMENTS A. Section 05 50 00 - Metal Fabrications:

More information

LOG COLLEGE MIDDLE SCHOOL

LOG COLLEGE MIDDLE SCHOOL PART 1-GENERAL 1.1 SUMMARY A. This section includes the following: 1. Curb-mounted plastic glazed skylights. B. Refer to roofing system sections for roofing accessories to be built into the roofing system

More information

SECTION EXTERIOR SUN SHADES

SECTION EXTERIOR SUN SHADES SECTION 10 71 13 EXTERIOR SUN SHADES USE THIS SECTION WHEN SPECIFYING C.R. LAURENCE 7700 SERIES ALUMINUM SUN SHADE SYSTEMS. THE CRL 7700 SERIES SUN SHADE SYSTEM IS A FIXED BAR GRILLE STYLE WITH A TAPERED

More information

SECTION IMPACT RESISTANT WALL PROTECTION

SECTION IMPACT RESISTANT WALL PROTECTION SECTION 10265 PART I - GENERAL 1.01 DESCRIPTION A. Scope: Work under this Section shall include all materials and installation necessary to provide Impact-Resistant Wall Protection including Wall guards,

More information

1. Division 01: Administrative, procedural, and temporary work requirements.

1. Division 01: Administrative, procedural, and temporary work requirements. SECTION 10 2219 DEMOUNTABLE PARTITIONS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Demountable partition system. 2. Doors. 3. Glazed panels. B. Related Sections: 1. Division 01: Administrative,

More information