1 CITY OF TACOMA Public Works Department, Facilities Management Division ADDENDUM NO. 2 DATE: July 18, 2018 REVISIONS TO: Request for Bids Specification No. PW N Point Defiance Senior Center, Roof Replacement NOTICE TO ALL BIDDERS: This addendum is issued to clarify, revise, add to or delete from, the original specification documents for the above project. This addendum, as integrated with the original specification documents, shall form the specification documents. The noted revisions shall take precedence over previously issued specification documents and shall become part of this contract. REVISIONS TO THE SUBMITTAL DEADLINE: The submittal deadline was revised to 11 a.m. Pacific Time, Thursday, July 26 th by Addendum #1 REVISIONS TO THE TECHNICAL SPECIFICATIONS: A following spec sections are removed and replaced with the attached: o Remove Section Thermoplastic Membrane Roofing and replace with Section Thermoplastic and PVC Membrane Roofing REVISIONS TO THE PLANS: The following drawings are removed and replaced with the attached: o Replace Sheet A2 Roof Details SUBSTITUTION REQUEST FORMS: Approved substitution request forms are attached. QUESTIONS AND ANSWERS: Question 1: Answer 1: Is there a noise restriction in place for this neighborhood? This project is located within a residential neighborhood. Construction and demolition activity shall NOT be performed between 9 pm and 7am on weekdays or between the hours of 9pm and 9am on weekends and federal holidays. Refer to Tacoma Municipal Code, Chapter Noise Enforcement for Contractor weekday/weekend work hours and noise. Form No. SPEC-220A Revised: 07/30/2015
2 Question 2: Answer 2: What is the rough building occupancy schedule? The regular schedule is Monday through Friday 9am to 3pm. Occasional classes outside those hours and on Saturdays. NOTE: Acknowledge receipt of this addendum by initialing the corresponding space as indicated on the proposal page. Vendors who have already submitted their bid/proposal may contact the Purchasing Division at and request return of their bid/proposal for acknowledgment and re-submittal. Or, a letter acknowledging receipt of this addendum may be submitted in an envelope marked Request for Bids Specification No. PW N Addendum No. 2. The City reserves the right to reject any and all bids, including, in certain circumstances, for failure to appropriately acknowledge this addendum. cc: Mina Zarelli, Facilities Management Form No. SPEC-220A Revised: 07/30/2015
3 SECTION THERMOPLASTIC AND PVC MEMBRANE ROOFING POINT DEFIANCE/RUSTON SENIOR CENTER SECTION THERMOPLASTIC AND PVC MEMBRANE PART 1 GENERAL 1.1 SECTION INCLUDES A. Adhered system with thermoplastic and PVC roofing membrane. B. Insulation, flat and tapered. C. Vapor retarder. D. Roofing cant strips, stack boots, roofing expansion joints, and walkway pads. 1.2 RELATED REQUIREMENTS A. Section Rough Carpentry: Wood nailers, deck sheathing and curbs. B. Section Roof Accessories: Roof mounted units; prefabricated curbs. C. Section Metal Framed Skylights: Skylight frame, integral curb, and counterflashing. 1.3 REFERENCE STANDARDS A. ASTM C1177/C1177M Standard Specification for Glass Mat Gypsum Substrate for Use as Sheathing; B. ASTM C1289 Standard Specification for Faced Rigid Cellular Polyisocyanurate Thermal Insulation Board; C. ASTM D6878/D6878M Standard Specification for Thermoplastic Polyolefin Based Sheet Roofing; D. ASTM E1980 Standard Practice for Calculating Solar Reflectance Index of Horizontal and Low Sloped Opaque Surfaces; E. NRCA ML104 The NRCA Roofing and Waterproofing Manual; Fifth Edition, with interim updates. F. ASTM D4434/D4434M Standard Specification for Poly (Vinyl Chloride) Sheet Roofing. 1.4 ADMINISTRATIVE REQUIREMENTS A. Preinstallation Meeting: Convene one week before starting work of this section. 1. Review preparation and installation procedures and coordinating and scheduling required with related work. 1.5 SUBMITTALS A. See Section Administrative Requirements, for submittal procedures. B. Product Data: Provide data indicating membrane materials, flashing materials, insulation, vapor retarder, surfacing, and fasteners. C. Sustainable Design Documentation: Test report showing solar reflectance index of membrane. D. Specimen Warranty: For approval. E. Shop Drawings: Indicate joint or termination detail conditions, conditions of interface with other materials, and paver layout. F. Manufacturer's Installation Instructions: Indicate membrane seaming precautions and perimeter conditions requiring special attention Page 1 of 6
4 POINT DEFIANCE/RUSTON SENIOR CENTER SECTION THERMOPLASTIC AND PVC MEMBRANE G. Manufacturer's Certificate: Certify that products meet or exceed specified requirements. H. Warranty: 1. Submit manufacturer warranty and ensure that forms have been completed in Owner's name and registered with manufacturer. 2. Submit installer's certification that installation complies with all warranty conditions for the waterproof membrane. 1.6 QUALITY ASSURANCE A. Perform work in accordance with NRCA ML104 and manufacturer's instructions. B. Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section with minimum three years of documented experience. C. Installer Qualifications: Company specializing in performing the work of this section: 1. Approved by membrane manufacturer. 1.7 DELIVERY, STORAGE, AND HANDLING A. Deliver products in manufacturer's original containers, dry, undamaged, with seals and labels intact. B. Store products in weather protected environment, clear of ground and moisture. C. Protect foam insulation from direct exposure to sunlight. 1.8 FIELD CONDITIONS A. Do not apply roofing membrane during unsuitable weather. B. Do not apply roofing membrane to damp or frozen deck surface or when precipitation is expected or occurring. C. Do not expose materials vulnerable to water or sun damage in quantities greater than can be weatherproofed the same day. 1.9 WARRANTY A. See Section Closeout Submittals, for additional warranty requirements. B. System Warranty: Provide manufacturer's system warranty agreeing to repair or replace roofing that leaks or is damaged due to wind or other natural causes. 1. Warranty Term: 20 years. 2. For repair and replacement include costs of both material and labor in warranty. PART 2 PRODUCTS 2.1 MANUFACTURERS A. Thermoplastic Polyolefin (TPO) Membrane Materials: 1. Carlisle Roofing Systems, Inc; Sure Weld TPO, Reinforced Membrane: syntec.com/sle. 2. Firestone Building Products, LLC; UltraPly TPO XR: 3. Flex Membrane International, TPO Plus: 4. Mule Hide, TPO: 5. Substitutions: See Section Product Requirements Page 2 of 6
5 POINT DEFIANCE/RUSTON SENIOR CENTER SECTION THERMOPLASTIC AND PVC MEMBRANE B. Insulation: 1. Atlas Roofing Corporation: 2. Carlisle SynTec: syntec.com/sle. 3. Versico, a division of Carlisle Construction Materials Inc: 4. Duro Guard ISO: last.com 5. Substitutions: See Section Product Requirements. C. Polyvinyl Chloride (PVC) Membrane Materials: 1. Duro Last, last.com 2. Sika Sarnafil, Sikaplan, ROOFING A. Thermoplastic Membrane Roofing: One ply membrane, fully adhered, over vapor retarder and insulation. B. Roofing Assembly Requirements: 1. Solar Reflectance Index (SRI): 78, minimum, calculated in accordance with ASTM E1980. a. Field applied coating may not be used to achieve specified SRI. 2. Insulation Thermal Value (R), minimum: R 38; provide insulation of thickness required. C. Acceptable Insulation Types Tapered Application: Any type that meets requirements and is approved by membrane manufacturer for application. 1. Uniform thickness polyisocyanurate board covered with tapered polyisocyanurate board. 2.3 ROOFING MEMBRANE AND ASSOCIATED MATERIALS A. Membrane: 1. Material: Thermoplastic polyolefin (TPO) complying with ASTM D6878/D6878M or Polyvinyl Chloride (PVC) complying with ASTM D4434/D4434M. 2. Reinforcing: Internal fabric. 3. Thickness: 60 mil (0.060 inch), minimum. 4. Sheet Width: Factory fabricated into largest sheets possible. 5. SRI Rating: 78, minimum, certified by Cool Roof Rating Council. 6. Color: White. B. Seaming Materials: As recommended by membrane manufacturer. C. Vapor Retarder: Material approved by roof manufacturer complying with requirements of fire rating classification; compatible with roofing and insulation materials. 1. Fire retardant adhesive. D. Flexible Flashing Material: Same material as membrane. 2.4 DECK SHEATHING AND COVER BOARDS A. Deck Sheathing: See Section Rough Carpentry B. Cover Board: Glass mat faced gypsum panels, ASTM C1177/C1177M, fire resistant type, 1/4 inch minimum 5/8 inch maximum thick. 1. Manufacturers: a. Georgia Pacific DensDeck, DensDeck Prime, or DensDeck DuraGuard: Page 3 of 6
6 POINT DEFIANCE/RUSTON SENIOR CENTER SECTION THERMOPLASTIC AND PVC MEMBRANE b. Substitutions: See Section Product Requirements. 2.5 INSULATION A. Polyisocyanurate Board Insulation: Rigid cellular foam, complying with ASTM C1289, Type II, Class 1, cellulose felt or glass fiber mat both faces; Grade 2 and with the following characteristics: 1. Compressive Strength: 20 psi. 2.6 ACCESSORIES A. Stack Boots: Prefabricated flexible boot and collar for pipe stacks through membrane; same material as membrane. B. Cant and Edge Strips: Wood fiberboard, compatible with roofing materials; cants formed to 45 degree angle. C. Insulation Joint Tape: Glass fiber reinforced type as recommended by insulation manufacturer, compatible with roofing materials; 6 inches wide; self adhering. D. Insulation Fasteners: Appropriate for purpose intended and approved by roofing manufacturer. E. Membrane Adhesive: As recommended by membrane manufacturer. F. Surface Conditioner for Adhesives: Compatible with membrane and adhesives. G. Thinners and Cleaners: As recommended by adhesive manufacturer, compatible with membrane. H. Insulation Adhesive: As recommended by insulation manufacturer. I. Sealants: As recommended by membrane manufacturer. J. Walkway Pads: Suitable for maintenance traffic, contrasting color or otherwise visually distinctive from roof membrane. 1. Composition: Asphaltic with mineral granule surface or Roofing membrane manufacturer's standard. 2. Surface Color: White or yellow. PART 3 EXECUTION 3.1 INSTALLATION GENERAL A. Perform work in accordance with NRCA ML104 and manufacturer's instructions. B. Do not apply roofing membrane during unsuitable weather. C. Do not apply roofing membrane when ambient temperature is outside the temperature range recommended by manufacturer. D. Do not apply roofing membrane to damp or frozen deck surface or when precipitation is expected or occurring. E. Do not expose materials vulnerable to water or sun damage in quantities greater than can be weatherproofed the same day Page 4 of 6
7 POINT DEFIANCE/RUSTON SENIOR CENTER SECTION THERMOPLASTIC AND PVC MEMBRANE 3.2 EXAMINATION A. Verify that surfaces and site conditions are ready to receive work. B. Verify deck is supported and secure. C. Verify deck is clean and smooth, flat, free of depressions, waves, or projections, properly sloped and suitable for installation of roof system. D. Verify deck surfaces are dry and free of snow or ice. E. Verify that roof openings, curbs, and penetrations through roof are solidly set, and cant strips are in place. 3.3 WOOD DECK PREPARATION A. Verify flatness and tightness of joints of wood decking. Fill knot holes with latex filler. B. Confirm dry deck by moisture meter with 12 percent moisture maximum. 3.4 VAPOR RETARDER AND INSULATION UNDER MEMBRANE A. Apply vapor retarder to deck surface with adhesive in accordance with manufacturer's instructions. 1. Extend vapor retarder under cant strips and blocking to deck edge. 2. Install flexible flashing from vapor retarder to air seal material of wall construction, lap and seal to provide continuity of the air barrier plane. B. Ensure vapor retarder is clean and dry, continuous, and ready for application of insulation. C. Attachment of Insulation: 1. Mechanically fasten first layer of insulation to deck in accordance with roofing manufacturer's instructions. 2. Embed second layer of insulation into full bed of adhesive in accordance with roofing and insulation manufacturers' instructions. D. Lay subsequent layers of insulation with joints staggered minimum 6 inch from joints of preceding layer. E. Place tapered insulation to the required slope pattern in accordance with manufacturer's instructions. F. Lay boards with edges in moderate contact without forcing. Cut insulation to fit neatly to perimeter blocking and around penetrations through roof. G. Tape joints of insulation in accordance with roofing and insulation manufacturers' instructions. H. At roof drains, use factory tapered boards to slope down to roof drains over a distance of 18 inches. I. Do not apply more insulation than can be covered with membrane in same day Page 5 of 6
8 POINT DEFIANCE/RUSTON SENIOR CENTER SECTION THERMOPLASTIC AND PVC MEMBRANE 3.5 MEMBRANE APPLICATION A. Roll out membrane, free from wrinkles or tears. Place sheet into place without stretching. B. Shingle joints on sloped substrate in direction of drainage. C. Overlap edges and ends and seal seams by contact adhesive, minimum 3 inches. Seal permanently waterproof. Apply uniform bead of sealant to joint edge. D. At intersections with vertical surfaces: 1. Extend membrane over cant strips and up a minimum of 4 inches onto vertical surfaces. 2. Fully adhere flexible flashing over membrane and up to nailing strips. E. Around roof penetrations, seal flanges and flashings with flexible flashing. F. Coordinate installation of roof drains and sumps and related flashings. 3.6 CLEANING A. Remove bituminous markings from finished surfaces. B. In areas where finished surfaces are soiled by work of this section, consult manufacturer of surfaces for cleaning advice and conform to their documented instructions. C. Repair or replace defaced or damaged finishes caused by work of this section. 3.7 PROTECTION A. Protect installed roofing and flashings from construction operations. B. Where traffic must continue over finished roof membrane, protect surfaces using durable materials. END OF SECTION Page 6 of 6
9 CONTINUOUS TAPERED TOP PLATE HIGH DOMED, CAPPED, GASKETED FASTENER 4" TYP. PRE-FINISHED GALVANIZED COPING WITH CONTINUOUS CLEAT AUSTINCINA ARCHITECTS, p.s. SLOPE TO ROOF FOR PARAPETS 24" HIGH OR LESS EXTEND BASE FLASHING MEMBRANE OVER PARAPET, TERMINATING FLASHING PLY AT OUTSIDE EDGE OF PARAPET & EXTENDING DOWN OUTSIDE FACE 2" PAST NAILER Pacific Ave. Suite C Tacoma, Washington P: F: E: architects@austincina.com ROOF CONSTRUCTION: TPO FULLY ADHERED 40 MIL. MEMBRANE PROTECTION BOARD R-38 RIGID INSULATION 1/2" PLYWOOD SHEATHING 12" AT HIGH WALL INSTALL TERMINATION BAR FASTENED AT 8" O.C. WITH SEALANT AT ALL WALL TYPES. USE APPROPRIATE FASTENERS FOR SUBSTRATE. USE DRIVE PINS AT CONCRETE WALLS REGISTERED ARCHITECT MICHAEL CINA STATE OF WASHINGTON 40. MIL TPO 4" CANT STRIP 1/2" PLYWOOD SHEATHING, WEATHER RESISTIVE BARRIER, FIBER CEMENT PANEL, PAINT. TERMINATION BAR FASTENED AT 8" O.C. TERMINATES MIN. 4" ABOVE FINISH ROOF LEVEL COUNTERFLASHING - TYPE AS APPLICABLE. SET INTO CONTINUOUS SEALANT TAPE. FASTEN EVERY PANEL RIB. 5/8" COVER BOARD 2 4 SINGLE PLY MEMBRANE BASE FLASHING EXTEND MIN. 4" ONTO FIELD TAPERED POLYISO INSULATION POLYISO INSULATION POLYISO INSULATION TREATED BUILT-UP 2x NAILERS APPROX. 8" SUBSTRATE BOARD VAPOR RETARDER/TEMP ROOF LAP SEALANT, PER ROOF MEMBRANE MANUFACTURE 40 MIL. TPO POLYISO INSULATION FULLY ADHERED (TAPER) POLYISO INSULATION FULLY ADHERED (FLAT) 5/8" DECK SHEATHING 2 4 TOP OF DECKING VAPOR RETARDER WITH FIRE-RETARDANT ADHESIVE (E) PLYWOOD OR CAR DECKING Z-FLASHING 2 TYPICAL BASE FLASHING NOT TO SCALE VERIFY THICKNESS OF EXISTING SIDING 4" (E) PLYWOOD SIDING (E) RIM JOIST (E) ROOF JOIST 2" 2x CURB, P.T. COVERBOARD EQUIPMENT CURB FLASHING A A SINGLE PLY BASE FLASHING 8" MIN. ADHERED ONTO FIELD. EXTEND UP AND OVER CURB MIN. 2" FASTENED AT 3" O.C. LAP SEALANT, PER ROOF MEMBRANE MANUFACTURE 40 MIL. TPO TERMINATION BAR FASTENED AT 8" O.C. WITH SEALANT SINGLE PLY MEMBRANE FULLY ADHERED TO CURB ROOF DETAILS RE-ROOF Pt. Defiance/Ruston Senior Center 4716 N. Baltimore Street, Tacoma, WA POLYISO INSULATION FULLY ADHERED (TAPER) DECK PER STRUCT. POLYISO INSULATION FULLY ADHERED (FLAT) 1 PARAPET, TYPICAL 24 x 36-6" = 1'-0" 12 x 18-3" = 1'-0" 3 VAPOR RETARDER/TEMP ROOF TYPICAL BASE MECHANICAL CURB NOT TO SCALE Job #: Date: Revs: April 5, 2018 A2 PRELIMINARY
10 Tyler CHase Verified by PDFfiller 07/06/2018 Cadence Construction 5821 S Fletcher St Seattle WA tyler@cadenceconstruction TPO Membrane Flex Membranes 60 mil TPO Product is equal to or better than No Changes needed No No Effect Nearly Identical product, nearly identical specs
11 SUBSTITUTION REQUEST FORM Point Defiance Senior Center, Roof Replacement SPECIFICATION NO.: PW N Page 2
12
13 SUBSTITUTION REQUEST FORM Point Defiance Senior Center, Roof Replacement SPECIFICATION NO.: PW N Page 2
14
15 SUBSTITUTION REQUEST FORM Point Defiance Senior Center, Roof Replacement SPECIFICATION NO.: PW N Page 2
SECTION THERMOPLASTIC MEMBRANE ROOFING PART 1 GENERAL 1.01 SECTION INCLUDES
SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING PART 1 GENERAL 1.01 SECTION INCLUDES A. Mechanically attached system with thermoplastic roofing membrane. B. Insulation, flat and tapered. C. Flashings. D.
More informationSECTION THERMOPLASTIC MEMBRANE ROOFING. C. Flashings. D. Roofing cant strips, stack boots, roofing expansion joints, and walkway pads.
McClellan Blakemore Architects New Warehouse Facility for SECTION 07540 THERMOPLASTIC MEMBRANE ROOFING PART 1 GENERAL 1.01 SECTION INCLUDES A. Adhered system with thermoplastic roofing membrane. B. Insulation,
More informationSECTION ELASTOMERIC MEMBRANE ROOFING
SECTION 07 5300 - PART 1 GENERAL 1.01 SECTION INCLUDES A. Elastomeric roofing membrane, mechanically fastened conventional application. B. Insulation, flat and tapered. C. Flashings. D. Roofing cant strips,
More informationROOFING EPDM ELASTOMERIC SHEET ROOFING FULLY ADHERED- CONVENTIONAL
ROOFING EPDM ELASTOMERIC SHEET ROOFING FULLY ADHERED- CONVENTIONAL PART 1 GENERAL 1.1 SECTION INCLUDES A. Insulation, membrane roofing, base flashings roofing membrane accessories joints, and counter flashings.
More informationWARREN WWTF IMPROVEMENTS ADDENDUM NO. 6
222967.03 WARREN WWTF IMPROVEMENTS NOTICE is hereby given to prospective Bidders of the following information, clarifications, and modifications to the Bidding Documents. The Bidding Documents remain unchanged
More informationSECTION ELASTOMERIC MEMBRANE ROOFING ADDENDUM 10 APRIL 20, 2011
SECTION 07553 ELASTOMERIC MEMBRANE ROOFING ADDENDUM 10 APRIL 20, 2011 PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Elastomeric roofing membrane (EPDM), conventional application at low slope roof
More informationSECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS
SECTION 075423 - THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Division 00 Bidding Requirements and other Division
More informationUniversity of New Hampshire Scholars' Repository
University of New Hampshire University of New Hampshire Scholars' Repository Division 07 Thermal and Moisture Protection Chapter 5 Technical Construction and Renovation Standards 1-25-2013 075423 - TPO
More informationSECTION 07530CP EPDM MEMBRANE ROOFING
PART 1 GENERAL 1.1 SUMMARY SECTION 07530CP EPDM MEMBRANE ROOFING A. Section includes: 1. Adhered membrane roofing and flashing 2. Mechanically fastened roof insulation 3. Walkway pads 1.2 ARCHITECTURAL
More informationROOF REPLACEMENT AND ALTERATIONS TO WOODSTOCK Barrett Architecture, PC WASTE WATER TREATMENT FACILITY - Woodstock, VT February 28, 2019 SECTION
SECTION 075400 PART 1 - GENERAL 1.1 GENERAL PROVISIONS A. Attention is directed to the CONTRACT AND GENERAL CONDITIONS and all Sections within DIVISION 01 - GENERAL REQUIREMENTS which are hereby made a
More informationTHERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Roof areas 1 & 3
PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 07 5423 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Roof areas 1 & 3 A. Tear off existing roof system down to gypsum roof deck and install new Thermoplastic membrane
More informationTHERMOPLASTIC-POLYOLEFIN ROOFING (TPO)
PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 07 5423 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) A. Thermoplastic membrane roofing system, including all components specified. B. Disposal of demolition debris
More informationSECTION MANUFACTURED ROOF EXPANSION JOINTS
SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationRECOMMENDED DESIGN SPECIFICATION
RECOMMENDED DESIGN SPECIFICATION SILICONE COATED SPF ROOFING 1 General 1.1 Section Includes A. Silicone coated SPF roofing system, including substrate board, roof insulation boards, foam insulation materials,
More informationTuscaloosa Police Station
Tuscaloosa Police Station 3801 Trevor S Phillips Ave Tuscaloosa, AL 35401 Core Cut: Spray Foam Roof- ½ thick +- Single Ply Membrane Tapered EPS Insulation 2-6 Metal Deck PART 1 GENERAL 1.1 SCOPE OF WORK
More informationDated 3/28/14 SECTION SINGLE PLY ROOFING
SECTION 0 0-0 0 PART - GENERAL CONTRACT CONDITIONS Work of this Section is bound by the Contract Conditions and Division, bound herewith, in addition to this Specification and accompanying Drawings. EXTENT
More information1. Decks, balconies, and sun porches 2. Walkways, ramps, and stairways 3. Patios and courtyards
SECTION 07185 TRAFFIC MEMBRANE PART 1 GENERAL 1.1 SECTION INCLUDES A. Traffic membrane, consisting of welded seam PVC waterproofing, over f following surfaces: 1. Decks, balconies, and sun porches 2. Walkways,
More informationSECTION 1 - ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING
Project Name: Jefferson City Jaycees Fairgrounds Main Building Roof Replacement Project Site Address: 1445 Fairgrounds Road, Jefferson City, MO 65109 Project Contact: Randy Weaver Project Contact phone
More informationSECTION MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Roof
SECTION 07550 MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Roof This section is based on the products of MFM Building Products Corp., which is located at: 525 Orange St. P. O. Box 340 Coshocton, OH 43812
More informationSECTION PREPARATION FOR RE-ROOFING
SECTION 07 01 50.19 PREPARATION FOR RE-ROOFING SPEC WRITER NOTES: 1. Delete text between // // not applicable to project. Edit remaining text to suit project. 2. Edit Summary article below after establishing
More informationLight-Metal Roof Edge, Raised
NAIL WOOD CANT TO BLOCKING 2 ROWS STAGGERED EACH ROW 24 O.C. 1/2 MIN. 10 0 MAX. FASTEN 18 O.C. WITH NEOPRENE GASKETED FASTENERS 3-1/2 MIN. 4 6 JOINT COVER PLATE SET IN TWO BEADS OF SEALANT 4 MIN. SPECIFIED
More informationSECTION ROOF AND DECK INSULATION
SECTION 07 22 00 ROOF AND DECK INSULATION SPEC WRITER NOTES: 1. Delete text between // // not applicable to project. Edit remaining text to suit project. 2. Follow recommendations of National Roofing Contractors
More informationSECTION SELF-ADHERED WATER-RESISTIVE ROOF UNDERLAYMENT
SECTION 07 30 05.01 SELF-ADHERED WATER-RESISTIVE ROOF UNDERLAYMENT SPEC WRITERS NOTE: This specification includes materials and installation procedures for SlopeShield SA Self-Adhered Water-Resistive Vapor
More informationOREGON CONVENTION CENTER CHILLER PLANT RE-DESIGN CD SET
SECTION 07 54 19 - POLYVINYL-CHLORIDE (PVC) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions and Division
More informationShort Form Guide Specification. Specifying Extruded Polystyrene Roof Insulation- STYROFOAM DECKMATE Plus Tapered
07 22 16.13 Short Form Guide Specification Specifying Extruded Polystyrene Roof Insulation- STYROFOAM DECKMATE Plus Tapered June 2006 SPEC NOTE: This guide specification is intended for use when specifying
More informationArchitectural Roof and Wall Products Guide Specifications
Architectural Roof and Wall Products Guide Specifications Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 FORMED METAL WALL PANELS This Guide Specification
More informationRoof Replacement. Notes: T-1 (Title Sheet) Roof Key Plan Russell House Student Union 1400 Greene Street Columbia, South Carolina 29208
Notes: Drawing Index T-1 Title R-1 Roof Plan - Existing Conditions R-2 Roof Plan - New D-1 Roof Details D-2 Roof Details D-3 Roof Details M-1 Mechanical - Roof Plan M-2 Mechanical - Details Roof Key Plan
More informationGuide Specification for the OSI QUAD Window and Door Flashing System
Henkel Corporation 26235 First Avenue Westlake, OH 1-866-591-2178 www.ositough.com Guide Specification for the OSI QUAD Window and Door Flashing System Specifier Note: The purpose of this guide specification
More informationDIVISION 07 THERMAL AND MOISTURE PROTECTION ROOFING
07 00 00 PART 1 - GENERAL 1.01 DESIGN CRITERIA A. Preferred roofing types include Membrane, Metal, and Composition Shingles. 1. Membrane roofing is preferred for flat roof decks. 2. Use of asphalt-based
More informationA. National Roofing Contractors Association (NRCA) Roofing and Waterproofing Manual
SECTION 07 22 16 - ROOF AND DECK INSULATION Specifier Note: There are numerous types of roof insulation, some which are installed in multiple-layer roof assemblies. Specifier to verify Project requirements
More informationHALIFAX HUMANE SOCIETY BOARDING AND GROOMING FACILITY SECTION STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS
SECTION 075216 - PART 1 - GENERAL 1.1 SUMMARY A. Section includes styrene-butadiene-styrene (SBS) modified bituminous membrane roofing. 1.2 DEFINITIONS A. Hot Roofing Asphalt: Roofing asphalt heated to
More informationSECTION MODIFIED BITUMINOUS SHEET WATERPROOFING
SECTION 07 13 52 MODIFIED BITUMINOUS SHEET WATERPROOFING SPEC WRITER NOTE: Delete text between // // not applicable to project. Edit remaining text to suit project. PART 1 - GENERAL 1.1 SUMMARY A. Section
More informationArchitectural Wall Products Guide Specifications
Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Wall Products Guide Specifications FORMED METAL WALL PANELS This Guide Specification is
More informationArchitectural Roof and Wall Products Guide Specifications
Architectural Roof and Wall Products Guide Specifications 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 FORMED METAL ROOF AND WALL PANELS This Guide Specification is to be used
More informationSECTION ADHERED SINGLE PLY MEMBRANE ROOFING
SECTION 07535 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered EPDM elastic sheet single ply membrane roofing. B. Related Sections: 1. Section 06100 - Carpentry: Wood deck and curbs. 2. Section
More informationJOB # ISSUED: 03/29/2017
SECTION 07 5213 - ATACTIC-POLYPROPYLENE (APP) MODIFIED BITUMINOUS MEMBRANE ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary
More informationWVU DESIGN GUIDELINES & CONSTRUCTION STANDARDS DIVISION 07 THERMAL AND MOISTURE PROTECTION
075000 ROOFING SYSTEMS PART 1 - GENERAL 1.1. Any deviation from the following instructions must be approved during design by WVU Facilities Management Personnel. 1.2. DEFINITIONS A. ASTM American Society
More informationSSL-175. Specifications
SSL-175 Specifications Everlast Metals 10 Enterprise Court Lebanon, PA 17042 Phone: (717) 270-6554 Fax: (717) 270-6569 www.everlastmetals.com 7410 Preformed Metal Roofing PART 1: GENERAL 1.01 SECTION INCLUDES
More informationSILICONE ROOF COATING RESTORATION (RCR) SYSTEM OVER METAL ROOF PANEL
SILICONE ROOF COATING RESTORATION (RCR) SYSTEM OVER METAL ROOF PANEL Part 1. 1.1 Description General Conditions A. Scope of Work Provide all materials, labor and equipment required for the installation
More informationBanyan Air Service November 18, 2011 AVE Aviation and Commerce Center Building 1 Miami, FL
SECTION 07543 - THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationLouis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1
Louis Armstrong New Orleans International Airport NOAB Project # 8910-01233 PART 1 - GENERAL SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS 1.1 RELATED DOCUMENTS A. Drawings and general provisions
More informationG October 2018
G-14-18 October 2018 The information contained in this supplement serves as a criteria for Specifiers and Authorized Applicators regarding the design and installation of Carlisle Roofing Systems and use
More informationSECTION FLUID-APPLIED WATERPROOFING
SECTION 07140 FLUID-APPLIED WATERPROOFING PART 1 GENERAL 1.1 SUMMARY A. Section includes fluid applied rubberized asphalt and/or elastomeric membrane waterproofing; and surface dusting and/or protective
More informationDL-200. Specifications
DL-200 Specifications Everlast Metals 10 Enterprise Court Lebanon, PA 17042 Phone: (717) 270-6554 Fax: (717) 270-6569 www.everlastmetals.com 7410 Structural Preformed Metal Roofing PART 1: GENERAL 1.01
More informationArchitectural Roof Products Guide Specifications
Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Roof Products Guide Specifications FORMED METAL ROOF AND WALL PANELS This Guide Specification
More informationArchitectural Roof Products Guide Specifications
Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Roof Products Guide Specifications FORMED METAL ROOF AND WALL PANELS This Guide Specification
More informationWICOMICO COUNTY BOARD OF EDUCATION
GLEN AVENUE ELEMENTARY SCHOOL RO REPLACEMENT PROJECT NUMBER: PSC #.00.9 SR CURRENT CODES: 05 INTERNATIONAL BUILDING CODE 05 INTERNATIONAL MECHANICAL CODE NATIONAL STANDARD PLUMBING CODE (MBPS) 05 EDITION
More informationC. Counterflashings at roof-mounted mechanical equipment, vent stacks, curbs, and miscellaneous roof penetrations.
ms1505 SECTION 07 60 00 - Page 1 PART 1 GENERAL 1.01 SECTION INCLUDES A. Coping flashing and cleats. B. Counterflashings at roof edge. C. Counterflashings at roof-mounted mechanical equipment, vent stacks,
More informationSECTION BATTEN SEAM COPPER ROOFING
PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 07 61 16 BATTEN SEAM COPPER ROOFING SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. Also delete any other item or paragraph as required
More information1 Exam Prep NRCA Roofing Manual: NRCA Roofing Manual: Membrane Roof Systems 2011 Tabs and Highlights
1 Exam Prep NRCA Roofing Manual: NRCA Roofing Manual: Membrane Roof Systems 2011 Tabs and s These 1 Exam Prep Tabs are based on the National Roofing Contractors Association (NRCA) manual listed below:
More informationSECTION METAL ROOF AND SOFFIT PANELS
Metal Panel Systems, Inc. 11506 Reading Road Cincinnati, Ohio 45241-2512 Telephone: 800-554-6126 or 513-554-6120 Fax: 513-554-6121 www.metalpanelsystems.com info@metalpanelsystems.com Specifications for
More informationSECTION COMMERCIAL CURB-MOUNT ACRYLIC DOUBLE DOME SKYLIGHTS
SECTION 08620 COMMERCIAL CURB-MOUNT ACRYLIC DOUBLE DOME SKYLIGHTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationSILICONE ROOF COATING RESTORATION (RCR) SYSTEM OVER GRAVEL SURFACE BUR
SILICONE ROOF COATING RESTORATION (RCR) SYSTEM OVER GRAVEL SURFACE BUR Part 1. 1.01 Description General Conditions A. Scope of Work Provide all materials, labor and equipment required for the installation
More informationSECTION BUILT-UP BITUMINOUS WATERPROOFING
SECTION 07 12 00 BUILT-UP BITUMINOUS WATERPROOFING SPEC WRITER NOTE: Delete any item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION: This section
More informationSECTION ROOF SPECIALTIES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 71 00 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 07 5323 - ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationE. Section Polymer Modified Cement Waterproofing. K. Section Sub drainage: Foundation perimeter drainage.
DELTA -MS CLEAR Section 07 10 00 Dampproofing and Waterproofing PART 1 GENERAL 1.1 SECTION INCLUDES A. Below grade waterproofing and dampproofing. 1.2 RELATED SECTIONS A. Section 07 11 13 - Bituminous
More informationC. Applicable building codes should always be checked prior to proposing the application to Mule-Hide or the building owner.
1.0 Insulation Guidelines A. The following is a list of generic insulations acceptable for use with Mule-Hide Single Ply Roofing Systems. Requests to use other types of insulation boards are to be made
More informationUpdate In Progress. Division 7 Thermal and Moisture Protection Page Section ROOFING AND WATERPROOFING
Section 07 10 00 ROOFING AND WATERPROOFING Page 07 10 00-1 1. GENERAL REQUIREMENTS A. Indicate applicable American Society for Testing and Materials (ASTM) specification in this section. 01. Fire resistance
More informationG October 2018
G-13-18 VacuSeal TM Vent Secured Roofing Systems October 2018 The information contained in this supplement serves as a criteria for Specifiers and Authorized Applicators regarding the design and installation
More informationACFoam -III Specifications Atlas Roofing
Division 07 Thermal and Moisture Protection Section 07 22 00 Roof and Deck Insulation Section 07 22 16 - Roof Board Insulation PART 1 GENERAL 1.1 SECTION INCLUDES A. HCFC FREE Polyiso Rigid board type
More informationDATE R2.2 ROOF DETAILS - BUILT UP ROOF DETAILS CURBS. An Company PHONE:
A B C D E F G H I J K L M N O P Q R S T U V 5 6 7 8 9 0 5 6 7 8 9 0 5 6 7 8 9 9 GENERAL ROOFING NOTES - VILLAGE POLICE STATION ROOF REPLACEMENT PROJECT - 06 PLANS AND DETAILS - MARCH 0TH, 06. CONTRACTOR
More informationASHLEY AVE. PARKING GARAGE CHILLER TOWER ROOF REPAIRS
NORTH CHILLER TOWER ROOF R-00 COVER SHEET R-0 ROOF PLAN DRAWING INDEX VICINITY MAP SITE MAP ASHLEY AVE. PARKING GARAGE CHILLER TOWER ROOF REPAIRS 58 ASHLEY AVE. CHARLESTON, SC 90 STATE PROJECT NO. H5-D5
More information2002 Advanced Building Products, Inc., P.O. Box 98, Springvale, Maine TEL: ; FAX: ; WEBSITE:
SECTION 07651 FLEXIBLE COPPER SHEET FLASHINGS Advanced Building Products, Inc. manufacturer many types of flexible copper sheet flashings. Due to their ductility, high tensile strength, and resistance
More informationACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO
SECTION 07 53 23 - ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions ofthe Contract, including General and Supplementary Conditions
More informationTGIK.R Roofing Systems, Uplift Resistance. Roofing Systems, Uplift Resistance
1 of 6 5/8/2012 4:19 PM TGIK.R9734 Roofing Systems, Uplift Resistance Page Bottom Roofing Systems, Uplift Resistance See General Information for Roofing Systems, Uplift Resistance KELLY CO-2001 INC 325
More informationSECTION MODIFIED BITUMINOUS SHEET WATERPROOFING
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 13 52 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or paragraph
More informationSOLAR COATING SYSTEMS SYSTEM EMULSION /ACRYLIC. Specification for Built-Up Roofing MULSION/A 1.01 SUMMARY
SOLAR COATING SYSTEMS 2-PLY EMULSION MULSION/A /ACRYLIC SYSTEM Specification for Built-Up Roofing 07590 PART 1. GENERAL 1.01 SUMMARY Name Address City, State, zip A. Furnish and install a seamless, reinforced
More informationArchitectural Roof and Wall Products Guide Specifications
Architectural Roof and Wall Products Guide Specifications 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 FORMED METAL ROOF AND WALL PANELS This Guide Specification is to be used
More informationSECTION CLAY BARREL TILE ROOFING. A. American Society for Testing and Materials (ASTM):
SECTION 07320 CLAY BARREL TILE ROOFING PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 02072 - Removals. 2. 07600 - Flashing and Sheet Metal. 1.02 REFERENCES A. American Society for Testing and Materials
More informationSECTION ROOF MOUNTED ATTIC EXHAUST VENT
SECTION 07 72 00 ROOF MOUNTED ATTIC EXHAUST VENT **This is a CSI Three-Part Specification using CSI MasterFormat 2004-2010 Section Numbers and Titles. This specification must be edited to suit your particular
More informationSECTION SELF-ADHERING SHEET FLASHING
MANUFACTURER S GUIDE SPECIFICATIONS SECTION 076526 SELF-ADHERING SHEET FLASHING 900 Hensley Lane Wylie TX 75098 800-527-7092 www.carlisleccw.com 604129 03.24.15 Carlisle, Flexphalt, Sure-Seal and CAV-GRIP
More informationMIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)
MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590
More informationCITY OF RICHMOND PINE CAMP COMMUNITY CENTER ROOF REPLACEMENT PROJECT RCS PROJECT NO
SECTION 07220 - ROOF INSULATION PART 1 - GENERAL 1.01 DESCRIPTION A. Work included: The Roofing Contractor will provide all polyisocyanurate insulation and high density wood fiber roof insulation (tapered
More informationACFoam-II HCFC Free "Green" Polyiso Specification
ACFoam-II HCFC Free "Green" Polyiso Specification To help owners and specifiers, the following specification strategies are offered as they relate to product performance when including HCFC FREE Green
More informationSECTION MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Seal
SECTION 07550 MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Seal This section is based on the products of MFM Building Products Corp., which is located at: 525 Orange St. P. O. Box 340 Coshocton, OH 43812
More informationSECTION SELF-ADHERING SHEET MEMBRANE WATERPROOFING
SECTION 07 13 26 PART 1 - GENERAL 1.1 SUMMARY A. Scope: 1. Apply waterproofing to: a. Exterior of walls below grade: 1) Waterproofing shall include exterior of walls surrounding elevator pits and sumps.
More informationInsulation. First Revison October DC14 Drainage Mat INSTALLATION GUIDE FOR RESIDENTIAL & COMMERCIAL APPLICATIONS
Insulation First Revison October 2016 DC14 Drainage Mat INSTALLATION GUIDE FOR RESIDENTIAL & COMMERCIAL APPLICATIONS 1. General Information This Guide describes the use of Kingspan GreenGuard DC14 Drainage
More informationSECTION STANDING-SEAM METAL ROOF PANEL
SECTION 074113 -STANDING-SEAM METAL ROOF PANEL PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
More informationCSI-Format Guide Specifications MECHANICALLY-ATTACHED POLYVINYL CHLORIDE ROOFING SECTION
POLYVINYL CHLORIDE ROOFING SECTION 07 54 19.14 PART 1 - GENERAL 1.1 SUMMARY A. This specifies the following mechanically-attached roofing system. 1. Seam-attached single-weld system 1.2 REFERENCES A. Current
More informationE. Section Polymer Modified Cement Waterproofing. K. Section Sub drainage: Foundation perimeter drainage.
DELTA -DRAIN Section 07 10 00 Dampproofing and Waterproofing PART 1 GENERAL 1.1 SECTION INCLUDES A. Below grade drainage sheets. B. Plaza deck and planter drainage sheets. 1.2 RELATED SECTIONS A. Section
More informationSECTION SINGLE-PLY ROOFING SYSTEM
PART 1 - GENERAL 1.01 SCOPE OF WORK A. The Contractor shall furnish all labor, materials, equipment and incidentals required to provide single-ply adhered roofing system. 1.02 COORDINATION A. The Contractor
More informationSPECIFYING EXTRUDED POLYSTYRENE FOR PROTECTED MEMBRANE ROOFING SYSTEM (IRMA)- PMR Short Form Guide Specification
07 22 16.21 Short Form Guide Specification SPECIFYING EXTRUDED POLYSTYRENE FOR PROTECTED MEMBRANE ROOFING SYSTEM (IRMA)- PMR June 2006 SPEC NOTE: This guide specification is intended for use when specifying
More informationGUIDE SPECIFICATIONS SECTION ELASTOMERIC MODIFIED BUILT-UP ROOFING KLB-100 4P I CS ENERGY STAR APPROVED
GUIDE SPECIFICATIONS SECTION 07500 ELASTOMERIC MODIFIED BUILT-UP ROOFING KLB-100 4P I CS ENERGY STAR APPROVED PART 1 GENERAL 1.01 RELATED SECTIONS Section 02050 Demolition Section 06100 Carpentry Section
More informationEverGuard Plaza Deck Roofing For Above-Grade Plaza Deck Applications
EverGuard Plaza Deck Roofing For Above-Grade Plaza Deck Applications Specifications Updated: 12/07 Quality You Can Trust Since 1886... From North America s Largest Roofing Manufacturer PLAZA DECK ROOFING
More informationSECTION A. ACSE 7 Minimum Loads for Buildings and other Structures.
SECTION 06 12 00 STRUCTURAL INSULATED PANELS ------------------------------------------------------------------------------------------------------------ PART 1- GENERAL ----------------------------- 1.1
More informationSECTION (07100) - DAMPPROOFING AND WATERPROOFING
SECTION 07 10 00 (07100) - DAMPPROOFING AND WATERPROOFING PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Sheet Membrane Waterproofing 2. Under-Slab-On-Grade Vapor Barrier B. Related Sections: 1.02
More informationSECTION A. ACSE 7 Minimum Loads for Buildings and other Structures.
SECTION 06 12 00 STRUCTURAL INSULATED PANELS ------------------------------------------------------------------------------------------------------------ PART 1- GENERAL ----------------------------- 1.1
More informationDIVISION 07 - THERMAL & MOISTURE PROTECTION
DIVISION 07 - THERMAL & MOISTURE PROTECTION DESIGN CRITERIA General Design Requirements: 1. When designing roof access ladders and stairways to roof shall not be alternating tread type. 2. Provide 18 gauge
More informationSoCal Dynamic Dome Skylight SECTION UNIT SKYLIGHTS
VELUX SECTION 08 62 00 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Dynamic dome unit skylight with formed curb counterflashing for mounting on site-built or prefabricated roof curbs, for flat, low-slope and
More information(Project Location) (your firm's name)
SECTION 07 21 00 THERMAL INSULATION PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including the Conditions of the Contract and Division 01 Specification Sections
More informationADDENDUM. ADDENDUM NO. 2 October 19, 2017
ADDENDUM ADDENDUM NO. 2 October 19, 2017 As a prospective bidder, note the following revisions to the Contract Documents for the TERMINAL ROOF REPLACEMENT PROJECT at ERIE INTERNATIONAL AIRPORT, TOM RIDGE
More informationTGIK.R Roofing Systems, Uplift Resistance. Roofing Systems, Uplift Resistance
UL TGIK.R9734 Roofing Syst. Uplift Resistance * www.2001company.com * 1.800.537.7663 * Page 1 of 6 Page 1 of 6 Page Bottom TGIK.R9734 Roofing Systems, Uplift Resistance Roofing Systems, Uplift Resistance
More informationOSU PROJECT NO PAGE 1 02 NOV 2006 SECTION METAL ROOF PANELS
OSU PROJECT NO. 30-04-15 PAGE 1 PART 1 GENERAL 1.1 SECTION INCLUDES A. Structural roofing system of preformed steel panels. B. Fastening system. C. Factory finishing. D. Accessories and miscellaneous components.
More informationSDI-1000 Steel Deck - Insulated
modifiedplus SDI-1000 Steel Deck - Insulated SPEC NOTE: This Guide Specification includes materials and methods for the application of an SBS modified bitumen roofing system over an insulated steel deck.
More informationD. Submit three sheet samples, approximately 8 inches x 10 inches, of base sheet and cap sheet.
GUIDE SPECIFICATIONS PART 1 GENERAL SECTION 07500 ELASTOMERIC MODIFIED BUILT-UP ROOFING COLD PROCESS POLYESTER BASE AND SBS CAP SHEET OVER INSULATED DECK CP 80-2MB-I-CS Edit to Suite Project Conditions
More information