1 10 Colinton Road Edinburgh, EH10 5DT T: F: E: I: w w w.rmp.biz BRIEF FOR CONSULTANCY: To assess the level of sound insulation of the party wall in the new build attached houses. Sound Insulation Test Easterton of Duntelchaig, Farr, Inverness, IV2 6AW Technical Report No. L/4067/06 PREPARED FOR: Richard Hillam Polarwall Unit 3 Old Mill Industrial Estate Stoke Canon Exeter EX5 4RJ For the attention of Richard Hillam THE ASSOCIATION OF NOISE is a consulting division of Napier University
2 Contents 1.0 Introduction Wall specification Equipment used Measurement procedure Results... 4
3 1.0 Introduction 1.1 We were instructed by Richard Hillam Polarwall to carry out measurements of the sound insulation of the party wall within the new build attached houses, situated at Easterton of Duntelchaig, Farr, Inverness, IV2 6AW. 1.2 The measurements were carried out on, by Dr. Sean Smith, B.Sc (Hons), Ph.D, M.I.O.A. 2.0 Wall specification 2.1 The sound insulation was measured between the adjacent first floor bedrooms of Plot 1 and The construction details were reported as follows: Single sheet of 12.5 mm plasterboard directly fixed onto a Polarwall insulating concrete formwork. 200 mm in-situ concrete core with 50 mm polystyrene insulation on each side. 3.0 Equipment used 3.1 The equipment used conformed to the requirements of Parts 4 (airborne) of BS EN ISO 140, Measurement of sound insulation in buildings and of building elements. Robin Mackenzie Partnership Page 2
4 3.2 The following items of equipment were used during the measurement:- Equipment Brüel & Kjær Modular Precision Sound Level Meter Type 2260 running Building Acoustics Module Type BZ7204 Serial No Brüel & Kjær Prepolarised Condenser Microphone Cartridge Type Brüel & Kjær Sound Level Calibrator Type Brüel & Kjær Sound Source Type Measurement procedure 4.1 The measurement procedure conformed to the requirements of the Building Standards (Scotland) Regulations The sound level meter was calibrated before and after the measurements. A 0.1 db deviation from the calibration level of 94 db re 2 x 10-5 Pa at 1000 Hz was recorded. Robin Mackenzie Partnership Page 3
5 5.0 Results 5.1 The full airborne sound insulation results of the separating wall construction are given in Figure 1. The single figure sound insulation ratings calculated in accordance with BS EN ISO 717: 1997 are shown in Table 1 relative to the requirements of Section 5 of the Building Standards (Scotland) Regulations. Table 2 shows the sound insulation performance of the party wall relative to Part E of the building regulation England and Wales. Table 1. Party Wall (Scottish regulations) airborne sound insulation Airborne D nt,w (db) Building Standards (Scotland) Regulations 2004 Plot 2 first floor bedroom to Plot 1 first floor bedroom Mean: not less than 53 Individual: not less than (Pass) Table 2. Party wall (England and Wales regulations) airborne sound insulation D nt,w + C tr Source room Receiving room Regulation criterion Measured D nt,w + C tr Description Volume (m3) Description Volume (m3) min db db Plot 2 first floor bedroom ~ 45 Plot 1 first floor bedroom ~ (Pass) 5.2 The result given in Table 1 indicates that the sound insulation of the tested wall construction has complied with the requirements laid down in the aforementioned Scottish regulations. Robin Mackenzie Partnership Page 4
6 5.3 The result given in Table 2 indicates that the sound insulation of the tested wall construction has complied with the Part E requirements and Approved Document E 2003 for England and Wales. Prepared by: Approved by: Clement Luciani B.Eng (Hons), M.Sc, A.M.I.O.A. Dr. Sean Smith B.Sc (Hons), Ph.D, M.I.O.A Robin Mackenzie Partnership Page 5
7 Figure 1. Airborne Sound Insulation Measurement Standardised Level Difference: Field Method BS EN ISO 140-4:1998 Client : Richard Hillam Polarwall Date of Test: 08-May-06 Test Partition: Wall Site Address : Easterton of Duntelchaig Test Location (S): Plot 2 first floor bedroom Farr, Inverness Test Location (R): Plot 1 first floor bedroom IV2 6AW Construction Details: Single sheet of 12.5 mm plasterboard directly fixed onto a Polarwall insulating concrete formwork. 200 mm in-situ concrete core with 50 mm polystyrene insulation on each side. Third Octave Frequency (Hz) Standarised Level Difference D nt (db) Result A Shifted Reference Unfavourable Deviations k k k k k k k k 66.0 D nt,w (C; C tr ) 53 (-3;-6) Standardised Level Difference, D nt (db) Test Data A Shifted Reference Curve Fixed Reference Curve Source Room Volume: ~45 m 3 Receiver Room Volume: ~30 m k 3.15k Frequency (Hz) Single Figure Rating Calculated According to BS EN ISO 717-1:1997 D nt,w = 53 db Evaluation based on field measurement results. Test Report No.: L/4067/06 Name of Test Institute : Robin Mackenzie Partnership Date : Signature :
Measurement of Airborne & Impact Sound Insulation. University of Durham, Pavilion H, Howlands Farm, Durham.
FAO: CARL SUTCLIFFE noise.co.uk noise.co.uk Ltd Report No U20 Measurement of Airborne & Impact Sound Insulation University of Durham, Pavilion H, Howlands Farm, Durham. For: The Concrete Centre 9/9/2005
More informationTHE FRAME RESIDENTIAL DEVELOPMENT, SPORTCITY, MANCHESTER THE CONCRETE CENTRE LTD 1.0 INTRODUCTION...2
Concrete Centre Limited The Frame Residential Development, Sport City, Manchester Sound Insulation Test Report 2 August 2005 PROJECT: CLIENT: The Frame Residential Development, Sportcity, Manchester Concrete
More informationNO. 19 WILBERFORCE ROAD COXHEATH, MAIDSTONE, KENT ME17 4HD SOUND INSULATION TESTING. On behalf of: Oscar Acoustics
NO. 19 WILBERFORCE ROAD COXHEATH, MAIDSTONE, KENT ME17 4HD SOUND INSULATION TESTING On behalf of: Oscar Acoustics Report No. MRL/100/093c.1v1 November 2011 Report No. MRL/100/093c.1v1 November 2011 NO.
More information1.0 INTRODUCTION BUILDING REGULATIONS SOUND INSULATION REQUIREMENTS TEST PROCEDURE AND ANALYSIS...3
Concrete Centre Limited Bron Derw Residential Development, Colwyn Bay Sound Insulation Test Report 25 July 2005 PROJECT: CLIENT: Bron Derw Residential Development, Colwyn Bay Concrete Centre Limited Riverside
More informationOLIVE VILLAS, SANDOWN LANE, LIVERPOOL, L15 4HU
MEASUREMENT OF THE SOUND INSULATION OF SEPARATING FLOORS on behalf of URBAN BUBBLE LTD for the development at OLIVE VILLAS, 38-40 SANDOWN LANE, LIVERPOOL, L15 4HU REPORT DATE: 14 OCTOBER 2015 REPORT NUMBER:
More informationConducting A Sound Insulation Test
Conducting A Sound Insulation Test . Why Test? Dwelling-houses, flats and rooms for residential purposes shall be designed and constructed in a such a way that they provide reasonable resistance to sound
More informationB Page 1 of 21-
Airborne and impact sound transmission measurements were performed on three floor assemblies which comprised the NRC 150 mm reference concrete slab and a 102 mm floating concrete slab. For report purposes,
More informationKINETICS NOISE CONTROL TEST REPORT #AT001021B
KINETICS NOISE CONTROL TEST REPORT #AT001021B KINETICS NOISE CONTROL PRODUCTS: o ICW ACOUSTICAL RATINGS: o STC 76 o IIC 62 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B3463.13 KINETICS DRAWING NUMBER:
More informationRobin Mackenzie Partnership Design of Separating Constructions that are Resistant to the Transmission of Noise PART 1 of 2
Robin Mackenzie Partnership Design of Separating Constructions that are Resistant to the Transmission of Noise PART 1 of 2 October 2007 Report prepared by: Dr Sean Smith and Richard Mackenzie RMP Acoustics
More informationFIELD IMPACT INSULATION TESTS 133 SCARBOROUGH STREET, SOUTHPORT TEST REPORT
Commissioned by: National Flooring Distributors Pty Ltd Date: 26 June 2015 Project number: 3872 Version: V.0 Author: Eric Huang 24 Mexicanus Drive, PO Box 790, Park Ridge Queensland 4125 Australia p. +61
More informationTEST AND PERFORMANCE REQUIREMENTS (TR01)
Robust Details Limited TEST AND PERFORMANCE REQUIREMENTS (TR01) Major version Reason for change Description of main change(s) 1 New edition No material changes. Minor edits and text improvements. 2 Inclusion
More informationINTRODUCTION SPECIMEN DESCRIPTION
INTRODUCTION SPECIMEN DESCRIPTION Airborne sound transmission measurements were performed on a wall assembly with a single layer of the product identified by the client as QuietRock QR-530 Serenity on
More informationThe specimen B W was identified by the client as a Skyfold Classic operable partition, with panels, seals, and clearances in configuration 4E.
TestingLaboratory: Client: Specimen: SpecimenID: Manufacturer: ConstructionDates: Testspecimenmountedby: NationalResearchCouncilCanada InstituteforResearchinConstruction 1200MontrealRoad Ottawa,OntarioK1A0R6
More informationTest report No B0082 IN CM 26-M56-I
Test report No B0082 IN CM 26-M56-I AKUSTIKA ARLOA kudeatzailea: ACOUSTIC AREA managed by: Laboratory measurements of sound insulation TEST SPECIMEN: False ceiling (3 plasterboards) with Akustik 4 supports
More informationTest report No B0082 IN CM 26-M55-I
Test report No B0082 IN CM 26-M55-I AKUSTIKA ARLOA kudeatzailea: ACOUSTIC AREA managed by: Laboratory measurements of sound insulation TEST SPECIMEN: False ceiling (2 plasterboards) with Akustik 4 supports
More informationKINETICS NOISE CONTROL TEST REPORT #AT001049
KINETICS NOISE CONTROL TEST REPORT #AT001049 KINETICS NOISE CONTROL PRODUCTS: o NONE ACOUSTICAL RATINGS: o STC 53 o IIC 27 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA o B-3463.1
More informationKINETICS NOISE CONTROL TEST REPORT #AT001067
KINETICS NOISE CONTROL TEST REPORT #AT001067 KINETICS NOISE CONTROL PRODUCTS: o FLM- NEOPRENE PAD ACOUSTICAL RATINGS: o STC 69 o IIC 61 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA
More informationICF/Building System FSTC Test Report
REP ICF STC test.doc 1of5 2003 03 12 C/o Michel Philippe IntegraSpec Insulating Concrete Forms (ICF) Building System By: Phil-Insul Corporation 735 Arlington Park Place, 11U Kingston, ON, K7M 8M8 TEL:
More informationLABORATORY MEASUREMENTS OF THE SOUND REDUCTION INDEX ROCKWOOL ABLATIVE COATED BATTS
eport No. L/3132 Page 1 of 10 for ockwool UK Limited Pencoed Bridgend CF35 6NY Dated: 30 November 2009 LABOATOY MEASUEMENTS OF THE SOUND EDUCTION INDEX OF OCKWOOL ABLATIVE COATED BATTS eport Author: M
More informationKINETICS NOISE CONTROL TEST REPORT #AT001052
KINETICS NOISE CONTROL TEST REPORT #AT001052 KINETICS NOISE CONTROL PRODUCTS: o ISOMAX CLIPS ACOUSTICAL RATINGS: o STC 66 o IIC 44 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA
More informationpalmer acoustics TEST REPORT
FIELD IMPACT INSULATION TESTS Commissioned by: National Flooring Date: 20 February 2018 Project number: 4355 Version: V.0 Author: Rasika Chandrasekara 24 Mexicanus Drive PO Box 790 Park Ridge Queensland
More informationReport Number BTC 13236A
The Building Test Centre British Gypsum Limited East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email btc.testing@bpb.com Report Number BTC 13236A ACOUSTIC TEST REPORT COVERING
More informationSOUND INSULATION DESIGN OF MODULAR CONSTRUCTION HOUSING
SOUND INSULATION DESIGN OF MODULAR CONSTRUCTION HOUSING D Yates L Hughes A Campbell Buro Happold Ltd, London, UK Buro Happold Ltd, Newcastle, UK WSP, Bristol, UK 1 INTRODUCTION This paper provides an insight
More informationImportant Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA
Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure
More informationReport Number BTC 13505A
Report Number BTC 13505A AN ACOUSTIC TEST REPORT COVERING A SERIES OF LABORATORY SOUND INSULATION TESTS TO BS EN ISO 140-3:1995 ON A 142MM THICK KINGSPAN TEK PANEL WITH VARIOUS DIRECT FIX AND INDEPENDENT
More informationImportant Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA
Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure
More informationKINETICS NOISE CONTROL TEST REPORT #AT001110
KINETICS NOISE CONTROL TEST REPORT #AT001110 KINETICS NOISE CONTROL PRODUCTS: o NONE ACOUSTICAL RATINGS: o STC 53 o IIC 29 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o REPORT NO. A1-010601.1 o DATED:
More informationSubPrimo. subprimo. Acoustic insulation for timber & laminate flooring. Uniclass L5395:N372 EPIC E485:Y45. CI/SfB (43) T (P2)
Acoustic insulation for timber & laminate flooring Uniclass L5395:N372 CI/SfB EPIC E485:Y45 (43) T (P2) subprimo Introduction Introduction Sound Reduction Systems Ltd. (SRS) manufacture acoustic insulation
More informationKINETICS NOISE CONTROL TEST REPORT #AT001035
KINETICS NOISE CONTROL TEST REPORT #AT001035 KINETICS NOISE CONTROL PRODUCTS: o RIM I-2-16 ACOUSTICAL RATINGS: o STC 66 o IIC 63 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B-3140.1 KINETICS DRAWING
More informationKINETICS NOISE CONTROL TEST REPORT #AT001032
KINETICS NOISE CONTROL TEST REPORT #AT001032 KINETICS NOISE CONTROL PRODUCTS: o ICC ACOUSTICAL RATINGS: o STC 84 o IIC 70 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B-3448.12 KINETICS DRAWING NUMBER:
More informationOzone Panel 120 Acoustic Assessment and Optimization
Vipac Engineers & Scientists Ltd 279 Normanby Road, Private Bag 16 Document No. Port Melbourne VIC 3207 30U-12-0010-DRP-258904-0 Australia t. +61 3 9647 9700 f. +61 3 9646 4370 1 Aug 2012 www.vipac.com.au
More informationKINETICS NOISE CONTROL TEST REPORT # AT001084
KINETICS NOISE CONTROL TEST REPORT # AT001084 KINETICS NOISE CONTROL PRODUCTS: o MODEL ISOGRID ACOUSTICAL RATINGS: o STC 63 o IIC 50 TESTING AGENCY & REPORT NUMBER: o NRC-CNRC o B-3463.6 KINETICS DRAWING
More informationDetermination of the sound reduction and sound absorption of a railroad noise barrier
TEST REPORT No. VTT-S-04940-14 October 29, 2014 Determination of the sound reduction and sound absorption of a railroad noise barrier Requested by: Soundim Oy TEST REPORT No. VTT-S-04940-14 1 (3) Requested
More informationCONSIDERATIONS REGARDING IMPACT SOUND INSULATION PERFORMANCES OF DIFFERENT FLOOR MATERIALS
JAES_1(14)_1_2011 TAMAS-GAVREA D.R. et all, pp.111-116 SECTION Civil Engineering and Installations CONSIDERATIONS REGARDING IMPACT SOUND INSULATION PERFORMANCES OF DIFFERENT FLOOR MATERIALS TĂMAŞ-GAVREA
More informationBELLOTI, S.p.a. Via San Francesco, Cermenate (CO) - ITALY TEST REPORT
LGAI Technological Center, S.A. Campus de la UAB Ronda de la Font del Carme, s/n E - 08193 BELLATERRA (Barcelona) T +34 93 567 20 00 F +34 93 567 20 01 www.appluslaboratories.com 9/LE766 Bellaterra: 27th
More informationReport Number BTC 14020A
Report Number BTC 14020A AN ACOUSTIC TEST REPORT COVERING A LABORATORY SOUND INSULATION TEST TO BS EN ISO 140-3:1995 ON A BRITISH GYPSUM GYPWALL QUIET SF PARTITION. TWO SETS OF TWO GANG CAVITY WALLBOXES
More informationASSESSMENT OF INWARD TRAFFIC NOISE IMPACT AT RESIDENTIAL DEVELOPMENT, WONDERFUL BARN, LEIXLIP, CO. KILDARE
ASSESSMENT OF INWARD TRAFFIC NOISE IMPACT AT RESIDENTIAL DEVELOPMENT, WONDERFUL BARN, LEIXLIP, CO. KILDARE Technical Report Prepared For Ardstone Capital Ltd. 48 Fitzwilliam Square Dublin Technical Report
More informationHive Acoustic Report.
Hive Acoustic Report www.connection.uk.com Introduction An acoustic report of the equivalent sound absorption area of selected Connection products carried out by AIRO Acoustics Laboratory. The original
More informationDownlight Mitts Downlight Mitt Acoustic Test Report
Vipac Engineers & Scientists Ltd 279 Normanby Road, Private Bag 16 Document No. Port Melbourne VIC 3207 30B-11-0090-TRP-595139-1 t. +61 3 9647 9700 f. +61 3 9646 4370 23 May 2011 www.vipac.com.au Page
More informationReport Number BTC 16234A
Report Number BTC 16234A An acoustic test report covering laboratory sound insulation testing to BS EN ISO 140-3:1995 on a British Gypsum GypWall Partition, incorporating Gypframe 92mm Studs (92S50) at
More informationAcoustic Detailing For Steel Construction
SCI PUBLICATION P372 Acoustic Detailing For Steel Construction A G J Way MEng CEng MICE G H Couchman MA PhD CEng MICE Published by: The Steel Construction Institute Silwood Park Ascot Berkshire SL5 7QN
More informationCJ Buma. To: Steelform Building Products Inc. Wednesday, 2007 May Avenue Edmonton, AB, T6B 2V2. Attn: Mr.
To: Steelform Building Products Inc. Wednesday, 2007 May 7 4104 69 Avenue Edmonton, AB, T6B 2V2 Attn: Mr. Marty MacDonald aci Acoustical Consultants Inc. Suite 107, 9920-63Ave Edmonton, Alberta, Canada
More informationROUND ROBIN ON UNCERTAINTY IN SOUND INSULATION MEASUREMENTS.
http://www.pdaltd.com Proceedings of the Institute of Acoustics ROUND ROBIN ON UNCERTAINTY IN SOUND INSULATION MEASUREMENTS. I C Critchley MIOA, MInstSCE, P R Dunbavin MSc, FIOA, MIOSH, MSEE, MInstSCE,
More informationLaboratory measurements of the reduction of transmitted impact sound by floor coverings on a heavyweight reference floor (According to ISO )
Reference no. T1638-1 Laboratory measurements of the reduction of transmitted impact sound by floor coverings on a heavyweight reference floor (According to ISO 10140 3) AUCKLAND UNISERVICES LIMITED a
More informationCERTIFICATE OF PERFORMANCE. IMPACT NOISE TESTING (6mm ABODE PRIME RIGID PLANK) PROLINE FLOORS
CERTIFICATE OF PERFORMANCE IMPACT NOISE TESTING (mm ABODE PRIME RIGID PLANK) PROLINE FLOORS DOCUMENT CONTROL Project Title Certificate Performance Impact Noise Testing ( mm Rigid Plank) Proline s Our Project
More informationFIELD FLOOR IMPACT SOUND ISOLATION
FIELD FLOOR IMPACT SOUND ISOLATION 46 OAKDENE DRIVE 15 th September 2015 For BUILD IT ECO Unit 8 / 49 Prindiville Drive WANGARA WA 6065 UNIT 3 / 2 HARDY STREET, SOUTH PERTH 6151 TEL: 9474 5966 EMAIL: reception@gabriels.net.au
More informationHudson Series 200 Acoustic Louvre
Louvreclad s Hudson Series is an acoustic louvre. It is the ideal solution when aesthetics are as important as noise reduction, ventilation, and weather protection. Distinctive Features + Diverse Applications
More informationJune Non - Residential Refurbishment Separating floors
June 2010 Non - Residential Refurbishment 5.6.2 Separating floors Non-residential refurbishment 5.0 Non-residential Refurbishment Separating Floors Contents Introduction find online page Solution optimiser
More informationHudson Series 300 Acoustic Louvre
Louvreclad s Hudson Series is an acoustic louvre. It is the ideal solution when aesthetics are as important as noise reduction, ventilation, and weather protection. Distinctive Features + Diverse Applications
More informationLaboratory Airborne Sound Insulation of Stud Walls with Warmcel 500 Insulation. Prepared for:
Laboratory Airborne Sound Insulation of Stud Walls with Warmcel 500 Insulation Prepared for: Excel Industries Limited Maerdy Industrial Estate (South) Rhymney Gwent NP22 5PY 18 th June 2010 0578 Tested
More informationJune Residential Refurbishment Separating floors
June 2010 Residential Refurbishment 3.6.2 Separating floors Residential refurbishment 3.0 Residential Refurbishment Separating Floors Contents Introduction find online page Solution optimiser and pathfinder
More informationLaboratory Airborne and Impact Sound Insulation of a Robust Details Appendix F Floor with PhotonStar LED Ltd. Downlights
Laboratory Airborne and Impact Sound Insulation of a Robust Details Appendix F Floor with PhotonStar LED Ltd. Downlights Prepared for: PhotonStar LED Group plc Unit 8 Westlink Belbins Business Park Romsey
More informationCERTIFICATE OF PERFORMANCE. IMPACT NOISE TESTING (6 mm RIGID PLANK) PROLINE FLOORS
CERTIFICATE OF PERFORMANCE IMPACT NOISE TESTING ( mm RIGID PLANK) PROLINE FLOORS DOCUMENT CONTROL Project Title Certificate Performance Impact Noise Testing ( mm Rigid Plank) Proline s Our Project Number
More informationImpact Sound Testing of Floor Covering on a Heavyweight Standard Floor
Impact Sound Testing of Floor Covering on a Heavyweight Standard Floor Report INR171/R1 June 2011 Gerflor Australasia Pty Ltd 17 Cato Street Hawthorn East VIC 3123 Enquiries should be addressed to: Manager
More informationASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements
ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements 1 of 7 TEST : Acoustical Surfaces, Inc. Report Date: May 25, 2011 Test Date: September 28, 2010 Test
More informationASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements
ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements 1 of 7 TEST : Acoustical Surfaces, Inc. Report Date: May 25, 2011 Test Date: September 28, 2010 Test
More informationEvidence of Performance Joint sound reduction of filling material
Evidence of Performance Test Report No. 13-002455-PR01 (PB Z6-K02-04-en-01) ift Rosenheim 13.09.2013 Client Soudal N. V. Everdongenlaan 18-20 2300 Turnhout Belgium Product Designation Thickness of sealant
More informationCOMPARISON OF MEASURED AND PREDICTED SOUND INSULATION FOR A THERMAL RETROFITTED BUILDING
Invited Paper COMPARISON OF MEASURED AND PREDICTED SOUND INSULATION FOR A THERMAL RETROFITTED BUILDING C. Guigou-Carter 1, R. Foret 2, R. Wetta 1, P. Ducruet 1, M. Villot 1 Affiliation: { 1 CSTB, 24 Rue
More informationApproved Document E Technical Design Report
Approved Document E Technical Design Report Report No 15692 Date 15 th April 2013 Sound Solution Consultants Ltd. Ref 15692 Page 1 Client: Site Address Brighton Our Report Ref:15692 Table of Contents 1.
More informationAcoustics Rating of sound insulation in buildings and of building elements. Part 1: Airborne sound insulation
Provläsningsexemplar / Preview INTERNATIONAL STANDARD ISO 717-1 Third edition 2013-03-01 Acoustics Rating of sound insulation in buildings and of building elements Part 1: Airborne sound insulation Acoustique
More informationCONSIDERATIONS ON THE AIRBORNE SOUND INSULATION OF A MODERNISED HOTEL
JAES_1(14)_3_2011 MUNTEANU C. et all., pp.81-88 SECTION Civil Engineering and Installations CONSIDERATIONS ON THE AIRBORNE SOUND INSULATION OF A MODERNISED HOTEL MUNTEANU Constantin, TĂMAŞ-GAVREA Daniela-Roxana*,
More informationEvidence of Performance Airborne sound insulation of building components
Evidence of Performance Airborne sound insulation of building components Test Report No. 14-000251-PR01 (PB Z09-H01-04-en-02) Client Product Designation PRESS GLASS SA Nowa Wies Kopalniana 9 42-262 Poczesna
More informationJune Residential Refurbishment Separating walls
June 2010 Residential Refurbishment 3.6.1 Separating walls Residential refurbishment 3.0 Residential Refurbishment Separating Walls Contents Introduction find online page Solution optimiser and pathfinder
More informationEvidence of Performance Joint sound reduction of filling material
Evidence of Performance Test Report No. 13-002455-PR02 (PB-K05-04-en-01) ift Rosenheim 10.09.2013 Client Soudal N. V. Everdongenlaan 18-20 2300 Turnhout Belgium Product Designation Density Special features
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to REGUPOL AMERICA Series/Model: 3 mm Regupol Sonus Rubber Underlayment Specimen Type: Floor/Ceiling Assembly Overall Size:
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to REGUPOL AMERICA Series/Model: 5 mm Regupol Sonus Rubber Underlayment Specimen Type: Floor/Ceiling Assembly Overall Size:
More informationACOUSTIC PERFORMANCE AND STC RATING OF A PARTITION WALL WITH DOUBLE SOCKETS AND POLYSEAM PUTTY PADS
Our Ref: MK1801 ACOUSTIC PERFORMANCE AND STC RATING OF A PARTITION WALL WITH DOUBLE SOCKETS AND POLYSEAM PUTTY PADS AUCKLAND UNISERVICES LIMITED a wholly owned company of THE UNIVERSITY OF AUCKLAND PROJECT
More informationTECHNICAL DOCUMENT - SOUND INSULATION R9 SYSTEM. Dated: 30 August 2013
Level 2, 6 Kings Park Road West Perth, Western Australia, 6000 Phone: +61 8 9488 0848 ABN: 54 160 488 175 ACN: 160 488 175 FBM Licence Limited E-Mail: info@fbmlicence.com.au Web: www.fbmlicence.com.au
More informationLABORATORY MEASUREMENT OF THE SOUND REDUCTION IMPROVEMENT INDEX BY ACOUSTICAL LININGS DUE ONLY TO RESONANT TRANSMISSION
LABORATORY MEASUREMENT OF THE SOUND REDUCTION IMPROVEMENT INDEX BY ACOUSTICAL LININGS DUE ONLY TO RESONANT TRANSMISSION PACS REFERENCE: 3.55 Rg Hopkins, Carl Acoustics Centre BRE Watford WD25 9XX UK Tel:
More informationThe development of robust details for sound insulation in new build attached dwellings
Fax: þ 44 (0)131 455 2563 The development of robust details for sound insulation in new build attached dwellings Received: 30th September, 2005 Sean Smith BSc, PhD, MIOA is RC UK Research Fellow and Principal
More informationHorizontal Impact Sound Insulation: Field Observations
Proceedings of ACOUSTICS 6 20-22 November 6, Christchurch, New Zealand Horizontal Impact Sound Insulation: Field Observations Michael Sullivan, Richard Finley and Arif Zaher Acoustic Division, NDY Sound,
More informationApril Section 4.3. Separating Floors
April 2012 Section Separating Floors Separating Floors Separating floors Separating floor design Mineral wool products offer substantial advantages when used as both sound absorbent and resilient layers
More informationComparison of measured and predicted sound insulation for a thermal retrofitted building
Comparison of measured and predicted sound insulation for a thermal retrofitted building C. Guigou-Carter, R. Foret, R. Wetta,P. Ducruet, M. Villot CSTB Inter-Noise 2010 Lisbon, Portugal PAGE 1 Introduction
More informationSignatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.
ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 492: Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using
More informationD R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to REGUPOL AMERICA Regupol Sonus HS300 3 mm Underlayment Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632
More informationIMPACT NOISE TESTING TIMBER FLOORING & ACOUSTIC UNDERLAY TESTING SCHNEID FLOORING AUSTRALIA PTY LTD
IMPACT NOISE TESTING TIMBER FLOORING & ACOUSTIC UNDERLAY TESTING SCHNEID FLOORING AUSTRALIA PTY LTD Date: Monday, th May 5 File Reference: 76C55mfcSchneidingAustralia Koikas Acoustics Pty Ltd Commercial,
More informationLOXO CLADDING SOUND INSULATION PERFORMANCE. Opinion on Acoustic Performance of. Loxo Cladding Systems Utilising Aerated Concrete.
LOXO CLADDING SOUND INSULATION PERFORMANCE Opinion on Acoustic Performance of Loxo Cladding Systems Utilising Aerated Concrete Rp001 2012195C 08 May 2012 Level 369 Cambridge Terrace PO Box 4071 Christchurch
More informationA L I O N Technical Center. Test Report
FOR: Lebanon, PA Impact Sound Transmission CONDUCTED: 2017-07-12 Page 1 of 8 ON: Quarry Floor Tiles and Regupol SonusPlus (underlayment) over 8 inch Concrete Slab (no Ceiling) TEST METHOD Riverbank Acoustical
More informationAirbourne Sound Transmission Test
Airbourne Sound Transmission Test 1.0 INTRODUCTION AND TEST RESULTS SUMMARY This National Acoustic Laboratories were commissioned by Modular Wall Systems to measure the acoustical transmission loss of
More informationFLANKING TRANSMISSION IN STEEL-CONCRETE COMPOSITE FLOORS
FLANKING TRANSMISSION IN STEEL-CONCRETE COMPOSITE FLOORS Beth Paxton and Jack Harvie-Clark Apex Acoustics, Design Works, William Street, Gateshead, UK email: jack.harvie-clark@apexacoustics.co.uk This
More informationD R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to REGUPOL AMERICA Series/Model: Regupol Sonus LV200 2mm Underlayment Specimen Type: Floor/Ceiling Assembly Overall Size:
More informationPreliminary study of the acoustic behavior concerning an innovative prototype for indoor modular partitioning
Preliminary study of the acoustic behavior concerning an innovative prototype for indoor modular partitioning Gonçalo SIMÕES1; Jorge PATRÍCIO2; Paulina FARIA3 1 2 FCT-UNL, 2829-16 Caparica, Portugal LNEC,
More informationSignatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.
ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 492: Laboratory Measurement of Impact Sound Transmission through Floor- Ceiling Assemblies Using
More informationAcoustic Performance of Light Steel Framed Systems
Light Steel Framing?i 446 Acoustic Performance of Light Steel Framed Systems Meeting the new requirements of Part E of the Building Regulations (2003) Technical Information Sheet External brickwork fixed
More informationIWS FAST BOARD. Non-combustible sheathing board. Technical Guide. built in. Fire protection. excellent Acoustics. integrated Structural engineering
IWS FAST built in FAST BOARD Non-combustible sheathing board 0-10 -20 Fire protection excellent Acoustics integrated Structural engineering optimal Thermal performance Technical Guide IWS-FAST Board is
More informationResults of FIIC and FSTC Measurements at Harvard Estates
Harvard Estates FIIC and FSTC Tests STEWART AIT ALLAOUA PERKINS 6042 Seaview Ave. NW, Suite 102 Seattle, WA 98107 Phone: (206) 839-0819 Fax: (206) 839-0824 January 21, 2005 Charles Strazzara, AIA Studio
More informationA L I O N Technical Center. Test Report
FOR: Lebanon, PA Sound Transmission Loss CONDUCTED: 2017-07-12 Page 1 of 9 ON: Quarry Floor Tiles and Regupol SonusPlus (underlayment) over 8 inch Concrete Slab (no Ceiling) TEST METHOD Riverbank Acoustical
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: Denver, Colorado Impact Sound Transmission RAL-IN16-035 CONDUCTED: 2016-11-01 Page 1 of 7 ON: Porcelain Tile flooring - Thinset Mortar - Whisper Mat underlayment - 8 inch Concrete Slabs - No Ceiling
More informationProposed Lidl Food Store West Hendford Yeovil. Environmental Noise Report for Planning
Proposed Lidl Food Store West Hendford Yeovil Environmental Noise Report for Planning Reference: 6087/BL/pw October 2015 2 Proposed Lidl Food Store, West Hendford, Yeovil Environmental Noise Report for
More informationLABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF PIR ROOF PANELS (According to ISO )
Ref no: LABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF PIR ROOF PANELS (According to ISO 10140 2) AUCKLAND UNISERVICES LIMITED a wholly owned company of THE UNIVERSITY OF AUCKLAND Report prepared
More informationSeparating walls. Countryside Properties, Lock 38, Stoke-on-Trent
Separating walls Countryside Properties, ock 8, Stoke-on-Trent Separating Masonry walls Walls Separating Masonry wallswalls Approved Document E 200 Clause E Approved Document 200 - Requirements Walls >>
More informationMeasurements of junction vibration level differences of timber framed constructions
Measurements of junction vibration level differences of timber framed constructions Anders HOMB 1 1 NTNU Trondheim. Norwegian University of Science and Technology ABSTRACT Flanking transmission of supporting
More informationSOUND INSULATION TESTING IN DWELLINGS
SOUND INSULATION TESTING IN DWELLINGS Chris Dilworth, AWN Consulting This Presentation Discusses the standards by which we judge sound insulation performance. Presents the results of sound insulation tests
More informationThe uncertainty in sound insulation of an industrially prefabricated lightweight timber construction
The uncertainty in sound insulation of an industrially prefabricated lightweight timber construction Rikard ÖQVIST 1 1 Tyréns AB, Sweden ABSTRACT The variations in sound insulation are often large for
More informationLABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF STEEL CLAD PIR WALL PANELS (According to ISO )
Ref no: LABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF STEEL CLAD PIR WALL PANELS (According to ISO 10140 2) AUCKLAND UNISERVICES LIMITED a wholly owned company of THE UNIVERSITY OF AUCKLAND Report
More informationG R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to PROFLEX PRODUCTS, INC.
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to PROFLEX PRODUCTS, INC. Series/Model: 4 mm Luxury Vinyl Plank over LV200 Specimen Type: Concrete Slab - 152 mm Overall Size:
More informationSPEEDPANEL. Fire & Acoustic Rated Wall Systems. Speedpanel. Intertenancy systems SPEEDPANEL
SPEEDPANEL R Fire & Acoustic Rated Wall Systems Speedpanel Intertenancy systems 3 SPEEDPANEL CONTENTS 51mm Speedpanel Intertenancy System 04 Wall Type: 22D 05 Footprint 187mm FRL -/60/60 Rw + Ctr 50 Report
More informationG R1 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to PROTECTO WRAP COMPANY
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to PROTECTO WRAP COMPANY Series/Model: Protecto Wrap Whispermat LVT Specimen Type: Concrete Slab - 152 mm Overall Size: 3023
More informationMeasurement of the insertion loss of the pipe clamp FRSPlus for 4 sewer pipes
Prof. Dr.-Ing. H.M. Fischer Report Nr. FEB/FS-75/13 3e Measurement of the insertion loss of the pipe clamp FRSPlus for 4 sewer pipes Client: fischerwerke GmbH & Co. KG Weinhalde 14 18 72178 Waldachtal
More informationCI/SfB. November Design Guide Concrete block masonry
CI/SfB November 1997 Ff Design Guide Concrete block masonry Design Guide concrete block masonry This Topblock Design Guide contains detailed information on the design and performance of constructions using
More information