1 eport No. L/3132 Page 1 of 10 for ockwool UK Limited Pencoed Bridgend CF35 6NY Dated: 30 November 2009 LABOATOY MEASUEMENTS OF THE SOUND EDUCTION INDEX OF OCKWOOL ABLATIVE COATED BATTS eport Author: M Sawyer MIOA ACOUSTICAL INVESTIGATION & ESEACH OGANISATION LTD Duxons Turn Maylands Avenue Hemel Hempstead Hertfordshire HP2 4SB Telephone:

2 LABOATOY MEASUEMENTS OF THE SOUND EDUCTION INDEX OF OCKWOOL ABLATIVE COATED BATTS 1. INTODUCTION This report presents the results of measurements made in the AIO Acoustics Laboratory of the airborne sound insulation of ockwool Ablative Coated Batts when installed into a masonry wall. The measurements were made on 10 and 13 June Measurements of airborne sound insulation, Sound eduction Index (), were conducted in accordance with British Standard BS EN ISO 140 (ref 1). Single figure ratings of sound insulation performance, known as the Weighted Sound eduction Index ( w ) and Spectrum Adaptation Terms (C and C tr ), are derived from these measurements in accordance with British Standard BS EN ISO 717 (ref 2). AIO is a UKAS accredited testing laboratory No and measurements to the above British Standards are included on our schedule of accreditation. UKAS is the United Kingdom Accreditation Service. 2. SUMMAY OF ESULTS The results of the measurements presented in this report are summarised in the following table: AIO Test No. Test Specimen w (C;C tr ) db L/3132/1 Wall only 58 (-2;-6) L/3132/2 Wall with ockwool Ablative Coated Batts (double layer) 52 (-4;-6) L/3132/3 Wall with ockwool Ablative Coated Batts (single layer) 34 (-1;-2) Approved by: eport Author: D L Watts Eur Ing D L Watts BEng CEng FIOA Principal Consultant M Sawyer M Sawyer MIOA Laboratory Supervisor Page 2 of 10

3 3. TEST SPECIMEN DETAILS AND CONDITIONS 3.1 Wall only Test No. L/3132/1 The specimen filled a 2920 mm wide x 3005 mm high test aperture and comprised a 240 mm deep wall constructed from 100 mm thick dense aggregate concrete blocks laid flat and finished each side with sand and cement render. The estimated mass of the wall was 460 kg/m². See Data Sheet L/3132/D for further details. The blockwork wall was supplied and installed by a local builder working under AIO's direction. 3.2 Wall with ockwool Ablative Coated Batts (double layer) Test No. L/3132/2 The specimen filled a 2920 mm wide x 3005 mm high test aperture and comprised a 240 mm deep wall constructed from 100 mm thick dense aggregate concrete blocks laid flat and finished each side with sand and cement render. The estimated mass of the wall was 460 kg/m². A 600 mm x 600 mm hole was cut in the wall into which were set 2 no. mm ockwool Ablative Coated Batts set flush with the wall faces. 4.5 mm long water filled 48 mm OD PVC and 15 mm OD copper pipes passed through the coated panels. All joints were sealed with ockwool Acoustic Intumescent Sealant. See Data Sheet L/3132/D for further details. The blockwork wall was supplied and installed by a local builder working under AIO's direction, and the ockwool products and pipework by contractors working under the direction of ockwool Limited. 3.3 Wall with ockwool Ablative Coated Batts (single layer) Test No. L/3132/3 The specimen filled a 2920 mm wide x 3005 mm high test aperture and comprised a 240 mm deep wall constructed from 100 mm thick dense aggregate concrete blocks laid flat and finished each side with sand and cement render. The estimated mass of the wall was 460 kg/m². A 600 mm x 600 mm hole was cut in the wall into which was set a mm ockwool Ablative Coated Batt set flush with one wall face. 4.5 m long water filled 48 mm OD PVC and 15 mm OD copper pipes passed through the coated panels. All joints were sealed with ockwool Acoustic Intumescent Sealant. See Data Sheet L/3132/D for further details. The blockwork wall was supplied and installed by a local builder working under AIO's direction, and the ockwool products and pipework by contractors working under the direction of ockwool Limited. Page 3 of 10

4 AIO Date NOVEMBE 2009 No. L/3132/D DATA SHEET Client oc k woo I UK L" Imlte. d Drawing of Test Specimen Test Nos. L/ to L/3132/3: Test Configurations Test No. l/3132/1... Blockwork wall Test No. L/3132/2 Blockwork wall 15 Copper pipe 48 PVC pipe ockwool Ablative Coated Batts in 600 x 600 hole Test No. L/3132/3 Blockwork wall 15 Copper pipe 48 PVC pipe ockwool Ablative Coated Batts in 600 x 600 hole Not to scale Page 4 of 10 All dimensions in mm 01

5 Sound eduction Index according to BS EN ISO 140-3:1995 Test No. L/3132/1 Date of Test: 10 June 2002 Client: ockwool Limited Specimen: Wall only Installed by: AIO Specimen area: 8.77 m² Chamber Conditions Volume Air Temperature elative Humidity Source Chamber 98 m³ 17 C 85% eceiving Chamber 210 m³ 16 C % Frequency (Hz) One-third Measured result Shifted w reference curve Sound eduction Index, Frequency (Hz) ating according to BS EN ISO 717-1:1997 C -31 =-- db C -00 =-- db C = -1 db w (C;C tr ) = 58 (-2;-6) db C tr,-31 =-- db C tr,-00 =-- db C tr, = -6 db Evaluation based on laboratory measurement results obtained by an engineering method Approved by: D L Watts Eur Ing D L Watts BEng CEng FIOA Principal Consultant eport Author: M Sawyer M Sawyer MIOA Laboratory Supervisor Page 5 of 10

6 Sound eduction Index according to BS EN ISO 140-3:1995 Test No. L/3132/2 Date of Test: 13 June 2002 Client: ockwool UK Limited Specimen: Wall with ockwool Ablative Coated Batts (double layer) Installed by: AIO and ockwool UK Limited Specimen area: 8.77 m² Chamber Conditions Volume Air Temperature elative Humidity Source Chamber 98 m³ 18 C % eceiving Chamber 210 m³ 16 C % Frequency (Hz) One-third Measured result Shifted w reference curve Sound eduction Index, Frequency (Hz) ating according to BS EN ISO 717-1:1997 C -31 =-- db C -00 =-- db C = -3 db w (C;C tr ) = 52 (-4;-6) db C tr,-31 =-- db C tr,-00 =-- db C tr, = -6 db Evaluation based on laboratory measurement results obtained by an engineering method Approved by: D L Watts Eur Ing D L Watts BEng CEng FIOA Principal Consultant eport Author: M Sawyer M Sawyer MIOA Laboratory Supervisor Page 6 of 10

7 Sound eduction Index according to BS EN ISO 140-3:1995 Test No. L/3132/3 Date of Test: 13 June 2002 Client: ockwool UK Limited Specimen: Wall with ockwool Ablative Coated Batts (single layer) Installed by: AIO and ockwool UK Limited Specimen area: 8.77 m² Chamber Conditions Volume Air Temperature elative Humidity Source Chamber 98 m³ 18 C % eceiving Chamber 210 m³ 16 C % Frequency (Hz) One-third Measured result Shifted w reference curve Sound eduction Index, Frequency (Hz) ating according to BS EN ISO 717-1:1997 C -31 =-- db C -00 =-- db C = 0 db w (C;C tr ) = 34 (-1;-2) db C tr,-31 =-- db C tr,-00 =-- db C tr, = -2 db Evaluation based on laboratory measurement results obtained by an engineering method Approved by: D L Watts Eur Ing D L Watts BEng CEng FIOA Principal Consultant eport Author: M Sawyer M Sawyer MIOA Laboratory Supervisor Page 7 of 10

8 APPENDIX A1 - METHOD OF MEASUEMENT TO BS EN ISO 140-3:1995 The insulation of a specimen against airborne sound is measured under reverberant sound conditions in which sound is incident on one side of the specimen from all directions. The test specimen is erected in an aperture of approximately 9 square metres between two horizontally adjacent reverberant chambers which have been constructed to suppress the transmission of sound by flanking paths. To improve the diffusion of the sound fields, both chambers are irregularly shaped and contain several reflecting diffuser panels. If the test specimen is smaller than the test aperture, the test specimen is installed within a highly insulating infill partition, purpose built within the test aperture. When the test specimen is intended to be openable, then it is opened and closed five times immediately prior to testing. A steady sound source with a continuous spectrum in the frequency bands of interest is used to drive an omnidirectional loudspeaker which is located sequentially in two positions in the source chamber. Measurements of the sound levels are made simultaneously in both chambers at the one-third octave intervals from 100 Hz to 00 Hz as prescribed in the Standard (ref 1). The measurements are made with a microphone attached to a rotating microphone boom to obtain a good average of the sound pressure levels in each chamber. Measurements are also made of the noise level in the receiving chamber in the absence of the noise source in order that corrections for background noise may be made if appropriate. The Sound eduction Index () in decibels is calculated in each frequency band using the equation: S = L1 - L lg db Equation (i) A where: L 1 is the average sound pressure level in the source chamber L 2 S A is the average sound pressure level in the receiving chamber is the area of the test specimen (m²) is the equivalent absorption area in the receiving chamber (m²) The equivalent absorption area in the receiving chamber is determined from six sets of reverberation time measurements using a microphone connected to a rotating microphone boom. The measurements are made in accordance with International Standard ISO 354:1985 (ref 3) and the value of 'A' determined using Sabine's formula: A = 0.16V m² Equation (ii) T where: V is the volume of the receiving chamber (m³) T is the reverberation time of the receiving chamber (seconds) Page 8 of 10

9 The Weighted Sound eduction Index ( w ) in decibels and the Spectrum Adaptation Terms (C and C tr ), also in decibels, are calculated in accordance with British Standard BS EN ISO 717-1:1997 (ref 2) by comparison of the sixteen values of Sound eduction Index from 100 Hz to 31 Hz with the relevant curves. The calibration of all equipment is traceable via an unbroken chain to National Standards. APPENDIX A2 - PACTICAL APPLICATION OF TEST ESULTS It should be noted that the Sound eduction Index is a property of the test specimen alone. When the test specimen forms part of an enclosure, the sound insulation obtained will depend on additional factors such as the relative surface areas involved and the nature and acoustic characteristics of the receiving space. Also, in buildings the transmission of sound via alternative paths may not be negligible in comparison with transmission through the test specimen alone, particularly when the sound insulation of the test specimen is high. Such indirect sound transmission would result in a lower effective insulation. APPENDIX A3 - EFEENCES 1. British Standard BS EN ISO 140 Acoustics - Measurement of sound insulation in buildings and of building elements BS EN ISO 140-3:1995 Laboratory measurement of airborne sound insulation of building elements 2. British Standard BS EN ISO 717 Acoustics - ating of sound insulation in buildings and of building elements BS EN ISO 717-1:1997 Airborne sound insulation 3. International Standard ISO 354:1985 Acoustics - Measurement of sound absorption in a reverberation room Page 9 of 10

10 APPENDIX A4 - SCHEDULE OF EQUIPMENT Use Type Serial No. Measuring B&K 2144 eal Time Frequency Analyzer System B&K 4165 ½" Condenser Microphone B&K 4165 ½" Condenser Microphone B&K 2669 Microphone Pre-Amplifier B&K 2669 Microphone Pre-Amplifier NEAS 212 otating Microphone Boom NEAS 212 otating Microphone Boom Calibration B&K 4228 Pistonphone Page 10 of 10

Hive Acoustic Report.

Hive Acoustic Report. Hive Acoustic Report www.connection.uk.com Introduction An acoustic report of the equivalent sound absorption area of selected Connection products carried out by AIRO Acoustics Laboratory. The original

More information

Measurement of Airborne & Impact Sound Insulation. University of Durham, Pavilion H, Howlands Farm, Durham.

Measurement of Airborne & Impact Sound Insulation. University of Durham, Pavilion H, Howlands Farm, Durham. FAO: CARL SUTCLIFFE noise.co.uk noise.co.uk Ltd Report No U20 Measurement of Airborne & Impact Sound Insulation University of Durham, Pavilion H, Howlands Farm, Durham. For: The Concrete Centre 9/9/2005

More information

Report Number BTC 13505A

Report Number BTC 13505A Report Number BTC 13505A AN ACOUSTIC TEST REPORT COVERING A SERIES OF LABORATORY SOUND INSULATION TESTS TO BS EN ISO 140-3:1995 ON A 142MM THICK KINGSPAN TEK PANEL WITH VARIOUS DIRECT FIX AND INDEPENDENT

More information

Report Number BTC 13236A

Report Number BTC 13236A The Building Test Centre British Gypsum Limited East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email btc.testing@bpb.com Report Number BTC 13236A ACOUSTIC TEST REPORT COVERING

More information

Laboratory Airborne Sound Insulation of Stud Walls with Warmcel 500 Insulation. Prepared for:

Laboratory Airborne Sound Insulation of Stud Walls with Warmcel 500 Insulation. Prepared for: Laboratory Airborne Sound Insulation of Stud Walls with Warmcel 500 Insulation Prepared for: Excel Industries Limited Maerdy Industrial Estate (South) Rhymney Gwent NP22 5PY 18 th June 2010 0578 Tested

More information

ACOUSTIC PERFORMANCE AND STC RATING OF A PARTITION WALL WITH DOUBLE SOCKETS AND POLYSEAM PUTTY PADS

ACOUSTIC PERFORMANCE AND STC RATING OF A PARTITION WALL WITH DOUBLE SOCKETS AND POLYSEAM PUTTY PADS Our Ref: MK1801 ACOUSTIC PERFORMANCE AND STC RATING OF A PARTITION WALL WITH DOUBLE SOCKETS AND POLYSEAM PUTTY PADS AUCKLAND UNISERVICES LIMITED a wholly owned company of THE UNIVERSITY OF AUCKLAND PROJECT

More information

Report Number BTC 16234A

Report Number BTC 16234A Report Number BTC 16234A An acoustic test report covering laboratory sound insulation testing to BS EN ISO 140-3:1995 on a British Gypsum GypWall Partition, incorporating Gypframe 92mm Studs (92S50) at

More information

Test Report No. 100/12

Test Report No. 100/12 CENTUM STAVEBNÍHO INŽENÝSTVÍ, a. s. CENTE OF BUILDING CONSTUCTION ENGINEEING, Joint Stock Company workplace Zlín, K Cihelně 304, 764 32 Zlín - Louky Door and window testing laboratory, heat and acoustical

More information

Report Number BTC 14020A

Report Number BTC 14020A Report Number BTC 14020A AN ACOUSTIC TEST REPORT COVERING A LABORATORY SOUND INSULATION TEST TO BS EN ISO 140-3:1995 ON A BRITISH GYPSUM GYPWALL QUIET SF PARTITION. TWO SETS OF TWO GANG CAVITY WALLBOXES

More information

Determination of the sound reduction and sound absorption of a railroad noise barrier

Determination of the sound reduction and sound absorption of a railroad noise barrier TEST REPORT No. VTT-S-04940-14 October 29, 2014 Determination of the sound reduction and sound absorption of a railroad noise barrier Requested by: Soundim Oy TEST REPORT No. VTT-S-04940-14 1 (3) Requested

More information

Laboratory Airborne and Impact Sound Insulation of a Robust Details Appendix F Floor with PhotonStar LED Ltd. Downlights

Laboratory Airborne and Impact Sound Insulation of a Robust Details Appendix F Floor with PhotonStar LED Ltd. Downlights Laboratory Airborne and Impact Sound Insulation of a Robust Details Appendix F Floor with PhotonStar LED Ltd. Downlights Prepared for: PhotonStar LED Group plc Unit 8 Westlink Belbins Business Park Romsey

More information

INTRODUCTION SPECIMEN DESCRIPTION

INTRODUCTION SPECIMEN DESCRIPTION INTRODUCTION SPECIMEN DESCRIPTION Airborne sound transmission measurements were performed on a wall assembly with a single layer of the product identified by the client as QuietRock QR-530 Serenity on

More information

TECHNICAL DOCUMENT - SOUND INSULATION R9 SYSTEM. Dated: 30 August 2013

TECHNICAL DOCUMENT - SOUND INSULATION R9 SYSTEM. Dated: 30 August 2013 Level 2, 6 Kings Park Road West Perth, Western Australia, 6000 Phone: +61 8 9488 0848 ABN: 54 160 488 175 ACN: 160 488 175 FBM Licence Limited E-Mail: info@fbmlicence.com.au Web: www.fbmlicence.com.au

More information

KINETICS NOISE CONTROL TEST REPORT #AT001052

KINETICS NOISE CONTROL TEST REPORT #AT001052 KINETICS NOISE CONTROL TEST REPORT #AT001052 KINETICS NOISE CONTROL PRODUCTS: o ISOMAX CLIPS ACOUSTICAL RATINGS: o STC 66 o IIC 44 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA

More information

The specimen B W was identified by the client as a Skyfold Classic operable partition, with panels, seals, and clearances in configuration 4E.

The specimen B W was identified by the client as a Skyfold Classic operable partition, with panels, seals, and clearances in configuration 4E. TestingLaboratory: Client: Specimen: SpecimenID: Manufacturer: ConstructionDates: Testspecimenmountedby: NationalResearchCouncilCanada InstituteforResearchinConstruction 1200MontrealRoad Ottawa,OntarioK1A0R6

More information

LABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF STEEL CLAD PIR WALL PANELS (According to ISO )

LABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF STEEL CLAD PIR WALL PANELS (According to ISO ) Ref no: LABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF STEEL CLAD PIR WALL PANELS (According to ISO 10140 2) AUCKLAND UNISERVICES LIMITED a wholly owned company of THE UNIVERSITY OF AUCKLAND Report

More information

Evidence of Performance Airborne sound insulation of building components

Evidence of Performance Airborne sound insulation of building components Evidence of Performance Airborne sound insulation of building components Test Report No. 14-000251-PR01 (PB Z09-H01-04-en-02) Client Product Designation PRESS GLASS SA Nowa Wies Kopalniana 9 42-262 Poczesna

More information

BELLOTI, S.p.a. Via San Francesco, Cermenate (CO) - ITALY TEST REPORT

BELLOTI, S.p.a. Via San Francesco, Cermenate (CO) - ITALY TEST REPORT LGAI Technological Center, S.A. Campus de la UAB Ronda de la Font del Carme, s/n E - 08193 BELLATERRA (Barcelona) T +34 93 567 20 00 F +34 93 567 20 01 www.appluslaboratories.com 9/LE766 Bellaterra: 27th

More information

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure

More information

KINETICS NOISE CONTROL TEST REPORT #AT001035

KINETICS NOISE CONTROL TEST REPORT #AT001035 KINETICS NOISE CONTROL TEST REPORT #AT001035 KINETICS NOISE CONTROL PRODUCTS: o RIM I-2-16 ACOUSTICAL RATINGS: o STC 66 o IIC 63 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B-3140.1 KINETICS DRAWING

More information

LABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF PIR ROOF PANELS (According to ISO )

LABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF PIR ROOF PANELS (According to ISO ) Ref no: LABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF PIR ROOF PANELS (According to ISO 10140 2) AUCKLAND UNISERVICES LIMITED a wholly owned company of THE UNIVERSITY OF AUCKLAND Report prepared

More information

KINETICS NOISE CONTROL TEST REPORT #AT001067

KINETICS NOISE CONTROL TEST REPORT #AT001067 KINETICS NOISE CONTROL TEST REPORT #AT001067 KINETICS NOISE CONTROL PRODUCTS: o FLM- NEOPRENE PAD ACOUSTICAL RATINGS: o STC 69 o IIC 61 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA

More information

Laboratory measurements of the reduction of transmitted impact sound by floor coverings on a heavyweight reference floor (According to ISO )

Laboratory measurements of the reduction of transmitted impact sound by floor coverings on a heavyweight reference floor (According to ISO ) Reference no. T1638-1 Laboratory measurements of the reduction of transmitted impact sound by floor coverings on a heavyweight reference floor (According to ISO 10140 3) AUCKLAND UNISERVICES LIMITED a

More information

Classification report Airbourne sound insulation of building elements

Classification report Airbourne sound insulation of building elements Classification report Airbourne sound insulation of building elements Test report 161 32407/Z9e*) *) This is a translation of the test report No. 161 32407/Z9 dated 9 th October 2006 Client Reynaers Aluminium

More information

KINETICS NOISE CONTROL TEST REPORT #AT001021B

KINETICS NOISE CONTROL TEST REPORT #AT001021B KINETICS NOISE CONTROL TEST REPORT #AT001021B KINETICS NOISE CONTROL PRODUCTS: o ICW ACOUSTICAL RATINGS: o STC 76 o IIC 62 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B3463.13 KINETICS DRAWING NUMBER:

More information

Evidence of Performance Joint sound reduction of filling material

Evidence of Performance Joint sound reduction of filling material Evidence of Performance Test Report No. 13-002455-PR01 (PB Z6-K02-04-en-01) ift Rosenheim 13.09.2013 Client Soudal N. V. Everdongenlaan 18-20 2300 Turnhout Belgium Product Designation Thickness of sealant

More information

B Page 1 of 21-

B Page 1 of 21- Airborne and impact sound transmission measurements were performed on three floor assemblies which comprised the NRC 150 mm reference concrete slab and a 102 mm floating concrete slab. For report purposes,

More information

KINETICS NOISE CONTROL TEST REPORT #AT001049

KINETICS NOISE CONTROL TEST REPORT #AT001049 KINETICS NOISE CONTROL TEST REPORT #AT001049 KINETICS NOISE CONTROL PRODUCTS: o NONE ACOUSTICAL RATINGS: o STC 53 o IIC 27 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA o B-3463.1

More information

Signatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.

Signatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only. ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 492: Laboratory Measurement of Impact Sound Transmission through Floor- Ceiling Assemblies Using

More information

1.0 INTRODUCTION BUILDING REGULATIONS SOUND INSULATION REQUIREMENTS TEST PROCEDURE AND ANALYSIS...3

1.0 INTRODUCTION BUILDING REGULATIONS SOUND INSULATION REQUIREMENTS TEST PROCEDURE AND ANALYSIS...3 Concrete Centre Limited Bron Derw Residential Development, Colwyn Bay Sound Insulation Test Report 25 July 2005 PROJECT: CLIENT: Bron Derw Residential Development, Colwyn Bay Concrete Centre Limited Riverside

More information

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure

More information

KINETICS NOISE CONTROL TEST REPORT #AT001110

KINETICS NOISE CONTROL TEST REPORT #AT001110 KINETICS NOISE CONTROL TEST REPORT #AT001110 KINETICS NOISE CONTROL PRODUCTS: o NONE ACOUSTICAL RATINGS: o STC 53 o IIC 29 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o REPORT NO. A1-010601.1 o DATED:

More information

TEST REPORT No : DATE OF ISSUE : 3 October 2016 Page 1 of 9

TEST REPORT No : DATE OF ISSUE : 3 October 2016 Page 1 of 9 Acoustic Testing Laboratory College of Science & Technology The University of Salford Salford, Greater Manchester M5 4WT, United Kingdom T: +44 (0) 161 295 4615 F: +44 (0) 161 295 4456 E: d.j.mccaul@salford.ac.uk

More information

TEST REPORT No : DATE OF ISSUE : 5 October 2016 Page 1 of 9

TEST REPORT No : DATE OF ISSUE : 5 October 2016 Page 1 of 9 Acoustic Testing Laboratory College of Science & Technology The University of Salford Salford, Greater Manchester M5 4WT, United Kingdom T: +44 (0) 161 295 4615 F: +44 (0) 161 295 4456 E: d.j.mccaul@salford.ac.uk

More information

ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements

ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements 1 of 7 TEST : Acoustical Surfaces, Inc. Report Date: May 25, 2011 Test Date: September 28, 2010 Test

More information

ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements

ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements 1 of 7 TEST : Acoustical Surfaces, Inc. Report Date: May 25, 2011 Test Date: September 28, 2010 Test

More information

TEST REPORT No. VTT-S

TEST REPORT No. VTT-S TEST REPORT No. VTT-S-03117-16 1.8.2016 Determination of sound absorption and class of Yeseco Acoustic Panels in a reverberation room according to SFS EN ISO 354-2003 and SFS EN ISO 11654-1997 Requested

More information

Sound Insulation for Glass and Panel

Sound Insulation for Glass and Panel SEMINAR ON TESTING AND CERTIFICATION OF GREEN CONSTRUCTION MATERIALS Sound Insulation for Glass and Panel Ir Dr CHONG Fan HIGHLIGHTS 1. Sound insulation of building construction 2. Sound insulation tests

More information

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: PAC INTERNATIONAL, LLC

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: PAC INTERNATIONAL, LLC ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: PAC INTERNATIONAL, LLC TYPE: Wall, Steel (0.018" / 25 ga), RSIC-V, STC 67 DATA FILE NO: E4748.01A STC 67 OITC 56 Test Specimen Identification: (Source

More information

SPEEDPANEL. Fire & Acoustic Rated Wall Systems. Speedpanel. Intertenancy systems SPEEDPANEL

SPEEDPANEL. Fire & Acoustic Rated Wall Systems. Speedpanel. Intertenancy systems SPEEDPANEL SPEEDPANEL R Fire & Acoustic Rated Wall Systems Speedpanel Intertenancy systems 3 SPEEDPANEL CONTENTS 51mm Speedpanel Intertenancy System 04 Wall Type: 22D 05 Footprint 187mm FRL -/60/60 Rw + Ctr 50 Report

More information

Evidence of Performance Joint sound reduction of filling material

Evidence of Performance Joint sound reduction of filling material Evidence of Performance Joint sound reduction of filling material Test report 167 41891/1e*) *)This is a translation of the test report 167 41891/Z1 dated 8 October 2009 Client VBH Holding AG Siemensstr.

More information

THE FRAME RESIDENTIAL DEVELOPMENT, SPORTCITY, MANCHESTER THE CONCRETE CENTRE LTD 1.0 INTRODUCTION...2

THE FRAME RESIDENTIAL DEVELOPMENT, SPORTCITY, MANCHESTER THE CONCRETE CENTRE LTD 1.0 INTRODUCTION...2 Concrete Centre Limited The Frame Residential Development, Sport City, Manchester Sound Insulation Test Report 2 August 2005 PROJECT: CLIENT: The Frame Residential Development, Sportcity, Manchester Concrete

More information

KINETICS NOISE CONTROL TEST REPORT # AT001084

KINETICS NOISE CONTROL TEST REPORT # AT001084 KINETICS NOISE CONTROL TEST REPORT # AT001084 KINETICS NOISE CONTROL PRODUCTS: o MODEL ISOGRID ACOUSTICAL RATINGS: o STC 63 o IIC 50 TESTING AGENCY & REPORT NUMBER: o NRC-CNRC o B-3463.6 KINETICS DRAWING

More information

Measurement of Sound Absorption Coefficient for Perfopan slotted Wall Panels Code No. SLT 7x7-PR 12%, DS 270, on 45 mm mineral wool

Measurement of Sound Absorption Coefficient for Perfopan slotted Wall Panels Code No. SLT 7x7-PR 12%, DS 270, on 45 mm mineral wool DELTA Test Report TEST Reg. no. 100 Measurement of Sound Absorption Coefficient for Perfopan slotted Wall Panels Code No. SLT 7x7-PR 12%, DS 270, on 45 mm mineral wool Client: Aktan Mobilya Fabrikasi,

More information

19 th INTERNATIONAL CONGRESS ON ACOUSTICS MADRID, 2-7 SEPTEMBER 2007 A METHODOLOGY TO MEASURE THE ACOUSTIC PERFORMANCE OF ACCESS FLOORS

19 th INTERNATIONAL CONGRESS ON ACOUSTICS MADRID, 2-7 SEPTEMBER 2007 A METHODOLOGY TO MEASURE THE ACOUSTIC PERFORMANCE OF ACCESS FLOORS 19 th INTERNATIONAL CONGRESS ON ACOUSTICS MADRID, 2-7 SEPTEMBER 2007 A METHODOLOGY TO MEASURE THE ACOUSTIC PERFORMANCE OF ACCESS FLOORS PACS: 43.55.-e Asdrubali, Francesco 1 ; D Alessandro, Francesco 2

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ACOUSTIBLOK, INC. WALL ASSEMBLY: #1

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ACOUSTIBLOK, INC. WALL ASSEMBLY: #1 ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: ACOUSTIBLOK, INC. WALL ASSEMBLY: #1 TYPE: Standard 8" Hollow Block Wall With Single Stud Wall Construction SOUND ISOLATION MATERIAL: Acoustiblok

More information

Evidence of Performance Joint sound reduction of filling material

Evidence of Performance Joint sound reduction of filling material Evidence of Performance Test Report No. 13-002455-PR02 (PB-K05-04-en-01) ift Rosenheim 10.09.2013 Client Soudal N. V. Everdongenlaan 18-20 2300 Turnhout Belgium Product Designation Density Special features

More information

A L I O N Technical Center. Test Report

A L I O N Technical Center. Test Report FOR: Spartanburg, SC Sound Absorption CONDUCTED: 2018-09-14 Page 1 of 8 ON: R_1 76778 D01-0445B EFSL61W Fabric over 2 in. fiberglass insulation TEST METHOD Riverbank Acoustical Laboratories is accredited

More information

A L I O N Technical Center. Test Report

A L I O N Technical Center. Test Report FOR: Spartanburg, SC Sound Absorption CONDUCTED: 2018-09-14 Page 1 of 9 ON: R_1 76437 11634-12A EFFL61W Fabric over 2 in. fiberglass insulation TEST METHOD Riverbank Acoustical Laboratories is accredited

More information

Laboratory Measurement of Impact Sound Insulation of Floor Coverings on a Heavyweight Concrete Slab Floor

Laboratory Measurement of Impact Sound Insulation of Floor Coverings on a Heavyweight Concrete Slab Floor Laboratory Measurement of Impact Sound Insulation of Floor Coverings on a Heavyweight Concrete Slab Floor Report INR183/R1 April 2013 Golden Field Corporation Pty Ltd 13 Olver Street Preston VIC, 3072

More information

Downlight Mitts Downlight Mitt Acoustic Test Report

Downlight Mitts Downlight Mitt Acoustic Test Report Vipac Engineers & Scientists Ltd 279 Normanby Road, Private Bag 16 Document No. Port Melbourne VIC 3207 30B-11-0090-TRP-595139-1 t. +61 3 9647 9700 f. +61 3 9646 4370 23 May 2011 www.vipac.com.au Page

More information

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS EXPOSED NU SHADEX PERFORATED PLASTER CEILING TILES (600MM

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS EXPOSED NU SHADEX PERFORATED PLASTER CEILING TILES (600MM RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON

More information

KINETICS NOISE CONTROL TEST REPORT #AT001032

KINETICS NOISE CONTROL TEST REPORT #AT001032 KINETICS NOISE CONTROL TEST REPORT #AT001032 KINETICS NOISE CONTROL PRODUCTS: o ICC ACOUSTICAL RATINGS: o STC 84 o IIC 70 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B-3448.12 KINETICS DRAWING NUMBER:

More information

FIELD IMPACT INSULATION TESTS 133 SCARBOROUGH STREET, SOUTHPORT TEST REPORT

FIELD IMPACT INSULATION TESTS 133 SCARBOROUGH STREET, SOUTHPORT TEST REPORT Commissioned by: National Flooring Distributors Pty Ltd Date: 26 June 2015 Project number: 3872 Version: V.0 Author: Eric Huang 24 Mexicanus Drive, PO Box 790, Park Ridge Queensland 4125 Australia p. +61

More information

Testing Procedure: AS ISO

Testing Procedure: AS ISO RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON

More information

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: GAMCO CORPORATION. Series/Model: CW250

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: GAMCO CORPORATION. Series/Model: CW250 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: GAMCO CORPORATION Series/Model: CW250 Type: Two-Lite Curtain Wall System Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC

More information

Roomtmove 3/9 Church Road MAddington WA 6109

Roomtmove 3/9 Church Road MAddington WA 6109 Report ALA 14-084-1 Measurement of the Sound Absorption in a Reverberation Room ENDUROPANEL 40/10 Perf 18mm slotted ply Tested to AS / ISO 354-2006 Revision 1 Roomtmove 3/9 Church Road MAddington WA 6109

More information

H R2 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CR LAURENCE CO., INC. Series/Model: 487-AR. Type: Office Partition

H R2 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CR LAURENCE CO., INC. Series/Model: 487-AR. Type: Office Partition H0258.01-303-11-R2 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: CR LAURENCE CO., INC. Series/Model: 487-AR Type: Office Partition Glazing: 1/4" Tempered Interior, 3-1/2" Air Space, 1/4" Tempered

More information

H R2 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CR LAURENCE CO., INC. Series/Model: 487-AR. Type: Office Partition

H R2 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CR LAURENCE CO., INC. Series/Model: 487-AR. Type: Office Partition H0258.04-303-11-R2 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: CR LAURENCE CO., INC. Series/Model: 487-AR Type: Office Partition Glazing: 1/4" Laminate Interior, 3-1/2" Air Space, 3/8" Laminate

More information

Test report No B0082 IN CM 26-M56-I

Test report No B0082 IN CM 26-M56-I Test report No B0082 IN CM 26-M56-I AKUSTIKA ARLOA kudeatzailea: ACOUSTIC AREA managed by: Laboratory measurements of sound insulation TEST SPECIMEN: False ceiling (3 plasterboards) with Akustik 4 supports

More information

Test report No B0082 IN CM 26-M55-I

Test report No B0082 IN CM 26-M55-I Test report No B0082 IN CM 26-M55-I AKUSTIKA ARLOA kudeatzailea: ACOUSTIC AREA managed by: Laboratory measurements of sound insulation TEST SPECIMEN: False ceiling (2 plasterboards) with Akustik 4 supports

More information

Impact Sound Testing of Floor Covering on a Heavyweight Standard Floor

Impact Sound Testing of Floor Covering on a Heavyweight Standard Floor Impact Sound Testing of Floor Covering on a Heavyweight Standard Floor Report INR171/R1 June 2011 Gerflor Australasia Pty Ltd 17 Cato Street Hawthorn East VIC 3123 Enquiries should be addressed to: Manager

More information

A L I O N Technical Center. Test Report. RAL -A CONDUCTED: Page 1 of 9 ON: BioMontage Panels, Pole Moss

A L I O N Technical Center. Test Report. RAL -A CONDUCTED: Page 1 of 9 ON: BioMontage Panels, Pole Moss CLIENT: Sound Absorption Waterbury, CT CONDUCTED: 2019-02-28 Page 1 of 9 ON: BioMontage Panels, Pole Moss TEST METHODOLOGY Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce,

More information

Sound Insulation Test Easterton of Duntelchaig, Farr, Inverness, IV2 6AW

Sound Insulation Test Easterton of Duntelchaig, Farr, Inverness, IV2 6AW 10 Colinton Road Edinburgh, EH10 5DT T:0845 062 0000 F: 0131 455 2563 E: rmp@napier.ac.uk I: w w w.rmp.biz BRIEF FOR CONSULTANCY: To assess the level of sound insulation of the party wall in the new build

More information

PFC Corofil Coated Panel System

PFC Corofil Coated Panel System FIRE RATINGS. Tested to BS 476:Parts 20 & 22:1987 EN:1366-3:2009 0 2hr 4hr Fire Rating TECHNICAL INFORMATION. Available from our technical sales office. Email tech@pfc-corofil.com for: Safety Data Sheet

More information

Report. Laboratory for Acoustics. determination of the airborne sound insulation of a Rockdelta NoiStop Green barrier

Report. Laboratory for Acoustics. determination of the airborne sound insulation of a Rockdelta NoiStop Green barrier Report Member ONRI ISO-9001: 2000 certified Laboratory for Acoustics determination of the airborne sound insulation of a Rockdelta NoiStop Green barrier Report number H 3375-1E dd. 22 December 2008 Peutz

More information

NO. 19 WILBERFORCE ROAD COXHEATH, MAIDSTONE, KENT ME17 4HD SOUND INSULATION TESTING. On behalf of: Oscar Acoustics

NO. 19 WILBERFORCE ROAD COXHEATH, MAIDSTONE, KENT ME17 4HD SOUND INSULATION TESTING. On behalf of: Oscar Acoustics NO. 19 WILBERFORCE ROAD COXHEATH, MAIDSTONE, KENT ME17 4HD SOUND INSULATION TESTING On behalf of: Oscar Acoustics Report No. MRL/100/093c.1v1 November 2011 Report No. MRL/100/093c.1v1 November 2011 NO.

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ALL SEASONS DOOR & WINDOW, MFG SERIES/MODEL: A500. TYPE: Double Hung Window

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ALL SEASONS DOOR & WINDOW, MFG SERIES/MODEL: A500. TYPE: Double Hung Window ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: ALL SEASONS DOOR & WINDOW, MFG SERIES/MODEL: A500 TYPE: Double Hung Window Data File No. 97455.01 Summary of Test Results Glazing (Nominal Dimensions)

More information

A L I O N Technical Center. Test Report

A L I O N Technical Center. Test Report FOR: Lebanon, PA Impact Sound Transmission CONDUCTED: 2017-07-12 Page 1 of 8 ON: Quarry Floor Tiles and Regupol SonusPlus (underlayment) over 8 inch Concrete Slab (no Ceiling) TEST METHOD Riverbank Acoustical

More information

CONDUCTED: 28 November 2012 Page 1 of 5

CONDUCTED: 28 November 2012 Page 1 of 5 FOR: Guayaquil, Ecuador Sound Absorption CONDUCTED: 28 November 2012 Page 1 of 5 ON: Acoustical Panels TEST METHOD The test method conformed explicitly with the requirements of the ASTM Standard Test Method

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Classic-Craft, Fiber Classic, and Smooth Star

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Classic-Craft, Fiber Classic, and Smooth Star ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Classic-Craft, Fiber Classic, and Smooth Star TYPE: 3/8 Impact Rated Side Hinged Door ATI Data File No. 74385.01A*

More information

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS CELL AIR 1200MM

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS CELL AIR 1200MM RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON

More information

A L I O N Technical Center. Test Report. RAL -A CONDUCTED: Page 1 of 9 ON: BioMontage Panels - Reindeer Moss

A L I O N Technical Center. Test Report. RAL -A CONDUCTED: Page 1 of 9 ON: BioMontage Panels - Reindeer Moss CLIENT: Sound Absorption Waterbury, CT CONDUCTED: 2019-02-25 Page 1 of 9 ON: BioMontage Panels - Reindeer Moss TEST METHODOLOGY Riverbank Acoustical Laboratories is accredited by the U.S. Department of

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Liberty, MO. Sound Transmission Loss CONDUCTED: 2016-02-09 Page 1 of 8 ON: 3/4" Insulated Glazed Unit TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce,

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 8/0 Sliding Patio Door Summary of Test Results ATI Data File No. Glazing (Nominal Dimensions) STC

More information

A L I O N Technical Center. Test Report

A L I O N Technical Center. Test Report FOR: Dublin, OH Sound Transmission Loss CONDUCTED: 2018-03-30 Page 1 of 8 ON: KNM-100B Limp Mass Vinyl TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce, National

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Margate, FL. Sound Absorption CONDUCTED: 2015-09-22 Page 1 of 8 ON: Micro-Perforated Acoustical Aluminum Ceiling Tile with SoundTex - #MPA-1 Over 3.5" R-13 Fiberglass TEST METHOD Riverbank Acoustical

More information

LABORATORY MEASUREMENT OF THE SOUND REDUCTION IMPROVEMENT INDEX BY ACOUSTICAL LININGS DUE ONLY TO RESONANT TRANSMISSION

LABORATORY MEASUREMENT OF THE SOUND REDUCTION IMPROVEMENT INDEX BY ACOUSTICAL LININGS DUE ONLY TO RESONANT TRANSMISSION LABORATORY MEASUREMENT OF THE SOUND REDUCTION IMPROVEMENT INDEX BY ACOUSTICAL LININGS DUE ONLY TO RESONANT TRANSMISSION PACS REFERENCE: 3.55 Rg Hopkins, Carl Acoustics Centre BRE Watford WD25 9XX UK Tel:

More information

Conducting A Sound Insulation Test

Conducting A Sound Insulation Test Conducting A Sound Insulation Test . Why Test? Dwelling-houses, flats and rooms for residential purposes shall be designed and constructed in a such a way that they provide reasonable resistance to sound

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 6/8 Sliding Patio Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 6/8 Sliding Patio Door ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 6/8 Sliding Patio Door ATI Data File No. 74387.01 74387.01A* Summary of Test Results Glazing (Nominal

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: St. Louis, MO. Sound Absorption CONDUCTED: 2015-04-08 Page 1 of 7 ON: Acoustical Wrapped Panel(AWP) - 2 Inch Truetone with Polyester Svelte Face TEST METHOD Riverbank Acoustical Laboratories is accredited

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Liberty, MO. Sound Transmission Loss CONDUCTED: 2016-02-09 Page 1 of 8 ON: 3/4" Insulated Glazed Unit with Absorbar Impact Absorption Muntins + Absorbud Impact Absorption Intersects TEST METHOD Riverbank

More information

FIREPRO FIRESTOP PIPE COLLARS. Firestop solution for plastic pipework penetrations

FIREPRO FIRESTOP PIPE COLLARS. Firestop solution for plastic pipework penetrations FIREPRO FIRESTOP PIPE COLLARS Firestop solution for plastic pipework penetrations FIREPRO FIRESTOP PIPE COLLARS Firestop solution for plastic pipework penetrations. ROCKWOOL Firestop Pipe s provide a simple

More information

A L I O N Technical Center. Test Report

A L I O N Technical Center. Test Report FOR: Dublin, OH Sound Transmission Loss CONDUCTED: 2018-03-30 Page 1 of 9 ON: KNM-100AL Limp Mass Vinyl with Reinforced Aluminum Foil Face TEST METHOD Riverbank Acoustical Laboratories is accredited by

More information

REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT

REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E90 SOUND TRANSMISSION LOSS TESTING ON A STEEL STUD WALL ASSEMBLY WITH SONUSCLIP REPORT NUMBER H7677.03-113-11-R0 TEST DATE 11/20/17

More information

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP. TYPE: Picture Window

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP. TYPE: Picture Window AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP TYPE: Picture Window ATI Data File No. 71965.01A 71965.01B Summary of Test Results Glazing

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door with Impact Glass

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door with Impact Glass ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 8/0 Sliding Patio Door with Impact Glass ATI Data File No. 74391.01 74391.01A* Summary of Test Results

More information

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: Fabri Trak System. TYPE: Upholstered Panel

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: Fabri Trak System. TYPE: Upholstered Panel ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: Fabri Trak System TYPE: Upholstered Panel Summary of Test Results Sample ID Number & Sample Description 1/3 Octave

More information

A L I O N Technical Center. Test Report

A L I O N Technical Center. Test Report FOR: Beachwood, OH Impact Sound Transmission CONDUCTED: 2017-11-15 Page 1 of 8 ON: LVT flooring over Peacemaker Soundproofing Underlayment over 8" Concrete Slab No Ceiling TEST METHOD Riverbank Acoustical

More information

REPORT 3933 US ROUTE 11, CORTLAND, NEW YORK, 13045

REPORT 3933 US ROUTE 11, CORTLAND, NEW YORK, 13045 REPORT 3933 US ROUTE 11, CORTLAND, NEW YORK, 13045 FOR THE SCOPE OF LAB CODE 100402-0. Order No. 100667931 Date: May 23, 2012 REPORT NO. 100667931CRT-001a SOUND TRANSMISSION LOSS TEST AND CLASSIFICATION

More information

Ozone Panel 120 Acoustic Assessment and Optimization

Ozone Panel 120 Acoustic Assessment and Optimization Vipac Engineers & Scientists Ltd 279 Normanby Road, Private Bag 16 Document No. Port Melbourne VIC 3207 30U-12-0010-DRP-258904-0 Australia t. +61 3 9647 9700 f. +61 3 9646 4370 1 Aug 2012 www.vipac.com.au

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 900 Series. TYPE: Out-swing Double Terrace Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 900 Series. TYPE: Out-swing Double Terrace Door ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: UNITED STATES ALUMINUM SERIES/MODEL: 900 Series TYPE: Out-swing Double Terrace Door ATI Data File No. 63136.01 Summary of Test Results Glazing

More information

OLIVE VILLAS, SANDOWN LANE, LIVERPOOL, L15 4HU

OLIVE VILLAS, SANDOWN LANE, LIVERPOOL, L15 4HU MEASUREMENT OF THE SOUND INSULATION OF SEPARATING FLOORS on behalf of URBAN BUBBLE LTD for the development at OLIVE VILLAS, 38-40 SANDOWN LANE, LIVERPOOL, L15 4HU REPORT DATE: 14 OCTOBER 2015 REPORT NUMBER:

More information

Analysis Joint sound insulation of filler materials

Analysis Joint sound insulation of filler materials Analysis Joint sound insulation of filler materials Testing Report 167 43780/Z2 Basis ift regulation SC-01 determination of joint sound insulation degree of 2002 Diagram Applicant Hanno-Werk GmbH & Co.

More information

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9100AB REVRB. TYPE: Acoustic Baffles

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9100AB REVRB. TYPE: Acoustic Baffles ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9100AB REVRB TYPE: Acoustic Baffles Sample ID Number & Sample Description D9015.01 Series/Model 9100AB REVRB,

More information

ACOUSTICAL LABORATORIES

ACOUSTICAL LABORATORIES An AL IO N Technical Center RIVERBANK.ALIONSCIENCE.COM FOR: Tampa, FL Sound Transmission Loss CONDUCTED: Page 1 of 10 ON: Dbl. metal std. wall, 18 ga. 6"studs 24"oc, 2" Air gap, Dbl lyr 5/8" Type X (Sor.)

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Wichita, KS Sound Transmission Loss CONDUCTED: 2017-03-20 (Report Revised 2017-05-11) Page 1 of 10 ON: Composite Wall Section with PCS-1B Silicone Compression Seal System - Double Installation in

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Wichita, KS Sound Transmission Loss CONDUCTED: 2017-03-14 (Report Revised 2017-05-11) Page 1 of 10 ON: Composite Wall Section with PCS-1C Silicone Compression Seal System - Double Installation in

More information

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Base 10

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Base 10 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to Series/Model: Base 10 Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632 mm Summary of Test Results Data File Result

More information

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS CASINO 600MM

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS CASINO 600MM RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON

More information