1 Whitepaper Cross-Contamination Protection in HVAC I N D U S T R Y I N S I G H T S Norman A. Goldschmidt September 30, 2011 Principal, Engineering

2 I N D U S T R Y I N S I G H T S Genesis periodically publishes white papers and reports about topics of special interest to the industries we serve. As veteran advisors for major corporate infrastructure, energy management, facilities, technology, manufacturing and building systems of every type, our leaders share their perspectives to help both clients and the public at large make high value decisions by having the best available information. All information contained herein is copyrighted and cannot be reproduced without permission. For academic uses, please contact us. Copyright Genesis Engineers All rights reserved - Do not reproduce without written permission. 2

3 Whitepaper Cross-Contamination Protection in HVAC Introduction In order to comply with widely established GMP regulations requiring minimizing the risk of contamination caused by recirculation or re-entry of untreated or insufficiently treated air An evaluation of potential for cross-contamination via HVAC should be part of the risk assessment in multi-product facilities. As outlined in the ISPE Risk MAPP guide, two HEPA filters in series within an air recirculation system (on supply and/or return) can reduce the mass of product in an airstream by an acceptable amount. But this approach is certainly not the only way to achieve an acceptable reduction in airborne contamination. Assuming that the risk potential of the products being processed has been determined, and that the unit operations and engineering controls have been chosen, the mass of a product that could contaminate another product via the HVAC may assessed. By establishing the mass of airborne contaminant product, the reduction in airborne contaminant in the HVAC airstream (due to filtration) and comparing this reduced contaminant mass to the mass of the potentially contaminated product, it is possible to determine the potential concentration per unit dose. Employing the filter efficiency rating (ASHRAE Efficiency %) as an adjustment to the airborne mass of particulate has been proposed as a method to achieve this evaluation; this is generally unsatisfactory as it provides only a rough estimate without the level of assurance desired for these critical calculations. However, by employing a mix of well defined cleanroom testing, Industrial Hygiene and filter classification techniques, it is possible to perform a quantitative assessment of the cross contamination protection, or potential, of an HVAC system - with rigor. Copyright Genesis Engineers All rights reserved - Do not reproduce without written permission. 3

4 Principles The risk for cross-contamination from HVAC exists primarily when a drug product is exposed to the air that has come from a room where a second drug is being processed. This risk is tied to the amount of airborne product emitted by the process and is easily understood for a class of compound on a particular piece of equipment, in a particular room. Assuming that the risk potential of the products (or types of products) being processed has been evaluated; the mass of a product that could contaminate another product via the HVAC may be evaluated by the same method used to evaluate the operator exposure risk: 1. Evaluating the mass or volume of airborne contaminant product in the environment. 2. Evaluating the "protection factor", the reduction in airborne contaminant, afforded by components of the HVAC system. 3. Evaluate the exposure over the potential duration of a batch, accounting for the ventilation parameters within the space. This information alone may be sufficient to evaluate risk, if the quantity of product in the air is sufficiently low. However, a complete analysis would include a further evaluation step: 4. Comparing the contaminant mass to the processed product mass and number of doses to determine potential concentration per unit dose. In the following sections we will discuss the methodology and examples of the protection provided by HVAC components. Methodology The factor of protection from HVAC filtration may be utilized in much the same manner as the protection from Personal Protective Equipment (PPE) is applied to a known airborne contamination level (normally expressed in mcg/m3) to determine if an environment/ppe combination yields and acceptable operator exposure according to the formula: Ambient Concentration mcg/cm 3 x Protection Factor = Exposure mcg/cm 3 The data needed to determine the protection factor from filtration is available from ANSI/ASHRAE standard 52.2 testing performed by filter manufacturers. This standard determines the particle stopping capability of filters by particle size. This method allows for extremely precise assessments where the particle size distribution in an airstream has been characterized. Where empirical data is not available a set of assumptions may be made based upon basic information about common pharmaceutical ingredients in order to arrive at an acceptable approximation. Copyright Genesis Engineers All rights reserved - Do not reproduce without written permission. 4

5 Where only the overall mass of product in an environment is known, the older ANSI/ASHRAE standard test 52.1 or it s Eurovent equivalent can be utilized to effectively understand the mass reduction (and therefore cross-contamination reduction) capability of filters in the HVAC system. In the following examples we demonstrate the effectiveness of this method and the surprising effectiveness of medium efficiency filters at reducing airborne contamination. Example Mass Reduction through Medium Efficiency s Example - Total Mass Reduction from MERV 11 Filtration Size Total Mass units Efficiency Units Mass units 0.1µ 1.0E-01 mcg x % mcg/cm 3 = 8.5E-02 mcg/m 3 0.5µ 1.0E+00 mcg x % mcg/cm 3 = 7.1E-01 mcg/m 3 1.0µ 1.0E+01 mcg x % mcg/cm 3 = 5.1E+00 mcg/m 3 5µ 1.0E+02 mcg x % mcg/cm 3 = 5.9E+00 mcg/m 3 10µ 1.0E+03 mcg x % mcg/cm 3 = 3.3E+01 mcg/m 3 Total 1.11E mcg/m 3 Example - Total Mass Reduction from MERV 13 Filtration Size Total Mass units Efficiency Units Mass units 0.1µ 8.5E-02 mcg x % mcg/cm 3 = 5.5E-02 mcg/m 3 0.5µ 7.1E-01 mcg x % mcg/cm 3 = 2.4E-01 mcg/m 3 1.0µ 5.1E+00 mcg x % mcg/cm 3 = 9.3E-01 mcg/m 3 5µ 5.9E+00 mcg x % mcg/cm 3 = 7.1E-02 mcg/m 3 10µ 3.3E+01 mcg x % mcg/cm 3 = 6.6E-02 mcg/m 3 Total 1.37E+00 mcg/m 3 Example - Total Mass Reduction from MERV 15 Filtration Size Total Mass units Efficiency Units Mass units 0.1µ 1.0E-01 mcg x % mcg/cm 3 = 5.0E-02 mcg/m 3 0.5µ 1.0E+00 mcg x % mcg/cm 3 = 7.5E-02 mcg/m 3 1.0µ 1.0E+01 mcg x % mcg/cm 3 = 2.6E-01 mcg/m 3 5µ 1.0E+02 mcg x % mcg/cm 3 = 5.0E-01 mcg/m 3 10µ 1.0E+03 mcg x % mcg/cm 3 = 1.0E-05 mcg/m 3 Total 1.11E mcg/m 3 This simple analysis shows that a MERV 15 (~95% ASHRAE) filter provides a 3 log reduction in contaminants. More importantly, a MERV 11 (~50% ASHRAE ) gives a 1.5 log (20:1) reduction in airborne contamination. Copyright Genesis Engineers All rights reserved - Do not reproduce without written permission. 5

6 Example Mass Reduction through HEPA s In Series Size Mass units Efficiency Mass units 0.1µ 1.0E-01 mcg/m 3 x % = 1.0E-06 mcg/m 3 0.5µ 1.0E+00 mcg/m 3 x % = 1.0E-04 mcg/m 3 1.0µ 1.0E+01 mcg/m 3 x % = 1.0E-04 mcg/m 3 5µ 1.0E+02 mcg/m 3 x % = 1.0E-04 mcg/m 3 10µ 1.0E+03 mcg/m 3 x % = 1.0E-04 mcg/m 3 Total 1.1E+03 mcg/m 3 4.0E-04 mcg/m 3 Size Array Evaluation Example - Total Mass Reduction from HEPA Filtration Example - Total Mass Reduction from HEPA Filtration Mass units Efficiency Mass units 0.1µ 1.0E-06 mcg/m 3 x % = 1.0E-11 mcg/m 3 0.5µ 1.0E-04 mcg/m 3 x % = 1.0E-08 mcg/m 3 1.0µ 1.0E-04 mcg/m 3 x % = 1.0E-09 mcg/m 3 5µ 1.0E-04 mcg/m 3 x % = 1.0E-10 mcg/m 3 10µ 1.0E-04 mcg/m 3 x % = 1.0E-11 mcg/m 3 Total 4.0E-04 mcg/m E-08 mcg/m 3 Unsurprisingly, two HEPA filters in series yield an 11 log reduction in contamination, reducing airborne contamination from about one milligram per cubic meter to about ten femtograms, far below limits of detection or concern for any material we've encountered. Assuming that the return air is representative of the airborne contamination level (normally expressed in mcg/m3) in the room, as measured or calculated... The first step in the process is to determine the Mixed Air concentration and account for differences between the concentration in the airstream coming from the room where the "contaminant" is being processed and any dilution that may take place prior to introduction into the room "being contaminated". Return Air Concentration mcg/cm 3 x % Return Air in supply = Mixed Air mcg/cm 3 The second step is to determine the protection from HVAC filtration according to the formula: Ambient Concentration mcg/cm 3 x Protection Factor = Exposure mcg/cm 3 Copyright Genesis Engineers All rights reserved - Do not reproduce without written permission. 6

7 The next step in the process is to determine the ventilation rate or airflow of the room "being contaminated". Mixed Air Concentration mcg/cm 3 x Airflow m 3/ hr= Supply Air Product Rate mcg/hr Then the period of exposure in the room "being contaminated" is accounted for as: Supply Air Product Rate mcg/hr x Exposure Duration mcg / hr= Total Product Exposure mcg Next, an adjustment to determine the exposure per unit is applied, assuming uniform and full airborne contribution to the product "being contaminated" according to the formula: Total Product Exposure mcg / Total Units produced = Max. Potential Contamination/unit Finally, sensitivity analysis should be applied by testing assumptions around filter integrity and upset (e.g. spill) cases, to assure that the system is robust and that non-attainment cases are understood, to set process limits. Example Max. Airborne Cross-Contamination Potential Calculation Starting with an airborne contamination (after dual HEPA filtration) of 1,000 mcg/m3 a 100 m 3 room with a ventilation rate of 20 Air Changes per hour might have a maximum airborne cross-contamination potential as follows... Cross Contamination Potential Calculation Room Airflow Calculation Room Vol units Ventilation Rate units Airflow Units 1000 m 3 x 20 AC/hr = 20,000 m 3 /hr Total Airborne Product Calculation Airflow units Airborne Product Concentration units Airborne Product Rate Units 20,000 m3/hr x 1.10E-08 mcg/m 3 = 2.20E-04 mcg/hr Total Airborne Product Available for Cross-Contamination Airborne Product Rate units Exposure Duration units Total ProdUnits 2.20E-04 mcg/hr x 8 hr = 1.76E-03 mcg As this example shows, the total contamination available in our example case is less than 2 picograms over an 8 hour shift. Further dividing this by the number of units produced in an 8 hour period will likely yield an inconsequential mass/unit. Copyright Genesis Engineers All rights reserved - Do not reproduce without written permission. 7

8 Other Factors to Consider While small particles (<10µ) are of interest in worker safety, due to their greater respirability, large (>10µ) particles are of greater interest in the prevention of cross contamination. This focus on large particles is due to: 1. Large particles represent the great preponderance of the mass of particles suspended in the air. 2. Their lower buoyancy (higher settling rate) makes them more likely to contaminate a product by falling out of an airstream as its velocity decreases in a production room (see graph below). 1.00E+00 Settling Velocities cm/s Size µ E E E E E-05 Settling Velocities cm/s The first of these facts is accounted for in our method, which models the mass of the airborne contaminant, not simply the particle count. It would be desirable to apply a reduction factor addressing the second item, accounting for the percentage of available airborne contamination that may be expected to actually settle on critical surfaces and contaminate a dose. However, since the data necessary to support these factors is difficult to obtain and particular to each product, absent the use of computational fluid dynamic models, it is reasonable to neglect this factor and accept the overstatement of potential contamination as a factor of safety. Conclusion The cross-contamination risk inherent in HVAC recirculation can be satisfactorily assessed using readily available information about the product and/or process, the HVAC system configuration and standard component performance information. Using the outlined method we can quantify the maximum cross contamination potential of HVAC system designs providing a rigorous method to assure control of airborne crosscontamination risk. Copyright Genesis Engineers All rights reserved - Do not reproduce without written permission. 8

Whitepaper HVAC Pre-filtration

Whitepaper HVAC Pre-filtration Whitepaper HVAC Pre-filtration In Pharmaceutical Facilities I N D U S T R Y I N S I G H T S Norman A. Goldschmidt September 11, 2011 Principal, Engineering www.geieng.com I N D U S T R Y I N S I G H T

More information

Whitepaper BMS and Process Historian Validation Strategy

Whitepaper BMS and Process Historian Validation Strategy Whitepaper BMS and Process Historian Validation Strategy I N D U S T R Y I N S I G H T S Norman A. Goldschmidt Principal, VP Engineering www.geieng.com I N D U S T R Y I N S I G H T S Genesis periodically

More information

APPLICATIONS Filtration

APPLICATIONS Filtration APPLICATIONS Filtration Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They

More information

STANDARDS FOR COMPOUNDING PHARMACIES

STANDARDS FOR COMPOUNDING PHARMACIES STANDARDS FOR COMPOUNDING PHARMACIES APPLICATION NOTE LC-139 (US) Introduction This publication provides excerpts from some of the many guidelines and standards that pertain to compounding pharmacies.

More information

Indoor Air Quality Solutions

Indoor Air Quality Solutions Indoor Air Quality Solutions Ultimate Solutions for Indoor Air Quality Investigation Demand for quality indoor air continues to increase as we are spending more time indoors than ever before. Indoor air

More information

AIR FILTERS: REAL WORLD PERFORMANCE

AIR FILTERS: REAL WORLD PERFORMANCE AIR FILTERS: REAL WORLD PERFORMANCE B. Dean Arnold Kimberly-Clark Corporation, 1 Holcomb Bridge Road, Roswell, GA 376 ABSTRACT This paper describes the results of studies conducted to investigate the actual

More information

INSPECTOR S OBSERVATIONS AND WARNING LETTER

INSPECTOR S OBSERVATIONS AND WARNING LETTER Microrite, Inc. San Jose, CA, USA, http://www.microrite.com AIR VELOCITY MEASUREMENTS AND CORRELATION TO SMOKE STUDIES FOR ASEPTIC OPERATIONS KEYWORDS Air Velocity, Air Flows, Smoke Study, Air Pattern

More information

THE WORLD LEADER IN CLEAN AIR SOLUTIONS. Indoor Firing Range Clean Air Solutions PARTICULATE AND GASEOUS FILTRATION

THE WORLD LEADER IN CLEAN AIR SOLUTIONS. Indoor Firing Range Clean Air Solutions PARTICULATE AND GASEOUS FILTRATION THE WORLD LEADER IN CLEAN AIR SOLUTIONS Indoor Firing Range Clean Air Solutions PARTICULATE AND GASEOUS FILTRATION AAF Flanders has an in-depth understanding of the filtration challenges for indoor firing

More information

HVAC and Risk Management RACI Meeting 7 th December Agenda. Design. Project Management. Context. Qualification. Construction

HVAC and Risk Management RACI Meeting 7 th December Agenda. Design. Project Management. Context. Qualification. Construction HVAC and Risk Management RACI Meeting 7 th December 2011 Dr Stephen Firmer Asia Pacific Consultants Pty Ltd Agenda Context Project Management Design Construction Qualification Routine Control /Potential

More information

Pleat Filter Media: Working Through the Maze. By Michael Gross. The maze of filtration media continues to be complex. The industry debate about the

Pleat Filter Media: Working Through the Maze. By Michael Gross. The maze of filtration media continues to be complex. The industry debate about the Special to Indoor Environment Connections Pleat Filter Media: Working Through the Maze By Michael Gross The maze of filtration media continues to be complex. The industry debate about the effectiveness

More information

Supplementary Training Modules on Good Manufacturing Practice. Validation. WHO Technical Report Series, No. 937, Annex 4.

Supplementary Training Modules on Good Manufacturing Practice. Validation. WHO Technical Report Series, No. 937, Annex 4. Supplementary Training Modules on Good Manufacturing Practice Validation WHO Technical Report Series, No. 937, 2006. Annex 4. Validation Slide 1 of 48 August 2006 Validation! Part 1. General overview on

More information

HealthWay dfs Technology VS HEPA

HealthWay dfs Technology VS HEPA HealthWay dfs Technology VS HEPA Introduction and Background of HealthWay DFS Technology The HealthWay DFS Air Purification System technology was originally developed through a government grant focused

More information

Filtration Standards and Applications. Arkansas Chapter of ASHRAE December 6 & 7, 2006

Filtration Standards and Applications. Arkansas Chapter of ASHRAE December 6 & 7, 2006 Filtration Standards and Applications Arkansas Chapter of ASHRAE December 6 & 7, 2006 Outline Important Aspects of Particulate Filters Particulate Filter Test Standards Local Codes & Requirements Application

More information

CADMIUM AWARENESS Revision Date: 04/2017

CADMIUM AWARENESS Revision Date: 04/2017 CADMIUM AWARENESS 7.1 PURPOSE 7.1.1 The purpose of this policy is to provide guidelines for safely working with cadmium. It includes provisions for training, PPE guidelines, monitoring, medical surveillance,

More information

Whitepaper. High temperature HEPA filtration. Dr.-Ing. Marc Schmidt, Dr.-Ing. Lothar Gail, Hugo Hemel MSc. Preview

Whitepaper. High temperature HEPA filtration. Dr.-Ing. Marc Schmidt, Dr.-Ing. Lothar Gail, Hugo Hemel MSc. Preview High temperature HEPA filtration Air filtration challenges and answers for dry heat sterilization tunnels Whitepaper Preview Dr.-Ing. Marc Schmidt, Dr.-Ing. Lothar Gail, Hugo Hemel MSc. Air filtration

More information

FDA s Guidance for Industry

FDA s Guidance for Industry Sterile Drug Products Produced by Aseptic Processing - CGMPs Midwest FDC Conference November 4 2005 Susan Bruederle, Investigator FDA / ORA / Central Region Chicago District / Hinsdale IL FDA s Guidance

More information

IAQ & Energy Impact of Exhaust Air Transfer Ratio

IAQ & Energy Impact of Exhaust Air Transfer Ratio This article was published in ASHRAE Journal, November 207. Copyright 207 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission

More information

Compounding Aseptic Isolators (CAI) James T Wagner

Compounding Aseptic Isolators (CAI) James T Wagner Compounding Aseptic Isolators (CAI) James T Wagner jimwagner@cenvironment.com Disclaimer "Although I am a member of the USP Sterile Compounding Expert Committee, I am speaking today in my individual capacity

More information

Baxa Corporation. Technical Paper. Environmental Controls for Sterile Compounding

Baxa Corporation. Technical Paper. Environmental Controls for Sterile Compounding Baxa Corporation Environmental Controls for Sterile Compounding Technical Paper A guidance document on developing sterile preparation areas to meet the USP requirements for low and medium risk compounded

More information

Dynamic. The Dynamic V8 Air Cleaning System: A New Level of Performance and Savings from a New Category of Air Cleaner

Dynamic. The Dynamic V8 Air Cleaning System: A New Level of Performance and Savings from a New Category of Air Cleaner The Dynamic Air Cleaning System: A New Level of Performance and Savings from a New Category of Air Cleaner Dynamic The Dynamic is the new standard in air cleaning outperforming anything on the market in

More information

Environmental Monitoring of Aseptic Processing Areas - 2

Environmental Monitoring of Aseptic Processing Areas - 2 Environmental Monitoring of Aseptic Processing Areas - 2 A war against an invisible enemy DCVMN - Víctor Maqueda - May 30, 31, June 1 2016 1 Active Air Monitoring (Viables) Air Sieve Samplers Draw air

More information

Equipment cleaning and use record

Equipment cleaning and use record DOCUMENTATION Documentation is an essential part of the quality assurance system and, as such, should be related to all aspects of GMP. Its aim is to define the specifications for all materials and the

More information

This document is a preview generated by EVS

This document is a preview generated by EVS INTERNATIONAL STANDARD ISO 16170 First edition 2016-07-01 Corrected version 2017-04 In situ test methods for high efficiency filter systems in industrial facilities Méthodes d essai in situ pour les systèmes

More information

Sterile Compounding elearning Course Curriculum 28 lessons with 33 hours of CE. Fundamentals of Sterile Compounding (8 lessons/8 hours CE)

Sterile Compounding elearning Course Curriculum 28 lessons with 33 hours of CE. Fundamentals of Sterile Compounding (8 lessons/8 hours CE) Sterile Compounding elearning Course Curriculum 28 lessons with 33 hours of CE CriticalPoint s Sterile Compounding elearning curriculum is written by industry experts and covers both Chapter and

More information

http://www.sis.se http://www.sis.se http://www.sis.se http://www.sis.se http://www.sis.se Provläsningsexemplar / Preview SWEDISH STANDARD SS 2680:2004 Approved 2004-10-08 Edition 2 Contamination control

More information

The Basics of HVAC Filters and Savings

The Basics of HVAC Filters and Savings Session: High MERV / HEPA Filtration The Basics of HVAC Filters and Savings John Saams Siemens Government Technologies August 11, 2016 Rhode Island Convention Center Providence, Rhode Island Overview Discussion

More information

QUALITY ASSURANCE & AUDIT

QUALITY ASSURANCE & AUDIT QUALITY ASSURANCE & AUDIT Birinder Kaur Senior Pharmacist Pharmacy Dept National University Of Malaysia Medical Centre Kuala Lumpur birin@ppukm.ukm.edu.my LEARNING OBJECTIVES To define quality assurance

More information

Biocontamination control in pharmaceutical production

Biocontamination control in pharmaceutical production White Paper Data Sheet Biocontamination control in pharmaceutical production and compliance to ISO 14698 with validated active microbial air samplers Tim Sandle, Ph.D., Head of Microbiology at Bio Products

More information

ISO INTERNATIONAL STANDARD. Cleanrooms and associated controlled environments Part 4: Design, construction and start-up

ISO INTERNATIONAL STANDARD. Cleanrooms and associated controlled environments Part 4: Design, construction and start-up INTERNATIONAL STANDARD ISO 14644-4 First edition 2001-04-01 Cleanrooms and associated controlled environments Part 4: Design, construction and start-up Salles propres et environnements maîtrisés apparentés

More information

Performance Improvement Analysis for a Negative-pressurized Biosafety Level Laboratory

Performance Improvement Analysis for a Negative-pressurized Biosafety Level Laboratory Performance Improvement Analysis for a Negative-pressurized Biosafety Level Laboratory F.J. Wang* and J.S. Huang 1 Department of Refrigeration, Air Conditioning and Energy Engineering, National Chin-Yi

More information

APPLICATIONS Air-to-Air Energy Recovery

APPLICATIONS Air-to-Air Energy Recovery APPLICATIONS Air-to-Air Energy Recovery Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application

More information

On behalf of the PHSS Pharmaceutical and Healthcare Sciences Society (UK).

On behalf of the PHSS Pharmaceutical and Healthcare Sciences Society (UK). 31 st March 2015 Submission of comments on ' Concept paper on the revision of annex 1 of the guidelines on good manufacturing practice manufacture of sterile medicinal products EMA/INS/GMP/735037/2014

More information

Environmental Control Requirements. Gordon Farquharson July 2017

Environmental Control Requirements. Gordon Farquharson July 2017 Environmental Control Requirements Gordon Farquharson July 2017 Learning Objectives Learn how contamination control standards and guidance sets requirements for Critical Parameters ISO-14644-1 Classification

More information

THE REVISION OF STANDARD 62: WHAT A DIFFERENCE A DECADE MAKES

THE REVISION OF STANDARD 62: WHAT A DIFFERENCE A DECADE MAKES THE REVISION OF STANDARD 62: WHAT A DIFFERENCE A DECADE MAKES A Persily * National Institute of Standards and Technology, Gaithersburg, MD, USA ABSTRACT The American Society of Heating, Refrigerating and

More information

IAQ benchmarks of air-conditioned offices in Hong Kong

IAQ benchmarks of air-conditioned offices in Hong Kong Indoor Air 2008, 7-22 August 2008, Copenhagen, Denmark - Paper ID: 20 IAQ benchmarks of air-conditioned offices in Hong Kong K.W. Mui *, L.T. Wong ** and P.S. Hui Department of Building Services Engineering,

More information

Why Do I Test, What Do I Test & When Do I Test It? Ross Caputo, PhD Chief Technical Officer Eagle Analytical Services

Why Do I Test, What Do I Test & When Do I Test It? Ross Caputo, PhD Chief Technical Officer Eagle Analytical Services Why Do I Test, What Do I Test & When Do I Test It? Ross Caputo, PhD Chief Technical Officer Eagle Analytical Services Disclosures I, Ross Caputo, declare no conflicts of interest, real or apparent, and

More information

Streamlined Blow-Fill-Seal Insertion Technology Increases Flexibility and Safety in Aseptic Packaging of Pharmaceutical Liquids

Streamlined Blow-Fill-Seal Insertion Technology Increases Flexibility and Safety in Aseptic Packaging of Pharmaceutical Liquids Streamlined Blow-Fill-Seal Insertion Technology Increases Flexibility and Safety in Aseptic Packaging of Pharmaceutical Liquids Isolators adapted specifically for blow-fill-seal insertion applications

More information

Standard Operating Procedures for Servicing Laboratory Exhaust Systems

Standard Operating Procedures for Servicing Laboratory Exhaust Systems Standard Operating Procedures for Servicing Laboratory Exhaust Systems Policy Statement The following procedures were developed to protect Facilities & Services (F&S) personnel and University laboratory

More information

DFE. Dynamic Filter Efficiency. hyprofiltration.com/dfe

DFE. Dynamic Filter Efficiency. hyprofiltration.com/dfe DFE Dynamic Filter Efficiency What is DFE? DFE matches filter testing with real-life conditions All hydraulic and lube systems have a critical contamination tolerance level that is often defined by, but

More information

Joint Committee Issue Paper

Joint Committee Issue Paper NSF Standard(s) Impacted: Background: Provide a brief background statement indicating the cause and nature of concern, the impacts identified relevant to public health, public understanding, etc, and any

More information

SUPPLEMENTARY GUIDELINES ON GOOD MANUFACTURING PRACTICES (GMP): VALIDATION

SUPPLEMENTARY GUIDELINES ON GOOD MANUFACTURING PRACTICES (GMP): VALIDATION Pharmapathway.com SUPPLEMENTARY GUIDELINES ON GOOD MANUFACTURING PRACTICES (GMP): VALIDATION Page 1 of 43 1. INTRODUCTION Validation is an essential and integral part of Good Manufacturing Practice (GMP).

More information

Where Quality Meets Flexibility

Where Quality Meets Flexibility Where Quality Meets Flexibility is an industry leading 503B Outsourcing Facility providing sterile and non-sterile compounding services to hospitals, surgery centers, clinics, researchers & patients nationwide.

More information

DISPLACEMENT VENTILATION

DISPLACEMENT VENTILATION DISPLACEMENT VENTILATION D3 OVERVIEW The fundamental approach to displacement ventilation utilizes the natural buoyancy forces created by the convective flows from heat sources in the space. As supply

More information

DuPont Tyvek delivers trusted protection for pharmaceutical products

DuPont Tyvek delivers trusted protection for pharmaceutical products DuPont Tyvek delivers trusted protection for pharmaceutical products Protect your products and processes with DuPont Tyvek For the past 40 years, DuPont Tyvek has been helping to protect the health of

More information

PhEn-602 Notes # 4 J. Manfredi

PhEn-602 Notes # 4 J. Manfredi PhEn-602 Notes # 4 J. Manfredi Spring 2009 1 Basic definitions Clean Room: A room in which the concentration of airborne particles is controlled and contains one or more clean zones Clean Zone: A defined

More information

The New EPA National Emission Standard for Hazardous Air Pollutants (NESHAP), Rule 6X: Are You Compliant?

The New EPA National Emission Standard for Hazardous Air Pollutants (NESHAP), Rule 6X: Are You Compliant? WHITE PAPER The New EPA National Emission Standard for Hazardous Air Pollutants (NESHAP), Rule 6X: Are You Compliant? For years, many companies involved in welding and other metalworking operations have

More information

IMPACT OF THE SEMCO ANTI-STICK FACE COATING ON THE COLLECTION AND CLEANING OF ENVIRONMENTAL TOBACCO SMOKE FROM THE WHEEL SURFACE RESEARCH FINDINGS

IMPACT OF THE SEMCO ANTI-STICK FACE COATING ON THE COLLECTION AND CLEANING OF ENVIRONMENTAL TOBACCO SMOKE FROM THE WHEEL SURFACE RESEARCH FINDINGS AIR QUALITY ANTI-STICK EFFICIENT IMPACT OF THE SEMCO ANTI-STICK FACE COATING ON THE COLLECTION AND CLEANING OF ENVIRONMENTAL TOBACCO SMOKE FROM THE WHEEL SURFACE 2 ANTI-STICK WHEEL FACE COATING Impact

More information

C-Air Filtration Carbon Filter Range

C-Air Filtration Carbon Filter Range C-Air Filtration Carbon Filter Range Carbon filters are ideal for removing unpleasant or even dangerous odours and gases from a wide variety of places. The awareness of this problem from public health

More information

ASHRAE s. Indoor Air Quality Procedure. in Ventilation Design

ASHRAE s. Indoor Air Quality Procedure. in Ventilation Design Elliott Horner, PhD UL Environment elliott.horner@ul.com M: 678-249-8856 ASHRAE s Indoor Air Quality Procedure Jim Dennison, CIH, PhD Century Environmental Hygiene jim@centuryenvironmental.com O: 970-266-8000

More information

CONSTRUCTION INDUSTRY SAFETY COALITION

CONSTRUCTION INDUSTRY SAFETY COALITION CONSTRUCTION INDUSTRY SAFETY COALITION History of the Silica Standard Procedural Background Publication of Final Rule Obligations under the Standard. (k) Dates. (1) This section shall become effective

More information

ACCESS CONTROL AND WORK AREA SETUP RCT STUDY GUIDE State responsibilities in using or initiating a RWP.

ACCESS CONTROL AND WORK AREA SETUP RCT STUDY GUIDE State responsibilities in using or initiating a RWP. LEARNING OBJECTIVES: 2.10.01 State the purpose of and information found on a Radiological Work Permit (RWP) including the different classifications at your site. 2.10.02 State responsibilities in using

More information

A NUSAGE-PharmEng Pharmaceutical and Biotechnology Training Program

A NUSAGE-PharmEng Pharmaceutical and Biotechnology Training Program A NUSAGE-PharmEng Pharmaceutical and Biotechnology Training Program Shaping Human Capital for Challenges in the Pharmaceutical Industry CLEANROOM DESIGN FOR ASEPTIC PROCESSING Instructor Loh Kean Chong

More information

Heating, ventilation, and air system encompasses heating, ventilation, and air conditioning, which is integral component of

Heating, ventilation, and air system encompasses heating, ventilation, and air conditioning, which is integral component of REVIEW ARTICLE Demand of pharmaceutical facility functionality: Validation and qualification of HVAC system Anamika Singh, Sapna Malviya, Anil Kharia Department of Quality Assurance of Modern Institute

More information

Indoor Air Quality through Design

Indoor Air Quality through Design Indoor Air Quality through Design Kate Goldstein Editor Werner Lang Aurora McClain csd Center for Sustainable Development I-Context Comfort 2 1.7 Indoor Air Quality through Design Indoor Air Quality through

More information

MEP's Letter of Assurance

MEP's Letter of Assurance MEP's Letter of Assurance Instructions WELL Certification is determined by onsite Performance Verification and documentation, including Letters of Assurance from the appropriate professionals overseeing

More information

This document is a preview generated by EVS

This document is a preview generated by EVS INTERNATIONAL STANDARD ISO 16890-2 First edition 2016-12-01 Air filters for general ventilation Part 2: Measurement of fractional efficiency and air flow resistance Filtres à air de ventilation générale

More information

Dynamic Reset for Multiple-Zone Systems

Dynamic Reset for Multiple-Zone Systems This article was published in ASHRAE Journal, March 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be

More information

OSHA S RULE ON CRYSTALLINE SILICA: TRAINING ON WHAT YOU NEED TO KNOW

OSHA S RULE ON CRYSTALLINE SILICA: TRAINING ON WHAT YOU NEED TO KNOW OSHA S RULE ON CRYSTALLINE SILICA: TRAINING ON WHAT YOU NEED TO KNOW Bradford T. Hammock, Jackson Lewis P.C. OVERVIEW Health Effects of Silica Exposure Controls and PPE Requirements Written Exposure Control

More information

Particle Sample Tube Lengths for Pharmaceutical Monitoring. Version 01. Rev 01.

Particle Sample Tube Lengths for Pharmaceutical Monitoring. Version 01. Rev 01. T E C H N I C A L P A P E R Particle Sample Tube Lengths for Pharmaceutical Monitoring Version 01. Rev 01. Particle Sample Tube Lengths for Pharmaceutical Monitoring Lighthouse Worldwide Solutions Airborne

More information

WHO DRAFT PHARMACEUTICAL DEVELOPMENT FOR MULTISOURCE (GENERIC) PHARMACEUTICAL PRODUCTS

WHO DRAFT PHARMACEUTICAL DEVELOPMENT FOR MULTISOURCE (GENERIC) PHARMACEUTICAL PRODUCTS 23 April 2008 Quality Assurance Programme Quality Assurance and Safety: Medicines (QSM) Department of Medicines Policy and Standards (PSM) World Health Organization CH-1211 Geneva 27 Switzerland WHO DRAFT

More information

FILTER EFFICIENCY OF SELECTED HVAC FILTERS

FILTER EFFICIENCY OF SELECTED HVAC FILTERS FILTER EFFICIENCY OF SELECTED HVAC FILTERS ES Moyer *, MA Commodore, J Hayes, and SA Fotta National Institute for Occupational Safety and Health, Division of Respiratory Disease Studies, Laboratory Research

More information

Indoor Air Quality (IAQ) Requirements

Indoor Air Quality (IAQ) Requirements University of New Hampshire University of New Hampshire Scholars' Repository Division 01 General Requirements Chapter 5 Technical Construction and Renovation Standards 1-25-2013 013560 - Indoor Air Quality

More information

Tasks estimated to generate a TWA of 50 micrograms per cubic meter of air include:

Tasks estimated to generate a TWA of 50 micrograms per cubic meter of air include: Lead Exposure Compliance Program for Construction The purpose of this program is to inform interested persons, including employees, that Prairie Construction is complying with the OSHA Lead Standard, Title

More information

Sterile Compounding elearning Course Curriculum 28 lessons with 33 hours of CE. Fundamentals of Sterile Compounding (8 lessons/8 hours CE)

Sterile Compounding elearning Course Curriculum 28 lessons with 33 hours of CE. Fundamentals of Sterile Compounding (8 lessons/8 hours CE) Sterile Compounding elearning Course Curriculum 28 lessons with 33 hours of CE Fundamentals of Sterile Compounding (8 lessons/8 hours CE) The History of Compounding and USP Sterile Compounding Chapters

More information

U.S. INDOOR AIR QUALITY MARKET

U.S. INDOOR AIR QUALITY MARKET U.S. INDOOR AIR QUALITY MARKET ENV003D July 2012 Andrew McWilliams Project Analyst ISBN: 0-89336-058-9 BCC Research 49 Walnut Park, Building 2 Wellesley, MA 02481 Phone: 866-285-7215 (sales) Web Address:

More information

Control Banding. Presentation in HKIOEH Conference TW TSIN 14 th April 2007

Control Banding. Presentation in HKIOEH Conference TW TSIN 14 th April 2007 Control Banding Presentation in HKIOEH Conference 2007 TW TSIN 14 th April 2007 1 Outline of presentation Background a scenario Concept of control banding Putting into operation Applications Looking forward

More information

Copyright 2004 The Pharmaceutical & Healthcare Sciences Society

Copyright 2004 The Pharmaceutical & Healthcare Sciences Society Whyte, W., and Eaton, T. (2004) Microbiological contamination models for use in risk assessment during pharmaceutical production.european Journal of Parenteral and Pharmaceutical Sciences, 9 (1). pp. 11-15.

More information

Microbiological Consideration for Non-Sterile Pharmaceutical

Microbiological Consideration for Non-Sterile Pharmaceutical May 1-3, 2012 Javits Center New York, NY Microbiological Consideration for Non-Sterile Pharmaceutical Dr. Leonard W. Mestrandrea Principal Consultant MESTRANDREA CONSULTING LLC Title Date Microbial Control

More information

MODELING THE SPREAD OF ANTHRAX IN BUILDINGS

MODELING THE SPREAD OF ANTHRAX IN BUILDINGS MODELING THE SPREAD OF ANTHRAX IN BUILDINGS RG Sextro *, DM Lorenzetti, MD Sohn, and TL Thatcher Indoor Environment Dept., Lawrence Berkeley National Lab, Berkeley, CA, USA ABSTRACT The recent contamination

More information

Field Accuracy of Temperature Measurements in TAB Work Andrew P. Nolfo, PE

Field Accuracy of Temperature Measurements in TAB Work Andrew P. Nolfo, PE Field Accuracy of Temperature Measurements in TAB Work Andrew P. Nolfo, PE The purpose of this article is to discuss the measuring and reporting of temperatures at heat transfer equipment during the Testing

More information

Pharmaceutical Industry s Approach to Safe Handling of New Molecular Entities

Pharmaceutical Industry s Approach to Safe Handling of New Molecular Entities Pharmaceutical Industry s Approach to Safe Handling of New Molecular Entities Donna S. Heidel, CIH The findings and conclusions in this presentation have not been formally disseminated by the National

More information

Guidelines for Collecting Qualitative Environmental Samples of Anthrax

Guidelines for Collecting Qualitative Environmental Samples of Anthrax Guidelines for Collecting Qualitative Environmental Samples of Anthrax Adapted from Centers for Disease Control Procedures for Collecting Environmental Samples of Anthrax (October 23, 2001 draft) Maryland

More information

LEAD HAZARD CONTROL PROGRAM

LEAD HAZARD CONTROL PROGRAM LEAD HAZARD CONTROL PROGRAM Supervisor s Manual Prepared by Environmental Health and Safety Services Occupational Safety Programs GLOSSARY Abatement or Deleading CFR Control Measure Encapsulation EPA HEPA

More information

AIR QUALITY ASSESSMENT FOR TAYLOR STANLEY MARKETING PTE LTD 71, TANNERY LANE #-7-07, CITY INDUSTRIAL BUILDING SINGAPORE

AIR QUALITY ASSESSMENT FOR TAYLOR STANLEY MARKETING PTE LTD 71, TANNERY LANE #-7-07, CITY INDUSTRIAL BUILDING SINGAPORE Our Ref: ATS/IH/84/05KKL Date: 26 August, 2005 Page 1 of 33 AIR QUALITY ASSESSMENT FOR TAYLOR STANLEY MARKETING PTE LTD 71, TANNERY LANE #-7-07, CITY INDUSTRIAL BUILDING SINGAPORE 347807 Date of Survey

More information

PART 30: LABORATORIES

PART 30: LABORATORIES PART 30: LABORATORIES GENERAL REQUIREMENTS Definitions 30.7.1 In sections 30.8 to 30.11: laboratory fume hood operational face opening sash Laboratory fume hoods means an enclosed and mechanically ventilated

More information

UNDER SECRETARY FOR HEALTH S INFORMATION LETTER MICROBIOLOGICAL ASSESSMENT OF PHARMACEUTICAL CLEANROOMS

UNDER SECRETARY FOR HEALTH S INFORMATION LETTER MICROBIOLOGICAL ASSESSMENT OF PHARMACEUTICAL CLEANROOMS DEPARTMENT OF VETERANS AFFAIRS Veterans Health Administration Washington DC 20420 IL 10-2006-008 In Reply Refer To: 10NB UNDER SECRETARY FOR HEALTH S INFORMATION LETTER MICROBIOLOGICAL ASSESSMENT OF PHARMACEUTICAL

More information

AIR HYGIENE TEST SUITABLE FOR ALLERGIC PEOPLE

AIR HYGIENE TEST SUITABLE FOR ALLERGIC PEOPLE Scope of Test and Assessment Criteria for the Issue of the TÜV NORD Test Mark INDOOR AIR HYGIENE TEST SUITABLE FOR ALLERGIC PEOPLE for Indoor Air Purifiers (as at 08/13) I General The aim of these tests,

More information

Asbestos in the Workplace: A Guide to Removal of Friable Asbestos Containing Materials

Asbestos in the Workplace: A Guide to Removal of Friable Asbestos Containing Materials Asbestos in the Workplace: A Guide to Removal of Friable Asbestos Containing Materials Revised November 21, 2013 Application Code of Practice Where asbestos is present or believed to be present in a workplace

More information

John F. Koerner, MPH, CIH

John F. Koerner, MPH, CIH Critical Elements of Containment and Ventilation Practice for Healthcare Microbial Remediation John F. Koerner, MPH, CIH Vice President, Environmental Sciences Compliance Environmental International, Inc.

More information

BIOTRAK REAL-TIME VIABLE PARTICLE COUNTER ROOT CAUSE INVESTIGATION GUIDANCE

BIOTRAK REAL-TIME VIABLE PARTICLE COUNTER ROOT CAUSE INVESTIGATION GUIDANCE BIOTRAK REAL-TIME VIABLE PARTICLE COUNTER ROOT CAUSE INVESTIGATION GUIDANCE APPLICATION NOTE CC-123 (US) Introduction This guidance provides recommendations for how the BioTrak Real-Time Viable Particle

More information

Chilled Beams Selection BY DAN INT-HOUT, FELLOW ASHRAE; AND LILLI WILBAR

Chilled Beams Selection BY DAN INT-HOUT, FELLOW ASHRAE; AND LILLI WILBAR This article was published in ASHRAE Journal, November 2014. Copyright 2014 ASHRAE. Reprinted here by permission from ASHRAE at www.krueger-hvac.com This article may not be copied nor distributed in either

More information

Airborne Particle Detection

Airborne Particle Detection Airborne Particle Detection Detects airborne particles from 0.3 to 5 µm Monitor 6 particle sizes simultaneously Choose from two models: Pro for normal environments CR for cleanrooms and clean areas Data

More information

Metrology & Clean Room Technology (A complete practical course)

Metrology & Clean Room Technology (A complete practical course) Metrology & Clean Room Technology (A complete practical course) In commemoration of world metrology day 2018 with the theme Constant evolution of the International System of Units, the academy of the International

More information

Cleaning validation of cleanrooms and preparation equipments

Cleaning validation of cleanrooms and preparation equipments Cleaning validation of cleanrooms and preparation equipments Dr Farshid SADEGHIPOUR Head of production Central Pharmacy, Geneva University Hospitals EAHP Foundation Seminar: Patient Safety; More About

More information

SECTION INDOOR AIR QUALITY MANAGEMENT PLAN. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION INDOOR AIR QUALITY MANAGEMENT PLAN. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. SECTION 018119 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting

More information

MEP's Letter of Assurance

MEP's Letter of Assurance MEP's Letter of Assurance Instructions Multifamily Residential WELL Certification is determined by onsite Performance Verification and documentation, including Letters of Assurance from the appropriate

More information

Local Exhaust Ventilation

Local Exhaust Ventilation Local Exhaust Ventilation University of Tennessee Safety Guide IH-001 Document Contact: EHS Date effective: August 1, 2014 Revision Date: July 1, 2016 Purpose The purpose of this document is to provide

More information

ISO INTERNATIONAL STANDARD. Hydraulic fluid power On-line automatic particle-counting systems for liquids Methods of calibration and validation

ISO INTERNATIONAL STANDARD. Hydraulic fluid power On-line automatic particle-counting systems for liquids Methods of calibration and validation INTERNATIONAL STANDARD ISO 11943 First edition 1999-08-01 Hydraulic fluid power On-line automatic particle-counting systems for liquids Methods of calibration and validation Transmissions hydrauliques

More information

MEP's Letter of Assurance

MEP's Letter of Assurance MEP's Letter of Assurance Instructions Educational Facilities WELL Certification is determined by onsite Performance Verification and documentation, including Letters of Assurance from the appropriate

More information

1.0 Purpose, Applicability, and Scope

1.0 Purpose, Applicability, and Scope Policy Subject: Local Exhaust Ventilation Policy Effective: 8/1/2014 Affected Area/Department: All Departments who use Local Exhaust Ventilation Systems Reviewed/Revised: 8/1/2014 1.0 Purpose, Applicability,

More information

SMART LABS. Reduce Energy Consumption, Improve Lab Safety, and Lower Deferred Maintenance

SMART LABS. Reduce Energy Consumption, Improve Lab Safety, and Lower Deferred Maintenance SMART LABS Reduce Energy Consumption, Improve Lab Safety, and Lower Deferred Maintenance From 1999 to 2016 The Georgia Institute of Technology constructed six laboratory buildings in its Bio- Quad region

More information

FZ LABORATORY SERVICES

FZ LABORATORY SERVICES FZ LABORATORY SERVICES For those working in biological product manufacturing/aseptic process filling: you can greatly benefit from support by Franz Ziel GmbH (FZ) with many years experience in scientific

More information

Achieving IAQ & Energy Conservation Goals with ASHRAE Requirements, Applications and Case Studies

Achieving IAQ & Energy Conservation Goals with ASHRAE Requirements, Applications and Case Studies Achieving IAQ & Energy Conservation Goals with ASHRAE 62.1-2004 Requirements, Applications and Case Studies Mr.Chris Muller - ASHRAE Distinguished Lecturer ASHRAE Standing Standard Project Committee 62.1

More information

Designed for Storage of Noxious and Odorous Evidence

Designed for Storage of Noxious and Odorous Evidence Designed for Storage of Noxious and Odorous Evidence Storage cabinets for storage of hazardous chemicals and other substances. Mini Safestore Provides Environmentally Safe Processing and Storage of Evidence

More information

Indoor Air Quality Assessments during Renovations at Waverly Elementary School Project #J (January 4, 12, 15, 25 and 29, 2018)

Indoor Air Quality Assessments during Renovations at Waverly Elementary School Project #J (January 4, 12, 15, 25 and 29, 2018) March 29, 2018 Mr. Jeff Klenk Howard County Public School System (HCPSS) 10910 Route 108 Ellicott City, MD 21043 RE: Indoor Air Quality Assessments during Renovations at Waverly Elementary School Project

More information

LEED Best Practices Save $$$

LEED Best Practices Save $$$ 16 Savings result where LEED has been applied to improve IAQ! LEED Best Practices Save $$$ A growing body of green building case studies document the benefits of healthy IAQ in the workplace Learn More

More information

Dr. Sheelpriya walde Professor Gurunanak college of pharmacy, Nagpur

Dr. Sheelpriya walde Professor Gurunanak college of pharmacy, Nagpur Dr. Sheelpriya walde Professor Gurunanak college of pharmacy, Nagpur GMP ( Adopted in 1975 ) In India Good manufacturing practices are the practices required in order to conform to guidelines recommended

More information

Meteorological and Air Dispersion Modeling Methodology and Discussion for INPRO Project

Meteorological and Air Dispersion Modeling Methodology and Discussion for INPRO Project Meteorological and Air Dispersion Modeling Methodology and Discussion for INPRO Project Introduction The transport and dilution of radioactive materials in the form of aerosols, vapors, or gases released

More information

Chapter 14 Indoor Air Quality

Chapter 14 Indoor Air Quality Chapter 14 Indoor Air Quality 1 Indoor Environment and Built Environment Buildings Transportations vehicles 2 1 Indoor Air Quality (IAQ) Indoor air quality (IAQ) is the quality of air in an indoor environment.

More information

PHCT 401 Aseptic Processes & Techniques

PHCT 401 Aseptic Processes & Techniques PHCT 401 Aseptic Processes & Techniques Principles of Aseptic Techniques Aseptic Processing Sterility Testing Laminar flow air cleaning Quality Control Tests Personnel Principles of Aseptic Techniques

More information