Xavier University of Louisiana

Size: px
Start display at page:

Download "Xavier University of Louisiana"

Transcription

1 Annual Savings Report Year 2 May 1, 2012 to April 30, 2013 July 2013 For Marion Bracy Vice President Xavier University Facilities Planning 1 Drexel Drive New Orleans LA (504) Submitted By Siemens Industry, Inc. Building Technologies Division 150 Teal Street Suite 100 St. Rose LA (504)

2 Executive Summary Siemens Industry, Inc. is pleased to submit the following Annual Savings Report for Xavier University of Louisiana (Xavier University). This report covers the second year of energy performance during the period from May 1, 2012 to April 30, Energy and cost savings are presented and compared to the contractual guaranteed savings. The facility improvement measures (FIMs) implemented with this project are listed in Table 1. Table 1 Facility Improvement Measures FIM DESCRIPTION Lighting Upgrades Upgrade of lighting in classrooms, corridors, and exterior locations of multiple facilities lighting fixtures with energy efficient lighting and devices. Chilled Water Optimization Chiller plant optimization to include variable frequency drives (VFDs), piping changes, and temperature/pressure sensors required to implement an advanced strategy to reduce electrical usage generated by the Central Chilled Water Plant. Energy Management and Implementation of scheduling and ventilation energy savings Control System (EMCS) strategies at multiple facilities. Mechanical Upgrades Implementation of mechanical upgrades at multiple facilities, including insulation, service valves, and air/water balancing. Water Management Upgrade of multiple facilities plumbing systems with more energy efficient water consuming devices. During this annual period, Xavier University realized total energy reductions in the amount of 10,001,493 kwh of electric energy, 48,169 ccf of natural gas, and 4,347 kgal of water. The total energy savings equate to a dollar savings in the amount of $1,020,566, 173 percent of the guaranteed cost savings of $588,371 $432,195 in excess savings. Table 2 shows kwh, ccf, and kgal annual reductions. Table 2 Annual Measured Savings FIM ELECTRIC ENERGY (kwh/yr) NATURAL GAS (ccf/yr) WATER (kgal/yr) TOTAL SAVINGS ($) Lighting Upgrades 2,216,109 $205,433 Chilled Water Optimization 6,180,956 $572,975 EMCS 1,604,428 32,121 $188,432 Water Conservation 16,048 4,347 $53,726 Water Conservation (CT Sewer Credits) $0 Total Savings 10,001,493 48,169 4,347 $1,020,566 Savings Guarantee 5,401,365 50,485 4,870 $588,371 Excess Savings / (Shortfall) 4,600,128 (2,316) (523) $432,195 Percent of Savings Achieved 173% Page 1 of 18

3 The utility costs used for savings calculations are based on agreed upon utility rates from the contract and the annual rate escalation of three percent. Table 3 shows the annual utility rates with escalation. Table 3 Utility Rates (Annual Rate Escalation of 3%) NATURAL ELECTRIC WATER SEWER YEAR GAS ($/kwh) ($/kgal) ($/kgal) ($/ccf) Baseline utility consumption by FIM is shown in Table 4. Total electric baseline consumption was 16,794,911 kwh, total natural gas baseline consumption was 89,561 ccf, and total water baseline consumption was 26,717 kgals for the year of January 2008 to December Additional buildings have been constructed on campus since baseline development in 2008, increasing electric, natural gas, and water consumption. Increased consumption from new buildings connected to the Central Chilled Water Plant, the Chapel and Qatar, has been mitigated by increased efficiency at the plant resulting from the chilled water optimization FIM. Table 4 Baseline Utility Consumption (January to December 2008) NATURAL ELECTRIC WATER FIM GAS (kwh) (kgal) (ccf) Lighting 3,523,989 Water 59,090 22,717 Water (CT Sewer Credits) 4,000 Chilled Water Optimization 10,775,383 EMCS 2,495,539 28,035 Piping Insulation 2,436 Total 16,794,911 89,561 26,717 Page 2 of 18

4 The contracted guaranteed savings for year 2 are detailed in Table 5. Table 5 Guaranteed Savings for Year 2 (from Contract) Annual Savings FIM FIM Title No. Electric Energy (kwh/yr) Natural Gas (ccf/yr) Water (kgal/yr) Total Savings ($) 1 Lighting Upgrades $113,862 2 Chilled Water Optimization $261,400 3 EMCS $142,090 4 Water Conservation $58,037 5 Water Conservation (CT Sewer Credits) $12,982 TOTAL 5,401,365 50,485 4,870 $588,371 The total project savings summary, Table 6, shows the annual and accumulated measured, guaranteed, and excess or shortfall savings totals. Table 6 Total Project Savings Summary YEAR Construction Period MEASURED SAVINGS GUARANTEED SAVINGS EXCESS SAVINGS/ (SHORTFALL) TOTAL ACCUMULATED PROJECT MEASURED SAVINGS TOTAL ACCUMULATED PROJECT GUARANTEED SAVINGS TOTAL ACCUMULATED PROJECT EXCESS SAVINGS/ (SHORTFALL) $215,277 $125,000 $90,277 $0 $0 $0 1 $786,871 $571,234 $215,637 $1,002,148 $696,234 $305,914 2 $1,020,566 $588,371 $432,195 $2,022,714 $1,284,605 $738, Page 3 of 18

5 Figure 1 shows job to date savings, including guaranteed and realized construction period savings, of $2,022,714 compared to the job to date guaranteed savings target of $1,284,605. $2,500,000 $2,000,000 $1,500,000 $1,000,000 $500,000 $0 $1,284,605 $2,022,714 Figure 1 Job to Date Savings Job to Date Guaranteed Savings Target Job to Date Savings Figure 2 shows the annual savings from each of the project years. The first annual period realized savings of $786,871. The second annual period achieved savings of $1,020,566. $1,200,000 $1,000,000 $800,000 $600,000 $400,000 $200,000 $0 $786,871 $1,020,566 Figure 2 Annual Savings Annual Period 1 Savings Annual Period 2 Savings These energy savings resulted in a significant reduction in green house gas emissions from power plants producing electricity in the New Orleans area. A reduction of 12,609,760 pounds of CO 2 was realized in the second year of this project. Page 4 of 18

6 The expected savings were exceeded through the implementation of lighting retrofits and air handling unit (AHU) time of day (TOD) scheduling, demand control ventilation (DCV), and Demand Flow chiller optimization controls and sequencing logic to allow the chiller plant equipment to slow down in times of reduced load and significantly reduce electricity consumption. Excess savings were also realized due to a significant increase in chilled water load at the plant. The additional load and savings associated with the chiller optimization FIM are detailed on page 7 of this report. Siemens believes that the best program to cost effectively achieve energy reductions by today s standards has been executed. Our service personnel continue to work closely with University staff and the Siemens PA group to improve and enhance performance. It is anticipated that with continued vigilance the projected energy savings will be met. Siemens remains a committed partner with Xavier University and looks forward to continuing a valued relationship on future energy savings projects. Sincerely, The Gulf Coast Performance Assurance Team Page 5 of 18

7 Annual Equipment Inspection/Installed Facility Improvement Measures (FIMs) The annual equipment inspection took place during recent site visits to Xavier University on July 2, 2013 and July 9, Siemens Performance Assurance and Service personnel met to discuss plant performance and operation and to view lighting and mechanical upgrades and water conservation measures in the Library and Xavier South. Lighting This FIM involved retrofitting existing, inefficient lighting systems in several buildings located throughout Xavier University with new energy efficient lighting equipment. Occupancy sensors were also installed to automatically turn lights off during unoccupied times. Figures 3 and 4 show lighting upgrades at Xavier South. Fixtures were retrofitted with four 30 watt T8 fluorescent lamps, the retrofitted equipment was operational. Figure 3 Lighting Retrofit Figure 4 Lighting Retrofit Page 6 of 18

8 Figure 5 shows a new LED exit sign with battery backup installed at Xavier South. Figure 5 Exit Sign Chilled Water Optimization This FIM involved optimizing the existing 2,400 ton capacity central chilled water plant that serves over fourteen (14) buildings on campus. Chilled water optimization included advanced energy management and control system strategies to enhance comfort and optimize energy efficiency. The optimization required physical upgrades, repairs, and additional mechanical installations that included the following: New VFDs on all chilled water pumps New fill on the Central Plant cooling tower New piping and valves in select buildings New chilled water temperature and flow sensors at multiple buildings New 2 way chilled water control valves on AHUs Cleaning of coils on select AHUs New Premium Efficiency Tertiary Pump Motors New VFDs on Building AHU Fans The following FIMs result in reduced cooling loads at the chiller plant: Lighting retrofits EMCS / TOD scheduling and DCV Piping Insulation The savings for this FIM are realized at the chilled water plant and are claimed with the chilled water optimization savings. The new Chiller No. 2 was the only operating chiller for this reporting period. The existing Chiller No. 1 was recently repaired and brought back online. Since the addition of Chiller No. 1, the plant is typically operating both chillers each with one compressor. Preliminary indications are that this configuration is producing greater efficiencies than the operation of one chiller with both stages. Page 7 of 18

9 Table 7 shows the chiller optimization performance analysis for year 2. The annual kw/ton efficiency for this reporting period is 0.689, an improvement over year 1 annual plant efficiency of kw/ton. Improved efficiency may be due in part to overall cooler temperatures during the year 2 reporting period from the year 1 reporting period. Cooling degree days were 3,627 in year 1 and 3,117 in year 2. However, the load has increased from year 1 to year 2. The year 1 chilled water ton hours total was 9,956,164 and year 2 was 12,061,497 ton hours. The calculated savings increased with additional load. Two new buildings have been connected to the chilled water plant since baseline development, which have substantially increased the chilled water load at the plant. The new Chapel was dedicated in October 2012 and Qatar was brought online prior to the year 1 reporting period; however, the building was not fully occupied. During this reporting period, animals have been moved to Qatar requiring 24/7 operation for a portion of the building. The improved efficiency this year mitigated the increase in ton hours from year 1 to year 2. The chiller optimization savings calculations are determined by the monthly total chilled water ton hours and the difference between the baseline efficiency in kw/ton and the post retrofit efficiency in kw/ton. Energy graphs for the Central Chilled Water Plant are included in the Appendix. Table 7 Demand Flow Chiller Optimization Performance Analysis SUMMARY PERFORMANCE ANALYSIS PRE RETROFIT BASELINE POST RETROFIT MONTHLY SAVINGS ACCUMULATED ANNUAL SAVINGS *** measured *** Month Chw Electric Efficiency Chw Electric Efficiency Electric Baseline Rate Baseline Rate Cost Savings Annual Total Baseline Rate Annual Cost Savings Achieved Guarantee YEAR 2 TonHrs kwh kw/ton TonHrs kwh kw/ton kwh $/kwh $ kwh $ % kwh May , , ,283, , ,034 $ $ 83, ,034 $ 83,613 40% Jun ,694 1,106, ,328,670 1,062, ,690 $ $ 51,542 1,501,724 $ 135,155 65% Jul ,442 1,144, ,681,856 1,244, ,524 $ $ 72,047 2,302,248 $ 207, % Aug ,442 1,144, ,649,101 1,305, ,883 $ $ 62,989 3,002,131 $ 270, % Sep ,694 1,106, ,589,371 1,121, ,952 $ $ 75,146 3,837,083 $ 345, % Oct 12 1,076,320 1,109, ,098, , ,086 $ $ 40,148 4,283,168 $ 385, % Nov , , , , ,789 $ $ 24,371 4,553,958 $ 409, % Dec , , , , ,436 $ $ 23,979 4,820,394 $ 433, % Jan , , , , ,589 $ $ 22,823 5,073,983 $ 456, % Feb , , , , ,331 $ $ 22,980 5,329,315 $ 479, % Mar , , , , ,484 $ $ 21,194 5,564,798 $ 500, % Apr , , , , ,157 $ $ 55,454 6,180,956 $ 556, % Totals 8,607,076 10,203, ,061,497 8,315, ,180,956 $ $ 556,286 6,180,956 $ 556, % Page 8 of 18

10 Table 8 shows weather conditions for the year 2 reporting period obtained from the National Weather Service, MSY Airport. Table 8 Weather Conditions May 2012 to April 2013 Weather Conditions Weather data for the New Orleans area is from the National Weather Service, MSY Airport. A summary of collected temperature data is listed below. Month May 2012 Jun 2012 Jul 2012 Aug 2012 Sep 2012 Oct 2012 Nov 2012 Dec 2012 Jan 2013 Feb 2013 Mar 2013 Apr 2013 Cooling Degree Days (65F) Heating Degree Days (65F) Avg Temperature (F) Avg Daily Max Temp (F) Avg Daily Min Temp (F) Maximum Temperature (F) Minimum Temperature (F) Average Daily Temperatures (F) Page 9 of 18

11 Figures 6 and 7 show VFDs for chilled water pumps 2 and 4. Figure 6 CHWP 2 VFD Figure 7 CHP 4 VFD Figure 8 shows chilled water pump 4 with motor. Figure 8 CHP 4 Pump and Motor Page 10 of 18

12 Figure 9 shows VFDs for condenser water pumps 3 and 4. Figure 9 CWP 3 and 4 VFDs EMCS Time of Day Scheduling and Demand Control Ventilation This FIM involved installing and/or enhancing the Apogee Energy Management and Control System in various buildings to perform a TOD scheduling function and for implementation of DCV of the Heating, Ventilating and Air Conditioning (HVAC) equipment. This FIM also included the installation of equipment necessary to provide advanced energy management and control system strategies for the Chilled Water Plant. The following list includes some of the additional equipment installed: Computer workstation and printer Control panel firmware and/or software upgrades Air flow measuring stations Outside air dampers Outside air damper electronic actuators Room CO 2 sensors Room temperature sensors Insertion probe temperature sensors for mixed air Insertion probe relative humidity sensors Unit equipment controllers or terminal equipment controllers Outside air temperature sensors Outside air dewpoint temperature sensor Room relative humidity sensors Page 11 of 18

13 Figure 9 shows the Apogee panels in the Central Plant. Figure 9 Apogee Panels Figure 10 shows a retrofitted control panel upgrade on the first floor of the Library. Figure 11 shows CO 2 and humidity sensors on the first floor of the Library. Figure 10 Retrofitted Control Panel Figure 11 CO 2 and Humidity Sensors Page 12 of 18

14 Figure 12 shows a damper actuator on the first floor of the Library. Figure 13 shows an air flow measuring station on the first floor of the Library. Figure 12 Damper Actuator Figure 13 Air Flow Measuring Station Figure 14 shows chilled water temperature sensors on the first floor of the Library. Figure 14 Chilled Water Temperature Sensors Page 13 of 18

15 Figure 15 shows an upgraded control panel on the 5 th floor of the Library Figure 15 Upgraded Control Panel Figure 16 shows an airflow measuring station on the fifth floor of the Library. Figure 17 shows a damper actuator on the fifth floor of the Library. Figure 16 Air Flow Measuring Station Figure 17 Damper Actuator Page 14 of 18

16 Figure 18 shows a control panel upgrade at the Xavier South Plant. Water Conservation Figure 18 Upgraded Control Panel This FIM involved the installation of low flow devises to reduce potable water consumption in various buildings. Figure 19 shows a urinal with a 0.5 gallons per flush (GPF) flush valve in the Library and Figure 20 shows a toilet with a 1.6 GPF flush valve in the Library. Figure GPF Flush Valve Figure GPF Flush Valve Page 15 of 18

17 Figure 21 shows the installation of a 0.5 gallons per minute (GPM) aerator on a faucet at Xavier South. Figure GPM Aerator Figure 22 shows the installation of a 1.6 GPF flush valve at Xavier South. Figure GPF Flush Valve Page 16 of 18

18 Water Conservation (Metered Cooling Tower Sewerage Savings) A flow meter was installed on the make up water line to the chilled water plant cooling tower. Most of the water consumed at the cooling tower is evaporated and does not reach the sewer system. The monthly consumption measured at the cooling tower flow meter should be recorded and reported to the Sewerage and Water Board so that a credit can be issued to the sewerage account. Currently, the water consumed at the cooling tower is not being reported to the Sewerage and Water Board, so no sewerage credits are being realized by Xavier University. Siemens is not reporting any cooling tower sewerage credits for this year, however, we reserve the right to initiate a baseline adjustment and claim these sewerage credits in future years. Page 17 of 18

19 Sustainability and Environmental Stewardship In addition to energy savings, this project resulted in a significant reduction in green house gases into the atmosphere from power plants producing electricity in the New Orleans area. A reduction in over 12,600,000 pounds of CO 2 was realized in the second year of this project and a reduction in over 21 million pounds of CO 2 has been realized over the two year term. Page 18 of 18

20 Annual Savings Report APPENDIX APPENDIX CHILLED WATER PLANT ENERGY GRAPHS Daily Chilled Water Usage Total Daily Chilled Water Usage [tonhrs] Average Daily Temperature [ F] Yea 2500 Avg Daily Chiller System Electric 2000 Average Daily Power [kw] Average Daily Temperature [ F] Year 2 Page 1 of 5

21 Annual Savings Report APPENDIX 1800 Chillers Electric Average Daily Power [kw] Average Daily Temperature [ F] Year Chilled Water Pumps Electric 250 Average Daily Power [kw] Average Daily Temperature [ F] Year 2 Page 2 of 5

22 Annual Savings Report APPENDIX 140 Condenser Pumps Electric 120 Average Daily Power [kw] Average Daily Temperature [ F] Year Cooling Towers Electric 200 Average Daily Power [kw] Average Daily Temperature [ F] Year 2 Page 3 of 5

23 Annual Savings Report APPENDIX 400 Total Condenser System Electric (Condenser Pumps & Cooling Tower) 350 Average Daily Power [kw] Average Daily Temperature [ F] Year Overall Chiller System Efficiency System Efficiency [kw/ton] ,000 1,500 2,000 2,500 3,000 Chilled Water Load [tons] Year 2 Page 4 of 5

24 Annual Savings Report APPENDIX Chiller System Component Efficiencies [kw/ton] Chiller System Efficiency Year Average Daily Temperature [ F] Overall System Chillers Pri & Sec Chw Pumps Cndsr Pumps Cooling Towers Chiller System Component Efficiencies [kw/ton] Chiller System Efficiency Year Average Daily Temperature [ F] Pri & Sec Chw Pumps Cndsr Pumps Cooling Towers Page 5 of 5

SIEMENS Year 3 Annual Energy Performance Report for Jackson County School District April 2010 May 2011

SIEMENS Year 3 Annual Energy Performance Report for Jackson County School District April 2010 May 2011 SIEMENS Year 3 Annual Energy Performance Report for Jackson County School District April 2010 May 2011 Submitted by: Siemens Industry, Inc. Building Technologies Division 150 Teal St. Suite 100 St. Rose,

More information

Condenser Water Heat Recovery"

Condenser Water Heat Recovery PLEASE MUTE CELL PHONES Condenser Water Heat Recovery" Julian de Bullet ASHRAE Distinguished Lecturer Director of Industry Relations McQuay International 703-395-5054 1 What Is Sustainability? sustainable

More information

Monitoring-Based Commissioning Best Practices Award Welch Hall

Monitoring-Based Commissioning Best Practices Award Welch Hall Monitoring-Based Commissioning Best Practices Award Welch Hall California State University, Dominguez Hills June 17th, 2014 Monitoring-Based Commissioning CSU Dominguez Hills Welch Hall Content Project

More information

Retrocommissioning Investigation Study of the Sheraton Chicago Hotel

Retrocommissioning Investigation Study of the Sheraton Chicago Hotel Retrocommissioning Investigation Study of the Sheraton Chicago Hotel & Towers Cityfront Center Tracy Phillips May 4, 2007 May 4, 2007 You can go anywhere you want, if you look serious and carry a clip

More information

Campus Annual Energy Use Report

Campus Annual Energy Use Report 2017 2018 Campus Annual Energy Use Report Macalester College 2017 2018 Energy Report Contents Year at a Glance... 3 Executive Summary... 3 Fuel Consumption & Cost... 4 Campus Fuel Consumption... 4 Campus

More information

LIBRARY ENERGY WALK- THROUGH. Andy Robinson, Training and Education, SEDAC

LIBRARY ENERGY WALK- THROUGH. Andy Robinson, Training and Education, SEDAC LIBRARY ENERGY WALK- THROUGH Andy Robinson, Training and Education, SEDAC ILLINOIS ENERGY NOW University of Illinois 360 Energy Group 2 WHAT WE DO SEDAC Free Services Outreach and Training Energy Assistance

More information

Retrocommissioning Investigation Report

Retrocommissioning Investigation Report Continuous Optimization for Commercial Buildings Program Retrocommissioning Investigation Report March 22, 2013 Prepared for: Thompson Rivers University International Building BC Hydro #:COP10-353 Prism

More information

Baffled Openings at Chain Link Fencing: Design shall consist of two end-posts set 4 feet apart, and a 10 foot wide chain-link fence panel equal in height as the adjacent fence. Chain link fence panel shall

More information

Energy Reduction Strategy Through 2020

Energy Reduction Strategy Through 2020 Through 2020 Revised: August 2017 Executive Summary Auburn University is a land, sea and space grant university established in 1856. The university consists of 11,629,000 square feet on 1,840 acres and

More information

PROJECT NAME CLEVELAND CLINIC PROJECT #

PROJECT NAME CLEVELAND CLINIC PROJECT # CLEVELAND CLINIC PROJECT # [This is a sample of a general project M&V specification these specifications should be incorporated into the HVAC Control specifications and modified to the specific job requirements]

More information

2/17/2017. Energy Accounting & Education. Topics (Electricity) Creating Electricity

2/17/2017. Energy Accounting & Education. Topics (Electricity) Creating Electricity Energy Accounting & Education Energy Managers Kermit King School District of La Crosse John Daily School District of Holmen 1 Topics (Electricity) Creating electricity Defining degree days Customer charges

More information

WAKE TECHNICAL COMMUNITY COLLEGE SUSTAINABLE ENERGY PLAN. Energy Plan

WAKE TECHNICAL COMMUNITY COLLEGE SUSTAINABLE ENERGY PLAN. Energy Plan Energy Plan 1 EXECUTIVE SUMMARY SCORECARD RESULTS An assessment of current energy management efforts was performed; current performance falls into all categories on the SEP-Performance Scorecard (Appendix

More information

ENERGY MANAGEMENT PLAN - HEADQUARTERS. ABC Winery 123 1st Street Franklin, NJ 12345

ENERGY MANAGEMENT PLAN - HEADQUARTERS. ABC Winery 123 1st Street Franklin, NJ 12345 ENERGY MANAGEMENT PLAN - HEADQUARTERS ABC Winery 123 1st Street Franklin, NJ 12345 TABLE OF CONTENTS Executive Summary 3 Background and Site Information 3 Summary 3 Energy Conservation Opportunities 4

More information

Sound HVAC Choices for Sustainable Design. Julian de Bullet

Sound HVAC Choices for Sustainable Design. Julian de Bullet PLEASE MUTE CELL PHONES Sound HVAC Choices for Sustainable Design Julian de Bullet Director of Industry Relations McQuay International ASHRAE Distinguished Lecturer 703-395-5054 1 2 Rising?? What Is Sustainability?

More information

National Indian Gaming Association 2005 Certification: Energy Management for Cost Savings Larry Kinney Synertech Systems Corporation On behalf of

National Indian Gaming Association 2005 Certification: Energy Management for Cost Savings Larry Kinney Synertech Systems Corporation On behalf of National Indian Gaming Association 2005 Certification: Energy Management for Cost Savings Larry Kinney Synertech Systems Corporation On behalf of CERT Wild Horse Casino in Umatilla Country, Oregon Dancing

More information

Reducing Hospital Energy Use and Maintaining Savings. Glen Anderson, PE

Reducing Hospital Energy Use and Maintaining Savings. Glen Anderson, PE Reducing Hospital Energy Use and Maintaining Savings Glen Anderson, PE AIA Quality Assurance The Building Commissioning Association is a Registered Provider with The American Institute of Architects Continuing

More information

Greening Your Business Energy Efficiency in Buildings

Greening Your Business Energy Efficiency in Buildings Greening Your Business Energy Efficiency in Buildings Ben J. Sliwinski Building Research Council School of Architecture University of Illinois at Urbana-Champaign Overview Introduction Where is the Money?

More information

Chilled Water Energy Savings Study

Chilled Water Energy Savings Study 1 Chilled Water Energy Savings Study Pressure Dependent Valve Sizing and Valve Authority Pressure Independent Valves (Mechanical and Electronic) Chilled Water System Design MIT Beta Site Study-Correcting

More information

Teague Research Center

Teague Research Center Continuous Commissioning Report for the Teague Research Center Building #445 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

ENERGY AS SERVICES COMPANY ESCO. Jamal E. Alostaz. Projects Engineer Al-Salem Johnson Controls

ENERGY AS SERVICES COMPANY ESCO. Jamal E. Alostaz. Projects Engineer Al-Salem Johnson Controls ENERGY AS SERVICES COMPANY ESCO Jamal E. Alostaz Projects Engineer Al-Salem Johnson Controls AGENDA About Johnson Controls Introduction to ESCO Case Study: Empire State Building, USA Project Information

More information

Energy Management Journey

Energy Management Journey Energy Management Journey Arnold Granger, P.E., CEM Director of Energy Management Dr. Yeqiao Zhu, P.E., MBA Director of Facilities Patient Care and Prevention Facilities Patient Treatment Research Facilities

More information

The baseline building system for compliance with Senate Bill 668 is defined by Appendix G,

The baseline building system for compliance with Senate Bill 668 is defined by Appendix G, Project: North Carolina A&T State University New Student Health Center SCO #: 08-08109-01A 1.0 Heating, Ventilating and Air Conditioning (HVAC) Baseline Building Systems Senate Bill 668 Compliance The

More information

Fifteen Year Plan for Energy Efficiency and Conservation Projects

Fifteen Year Plan for Energy Efficiency and Conservation Projects Fifteen Year Plan for Energy Efficiency and Conservation Projects Presented to the Board of Trustees of the Northeastern Ohio Universities Colleges of Medicine and Pharmacy, December, 2008, in accordance

More information

Xavier Energy Initiative

Xavier Energy Initiative Xavier Energy Initiative By Ron Perkins Report of August Site Visit To paraphrase Blaise Pascal, if I had more time I would have written a shorter report. In deference to those who do not share my enthusiasm

More information

A HYBRID MONITORING-MODELING PROCEDURE FOR ANALYZING THE PERFORMANCE OF LARGE CENTRAL CHILLING PLANTS

A HYBRID MONITORING-MODELING PROCEDURE FOR ANALYZING THE PERFORMANCE OF LARGE CENTRAL CHILLING PLANTS A HYBRID MONITORING-MODELING PROCEDURE FOR ANALYZING THE PERFORMANCE OF LARGE CENTRAL CHILLING PLANTS Ricardo Troncoso, P.E. Senior Engineer ACR Engineering, Incorporated 97 South Congress Avenue Austin,

More information

Optimizing Energy Use in a HealthCare Setting. Michael P. Della Barba Environmental Health & Engineering, Director of Commissioning

Optimizing Energy Use in a HealthCare Setting. Michael P. Della Barba Environmental Health & Engineering, Director of Commissioning Optimizing Energy Use in a HealthCare Setting Michael P. Della Barba Environmental Health & Engineering, Director of Commissioning AIA Quality Assurance The Building Commissioning Association is a Registered

More information

Optimizing Central Chilled Water Systems

Optimizing Central Chilled Water Systems Optimizing Central Chilled Water Systems OPTIMIZING CENTRAL CHILLED WATER SYSTEMS kent.peterson@p2seng.com 1 O P T I M I Z I N G C E N T R A L C H I L L E D W A T E R S Y S T E M S Kent W. Peterson, PE,

More information

CHERRY HILL TOWNSHIP SCHOOLS CHERRY HILL HIGH SCHOOL EAST 1750 KRESSON ROAD CHERRY HILL, NJ FACILITY ENERGY REPORT

CHERRY HILL TOWNSHIP SCHOOLS CHERRY HILL HIGH SCHOOL EAST 1750 KRESSON ROAD CHERRY HILL, NJ FACILITY ENERGY REPORT CHERRY HILL TOWNSHIP SCHOOLS CHERRY HILL HIGH SCHOOL EAST 1750 KRESSON ROAD CHERRY HILL, NJ 08003 FACILITY ENERGY REPORT TABLE OF CONTENTS I. HISTORIC ENERGY CONSUMPTION/COST... 2 II. FACILITY DESCRIPTION...

More information

UCSF Mission Bay Campus Arthur and Toni Rembe Rock Hall th Street San Francisco, California

UCSF Mission Bay Campus Arthur and Toni Rembe Rock Hall th Street San Francisco, California UCSF Mission Bay Campus Arthur and Toni Rembe Rock Hall 1550 4th Street San Francisco, California Monitoring Based Recommissioning Project Project Implementation: June 2005 to December 2005 Funded by a

More information

Hawaii Energy Policy Forum and Energy Industries Energy by Example Audit Awards Status Report October 2006-November 2007

Hawaii Energy Policy Forum and Energy Industries Energy by Example Audit Awards Status Report October 2006-November 2007 Hawaii Energy Policy Forum and Energy Industries Energy by Example Audit Awards Status Report October 2006-November 2007 Introduction In August 2006, the Hawaii Energy Policy Forum (Forum) invited over

More information

Application of a cooling tower model for optimizing energy use

Application of a cooling tower model for optimizing energy use Advances in Fluid Mechanics X 305 Application of a cooling tower model for optimizing energy use G. C. O Mary & D. F. Dyer Department of Mechanical Engineering, Auburn University, USA Abstract The overall

More information

REVISED: Year 4: July 2015 to June 2016 Energy Savings Performance Contracting Measurement and Verification Report

REVISED: Year 4: July 2015 to June 2016 Energy Savings Performance Contracting Measurement and Verification Report Year 4: July 2015 to June 2016 Energy Savings Performance Contracting Measurement and Verification Report University of Hawaii Community Colleges Oahu District REVISED: 10-28-16 Presented by: Joe Caldwell,

More information

Continuous Commissioning Leading Energy Project Process - An Industry Approach

Continuous Commissioning Leading Energy Project Process - An Industry Approach Continuous Commissioning Leading Energy Project Process - An Industry Approach Mingsheng Liu, Ph.D., P.E. Energy Systems Laboratory, University of Nebraska Jinrong Wang, P.E., Ken Hansen, P.E. Omaha Public

More information

Sample Reports. for. HAP v4.80 Example Problem

Sample Reports. for. HAP v4.80 Example Problem Sample Reports for HAP v4.80 Example Problem October, 2013 Carrier Software Systems Copyright 2013 Carrier Corporation, All Rights Reserved Introduction This document contains reports generated using the

More information

Texas Hospital. Central Plant Redesign. Central Utility Plant SECOND PLACE HEALTH CARE FACILITIES, EXISTING 2013 ASHRAE TECHNOLOGY AWARD CASE STUDIES

Texas Hospital. Central Plant Redesign. Central Utility Plant SECOND PLACE HEALTH CARE FACILITIES, EXISTING 2013 ASHRAE TECHNOLOGY AWARD CASE STUDIES This article was published in ASHRAE Journal, January 2014. Copyright 2014 ASHRAE. Posted at www. ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission

More information

Pharmaceutical Sustainability Initiatives

Pharmaceutical Sustainability Initiatives Pharmaceutical Sustainability Initiatives Duane Hagen, CEA Energy and Systems Optimization Steam and Condensate System Specialist Technical Training Instructor Primary Energy Sources Conversion of Energy

More information

Knowledge is Power Belimo Energy Valve CHW DELTA T MITIGATION STUDY AHR Expo Innovation Award Winner in the Category of Building Automation

Knowledge is Power Belimo Energy Valve CHW DELTA T MITIGATION STUDY AHR Expo Innovation Award Winner in the Category of Building Automation Knowledge is Power Belimo Energy Valve CHW DELTA T MITIGATION STUDY 2014 AHR Expo Innovation Award Winner in the Category of Building Automation The Belimo Energy Valve won the Technical Innovation of

More information

ENERGY AND WATER CONSERVATION AND DEMAND MANAGEMENT PLAN

ENERGY AND WATER CONSERVATION AND DEMAND MANAGEMENT PLAN ENERGY AND WATER CONSERVATION AND DEMAND MANAGEMENT PLAN 2014 2019 CONTENTS EXECUTIVE SUMMARY... 3 1. CENTENNIAL COLLEGE - DISTRIBUTION OF ENERGY CONSUMPTION IN 2012... 4 1.1. Overview of Centennial College

More information

AEE Technical Roundtable Measurement and Verification. Alec Stevens, PE April 8, 2014

AEE Technical Roundtable Measurement and Verification. Alec Stevens, PE April 8, 2014 AEE Technical Roundtable Measurement and Verification Alec Stevens, PE April 8, 2014 The Old Days What does DMI do? Engineering Consulting since 1989 Demand Management Institute Focused on Energy Efficiency,

More information

Project Information. Measure Description

Project Information. Measure Description Project Information Project ID#: CE07M016 Measure: Multiple Electric : 452,593 kwh, 8.84 kw, 39.26 kw Facility Type School Technology: Multiple Measure Description CH-1 - Chiller Plant Optimization and

More information

White Paper. HVLS Fans and Energy Savings. Dubai Case Study. Featuring Altra-Air Fans with WhalePower Technology from Envira-North Systems

White Paper. HVLS Fans and Energy Savings. Dubai Case Study. Featuring Altra-Air Fans with WhalePower Technology from Envira-North Systems HVLS Fans and Energy Savings Dubai Case Study White Paper This paper is designed to provide insight into a case study of a manufacturing facility in Dubai, UAE. At the 2,500m² air conditioned site, one

More information

Low-Hanging Fruit Simple Steps Toward Energy Effective Building Operations

Low-Hanging Fruit Simple Steps Toward Energy Effective Building Operations Low-Hanging Fruit Simple Steps Toward Energy Effective Building Operations Roger Ebbage Northwest Water / Energy Education Institute Lane Community College May 7-9 Enzian Inn - Leavenworth, Washington

More information

Project : Power & Fuel consumption - an engineering initiative. VPS Rockland, Dwarka.

Project : Power & Fuel consumption - an engineering initiative. VPS Rockland, Dwarka. Project : Power & Fuel consumption - an engineering initiative VPS Rockland, Dwarka. VPS Rockland Dwarka Well-designed compact 103 bed Multi speciality hospital Plot area of 1250 square meter, and build

More information

Strategies for Persistence: Measurement and Verification. Ryan Hughes PE, CEM, LEED AP Eaton Energy Solutions

Strategies for Persistence: Measurement and Verification. Ryan Hughes PE, CEM, LEED AP Eaton Energy Solutions Strategies for Persistence: Measurement and Verification Ryan Hughes PE, CEM, LEED AP Eaton Energy Solutions AIA Quality Assurance The Building Commissioning Association is a Registered Provider with The

More information

Timmins and District Hospital

Timmins and District Hospital Opportunity Assessment Timmins and District Hospital Draft Report December 10 th 2013 Submitted to: Tim Prokopetz, Manager, Materials - Biomedical Engineering Timmins and District Hospital Submitted by:

More information

Retro-Commissioning for Energy Efficiency

Retro-Commissioning for Energy Efficiency High Performance Buildings 2006 AABC Commissioning Group (ACG) April 6, 2006 Retro-Commissioning for Energy Efficiency Making buildings work. Better. Tom Poeling, P.E., CEM, LEED AP E M C Engineers, Inc.

More information

The Biggest Loser REDUCING HIGHER EDUCATION COSTS BY 50%

The Biggest Loser REDUCING HIGHER EDUCATION COSTS BY 50% The Biggest Loser REDUCING HIGHER EDUCATION COSTS BY 50% Ian Hadden, PE, LEED AP BD+C, CEM Director, Energy Management Services University of Arkansas at Little Rock 501-313-9597 ithadden@ualr.edu.com

More information

Optimizing Chilled Water Systems for Energy Efficiency and Occupant Comfort

Optimizing Chilled Water Systems for Energy Efficiency and Occupant Comfort AABC Commissioning Group AIA Provider Number 50111116 Optimizing Chilled Water Systems for Energy Efficiency and Occupant Comfort Course Number: CXENERGY1709 Mark Benevides Siemens April 26, 2017 Page

More information

City of Fort Collins Building Automation Systems Enhances Savings and Commissioning Efficiency Works Training

City of Fort Collins Building Automation Systems Enhances Savings and Commissioning Efficiency Works Training City of Fort Collins Building Automation Systems Enhances Savings and Commissioning Efficiency Works Training November 18, 2015 Agenda Commissioning Monitoring Based Commissioning Building Tune up Case

More information

Low Cost Building Automation System for Small- and Medium- Sized Commercial Buildings

Low Cost Building Automation System for Small- and Medium- Sized Commercial Buildings Low Cost Building Automation System for Small- and Medium- Sized Commercial Buildings Srinivas Katipamula, Ph.D. Staff Scientist, Pacific Northwest National Laboratory Other TAG Members: Irfan Rehmanji

More information

Indiana University Glick Eye Institute. LEED Measurement & Verification Plan

Indiana University Glick Eye Institute. LEED Measurement & Verification Plan Indiana University Glick Eye Institute LEED Measurement & Verification Plan April 10, 2012 1 Table of Contents General Introduction... 3 Facility Description... 4 M&V Objectives... 4 M&V Approach/Option...

More information

Greening Buildings at the Dallas/Fort Worth International Airport. Sustainable Communities Conference Dallas, TX. March 10, 2009

Greening Buildings at the Dallas/Fort Worth International Airport. Sustainable Communities Conference Dallas, TX. March 10, 2009 Greening Buildings at the Dallas/Fort Worth International Airport Sustainable Communities Conference Dallas, TX March 10, 2009 Agenda Energy Efficiency in New Construction Energy Efficiency in Retrofits

More information

NWC District Energy Campus Energy - RFQ Supporting Documentation. April 25, 2018

NWC District Energy Campus Energy - RFQ Supporting Documentation. April 25, 2018 NWC District Energy Campus Energy - RFQ Supporting Documentation April 25, 2018 ESTIMATED ENERGY DEMAND BY BUILDING Facility Name Area Energy Use Intensity Goal Estimated Total Energy Total Average Peak

More information

Retro-commissioning and on-going commissioning 23 November 2016

Retro-commissioning and on-going commissioning 23 November 2016 Retro-commissioning and on-going commissioning 23 November 2016 1 CONTENTS 1. Needs for Retro-Commissioning (RCx) 2. Retro-Commissioning (RCx) Definition and Scope 3. Briefing of RCx Process 4. Alternative

More information

September 22, Roy Hubbard HVAC Systems Technology

September 22, Roy Hubbard HVAC Systems Technology September 22, 2011 Roy Hubbard HVAC Systems Technology Lesson Objectives (YC-3) At the end of this session, you will understand: Understanding Chiller Energy Fundamentals Impact of VSDs (maintenance and

More information

OSU Richardson and Peavy Hall Energy Study: Energy Conservation Measure Analysis. January 25, 2012 {Revised April 30, 2012}

OSU Richardson and Peavy Hall Energy Study: Energy Conservation Measure Analysis. January 25, 2012 {Revised April 30, 2012} OSU Richardson and Peavy Hall Study: Conservation Measure Analysis January 25, 2012 OSU Richardson and Peavy Hall Study: Conservation Measure Analysis CONTENTS 1.0 Executive Summary... 1 2.0 Building

More information

Building Load and Energy Estimates Analysis. Instructor: Dr. Mumma. October 28, Thesis Building Sponsor s: INOVA Fairfax Hospital

Building Load and Energy Estimates Analysis. Instructor: Dr. Mumma. October 28, Thesis Building Sponsor s: INOVA Fairfax Hospital David Peterson Penn State AE, Mechanical INOVA Fairfax Hospital The INOVA Heart Institute David J. Peterson Mechanical Option Mechanical Technical Report #2b The INOVA HEART INSTITUTE AT INOVA Fairfax

More information

Allstream Centre Energy Performance Report

Allstream Centre Energy Performance Report Allstream Centre Energy Performance Report 2012 2014 TABLE OF CONTENTS INTRODUCTION... 1 ELECTRICAL CONSUMPTION... 2 ELECTRICAL ENERGY DISTRIBUTION... 3 BUILDING POWER AND SYSTEMS... 4 FACTORS CONTRIBUTING

More information

Water & Energy Conservation. Topics Covered

Water & Energy Conservation. Topics Covered Water & Energy Conservation Relationships & Opportunities Tony T. Gregg, P.E. Manager Water Conservation Program Austin Water Utility City of Austin, Texas Topics Covered 1. Basic Relationships Water/Energy

More information

Implementing Low-Cost Energy Savings Projects & Conducting Energy Audits

Implementing Low-Cost Energy Savings Projects & Conducting Energy Audits AEP Ohio Customer Seminar Implementing Low-Cost Energy Savings Projects & Conducting Energy Audits Presented by: Julie Birchfield Customer Manager Energy Optimizers, USA May, 2018 Test your Energy IQ 11

More information

Establishing a Baseline, Energy Audits and Energy Star s Portfolio Manager

Establishing a Baseline, Energy Audits and Energy Star s Portfolio Manager Establishing a Baseline, Energy Audits and Energy Star s Portfolio Manager Glenn Barnes Environmental Finance Center University of North Carolina at Chapel Hill 919-962-2789 glennbarnes@sog.unc.edu Energy

More information

9/13/2011. Mark Hanicits, Director of Facilities and Safety, MetroSouth Medical Center. Terry Malloy P.E., Cxa, Project Manager, Teng & Associates

9/13/2011. Mark Hanicits, Director of Facilities and Safety, MetroSouth Medical Center. Terry Malloy P.E., Cxa, Project Manager, Teng & Associates Mark Hanicits, Director of Facilities and Safety, MetroSouth Medical Center September 21 st, 2011 4:15pm 5:15pm Terry Malloy P.E., Cxa, Project Manager, Teng & Associates Energy consumption (BTU/SF) in

More information

18 th National Award Excellence in Energy Management Zonal Office, New Delhi

18 th National Award Excellence in Energy Management Zonal Office, New Delhi 18 th National Award Excellence in Energy Management 2017 Zonal Office, New Delhi Aug 30 & 31, 2017 Orientation Surrounded by green spaces in Lutyen s Delhi 5% façade facing South, 40 % façade facing West/SW

More information

University of San Diego

University of San Diego University of San Diego A comprehensive performance contract cuts utility costs, improves building operations and furthers sustainability initiatives. www.usa.siemens.com/usd s When it comes to sustainability,

More information

SMART HVAC & LIGHTING SYSTEMS. Savings From Two Major C&I End Uses

SMART HVAC & LIGHTING SYSTEMS. Savings From Two Major C&I End Uses SMART HVAC & LIGHTING SYSTEMS Savings From Two Major C&I End Uses September 21, 2016 PRESENTATION OVERVIEW Why this focus? Significant savings potential Smart controls coupled with more efficient technologies

More information

Water Auditing 101. William D. Chvala, Jr., CEM. Greg Sullivan, PE, CEM. Pacific Northwest National Laboratory. Pacific Northwest National Laboratory

Water Auditing 101. William D. Chvala, Jr., CEM. Greg Sullivan, PE, CEM. Pacific Northwest National Laboratory. Pacific Northwest National Laboratory Water Auditing 101 William D. Chvala, Jr., CEM Pacific Northwest National Laboratory Greg Sullivan, PE, CEM Pacific Northwest National Laboratory Water Auditing Goals Basic goals: Identify -- Quantify

More information

SURNA Grow Facility: Systems Comparison - IEA

SURNA Grow Facility: Systems Comparison - IEA SURNA Grow Facility: Systems Comparison - IEA May 2016 SURNA Grow Facility This analysis provides the projected energy and associated cost comparison between the Surna proposed facility in comparison to

More information

Advantages of Financing Continuous Commissioning As An Energy Conservation Retrofit Measure

Advantages of Financing Continuous Commissioning As An Energy Conservation Retrofit Measure Advantages of Financing Continuous Commissioning As An Energy Conservation Retrofit Measure Guanghua Wei, P.E. Malcolm Verdict, C.E.M Joseph T. Martinez Energy Systems Laboratory, 3581 TAMU Texas A&M University

More information

Results and Recommendations from Energy Audit of Koyukuk. For VEEP Grants. City of Koyukuk, Alaska

Results and Recommendations from Energy Audit of Koyukuk. For VEEP Grants. City of Koyukuk, Alaska ENERGY AUDIT POST INSTALLATION REPORT Results and Recommendations from Energy Audit of Koyukuk For VEEP Grants City of Koyukuk, Alaska June 20, 2012 Prepared By:, Inc. 6643 Brayton Drive Anchorage, AK

More information

TUR Continuing Education Conference November 20, 2008 PHILIPS

TUR Continuing Education Conference November 20, 2008 PHILIPS TUR Continuing Education Conference November 20, 2008 1. Who we are and what we do 2. The process we used for Asset Selection 3. Resource Conservation Plan for Water and Expected Change in Facility Wide

More information

YWCA 1503 S. Denver Tulsa, Oklahoma 5/18/2010 Performed By

YWCA 1503 S. Denver Tulsa, Oklahoma 5/18/2010 Performed By Energy Audit for YWCA 1503 S. Denver Tulsa, Oklahoma 5/18/2010 Performed By 220 E. 8th Street Tulsa, Oklahoma 74119 918-582.0229 Fax: 918.599.0665 www.craftontullsparks.com Table of Contents Cover Page...

More information

Union College Combined Cooling, Heat and Power Project

Union College Combined Cooling, Heat and Power Project Union College Combined Cooling, Heat and Power Project Presented by: Mark Donovan, PE Union College, Assistant Director of Utilities Aaron Bolhous, PEng CHA, Project Engineer Agenda Introduction to Union

More information

Local Government Energy Audit:

Local Government Energy Audit: Local Government Energy Audit: Energy Audit Report Alexander Kasser Theater Copyright 2017 TRC Energy Services. All rights reserved. Reproduction or distribution of the whole, or any part of the contents

More information

Building Operator Certification Level I

Building Operator Certification Level I Building Operator Certification Level I A Partnership of the CUNY Institute for Urban Systems Building Performance Lab, the CUNY School of Professional Studies, and the New York State Energy Research &

More information

Giuseppe Giordano Founder & CEO

Giuseppe Giordano Founder & CEO Giuseppe Giordano Founder & CEO www.enerbrain.com 1 Your innovation partner for a sustainable future 40% of the world s energy is consumed by buildings US Green Building Council and yet, how often have

More information

A Key Component of Environmental Sustainability Efforts and a Source of Substantial Cost Savings for FCGU. Dr. Simeon Komisar

A Key Component of Environmental Sustainability Efforts and a Source of Substantial Cost Savings for FCGU. Dr. Simeon Komisar ENERGY EFFICIENCY : A Key Component of Environmental Sustainability Efforts and a Source of Substantial Cost Savings for FCGU Dr. Simeon Komisar Environmental Sustainability Committee Member Associate

More information

Ground-Coupled Heat Pump And Energy Storage

Ground-Coupled Heat Pump And Energy Storage Ground-Coupled Heat Pump And Energy Storage By Ed Lohrenz, Member ASHRAE; and Sergio Almeida, P.Eng., Member ASHRAE Ground-coupled heat pump (GCHP) systems consume less purchased energy than an HVAC system

More information

Does Evaporative Cooling Make Sense in Arid Climates?

Does Evaporative Cooling Make Sense in Arid Climates? Does vaporative Cooling Make Sense in Arid Climates? xplores the trade-off between water use and energy savings, using three different water alternatives by employing energy and cost analyses of small-scale

More information

Mechanical Tech Report 2

Mechanical Tech Report 2 Mechanical Tech Report 2 Design Load Estimation and Energy Analysis M Resort Spa and Casino Tom M. Chirdon Faculty Advisor; William P. Bahnfleth October 24, 2008 Table of Contents 1.0 Executive summary

More information

Outline Chilled Water T Study AHU Coil Overview Cooling Overview Test Setup Data Analysis Findings Summary

Outline Chilled Water T Study AHU Coil Overview Cooling Overview Test Setup Data Analysis Findings Summary Improved Chilled Water Plant Performance with New Energy Valve (EV) Outline Chilled Water T Study AHU Coil Overview Cooling Overview Test Setup Data Analysis Findings Summary 6 December 2012 Boston Hotels

More information

Success with MEASUREMENT & VERIFICATION

Success with MEASUREMENT & VERIFICATION 2016 Success with MEASUREMENT & VERIFICATION Prepared for the North Carolina Department of Environmental Quality. Project funded by the U.S. Department of Energy, Office of Energy Efficiency and Renewable

More information

FirstEnergy s Pennsylvania Utilities. Energy Efficiency Programs for Business

FirstEnergy s Pennsylvania Utilities. Energy Efficiency Programs for Business FirstEnergy s Pennsylvania Utilities Energy Efficiency Programs for Business 2018 TODAY S AGENDA Introduction to Sodexo Summary of Pennsylvania Act 129 Overview of program website Overview of Application

More information

05/14/2012 THE CRIME OF IMPROPER ENERGY MANAGEMENT AGENDA

05/14/2012 THE CRIME OF IMPROPER ENERGY MANAGEMENT AGENDA THE CRIME OF IMPROPER ENERGY MANAGEMENT COOLING MANAGEMENT SOLUTIONS Dan Mascola AGENDA Promote Background Cooling Management Solutions Case Studies Additional Energy Savings Tips How To Start on Monday

More information

Sample Reports. for. HAP v4.90 Example Problem

Sample Reports. for. HAP v4.90 Example Problem Sample Reports for HAP v4.90 Example Problem December, 2014 Carrier Software Systems Copyright 2014 Carrier Corporation, All Rights Reserved Introduction This document contains reports generated using

More information

Integrating Standby Power and Steam Turbine Chillers for Better Resiliency at UNC Chapel Hill

Integrating Standby Power and Steam Turbine Chillers for Better Resiliency at UNC Chapel Hill Integrating Standby Power and Steam Turbine Chillers for Better Resiliency at UNC Chapel Hill IDEA 28 th Annual Campus Energy Conference Denver, Colorado Philip Barner, P.E. Director of Energy Services

More information

Optimized System for Your Bottom Line. Trane Training Class 1 Dec, 2017

Optimized System for Your Bottom Line. Trane Training Class 1 Dec, 2017 Optimized System for Your Bottom Line Trane Training Class 1 Dec, 2017 Total Cost of Ownership Setting your system for great payback Where is money spent over a 30 year lifetime? First Cost 4.9% Service

More information

1100 San Jacinto Legislative Budget Board (LBB) 1501 North Congress. Austin, Texas 78701

1100 San Jacinto Legislative Budget Board (LBB) 1501 North Congress. Austin, Texas 78701 October 1, 2018 Office of the Governor Mrs. Ursula Parks, Director 1100 San Jacinto Legislative Budget Board (LBB) Austin, Texas 78701 Robert E. Johnson Bldg. 5 th Floor 1501 North Congress Austin, Texas

More information

Final Report for National Grid USA Service Company. Evaluation of 2003 Custom HVAC Installations Part II. September 27, 2005.

Final Report for National Grid USA Service Company. Evaluation of 2003 Custom HVAC Installations Part II. September 27, 2005. Final Report for National Grid USA Service Company Evaluation of 2003 Custom HVAC Installations Part II September 27, 2005 Submitted by Select Energy Services, Inc. is the energy services subsidiary of

More information

Converting CAV to VAV in Florida: What does this really mean?

Converting CAV to VAV in Florida: What does this really mean? AABC Commissioning Group AIA Provider Number 50111116 Converting CAV to VAV in Florida: What does this really mean? Course Number: CXENERGY1707 Steve Harrell, CxA, CEM, SSRCx April 26, 2017 Credit(s) earned

More information

Energy Conservation at the University of Pittsburgh - FY2014 and Beyond

Energy Conservation at the University of Pittsburgh - FY2014 and Beyond Energy Conservation at the University of Pittsburgh - FY2014 and Beyond Energy Conservation has long been a priority in Facilities Management. Understanding the large impact of utility costs on the University

More information

LOGO. Trivium Level II Energy Audit

LOGO. Trivium Level II Energy Audit LOGO Trivium Level II Energy Audit Submission Date: 9/16/2016 Table of Contents 1.0 EXECUTIVE SUMMARY 3 2.0 SITE ENERGY CONSUMPTION 5 3.0 BACKGROUND INFORMATION 6 3.1 Description of the Client 6 3.2 Description

More information

VOORHEES TOWNSHIP BOARD OF EDUCATION OSAGE ELEMENTARY SCHOOL 128 E CHEWS LANDING RD, VOORHEES, NJ, FACILITY ENERGY REPORT

VOORHEES TOWNSHIP BOARD OF EDUCATION OSAGE ELEMENTARY SCHOOL 128 E CHEWS LANDING RD, VOORHEES, NJ, FACILITY ENERGY REPORT VOORHEES TOWNSHIP BOARD OF EDUCATION OSAGE ELEMENTARY SCHOOL 128 E CHEWS LANDING RD, VOORHEES, NJ, 08043 FACILITY ENERGY REPORT Voorhees Township Public Schools Osage Elementary School TABLE OF CONTENTS

More information

A Comprehensive Approach to Energy Management for Hotels & Resorts. PRESENTED BY: ROBERT GREENWALD, PEng, MBA May 18, 2011

A Comprehensive Approach to Energy Management for Hotels & Resorts. PRESENTED BY: ROBERT GREENWALD, PEng, MBA May 18, 2011 A Comprehensive Approach to Energy Management for Hotels & Resorts PRESENTED BY: ROBERT GREENWALD, PEng, MBA May 18, 2011 1 A Comprehensive Approach to Energy Management Continuous Improvement 2 Energy

More information

Commercial Retro-Commissioning Program Manual for 2015 SECTION 1

Commercial Retro-Commissioning Program Manual for 2015 SECTION 1 Commercial Retro-Commissioning Program Manual for 2015 SECTION 1 Introduction The Commercial Retro-Commissioning Program (RCx) is designed to achieve demand and energy savings in commercial facilities.

More information

Farm Energy IQ. Future. Tom Manning, New Jersey Agricultural Experiment Station

Farm Energy IQ. Future. Tom Manning, New Jersey Agricultural Experiment Station Farm Energy IQ Farms Farm Today Energy Securing Audits Our Energy Future Tom Manning, New Jersey Agricultural Experiment Station An energy audit is the process of determining energy consumption of a building

More information

K. RAHEJA CORPORATION PROGRAM OVERVIEW PROJECT TIMELINE: INORBIT MALL. India BUILDING RETROFIT CASE STUDY

K. RAHEJA CORPORATION PROGRAM OVERVIEW PROJECT TIMELINE: INORBIT MALL. India BUILDING RETROFIT CASE STUDY K. RAHEJA CORPORATION India BUILDING RETROFIT CASE STUDY PROGRAM OVERVIEW K. Raheja Corp (KRC), a leading real estate corporation that owns many properties in India, is working with the Clinton Climate

More information

Deep Dive Into Process Efficiency AEP November 14, 2017

Deep Dive Into Process Efficiency AEP November 14, 2017 Deep Dive Into Process Efficiency AEP November 14, 2017 Kelly Kissock Ph.D., P.E. Department of Mechanical and Aerospace Engineering / Renewable and Clean Energy University of Dayton, Dayton Ohio, U.S.A.

More information

Cornell University Chilled Water Best Management Practices Program 2015 Annual Report

Cornell University Chilled Water Best Management Practices Program 2015 Annual Report Cornell University Chilled Water Best Management Practices Program 2015 Annual Report Prepared by: Cornell University Facilities Services Energy and Sustainability Utilities Report Date: 26 January 2016

More information

ASHRAE. Wxá zç Performance Innovation Experience. Why Geothermal HVAC Systems Fill The Bill. Kirk Mescher, PE P PE. Education.

ASHRAE. Wxá zç Performance Innovation Experience. Why Geothermal HVAC Systems Fill The Bill. Kirk Mescher, PE P PE. Education. ASHRAE AEDG K-12K Why Geothermal HVAC Systems Fill The Bill Kirk Mescher, PE Education Wxá zç Performance Innovation Experience ENGINEERING Bright Solutions in Engineering P PE 1 Simply Efficient 1 2 3

More information

Existing Building Cx: Processes & Results A Cultural Journey. Barry Abramson Senior Vice President Servidyne

Existing Building Cx: Processes & Results A Cultural Journey. Barry Abramson Senior Vice President Servidyne Existing Building Cx: Processes & Results A Cultural Journey Barry Abramson Senior Vice President Servidyne AIA Quality Assurance Learning Objectives 1. Define the key steps in the process of retrocommissioning

More information