1 Designing Efficient Sub Slab Collection and Vapor Barrier Systems Presented By: Tom Hatton Clean Vapor, LLC cleanvapor.com 1

2 Effective and Efficient Vent Systems Start in the Planning Phase What is the history of contaminants in the soil? Phase I and Phase II Site Assessment Test On Site Buildings when Possible

3 Is There a Potential For Vapor Intrusion? Organic Vapors can travel 100 Feet Laterally and Vertically

4 Requirements for an Efficient Sub Slab Vent System Permeable sub slab material All under slab ground contact areas connected to a Soil Gas Conveyance Plenum Properly sized and streamlined under slab and riser piping A gas tight Vapor Barrier 4

5 Pressure Field Extension Sand Short pressure field extension Crushed Stone Increased pressure field extension Test fan Test holes 5

6 Permeable Sub Slab Support Material Proof Rolled Ground 8 ASSHTO #57 stone 4 free air flow Slab Cracking Slab Support 6

7 There Should be No Isolated Sub Slab Areas The collection system must be inclusive to the entire sub slab area within the occupancy envelope No isolated gravel beds Look for: Thickened slabs Grade changes 7

8 Sub Slab Piping Plumbing T fittings Standard vs. Chamfered Extensions Perforated Pipe Frequency of Drain Holes 8

9 Effective Soil Gas Collection Plenum Under slab piping should connect to a centrally located plenum box Larger diameter pipe with minimal fittings vents the plenum box to above the roof 9

10 GeoVent Highly efficient under slab plenum material Airflow properties similar to 4 PVC Most efficient when applied over crushed stone 10

11 GeoVent can be Used with under slab collection piping Installed for a fraction of the labor cost Lead to big savings 11

12 12

13 Plenum Box Construction 13

14 Riser Pipes are Grouped for future pairing and efficient construction 14

15 Sizing Collection Pipes A function of service area and friction loss Pipe Diameter Service Area in Square Feet 3 1, , ,000 15

16 What Pipe Diameter Should be Specified? 16

17 Pressure Drop Pipe Diameter Per 100 of PVC Pipe at 100 CFM Pipe Diameter Straight Pipe Resistance Per 100 of PVC Pipe at 100 CFM 6 90 elbow elbow elbow NOTE: units in inches of water column 17

18 Soil Gas Probes Embedded prior to vapor barrier installation Drilling Holes in slab will: Void Liquid Boot Warrantee Risk Damaging sub slab utilities 18

19 Disadvantage to Conventional Barriers Mostly unsealed Only partially effective at preventing soil gas entry 19

20 Why Choose Liquid Boot? Near gas tight seal over: Crushed stone Collection plenum Unlike conventional barrier, it doesn t leak at Wall joints Column pads Utility penetrations 20

21 21

22 Comparing Two Schools North Jersey School Standard Vapor Barrier and Vent System vs. Georgia School Liquid Boot Clean Vapor Vent System 38,000 ft 2 3 Story 24,000 ft 2 3 Story 22

23 4 crushed stone Original Design Schedule 80 sub slab piping Standard 3 plumbing Ts Many isolated areas Standard Polyethylene Vapor Barrier 39 vertical 3 risers North Jersey School watt roof mounted blowers Method of measuring pressure field extension Micromanometer, Drilling holes through slab and vapor barrier 23

24 4 crushed stone North Jersey School Schedule 80 sub slab piping Standard 3 plumbing Ts Amended Design Schedule 40 sub slab piping 4 chamfered Ts Many isolated areas No isolated areas Standard Polyethylene Vapor Barrier 39 vertical 3 risers 14 vertical 4 risers 14 - RP watt roof mounted blowers watt roof mounted blowers Method of measuring pressure field extension Micromanometer, Drilling holes through slab and vapor barrier 24

25 25

26 4 Road Bed Georgia School 3-24 diameter pipes w/ 3/8 holes 1 ¼ inches O.C. Schedule 40 sub slab piping Some isolated areas Liquid Boot system 3 vertical 6 risers Original Design watt roof mounted blowers Method of measuring pressure field extension: Micromanometer, Drilling holes through slab and barrier 26

27 Georgia School Amended Design 4 Road Bed 6 AASHTO #57 stone 3-24 diameter pipes w/ 3/8 holes 1 ¼ inches O.C. 3 collection plenums w/ collection pipe Schedule 40 sub slab piping Some isolated areas No isolated areas Liquid Boot system 1 - vertical 6 riser 3 vertical 6 risers watt roof mounted blower watt roof mounted blowers Method of measuring pressure field extension: Micromanometer, Drilling holes through slab and barrier Embedded Probes 27

28 28

29 24,000 ft 2 Depressurized with a Single 125 watt Blower

30 With Liquid Boot and an Efficient Sub Slab Collection System Design Vacuum distribution can be consistent and effective Suction Device Suction System In Riser Static Vac WC Air Flow CFM Watts Exhaust Diameter Test Probe Sub Slab Vacuum WC S T HP 220 S T S T T T

31 Final Performance Analysis North NJ Georgia Approx. Square Feet 38,000 24,000 Riser per Sq Ft One 4 per 2,700 One 6 per 24,000 Average Vacuum Sub Slab Blowers Estimated Annual Blower Cost * Est. Leakage per 10,000 Sq Ft Fourteen 118 watt blowers One 125 watt blower $457 $ CFM 49.5 CFM *cost per 10,000 ft 2 at $0.14 per KWH 31

32 Energy cost analysis Per 10,000 ft 2 of floor area North NJ Georgia Heating: **Factor H/E Cooling: * Factor C/E Overall Factor (E+H+C)/E = * Electric Cost at $0.14 per KWH ** Natural Gas Cost at $12.50 per 1,000 cubic feet 32

33 Energy Cost Analysis (cont.) North NJ Georgia Savings Electric* $457 $63 $394 Heating: ** $ 672 $77 $595 Cooling: * $96 $11 $85 Total Savings $1,074 * Electric Cost at $0.14 per KWH ** Natural Gas Cost at $12.50 per 1,000 cubic feet 33

34 Saving with Liquid Boot Per 10,000 ft 2 of floor area 4 Risers, average cost $4k per riser = $16,000 $394 per year in electricity $595 per year in heating $85 per year in cooling 57,697,920 cubic feet of heat loss* * Assuming a six month heating season 34

35 U.S. Dollars Savings with Liquid Boot and Efficient Sub Slab Venting System 140, , ,000 80,000 60,000 40,000 20,000 Liquid Boot Traditional VB Years 35

36 Conclusions Planned Sub Slab Ventilation Systems Highly Efficient Energy Savings Fiscally Sound Building Practice Improve Indoor Air Quality Contribute to Saving Lives 36

37 Acknowledgments Bill Brodhead, WPB Enterprises, Inc. Leo Moorman PhD, Radon Home Mitigation and Measurement Inc. Clean Vapor, LLC Team 37

38 Thanks for listening Presented By: Tom Hatton Clean Vapor, LLC cleanvapor.com 38

Presented by: Thomas Hatton

Presented by: Thomas Hatton Presented by: Thomas Hatton 1 What is Vapor Intrusion? Methods of Correction Building Investigation Designing Effective Systems VI Mitigation in Existing Buildings VI Mitigation in Construction of New

More information

Evaluating Large Buildings and Assessing the Feasibility of Applying Active Soil Depressurization as a Remedial Solution for Vapor Intrusion

Evaluating Large Buildings and Assessing the Feasibility of Applying Active Soil Depressurization as a Remedial Solution for Vapor Intrusion Evaluating Large Buildings and Assessing the Feasibility of Applying Active Soil Depressurization as a Remedial Solution for Vapor Intrusion ABSTRACT Thomas E. Hatton Clean Vapor, LLC 3 Maple Street Andover,

More information

DESIGNING COMMERCIAL SUB-SLAB DEPRESSURIZATION SYSTEMS

DESIGNING COMMERCIAL SUB-SLAB DEPRESSURIZATION SYSTEMS DESIGNING COMMERCIAL SUB-SLAB DEPRESSURIZATION SYSTEMS Presented at the 2002 - AARST - 12 th Annual International Radon Symposium in Reno, Nevada Bill Brodhead WPB Enterprises, Inc., 2844 Slifer Valley

More information

SCHOOL MITIGATION DESIGN CONSIDERATIONS

SCHOOL MITIGATION DESIGN CONSIDERATIONS SCHOOL MITIGATION DESIGN CONSIDERATIONS Presented at the 2003 AARST - 13 th Annual International Radon Symposium in Nashville, TN Bill Brodhead WPB Enterprises, Inc., 2844 Slifer Valley Rd., Riegelsville,

More information

Introduction to Aerated Floor Systems for Vapor Intrusion Mitigation

Introduction to Aerated Floor Systems for Vapor Intrusion Mitigation 2 nd Southeastern States Vapor Intrusion Symposium Introduction to Aerated Floor Systems for Vapor Intrusion Mitigation Atlanta, GA April 28, 2016 Justin Knight, P.E. Agenda Vapor Intrusion (VI) Conceptual

More information

Vapor Intrusion Mitigation. ITRC Shaping the Future of Regulatory Acceptance

Vapor Intrusion Mitigation. ITRC Shaping the Future of Regulatory Acceptance Vapor Intrusion Mitigation NEWMOA Workshop April/May 2015 Presented by Robin Mongeon, P.E. NH Department of Environmental Services ITRC Shaping the Future of Regulatory Acceptance Host organization Network

More information

Chapter 2: Foundation

Chapter 2: Foundation Chapter 2: Foundation Crawlspace [V502.1.2] [V502.1.2] [V502.1.3] Vents. Vents in the crawlspace help keep floor insulation and floor framing dry. Crawlspace vents also reduce the potential for radon buildup

More information

Testing Is Easy And Inexpensive

Testing Is Easy And Inexpensive Doug Kladder Center for Environmental Research and Technology, Inc. Testing Is Easy And Inexpensive Short And Long-Term Testing Devices Help Determine the Need for, and Effectiveness of, Radon Mitigation

More information

The Effects of Weather Induced Variables on Large Building Vapor Intrusion Mitigation Systems

The Effects of Weather Induced Variables on Large Building Vapor Intrusion Mitigation Systems The Effects of Weather Induced Variables on Large Building Vapor Intrusion Mitigation Systems Paper # 49 Presented at the: Vapor Intrusion, Remediation, and Site Closure Conference September 1-11, 214

More information

Vapor Intrusion Mitigation Methods & Strategies

Vapor Intrusion Mitigation Methods & Strategies Vapor Intrusion Mitigation Methods & Strategies NEWMOA Workshop on Vapor Intrusion Chelmsford, MA April 12, 2006 David J. Folkes P.E. Topics Overview of Mitigation Approaches Commercial Buildings Sub-Slab

More information

SUB-SLAB DEPRESSURIZATION SYSTEM DESIGN AND INSTALLATION

SUB-SLAB DEPRESSURIZATION SYSTEM DESIGN AND INSTALLATION SUB-SLAB DEPRESSURIZATION SYSTEM DESIGN AND INSTALLATION Prepared for: 1500 East Bannister Road, Room 2101 Kansas City, Missouri, 64131-3088 Prepared by: 6750 Antioch Road, Suite 305 Merriam, Kansas 66204

More information

Distribution Restriction Statement

Distribution Restriction Statement DEPARTMENT OF THE ARMY U.S. Army Corps of Engineers CEMP-ET Washington, DC 20314-1000 ETL 1110-3-438 Technical Letter No. 1110-3-438 15 September 1993 Engineering and Design INDOOR RADON PREVENTION AND

More information

SUB-SLAB DIAGNOSTICS

SUB-SLAB DIAGNOSTICS SUB-SLAB DIAGNOSTICS John W. Anderson, Jr. Quality conservation Spokane, WA ABSTRACT Sub-slab diagnostics have eluded most radon contractors because 90% of installed systems work OK. the contractors are

More information

Radon Vent Pipe System. Labeling Performance Indicators

Radon Vent Pipe System. Labeling Performance Indicators Section 6 Radon Vent Pipe Labeling Performance Indicators Radon Vent Pipe System Connected after sub-grade system installed Pipe cannot be trapped Provide space in chases Support at each floor level Discharge

More information

Radon Control Methods for Existing and New Residential Structures

Radon Control Methods for Existing and New Residential Structures Delivered at the October 2006 Meeting of the Colorado Chapter of the International Code Council Presented by: Douglas L. Kladder Center for Environmental Research & Technology, Inc. Through a grant from

More information

New Models to Support Vapor Intrusion Mitigation Design

New Models to Support Vapor Intrusion Mitigation Design New Models to Support Vapor Intrusion Mitigation Design USEPA Work Shop, AEHS 27th Annual International Conference on Soil, Water, Energy and Air March 23-26, 2015, San Diego, CA Dr. Ian Hers, Dr. Parisa

More information

Design of Below Sub-slab Vapour Management System for a Commercial Building

Design of Below Sub-slab Vapour Management System for a Commercial Building Design of Below Sub-slab Vapour Management System for a Commercial Building Soil Contamination Chemical vapor (residual or mobile NAPL) Migration Soil Contamination Indoor Air Chemical Vapour Transport

More information

IPEC San Antonio, TX Tony McDonald

IPEC San Antonio, TX Tony McDonald IPEC San Antonio, TX - 10.30.17 -Tony McDonald Project Location Chemicals of Concern Project Dimensions A-Z was contracted to design/build Sub Slab Depressurization (SSD) Systems in two buildings being

More information

RADON ABATEMENT FROM THE GROUND UP

RADON ABATEMENT FROM THE GROUND UP RADON ABATEMENT FROM THE GROUND UP The solution for a dry, comfortable, and durable basement! CLOSED-CELL 2018 Demilec, 3315 E. Division St., Arlington, TX 76011 Phone: 817.640.4900 Fax: 817.633.2000 Info@Demilec.com

More information

Foundations. Issue. Slab-On-Grade Liquid Water Control (See Figure 2-2) Goals. Guidance

Foundations. Issue. Slab-On-Grade Liquid Water Control (See Figure 2-2) Goals. Guidance www.epa.gov/iaq/moisture Foundations Issue Building foundations are vulnerable to moisture problems for a number of reasons, including: Water from rain and from plumbing leaks is drawn by gravity to foundations,

More information

2009 IECC with St Louis Amendments. Fenestration U-factor Skylight U-factor Glazed fenestration SHGC NR 0.

2009 IECC with St Louis Amendments. Fenestration U-factor Skylight U-factor Glazed fenestration SHGC NR 0. Comparison Between Residential 2009 IECC with St Louis amendments, the 2015 IECC, and 2015 IECC w/ Building Codes Review Committee (BCRC) proposals: Climate Zone 4 Note: This document does not contain

More information

VILLAGE OF DOWNERS GROVE REPORT FOR THE VILLAGE COUNCIL MEETING APRIL 1, 2014 AGENDA

VILLAGE OF DOWNERS GROVE REPORT FOR THE VILLAGE COUNCIL MEETING APRIL 1, 2014 AGENDA VILLAGE OF DOWNERS GROVE REPORT FOR THE VILLAGE COUNCIL MEETING APRIL 1, 2014 AGENDA ITEM ORD 00-05506 SUBJECT: TYPE: SUBMITTED BY: Adoption of Radon Mitigation Standards for New Residential Construction

More information

IRC 2012 Key Changes

IRC 2012 Key Changes IRC 2012 Key Changes Overview of changes between the 2009 and 2012 IRC A Webinar Provided by The Pennsylvania Housing Research Center November 4, 2011 Presented by Mike Turns; Associate Director, PHRC

More information

Paul V. Jennemann MARYLAND RADON LABORATORY, INC E Corporate Court Ellicott City, MD

Paul V. Jennemann MARYLAND RADON LABORATORY, INC E Corporate Court Ellicott City, MD Radon Mitigation Standards, 2000 International Residential Code vs. EPA Mitigation Standards Paul V. Jennemann MARYLAND RADON LABORATORY, INC. 3220-E Corporate Court Ellicott City, MD 2 1042 ABSTRACT This

More information

RADON WELLISUMP BASIN FOR NEW HOME CONSTRUCTION

RADON WELLISUMP BASIN FOR NEW HOME CONSTRUCTION RADON WELLISUMP BASIN FOR NEW HOME CONSTRUCTION Paul V. Jennemann Maryland Radon Laboratory, Inc. Ellicott City, MD ABSTRACT This paper will describe a radon-well/sump-basin (patent applied for) for installation

More information

Radon Resistant New Construction. Topic 8 - Audio 64

Radon Resistant New Construction. Topic 8 - Audio 64 Topic 8 - Audio 64 EPA Map of Radon Zones Designations drawn in by county boundary to match code jurisdictions Indicates the potential for a short-term measurement in the lowest portion of the home to

More information

Annex A STATEMENT OF WORK Radon Mitigation

Annex A STATEMENT OF WORK Radon Mitigation Annex A STATEMENT OF WORK Radon Mitigation OBJECTIVE Royal Canadian Mounted Police (RCMP) requires reduction of the annual radon concentration levels within the noted 15 properties (found on Appendix B)

More information

2009 IECC Chapter 1 Additions, alterations, renovations or repairs.

2009 IECC Chapter 1 Additions, alterations, renovations or repairs. 2009 IECC Chapter 1 Additions, alterations, renovations or repairs. Additions, alterations, renovations or repairs to an existing building, building system or portion thereof shall conform to the provisions

More information

Vapor Intrusion Challenges for Urban Infill Projects. Presented by Jeff Tyburski, PG, RSM Mid-Atlantic Associates, Inc. MAAONLINE.

Vapor Intrusion Challenges for Urban Infill Projects. Presented by Jeff Tyburski, PG, RSM Mid-Atlantic Associates, Inc. MAAONLINE. Vapor Intrusion Challenges for Urban Infill Projects Presented by Jeff Tyburski, PG, RSM Mid-Atlantic Associates, Inc. MAAONLINE.COM Urban Infill Sites Urban setting Real/perceived presence of contamination

More information

Standards for Jackson EMC s Right Choice Program Revised: June 2011

Standards for Jackson EMC s Right Choice Program Revised: June 2011 Standards for Jackson EMC s Right Choice Program Revised: June 2011 All homes in the program must meet the requirements of the Georgia Energy Code, which is the International Energy Conservation Code (IECC)

More information

A Design Review of Waterproofing Codes

A Design Review of Waterproofing Codes A Design Review of Waterproofing Codes Section 1807 of Chapter 18 of the International Building Code addresses waterproofing under the section title of Dampproofing and Waterproofing. The section defines

More information

County of Yolo Development Services Building Inspection Division

County of Yolo Development Services Building Inspection Division County of Yolo Development Services Building Inspection Division 292 W. Beamer Street Woodland, CA. 95695 www.yolocounty.org (530) 666-8775 Mechanical Plan Review Comments Plan Review No. Owners Name Job

More information

Measuring Air Velocity - presented by Lonnie Glen, Kice Industries 2/28/2018. (and why it is important) Applications for Air

Measuring Air Velocity - presented by Lonnie Glen, Kice Industries 2/28/2018. (and why it is important) Applications for Air (and why it is important) Wednesday, February 28, 2018 Presented by Lonnie Glen, Kice Technical Sales and Quickship Manager Applications for Air Air Activated Processing Grinders Granulators Hammermills

More information

ESTCP Research on Optimization of Vapor Intrusion Mitigation Systems in Large Military Buildings

ESTCP Research on Optimization of Vapor Intrusion Mitigation Systems in Large Military Buildings ESTCP Research on Optimization of Vapor Intrusion Mitigation Systems in Large Military Buildings Todd McAlary, Ph.D., P.Eng., P.G., CUT Principal and Practice Leader Vapor Intrusion Services Geosyntec

More information

INDOOR RADON PREVENTION AND MITIGATION

INDOOR RADON PREVENTION AND MITIGATION UFC 3-490-04A 15 May 2003 UNIFIED FACILITIES CRITERIA (UFC) INDOOR RADON PREVENTION AND MITIGATION APPROVED FOR PUBLIC RELEASE; DISTRIBUTION UNLIMITED UFC 3-490-04A 15 May 2003 UNIFIED FACILITIES CRITERIA

More information

UNIFIED FACILITIES CRITERIA (UFC) INDOOR RADON PREVENTION AND MITIGATION

UNIFIED FACILITIES CRITERIA (UFC) INDOOR RADON PREVENTION AND MITIGATION UFC 3-490-04A 15 May 2003 UNIFIED FACILITIES CRITERIA (UFC) INDOOR RADON PREVENTION AND MITIGATION APPROVED FOR PUBLIC RELEASE; DISTRIBUTION UNLIMITED UFC 3-490-04A 15 May 2003 UNIFIED FACILITIES CRITERIA

More information

Welcome to this continuing education seminar. This is the first of three parts of the Building Enclosure Fundamentals series.

Welcome to this continuing education seminar. This is the first of three parts of the Building Enclosure Fundamentals series. Welcome to this continuing education seminar. This is the first of three parts of the Building Enclosure Fundamentals series. 1 3 6 7 8 The primary reasons to build airtight buildings are to avoid drafts

More information

Welcome to this continuing education seminar. This is the first of two parts of the High- Performance Building series.

Welcome to this continuing education seminar. This is the first of two parts of the High- Performance Building series. Welcome to this continuing education seminar. This is the first of two parts of the High- Performance Building series. 1 3 6 7 8 An enclosure s basic function is to separate the outside from the inside.

More information

Structural Pest Control Section Division of Plant Industry Georgia Department of Agriculture

Structural Pest Control Section Division of Plant Industry Georgia Department of Agriculture Structural Pest Control Section Division of Plant Industry Georgia Department of Agriculture Compliance Fact Sheet Under-floor space ventilation This fact sheet is for structural pest control operators

More information

Controlling Air Leakage from Raised Access Floor Cavities

Controlling Air Leakage from Raised Access Floor Cavities Technical Bulletin #216 AIR LEAKAGE CONTROL Controlling Air Leakage from Raised Access Floor Cavities AIR LEAKAGE DEFINITION AND SIGNIFICANCE Air leakage is passage of pressurized air from an underfloor

More information

CONSEQUENCES OF INCORRECT DESIGN AND UNQUALIFIED REALIZATION ON RELIABILITY AND EFFECTIVENESS OF RADON REDUCTION MEASURES

CONSEQUENCES OF INCORRECT DESIGN AND UNQUALIFIED REALIZATION ON RELIABILITY AND EFFECTIVENESS OF RADON REDUCTION MEASURES CONSEQUENCES OF INCORRECT DESIGN AND UNQUALIFIED REALIZATION ON RELIABILITY AND EFFECTIVENESS OF RADON REDUCTION MEASURES Martin Jiránek, Czech Technical University, Faculty of Civil Engineering, Praha

More information

A Protocol. Advanced Air Sealing

A Protocol. Advanced Air Sealing A Protocol Advanced Air Sealing Efficiency Vermont is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES). Credit(s) earned on completion of this program

More information

THE CITY OF FAYETTEVILLE ADOPTED THE 2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) ON JULY 17, 2012

THE CITY OF FAYETTEVILLE ADOPTED THE 2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) ON JULY 17, 2012 THE CITY OF FAYETTEVILLE ADOPTED THE 2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) ON JULY 17, 2012 Compliance with the code for new residential construction, additions, and substantial remodels will

More information

Foundation/Site Work Code Requirements

Foundation/Site Work Code Requirements Q: What is a Foundation Only permit and why did I receive one when I filed for a full Building Permit? All Building Permits for new construction and additions are reviewed for zoning compliance. This review

More information

Questar ThermWise Duct Technical Specifications

Questar ThermWise Duct Technical Specifications Questar ThermWise Duct Technical Specifications 1. Introduction and Scope: This document sets forth the specifications for duct sealing and duct insulation in accordance to Questar ThermWise Weatherization

More information

Indoor Air Quality Testing at the Middle River Complex

Indoor Air Quality Testing at the Middle River Complex Indoor Air Quality Testing at the Middle River Complex September 2016 Lockheed Martin has been investigating, and more recently, cleaning up contaminants in soil and groundwater at the Middle River Complex.

More information

2/23/2009 R15-R20R20

2/23/2009 R15-R20R20 Foundations What is important to know about foundations? You (probably) won t design it What are the components that make up a properly designed and built foundation? Determine whether house has a good

More information

VANGUARD Packed Column Air Stripping Tower Specifications

VANGUARD Packed Column Air Stripping Tower Specifications . 185 US Highway 206 Roxbury Township, NJ 07866-0315 Telephone 973.586.2201 Fax 973.586.2243 www.deltacooling.com sales@deltacooling.com VANGUARD Packed Column Air Stripping Tower Specifications VANGUARD

More information

Evaluating a Poultry Farm s Energy Use

Evaluating a Poultry Farm s Energy Use Points of My Talk Evaluating a Poultry Farm s Energy Use Gary Van Wicklen Extension Poultry Engineer Dept. of Bioresources Engineering University of Delaware Georgetown, DE #1: Alternative energy is it

More information

2014 British Columbia Building Code Changes

2014 British Columbia Building Code Changes 2014 British Columbia Building Code Changes A City of Prince George interpretation of the 2014 Building Code Changes for 9.32 & 9.36 The following changes reflect the most notable revisions and staff interpretations.

More information

City of Grand Island Tuesday, March 25, 2014 Council Session (Corrected)

City of Grand Island Tuesday, March 25, 2014 Council Session (Corrected) City of Grand Island Tuesday, March 25, 2014 Council Session (Corrected) Item F-4 #9481 - Consideration of Amending Chapter 8-14 of the Grand Island City Code Relative to Buildings Staff Contact: Craig

More information

2. Heat Transfer is quantified in British Thermal Units (BTU s)

2. Heat Transfer is quantified in British Thermal Units (BTU s) Basic Concepts 2. Heat Transfer is quantified in British Thermal Units (BTU s) 1 Btu is approximately equal to the energy in a single match. 3 INNOVATION & INTEGRATION: Transforming the Energy Efficiency

More information

Introduction to Horizontal Remediation Wells for Improved Site Cleanup Training Workshop

Introduction to Horizontal Remediation Wells for Improved Site Cleanup Training Workshop Horizontal Wells for Sub-Slab Vapor Intrusion Mitigation and Remediation Southeastern States Vapor Intrusion Symposium February 8, 2018 Presenter: Kyle J. Carlton, PG kcarlton@directionaltech.com Senior

More information

CERTIFICATE OF FIELD VERIFICATION & DIAGNOSTIC TESTING (Page 1 of 8)

CERTIFICATE OF FIELD VERIFICATION & DIAGNOSTIC TESTING (Page 1 of 8) CERTIFICATE OF FIELD VERIFICATION & DIAGNOSTIC TESTING (Page 1 of 8) Builder or Installer Name Builder or Installer Contact Telephone Plan/Permit (Additions or Alterations) Number Compliance Method (Prescriptive)

More information

Administrative Changes

Administrative Changes Revised 11/29/06 Knox County Residential Building Codes Significant Changes From The 1995 CABO One And Two Family Dwelling Code To The 2006 International Residential Code All one and two family dwellings

More information

Indoor Air Quality and Mechanical Ventilation (Page 1 of 5)

Indoor Air Quality and Mechanical Ventilation (Page 1 of 5) Indoor Air Quality and Mechanical Ventilation (Page 1 of 5) Title 24, Part 6, Section 150.0(o) Ventilation for Indoor Air Quality. All dwelling units shall meet the requirements of ANSI/ASHRAE Standard62.2.

More information

Crawl Space Moisture Control

Crawl Space Moisture Control Crawl Space Moisture Control Crawl space foundations are found in many homes. Typically, these foundation types are equipped with operable vents designed to provide ventilation for moisture control. Unfortunately,

More information

Rhode Island Department of Environmental Mgmt. Office of Waste Management. NEWMOA TCE Vapor Intrusion Workshop Providence, Rhode Island April 13, 2015

Rhode Island Department of Environmental Mgmt. Office of Waste Management. NEWMOA TCE Vapor Intrusion Workshop Providence, Rhode Island April 13, 2015 Rhode Island Department of Environmental Mgmt. Office of Waste Management NEWMOA TCE Vapor Intrusion Workshop Providence, Rhode Island April 13, 2015 Current Groundwater Standards GA MCLs GB Developed

More information

Healthier Home Environments Benefit Everyone

Healthier Home Environments Benefit Everyone Healthier Home Environments Benefit Everyone ALA Health House Mission To improve the way homes are built, renovated and maintained in America to be: Healthier More energy efficient More resource efficient

More information

Evergreen Project Implementation Plan Instructions Low Income Housing Tax Credit Program

Evergreen Project Implementation Plan Instructions Low Income Housing Tax Credit Program Evergreen Project Implementation Plan Instructions Low Income Housing Tax Credit Program The following table provides a brief description of the documentation that will be required of successful LIHTC

More information

METATEK POWER HOUSE CONSTRUCTION BUILDER S GUIDE CHECKLIST

METATEK POWER HOUSE CONSTRUCTION BUILDER S GUIDE CHECKLIST BUILDER S GUIDE & CHECKLIST 1 Table of Contents OVERVIEW... 2 CONSTRUCTION GUIDELINES... 2 DO NOT MODIFY LIST... 3 OPTIONAL LIST... 3 BUILDING DRAWINGS... 4 CHECKLIST... 4 MATERIALS LIST... 15 MATERIALS

More information

Condi1oned A3cs and Crawlspaces. Making the Decision. Find This Presenta1on. Helpful Informa1on. page/

Condi1oned A3cs and Crawlspaces. Making the Decision. Find This Presenta1on. Helpful Informa1on. page/ Condi1oned A3cs and Crawlspaces Making the Decision Find This Presenta1on Helpful Informa1on h@p://www.kenergy.us/code- page/ It will be posted under 2009 IECC Learning Objec1ves Helpful Informa1on 1.

More information

ASHRAE 62.2: What s New in 2016

ASHRAE 62.2: What s New in 2016 ASHRAE 62.2: What s New in 2016 Rick Karg 2016 Residential Energy Dynamics, LLC What We Will Talk About Overview of mechanics of 62.2-2016. Logic behind the Standard. Sizing local ventilation (exhaust-only).

More information

A Closer Look Inspection Service 2015 IECC Residential DFW area handout

A Closer Look Inspection Service 2015 IECC Residential DFW area handout 103.2 Information required on construction documents 1. Designation of the Thermal Building Envelope on the plans 2. Insulation Material and their R Value 3. Fenestration U and SHGC values 4. Area weighted

More information

Date Rater Verified. Rater Verified. Slab / Pre-Drywall / Thermal Inspection

Date Rater Verified. Rater Verified. Slab / Pre-Drywall / Thermal Inspection Slab on Grade & Basements: A capillary break is installed on top of all footings Slab / Pre-Drywall / Thermal Inspection A minimum of 4" of clean or washed gravel (0.5" diameter or greater) is placed over

More information

Check the exterior foundation for mud tubes. This is particularly important for houses built on slabs, since this is one of the few inspectable areas.

Check the exterior foundation for mud tubes. This is particularly important for houses built on slabs, since this is one of the few inspectable areas. Page 1 of 2 Conducive Conditions for Pests Here are a few common things you can check in your home or a home you are about to buy: A detailed pest inspection can have 12 or more recommendations for repair,

More information

COMcheck Software Version Envelope Compliance Certificate

COMcheck Software Version Envelope Compliance Certificate COMcheck Software Version 4.0.2.8 Envelope Compliance Certificate Project Information Energy Code: 20 IECC Location: Cedar Hills, Utah Climate Zone: 5b Project Type: New Construction Vertical Glazing /

More information

IECC Residential Significant Changes Summary. Tier I

IECC Residential Significant Changes Summary. Tier I 2009-2015 IECC Residential Significant Changes Summary Tier I R401.2 Compliance options for compliance are now prescriptive path, Total UA (which is part of prescriptive), Performance and the new Energy

More information

Notes. Lesson overview. This lesson discusses how radon enters a home, where people can be exposed to unhealthy levels.

Notes. Lesson overview. This lesson discusses how radon enters a home, where people can be exposed to unhealthy levels. Lesson 3: How does radon enter a home? Lesson overview This lesson discusses how radon enters a home, where people can be exposed to unhealthy levels. Lesson objectives By the end of this lesson, the learners

More information

Mark Lawton, P.Eng., FEC. Airtightness in Buildings A Canadian History June 2017

Mark Lawton, P.Eng., FEC. Airtightness in Buildings A Canadian History June 2017 Mark Lawton, P.Eng., FEC Airtightness in Buildings A Canadian History June 2017 History of What? Understanding Measurement Implementation Air in Buildings Carries moisture to cold surfaces where condensation

More information

Encapsulated, Sealed & Closed Crawlspace Installation Manual

Encapsulated, Sealed & Closed Crawlspace Installation Manual YourCrawlSpace, Inc. 1007 Johnni4 Dodds Blvd. Mt. Pleasant, SC 29464 Toll Free: 877-44-CRAWL (27295) Local: (843) 593-1115 Encapsulated, Sealed & Closed Crawlspace Installation Manual Copyright 2017 Your

More information

FIELD COPY ATTACHMENT

FIELD COPY ATTACHMENT FIELD COPY ATTACHMENT The released plans for the project must be on site and available to the inspectors at all times. No inspection will be done without the released field plans. If you have any questions,

More information

Can you Believe Energy Savings Forecasts

Can you Believe Energy Savings Forecasts Can you Believe Energy Savings Forecasts By: Tony Woods Introduction Yes, says TonyWood. Especially when your project includes an upgrade to the building envelope. The relationship between high performance

More information

PLAN CHECK CORRECTION SHEET FOR METHANE MITIGATION SYSTEMS 2017 LAPC

PLAN CHECK CORRECTION SHEET FOR METHANE MITIGATION SYSTEMS 2017 LAPC PLAN CHECK CORRECTION SHEET FOR METHANE MITIGATION SYSTEMS 2017 LAPC This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS The following instructions are provided for the installation of Radon Guard rigid board sub-slab insulation and radon gas mitigation. Radon Guard should be installed by a professional

More information

FOR ADDITIONS and REMODELS Before filling out this application, read Green Building & Green Points Guideline Booklet for more in-depth information.

FOR ADDITIONS and REMODELS Before filling out this application, read Green Building & Green Points Guideline Booklet for more in-depth information. City of Boulder Residential Building Guide Green Building & Green Application Resource Conservation Ordinance 7565 www.bouldergeenpoints.com FOR ADDITIONS and REMODELS Before filling out this application,

More information

APPENDIX C. Chapter 9B-53 STANDARD FOR MITIGATION OF RADON IN EXISTING BUILDINGS

APPENDIX C. Chapter 9B-53 STANDARD FOR MITIGATION OF RADON IN EXISTING BUILDINGS Chapter 9B-53 STANDARD FOR MITIGATION OF RADON IN EXISTING BUILDINGS 9B-53.001 9B-53.002 9B -5 3.003 9B-53.004 Purpose and Intent. (Repealed) Definitions. Department Activities. Florida Standard for Mitigation

More information

Testing Is Easy And Inexpensive

Testing Is Easy And Inexpensive Radon Resistant New Construction Doug Kladder Center for Environmental Research and Technology, Inc. November 2012 Testing Is Easy And Inexpensive Page 1 Short And Long-Term Testing Devices Help Determine

More information

Compliance Certificate

Compliance Certificate REScheck Software Version 4.6.3 Compliance Certificate Project Energy Code: 2012 IECC Location: Frederick, Colorado Construction Type: Single-family Project Type: New Construction Conditioned Floor Area:

More information

Managing Radon PRESENTATION BY: KEITH, ROB, LISA, & WILLEM

Managing Radon PRESENTATION BY: KEITH, ROB, LISA, & WILLEM Managing Radon PRESENTATION BY: KEITH, ROB, LISA, & WILLEM MARCH 2018 INTRODUCTIONS BY WILLEM The focus for our presentation is requesting support for improvements to Building Code performance requirements

More information

SPECIFICATIONS FOR HONEYCOMB INTERNAL FLOATING ROOFS

SPECIFICATIONS FOR HONEYCOMB INTERNAL FLOATING ROOFS PETREX SPECIFICATIONS FOR HONEYCOMB INTERNAL FLOATING ROOFS APPLICATION: REGULAR HYDROCARBONS SCOPE The roof shall be full-surface contact type designed to eliminate the presence of air-vapor mixture under

More information

Sustainable Approaches for Soil Gas Mitigation Systems

Sustainable Approaches for Soil Gas Mitigation Systems Sustainable Approaches for Soil Gas Mitigation Systems Ian Hers 1 and Eric Hood 2 1 Golder Associates Ltd., #500-4260 Still Creek Drive, Burnaby, BC V5C 6C6 2 Golder Associates Ltd., 100 Scotia Court,

More information

Photographic Guide: Home Performance Dos and Don ts

Photographic Guide: Home Performance Dos and Don ts Use these photographic examples of best practices (and less-than-best practices) to achieve high quality home performance work in your customers homes. Contact Moe Srifi at moe@efficiencyfirstca.org for

More information

Revisions to the Residential Standards and ACM Calculations. June 13, 2007 Bruce Wilcox, P.E.

Revisions to the Residential Standards and ACM Calculations. June 13, 2007 Bruce Wilcox, P.E. Revisions to the Residential Standards and ACM Calculations June 13, 2007 Bruce Wilcox, P.E. Topics Refrigerant Charge Fan Watt Draw and Airflow Indoor Air Quality Ventilation New Solar Homes Partnership

More information

A Rational Approach to Vapor Intrusion Preferential Pathways

A Rational Approach to Vapor Intrusion Preferential Pathways A Rational Approach to Vapor Intrusion Preferential Pathways PRESENTED BY: David J. Folkes, PE Geosyntec Consultants, Inc. AEHS West Coast Conference EPA Vapor Intrusion Technical Workshop March 22, 2016

More information

Rehabbing/Restoring Vacant Buildings. Richard Reilly, LEED AP, BPI BA. EP & HHE, HES Assessor Energy Programs Manager

Rehabbing/Restoring Vacant Buildings. Richard Reilly, LEED AP, BPI BA. EP & HHE, HES Assessor Energy Programs Manager Rehabbing/Restoring Vacant Buildings Richard Reilly, LEED AP, BPI BA. EP & HHE, HES Assessor Energy Programs Manager Kinds of Projects The spectrum Deep Energy Retrofits Weatherization Air Sealing/Insulation

More information

Vapor Intrusion Panel Discussion. SCRD Fall 2009 Meeting Terry Evanson Wisconsin DNR,

Vapor Intrusion Panel Discussion. SCRD Fall 2009 Meeting Terry Evanson Wisconsin DNR, Vapor Intrusion Panel Discussion SCRD Fall 2009 Meeting Terry Evanson Wisconsin DNR, Theresa.Evanson@wisconsin.gov 608-266-0941 VI Issues at WI Dry Cleaner Sites Assessment of the vapor pathway at operating

More information

PLAN CHECK CORRECTION SHEET FOR METHANE MITIGATION SYSTEMS 2014 LAPC

PLAN CHECK CORRECTION SHEET FOR METHANE MITIGATION SYSTEMS 2014 LAPC PLAN CHECK CORRECTION SHEET FOR METHANE MITIGATION SYSTEMS 2014 LAPC This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

Material and Installation (M&I) Guidelines Training Webinar

Material and Installation (M&I) Guidelines Training Webinar Material and Installation (M&I) Guidelines Training Webinar In home Energy Program Your Instructor Mark Hutchins Quality Assurance (QA) Manager Conservation Services Group (CSG) mark.hutchins@csgrp.com

More information

Work Order (Bid Form) Upper East Tennessee Human Development Agency, Inc.

Work Order (Bid Form) Upper East Tennessee Human Development Agency, Inc. Upper East Tennessee Human Development Agency, Inc. WORK ORDER INFORMATION Work Order Type: Weatherization Audit Name: 18018UE10214 CLIENT INFORMATION Address: Bluff City, TN 37618 AGENCY INFORMATION Agency:

More information

by Richard D. Seifert Energy and Building Specialist Cooperative Extension Service University of Alaska Fairbanks

by Richard D. Seifert Energy and Building Specialist Cooperative Extension Service University of Alaska Fairbanks RADON ALASKA EXPERIENCES, COSTS, RESULTS Mitigation by Richard D. Seifert Energy and Building Specialist Cooperative Extension Service University of Alaska Fairbanks RAD-00755 INTRODUCTION Late in 1986,

More information

Module number 3 provides an on-line, self-paced training seminar on chapter 4, foundations and chapter 5, floors from the residential code of ohio.

Module number 3 provides an on-line, self-paced training seminar on chapter 4, foundations and chapter 5, floors from the residential code of ohio. Module number 3 provides an on-line, self-paced training seminar on chapter 4, foundations and chapter 5, floors from the residential code of ohio. 1 This chapter sets forth the prescriptive requirements

More information

Pneumatic Testing, Mathematical. and Optimize the Performance and. Slab Depressurization Systems

Pneumatic Testing, Mathematical. and Optimize the Performance and. Slab Depressurization Systems Pneumatic Testing, Mathematical Modeling and Flux Monitoring to Assess and Optimize the Performance and Establish Termination Criteria for Sub- Slab Depressurization Systems Todd McAlary, David Bertrand,

More information

SECTION 1000 ENGINEERING SPECIFICATION: AIR STRIPPER (REMOVABLE TRAY)

SECTION 1000 ENGINEERING SPECIFICATION: AIR STRIPPER (REMOVABLE TRAY) SECTION 1000 ENGINEERING SPECIFICATION: AIR STRIPPER (REMOVABLE TRAY) PART 1 GENERAL 1.1 SCOPE 1.1.1 The manufacturer shall furnish a low profile, multi-tray Air Stripper for removal of volatile organic

More information

Montana Homebuilder Brief: Residential Energy Code 1

Montana Homebuilder Brief: Residential Energy Code 1 1 Montana homebuyers appreciate the comfort and warmth of the energyefficient homes based on the energy code. All new houses in Montana must meet the minimum requirements of the 2012 International Energy

More information

Commissioning Agent s Guide for Inspecting & Testing Access Floor Air Plenums

Commissioning Agent s Guide for Inspecting & Testing Access Floor Air Plenums Access F l o o rs Commissioning Agent s Guide for Inspecting & Testing Access Floor Air Plenums Access Floors to the Power of 1 Proper inspection and testing of the underfloor air plenum is the best way

More information

Supplement B - Taking Credit for Reduced Air Leakage in Residential Buildings

Supplement B - Taking Credit for Reduced Air Leakage in Residential Buildings Supplement B Taking Credit for Reduced Air Leakage in Residential Buildings In recent years, a growing number of Washington State Energy code (WSEC) submittals have attempted to take credit for energy

More information

Environmental Management Plan Stone Quarry Apartments Project

Environmental Management Plan Stone Quarry Apartments Project DRAFT PLA Benefits Analysis City of Rochester Midtown Redevelopment Project Environmental Management Plan Stone Quarry Apartments Project Ithaca Neighborhood Housing Services, Inc. Ithaca, New York August

More information

Radon in civil engineering building code, building standards, guidelines for building professionals

Radon in civil engineering building code, building standards, guidelines for building professionals Radon in civil engineering building code, building standards, guidelines for building professionals STUK - Radiation and nuclear safety authority Finland IAEA Regional Workshop, Sofia, Bulgaria Oct 16,

More information