ASTM C 1363 Thermal Performance Test Report
|
|
- Arthur Powers
- 6 years ago
- Views:
Transcription
1 ASTM C 1363 Thermal Performance Test Report Test Number: Sponsor: Butler Research Center Liner System R-25 + R-11 Membrane liner system, R-25 fiberglass insulation between the purlins, R-11 fiberglass insulation over the purlins Test Date: 10/21/2010 Responsible Party: Mark J. Henry Operator: Larry Krueger Witness: Mark Henry Thermal Transmittance, U: Overall Thermal Resistance, Ru: Summary of Results: W/m 2 K (0.034 Btu/ hr ft 2 F) 5.2 m 2 K/W (29.4 hr ft 2 F/Btu)
2 ASTM C 1363 Thermal Performance Test Report Summary Prepared For: Butler Research Center Botts Road Grandview, Missouri Test Number: Test Start Date: 10/21/2010 Test End Date: 10/25/2010 Report Date: 11/15/2010 Test Information: Liner System R-25 + R-11 Membrane liner system, R-25 fiberglass insulation between the purlins, R-11 fiberglass insulation over the purlins Test Orientation / Heat Flow Direction: Normal Roof / Inside to Outside Specimen Size: 2.44 m x 3.05 m (8.00 ft x ft) Test Procedure: The Thermal Transmittance (U) and Thermal Resistance (Ru) were determined in general accordance with ASTM C , Standard Test Method for Thermal Performance of Building Materials and Envelope Assemblies by Means of a Hot Box Apparatus. ASTM Exceptions, if any: Summary of Test Setup: Average Warm Side Ambient Temperature deg C (99.99 deg F) Average Cold Side Ambient Temperature 9.98 deg C (49.96 deg F) Average Warm Side Air Velocity 0.29 m/s (57.87 fpm) Average Cold Side Air Velocity 1.30 m/s ( fpm) Summary of Results: Thermal Transmittance, U: Overall Thermal Resistance, Ru: W/m 2 K (0.034 Btu/ hr ft 2 F) 5.2 m 2 K/W (29.4 hr ft 2 F/Btu) Test Number: Page 1 of 8
3 Specimen Size: 2.44 m x 3.05 m (8.00 ft x ft) Panel Type: MR-24 roof system Insulation: Fiberglass, 2-layers Framing System: Z-purlins Specimen Construction: The assembly from Test was used. The roof panels were unseamed and removed. The panel clips were removed. The nominal R-11 fiberglass insulation was removed and set aside to be re-used. The nominal R-19 fiberglass insulation was removed. Pieces of nominal R-25 unfaced fiberglass insulation were cut to length and width. The insulation was placed between the purlins and between the purlins and the sides of the frame. The R-11 insulation was replaced over the R- 25 insulation and the purlins. New panel clips were installed. The roof panels were installed in a normal manner. The purlins, the membrane liner, and the steel banding were not changed or moved. Description of Test Construction of the specimen was supervised by Hal Robbins, Lamtec Corporation, and Carl Lewis, Bay Insulation Systems, Inc. The construction took place on October 7 and 8. The specimen was built to represent a typical field assembly. The steel banding was attached to the inside of face of the test frame. It was set at depth equal to that of the bottom of the purlins. The woven high density polyethylene fabric liner (Liner) was laid out on top of the banding and below the purlins. The two bands that ran perpendicular to the purlins were attached to the bottom flange of the purlins with self-drilling screws that are typical of field installations. The edges of the liner were turned up and then taped to the inside face of the test frame. Pieces of unfaced nominal R-19 insulation were cut to eight foot lengths and placed on the liner between the purlins and between the purlins and the side of the test frame. Pieces of unfaced nominal R-11 insulation were cut to 10 foot lengths and placed over the R- 19 insulation and the tops of the purlins. The MR24 Roof system panels were installed in a typical manner. The panel clips were attached to the purlins with standard self-tapping screws. Then thermal spacer blocks were placed between the panel clips and above the purlins. The MR-24 panels were placed and seamed in a normal manner. The perimeter of the roof panels was taped to the test frame to prevent air leakage. Specimen Conditioning: The assembly was built at the Butler Research Center and remained there until it was tested. It was in ambient environmental conditions for at least three days before testing. The insulation was "fluffed" in a manner similar to the NAHB procedure for quality testing of faced insulation, in order to promote the recovery of the insulation thickness. Test Number: Page 2 of 8
4 Material Name MR-24 Roof Panel Materials Used: Description MR-24 roof system panel, 24 gauge, 24 inch wide, Galvalume Plus finish Thermal Spacer Blocks 3/4 x 3-1/4 extruded polystyrene (FOAMULAR 250) Nominal thermal resistance: R-5 per inch R-11 Insulation Nominal R-11 unfaced fiberglass blanket insulation Measured thermal resistance: in hr ft 2 F/Btu R-25 Insulation Nominal R-25 unfaced fiberglass blanket insulation Measured Thermal Resistance: hr ft2 F/Btu Membrane Liner Bay Liner FP Fabric System Reinforced polyethylene film Sources for Materials Used: Butler Manufacturing supplied the roof panels, panel clips, and fasteners. Bay Insulation Systems supplied the insulation. The original manufacturer of the fiberglass insulation was Owens Corning. Test Number: Page 3 of 8
5 Measured Test Data Test Times Test Start Time Test End Time Time Required to Reach Steady State Steady State Start Time Steady State End Time 10/21/ :05 AM 10/25/2010 8:20 AM 73.9 Hours 10/24/ :00 PM 10/24/2010 8:55 PM Test Information Metered Area m 2 ( ft 2 ) Specimen Area 7.43 m 2 (80.00 ft 2 ) Average Warm Side Ambient Temperature deg C (99.99 deg F) Average Cold Side Ambient Temperature 9.98 deg C (49.96 deg F) Input Warm Side Heaters Warm Side Fans Warm Side AVT & RH Sensor Power watts ( Btu/hr) watts ( Btu/hr) 6.96 watts (23.75 Btu/hr) 1.24 watts (4.24 Btu/hr) Loss watts (82.66 Btu/hr) Surround Panel and Flanking Loss watts (69.74 Btu/hr) Side of Test Specimen Frame Adjustment 3.80 watts (12.96 Btu/hr) Meter Wall and Flanking Loss watts (-0.05 Btu/hr) Thermopile Voltage (E) mv Thermopile Null (E 0 ) mv Thermopile Slope (m) Total Heat Flow Through Test Specimen watts ( Btu/hr) Calculated Thermal Properties Specimen Thermal Transmittance (U) Specimen Overall Thermal Resistance (Ru) W/m 2 K (0.034 Btu/ hr ft 2 F) 5.2 m 2 K/W (29.4 hr ft 2 F/Btu) The estimated uncertainty of the results is ± 5 % Test Number: Page 4 of 8
6 Accreditations: Test Specification Description Accredited By ASTM C ASTM C International Accreditation Service, Inc. Latest Apparatus Calibration Date: August 2010 Butler Manufacturing will retain a copy of this test report for a minimum of four years. This report is the property of the Test Sponsor as mentioned in this test report and relates only to the products and assemblies as tested. This report may not be reproduced, except in full, without the prior written consent of Butler Manufacturing. The results obtained are tested values. This report is not an endorsement about the tested products and does not constitute a certification of the products tested. For Butler Manufacturing Mark J. Henry Senior Research Engineer Attachments: Revision Log Rev # Date Page(s) Revision(s) Original 11/15/2010 All Test Number: Page 5 of 8
7 Test Number: Page 6 of 8
8 Test Number: Page 7 of 8
9 Test Number: Page 8 of 8
ASTM C THERMAL PERFORMANCE TEST REPORT. Rendered to: WIRE-BOND. SERIES/MODEL: Masonry Tie Thermal Evaluations (2x6 Steel Stud Wall)
ASTM C 1363-11 THERMAL PERFORMANCE TEST REPORT Rendered to: WIRE-BOND SERIES/MODEL: Masonry Tie Thermal Evaluations (2x6 Steel Stud Wall) TYPE: Masonry Wall Assembly Summary of Results Test Unit R-Value
More informationValidation of Heating 7.2 Simulations Using Hot Box Test Data for RASTRA Wall Form System with Expanded Polystyrene Beads
Validation of Heating 7.2 Simulations Using Hot Box Test Data for RASTRA Wall Form System with Expanded Polystyrene Beads Jan KoÑny and Phill Childs Oak Ridge National Laboratory Buildings Technology Center
More informationFilled Cavity (FC) / Long Tab Banded Installation Instructions
Installation Instructions Installation Instructions Materials Required: Faced Fiberglass Insulation with Extended Tabs - Supplied in widths to match purlin spaces and lengths approximately 2 feet longer
More informationThermal Performance of Nvelope NV1 Clip System
Report Number: 5140108.00 December 18, 2014 Thermal Performance of Nvelope NV1 Clip System Presented to: Nvelope USA, LLC 16904 164 th Way S.E. Renton, WA 98058 Morrison Hershfield Suite 310, 4321 Still
More informationEnergy equivalent R-value
Mechanical & Aerospace Engineering Energy equivalent R-value Part 1: Integrated evaluation methodology for BE Mark Bomberg and Thomas Thorsell,, Syracuse University, Outline Objective: measure simultaneously
More informationOptiLiner Banded Liner System, Thermal, Metal Building
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
More informationWhy Insulate? - Thermal Control Certified Faced Insulation acts as a barrier to slow down the movement of heat, keeping it inside the building in wint
Insulation Why Insulate? - Thermal Control Certified Faced Insulation acts as a barrier to slow down the movement of heat, keeping it inside the building in winter and outside in summer. Why Insulate?
More informationTest Summaries: AWP 1818 & 3030
Test Summaries: AWP 1818 & 3030 ASTM C 1185/6 - Physical Properties Tests ASTM C 518 - Steady-State Heat Flex & Thermal Tests (R-Value) ASTM E 84 - Surface Burning Characteristics CAN/ULC - S102 Surface
More informationNRCC Guarded Hot Box Testing (ASTM C ) for Energy Efficiency of a Total Roof Assembly
Introduction 2001 Company, contracted NRCC/IRC to evaluate and determine both the thermal resistance and air leakage characteristics of five roofing specimens under controlled laboratory conditions. The
More information3-Dimensional Thermal Analysis of Lenmak EnvaTherm and SpandrelTherm Backpan Assemblies
Report Number: 5160440 August 18 th, 2016 3-Dimensional Thermal Analysis of Lenmak EnvaTherm and SpandrelTherm Backpan Assemblies Presented to: Lenmak Exterior Innovations Inc. 10404-176 Street Edmonton,
More informationAAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: Curtain Wall TYPE: Glazed Wall Systems (Site-built)
AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: GAMCO CORPORATION SERIES/MODEL: Curtain Wall TYPE: Glazed Wall Systems (Site-built) Summary of Results Thermal Transmittance (U-Factor) 0.47 Condensation
More informationThermal Performance of Northern Facades ISO Clip System Summary
Thermal Performance of Northern Facades ISO Clip Summary The Northern Facades ISO Thermal Clip is a steel clip system for attaching cladding systems to various types of exterior insulated wall assemblies.
More informationSECTION PRE-ENGINEERED BUILDING INSULATION
PART 1 GENERAL SECTION 07213 PRE-ENGINEERED BUILDING INSULATION Microsoft Word Instructions: Display hidden notes to specifier by using "Tools"/"Options"/"View"/"Hidden Text". 1.1 SECTION INCLUDES A. Pre-Engineered
More informationARCHITECT S GUIDE: Filled Cavity Systems for Metal Buildings
ARCHITECT S GUIDE: Filled Cavity Systems for Metal Buildings The Most Specified Name in Metal Building Vapor Retarders THE COMPANY LAMTEC S 0,000 square foot facility is situated on a -acre site in Northeastern
More informationThermal Bridging in Residential Construction
PHRC Webinar Series Tuesday, May 12, 2015 @ 1pm Thermal Bridging in Residential Construction Brian Wolfgang Housing Systems Specialist Pennsylvania Housing Research Center 219 Sackett Building University
More informationESR-1061 Reissued May 1, 2011 This report is subject to renewal in two years.
ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION Section: 07 21 00 Thermal Insulation Section: 07 25 00 Water-Resistive Barriers/Weather
More informationNational Fenestration Rating Council. Incorporated
National Fenestration Rating Council Incorporated NFRC 102-2014 [E1A1] Procedure for Measuring the Steady-State Thermal Transmittance of Fenestration Systems 2013 NATIONAL FENESTRATION RATING COUNCIL,
More informationThermal Performance of Nvelope NV1 Clip System
Report Number: 5140108.00 April 30, 2015 Thermal Performance of Nvelope NV1 Clip System Presented to: Nvelope USA, LLC 16904 164 th Way S.E. Renton, WA 98058 Morrison Hershfield Suite 310, 4321 Still Creek
More informationTEST REPORT. Rendered to: All Weather Insulated Panels Vacaville, California. PRODUCT TYPE: Roofing Panels SERIES/MODEL: SR Series
Architectural Testing TEST REPORT Report No.: C6304.01-301-44 Rendered to: All Weather Insulated Panels Vacaville, California PRODUCT TYPE: Roofing Panels SERIES/MODEL: SR Series Title Summary of Results
More informationConstruction Standards PAGE
Construction Standards PAGE 072100-1 SECTION 072100 PART 1 - GENERAL 1.1 M.S.U. ISSUES A. It the intent of MSU that insulation of its projects will comply with LEED NC 3 Credit Requirements EA Prerequisite
More informationThermal Analysis of CL-TALON Cladding Support System
Report Number: 180181400 February 16, 2018 Thermal Analysis of CL-TALON Cladding Support System Presented to: CL-TALON 3223 Dell Ave. North Bergen, NJ 07047 Morrison Hershfield Suite 310, 4321 Still Creek
More informationSECTION PRE-ENGINEERED METAL BUILDING
SECTION 13121 PRE-ENGINEERED METAL BUILDING PART 1 GENERAL 1.01 SCOPE OF WORK A. Furnish all labor, materials, equipment and incidentals required to design, fabricate, deliver to project site, and erect
More informationTrusted Tested Tough Kalaeloa Blvd, Kapolei, Hawaii Phone (808) Fax (808) Neighbor Islands (800)
MAC 200 STRUCTURAL STANDING SEAM METAL ROOF SYSTEM Trusted Tested Tough 91-104 Kalaeloa Blvd, Kapolei, Hawaii 96707 Phone (808) 682-3000 Fax (808) 682-3636 Neighbor Islands (800) 352-3920 www.kloecknermetals.com
More informationEVALUATION REPORT OF CENTRAL STATES MANUFACTURING, INC. 'CENTRAL-LOC PANEL' FLORIDA BUILDING CODE 5TH EDITION (2014) FLORIDA PRODUCT APPROVAL
- EVALUATION REPORT OF CENTRAL STATES MANUFACTURING, INC. 'CENTRAL-LOC PANEL' FLORIDA BUILDING CODE 5TH EDITION (2014) FLORIDA PRODUCT APPROVAL FL 14016.2-R2 STRUCTURAL COMPONENTS ROOF DECK Prepared For:
More informationAAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC.
Architectural Testing AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: TUBELITE, INC. SERIES/MODEL: 300ES Curtainwall (8" System) TYPE: Glazed Wall Systems (Site-built) Summary of Results Thermal
More informationREPORT HOLDER: R.L. ADAMS PLASTICS, INC CROSSROADS COMMERCE PARKWAY WYOMING, MICHIGAN EVALUATION SUBJECT: POLYCORE BRAND INSULATION
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3914 Reissued 10/2017 This report is subject to renewal 10/2018. DIVISION: 07 00
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: PAC INTERNATIONAL, LLC
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: PAC INTERNATIONAL, LLC TYPE: Wall, Steel (0.018" / 25 ga), RSIC-V, STC 67 DATA FILE NO: E4748.01A STC 67 OITC 56 Test Specimen Identification: (Source
More informationA. Thermal Conductivity: Thicknesses indicated are for thermal conductivity (k-value at 75 degrees F) specified for each material.
SECTION 07 20 00 - PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply
More informationSTANDING SEAM ROOF SYSTEM. Nucor CFR
STANDING SEAM ROOF SYSTEM Nucor CFR Nucor CFR Standing Seam Roof System Nucor CFR is a standing seam roof system designed to withstand a diverse range of climates and demanding roof conditions presenting
More informationThermal Insulation
University of New Hampshire University of New Hampshire Scholars' Repository Division 07 Thermal and Moisture Protection Chapter 5 Technical Construction and Renovation Standards 1-25-2013 072100 - Thermal
More informationA. Source Limitations: Obtain each type of building insulation through one source.
SECTION 07210 - BUILDING INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationRS32 Multi-Section Skylight System under/over seam clip double diverter
INSTALLATION INSTRUCTIONS RS32-x RS32 Multi-Section Skylight System under/over seam clip double diverter www.rnssales.com sales@rnssales.com 805.375.3980 Fax 805.375.3981 SKYLIGHT ACRYLIC skyline series
More information(Rev. 2000) STANDARD
202-96 MB311 v9:layout 11/21/08 4:06 PM Page 1 202-96 (Rev. 2000) STANDARD For Flexible Fiber Glass Insulation to be Laminated for Use in Metal Buildings www.naima.org 202-96 MB311 v9:layout 11/21/08 4:06
More informationFIRESTOP JOINT SPRAY CFS-SP WB. 2mm (0.079") WET FILM ± 7.5 ± 5
Design No. CEJ 27 P (HI/JS 20-05) Table. CONCRETE FLOOR ASSEMBLY: Max. two-hour rated concrete floor assembly made from either lightweight or normal weight concrete with a density of 00-50 pcf, with a
More informationAAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: W250C Awning TYPE: Projecting (Awning)
AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: GAMCO CORPORATION SERIES/MODEL: W250C Awning TYPE: Projecting (Awning) Summary of Results Thermal Transmittance (U-Factor) 0.48 Condensation Resistance
More informationsilvercote.com FOR NEW CONSTRUCTION
silvercote.com TM FOR NEW CONSTRUCTION A higher degree of insulation Through people, service and quality If it s important to you. It s important to us! We strive to provide an exceptional customer experience
More informationsilvercote.com FOR NEW CONSTRUCTION
silvercote.com TM FOR NEW CONSTRUCTION A higher degree of insulation Through people, service and quality If it s important to you. It s important to us! We strive to provide an exceptional customer experience
More informationAAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: COASTAL INNOVATIVE PRODUCTS
Architectural Testing AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: COASTAL INNOVATIVE PRODUCTS SERIES/MODEL: Outswing Aluminum Bi-Folding System TYPE: Swinging Door with Frame Summary of Results
More informationENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES OF INTEGRATED METHODOLOGY FOR EVALUATION OF ENERGY EQUIVALENT R-VALUE FOR BUILDING ENCLOSURES;
ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES OF INTEGRATED METHODOLOGY FOR EVALUATION OF ENERGY EQUIVALENT R-VALUE FOR BUILDING ENCLOSURES; Part 2: Examples of application to residential walls Thomas Thorsell
More informationAIR INFILTRATION TESTING
AIR INFILTRATION TESTING Prepared for Norbord Prepared by NAHB Research Center 400 Prince George s Blvd Upper Marlboro, MD 20774 www.nahbrc.com September 21, 2009 America s Housing Technology and Information
More information(Rev. 2000) STANDARD
202-96 (Rev. 2000) STANDARD For Flexible Fiber Glass Insulation to be Laminated for Use in Metal Buildings www.naima.org NAIMA 202-96 STANDARD (Rev. 2000) For Flexible Fiber Glass Insulation to be Laminated
More informationSection Roof/Ceiling Thermal Insulation
Section 07200 Roof/Ceiling Thermal Insulation Part 1 General 1.01 Summary A. Provide glass fiber thermal insulation for (roof) (ceiling) assembly as indicated in building plans. 1.02 Materials Provided
More informationTEST METHOD FOR THERMAL TRANSMITTANCE AND AIR INFILTRATION OF GARAGE DOORS
ANSI/DASMA 105-2017 AMERICAN NATIONAL STANDARD TEST METHOD FOR THERMAL TRANSMITTANCE AND AIR INFILTRATION OF GARAGE DOORS ANSI/DASMA 105-2017 Door & Access Systems Manufacturers Association, International
More informationRS24-10 Single-Section Skylight System
INSTALLATION INSTRUCTIONS RS24-10 VERSION 1.100316 DATED: 10/03/16 RS24-10 Single-Section Skylight System under/over seam clip double diverter US Patent D750,282 www.rnssales.com sales@rnssales.com 805.375.3980
More informationProfessional Educational Series BSP716 USGBC # Commercial Building Science Thermal Control in Building Envelopes
Professional Educational Series BSP716 USGBC # 90006736 Commercial Building Science Thermal Control in Building Envelopes CertainTeed Building Solutions 1.5 CertainTeed is a Registered Provider with the
More informationThis article will address the test methods used to determine R-values and their relative degree of accuracy.
Insulation R-value, What does it really mean? Every designer knows that the R-value of a material is important in specifying insulation products. Regulations abound that require minimum R-values for wall,
More informationDesign No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1
FIRESTOP JOINT SPRAY CFS-SP WB SILICONE JOINT SPRAY CFS-SP SIL F-RATING 2-HR. 2-HR. T-RATING -HR. -HR. APPLICATION THICKNESS PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table /8" WET FILM (/6"
More informationA. This Section includes duct and plenum insulation; accessories and attachments; and sealing compounds.
SECTION 230713 DUCT INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationGOWANDA, NEW YORK SEPTEMBER 18, 2008 ARCH PROJECT NO
SECTION 07210 BUILDING INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationWASHINGTON STATE ENERGY CODE, APPENDIX CHAPTERS
Chapter 51-11C WAC WASHINGTON STATE ENERGY CODE, APPENDIX CHAPTERS TABLE OF CONTENTS Appendix A Default Heat Loss Coefficients... AE-3 A101 General... AE-3 A101.1 Scope... AE-3 A101.2 Description... AE-3
More informationAIR DISTRIBUTION SOLUTIONS QUIETR ECOTOUCH SOFTR PROCAT
AIR DISTRIBUTION SOLUTIONS QUIETR ECOTOUCH SOFTR PROCAT Owens Corning Air Distribution Solutions 3 EcoTouch Insulation for Flexible Duct 4 QuietR Duct Board 5 ProCat Blown-in Insulation System 6 QuietR
More informationML200 Panel Technical Data Guide
Description ML200 is a mechanical seamed standing seam roofing panel used on low to steep sloped commercial applications. The panel is factory formed in continuous lengths up to 60-0 long. Attachment to
More informationPERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY
PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors / Round Top Single PRODUCT TYPE: In-swing Round Top Single Door RH-4 Title Uniform Load Deflection Test
More informationEXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD
SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board. 1.2 RELATED WORK A. Installation of steel framing members for walls, partitions,
More informationFire Testing Laboratory
Fire Testing Laboratory Page 1 of 39 TEST REPORT for 2148 S. 41st Street Lousiville, KY 40211 Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of Exterior Non-Load- Bearing
More informationENCLOSURE SOLUTIONS THERMAL BRIDGING GUIDE FIBERGLAS FOAMULAR THERMAFIBER
ENCLOSURE SOLUTIONS THERMAL BRIDGING GUIDE FIBERGLAS FOAMULAR THERMAFIBER This publication was prepared by Published by Owens Corning September 2018 DISCLAIMER This publication provides thermal transmittance
More informationREPORT ON COMPARATIVE AIR LEAKAGE PERFORMANCE:
REPORT ON COMPARATIVE AIR LEAKAGE PERFORMANCE: Knight Wall with Carlisle 705FR-A and Dow Styrofoam Ultra SL Compared To Z-Girts with Carlisle 705FR-A and Roxul CavityRock PROJECT: LOCATION: Knight Wall
More informationTEST REPORT. Report No.: F Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey
TEST REPORT Report No.: F399.01-109-44 Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey PRODUCT TYPE: ACP Panel System (Dry Seal) SERIES/MODEL: Dry Econect-RS Title Design Pressure Air Infiltration
More informationINSULATION VALUES TECHNICAL BULLETIN Vol. 3, No. 1 JANUARY 2017
INSULATION VALUES TECHNICAL BULLETIN Vol. 3, No. 1 JANUARY 2017 This is a thermal resistance guide for our insulated panels. This document is to serve as an explanation of code compliance and how these
More informationGUIDE SPECIFICATION: DUCT LINER
GUIDE SPECIFICATION: DUCT LINER This specification guide includes thermal & acoustical insulation for ductwork and air handling systems. This section is based on the format recommended by MICA (Midwest
More informationExterior Research & Design, L.L.C. Building Science and Envelope Consultants
Exterior Research & Design, L.L.C. Building Science and Envelope Consultants Certificate of Evaluation Report 4540.11.04-1-R1 Evaluation of R-Mer Span, R-Mer Loc and R-Mer Lite Non-Structural Metal Roofing
More informationINTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES
1.0 INTRODUCTION INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR COMPOSITE STEEL SHEET AND NONCOMBUSTIBLE SHEATHING PANELS EC 012-2016
More informationMILLENNIUM METALS, INC TEST REPORT
MILLENNIUM METALS, INC TEST REPORT SCOPE OF WORK WIND DRIVEN RAIN RESISTANCE TESTING OF MMI 26 GA OFF RIDGE VENT WITH DETACHABLE BAFFLE REPORT NUMBER H7685.03-450-18 R1 TEST DATE 11/29/17 ISSUE DATE 12/18/17
More informationPRESTON HEALTH SERVICES ARCHITECT S NO. 2700
SECTION 22 0700 - PLUMBING INSULATION PART 1 - GENERAL 1.1 DESCRIPTION OF WORK: A. All work covered in this section consists of furnishing all labor, equipment, materials and accessories, and performing
More informationArchitectural Roof Products Guide Specifications
Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Roof Products Guide Specifications FORMED METAL ROOF AND WALL PANELS This Guide Specification
More informationA. ASTM E84 Standard Test Method for Surface Burning Characteristics of Building Materials
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationLABORATORY TEST REPORT
LABORATORY TEST REPORT Report for: 5467 Evergreen Parkway Sheffield Village, OH 44054 Attention: Adam Mazzella Product Names: SMI 1.5 Mechanical Seam Standing Seam Manufacturer: Project No.: SHMI-005-02-01.1
More informationSECTION COLD-FORMED METAL TRUSSES
SECTION 054400 COLD-FORMED METAL TRUSSES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationArchitectural Roof Products Guide Specifications
Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Roof Products Guide Specifications FORMED METAL ROOF AND WALL PANELS This Guide Specification
More informationLocal Temperature Measurements on Full-Size Systems in the Laboratory: Insight into the Extent of Thermal Bridges in Building Envelope Components
Local Temperature Measurements on Full-Size Systems in the Laboratory: Insight into the Extent of Thermal Bridges in Building Envelope Components Thomas W. Petrie, Jan Ko ny, Jerald A. Atchley and André
More informationCertaPro Thermal FSK-25 Faced Batts
CertaPro Thermal FSK-25 Faced Batts ASTM C 553, Type I ASTM C 665, Type III, Class A, Category 1 New York City MEA 19-80-M Light-density fiber glass batts with a foil scrim kraft (FSK) fire resistant vapor
More informationROOFING EPDM ELASTOMERIC SHEET ROOFING FULLY ADHERED- CONVENTIONAL
ROOFING EPDM ELASTOMERIC SHEET ROOFING FULLY ADHERED- CONVENTIONAL PART 1 GENERAL 1.1 SECTION INCLUDES A. Insulation, membrane roofing, base flashings roofing membrane accessories joints, and counter flashings.
More informationPROJ. NO SECTION HVAC DUCT INSULATION
SECTION 23 07 13 HVAC DUCT INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationA. Metal Building System Description: Rigid modular, with interior columns with expandable endwall.
SECTION 13125 - METAL BUILDING SYSTEMS PART 1 - GENERAL 1.1 SECTION REQUIREMENTS A. Metal Building System Description: Rigid modular, with interior columns with expandable endwall. 1. Eave Height: 13-0
More informationA. Product Data: Identify thermal conductivity, thickness, and jackets (both factory and field applied, if any), for each type of product indicated.
SECTION 23 07 13 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
More informationAddendum #4 NEW LOW HEAD OXYGEN SYSTEM Contractor EXHIBIT T SPECIAL PROVISIONS SECTION METAL SHADE STRUCTURE
SECTION 13 34 00 METAL SHADE STRUCTURE PART 1 - GENERAL 1.01 STRUCTURE TYPE A. Structure shall be free standing rigid frame and gable roof with slopes as indicated. Structure shall also include foundation,
More informationAAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: WASHOE EQUIPMENT, INC. DBA SUNOPTICS PRISMATIC SKYLIGHTS
AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: WASHOE EQUIPMENT, INC. DBA SUNOPTICS PRISMATIC SKYLIGHTS SERIES/MODEL: 800MD Signature PRODUCT TYPE: Fixed Plastic Glazed Skylight Title Summary
More informationStanding Seam Systems. NBS Specification. KingZip SF Standing Seam Roofing System
NBS Specification KingZip SF Standing Seam Roofing System H31 METAL PROFILED/FLAT SHEET CLADDING/COVERING To be read with Preliminaries/General conditions. TYPE OF CLADDING SYSTEM 140 METAL PROFILED CLADDING
More informationAnalytical Investigation of Thermal Performance of Precast Concrete Three-Wythe Sandwich Wall Panels
Analytical Investigation of Thermal Performance of Precast Concrete Three-Wythe Sandwich Wall Panels Byoung-Jun Lee, Ph.D. Visiting Research Scientist Center for Advanced Technology for Large Structural
More informationSECTION THERMOPLASTIC MEMBRANE ROOFING PART 1 GENERAL 1.01 SECTION INCLUDES
SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING PART 1 GENERAL 1.01 SECTION INCLUDES A. Mechanically attached system with thermoplastic roofing membrane. B. Insulation, flat and tapered. C. Flashings. D.
More informationBXUV.V481. Fire Resistance Ratings - ANSI/UL 263. Design/System/Construction/Assembly Usage Disclaimer. Fire Resistance Ratings - ANSI/UL 263
Page Bottom BXUV.V481 Fire Resistance Ratings - ANSI/UL 263 Design/System/Construction/Assembly Usage Disclaimer Authorities Having Jurisdiction should be consulted in all cases as to the particular requirements
More informationASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: FabriSpan. TYPE: Ceiling System. Summary of Test Results
ASTM C 423 SOUND ABSORPTION TEST REPORT Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: FabriSpan TYPE: Ceiling System Summary of Test Results Sample ID Number & Sample Description C8714.01 Series/Model
More informationcalculated with factor of safety of 2.5 for bending stress, 3.0 for shear stresses and deflection limitation of L/180.
Metl-Span CF-42 Light Mesa Wall Panels 26 Ga. Exterior / 26 ga. Interior Facings Allowable Connection Load 1,7,8,9,10 (psf) Two or More Equal Spans Panel Type 2 Design Criteria 3,4,5,6 Support Span 5 ft
More informationFOR: CEMCO - California Expanded Metal Products Co. Sound Transmission Loss Test
FOR: CEMCO - California Expanded Metal Products Co. Sound Transmission Loss Test Industry, CA ON: Bare 1 Inch Thick USG LEVELROCK Brand CSD Floor Underlayment on USG LEVELROCK SRM-25 Sound Mat on CEMCO
More informationArchitectural Roof and Wall Products Guide Specifications
Architectural Roof and Wall Products Guide Specifications 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 FORMED METAL ROOF AND WALL PANELS This Guide Specification is to be used
More informationPERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY
PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors/Round Top Double PRODUCT TYPE: In-swing Round Top Double Door LH-4-5/8 Title Uniform Load Deflection
More informationConvective Loss in Loose-Fill Attic Insulation
Page 1 of 6 search The Magazine Subscribe to Home Energy Back to Contents Page Home Energy Index About Home Energy Home Energy Home Page Back Issues of Home Energy Home Energy Magazine Online May/June
More informationDIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS/WEATHER BARRIERS
0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1504 Reissued 03/2017 This report is subject to renewal 03/2018. DIVISION: 07 00
More informationPROJECT DIRECTIVE # FOR KALISPELL PUBLIC SCHOOLS
PROJECT DIRECTIVE #1 2010-11 FOR KALISPELL PUBLIC SCHOOLS GLACIER HIGH SCHOOL SITE INVESTIGATION SECOND FLOOR CLASSROOM PODS INSULATION AND VAPOR BARRIER INSPECTION TECHNICAL MEMORANDUM NO. 1.1 April 1,
More informationSpecifications. When specifying metal panel roof systems, roof. system designers and specifiers need to be aware
32 www.professionalroofing.net OCTOBER 2012 When specifying metal panel roof systems, roof system designers and specifiers need to be aware of specific standards. Sometimes, the standards applicable to
More informationBuilding Envelopes 101
Session: Foundation Building Block 1 Building Envelopes 101 Diana Hun, PhD Oak Ridge National Laboratory August 9, 2016 Rhode Island Convention Center Providence, Rhode Island US Primary Energy Consumption
More informationMetal Roof Panels
University of New Hampshire University of New Hampshire Scholars' Repository Division 07 Thermal and Moisture Protection Chapter 5 Technical Construction and Renovation Standards 1-25-2013 074113 - Metal
More informationEcoTouch Insulation with PureFiber Technology
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
More informationLISTING INFORMATION OF International Beams - IB Series Joists SPEC ID: 27316
LISTING INFORMATION OF International Beams - IB Series Joists SPEC ID: 27316 International Beams Inc. 2010 Boul. St-Elzear Quest Laval, QC H7L 3N4 CANADA This report is for the exclusive use of Intertek
More informationThermal Bridging and Whole Building Energy Performance
Thermal Bridging and Whole Building Energy Performance Steve Murray, P.Eng. PMP Morrison Hershfield May 8 & 9, 2013 1 Acknowledgments The real work for ASHRAE 1365 RP was done by others in MH s Vancouver
More informationSL175 Panel Technical Data Guide
Description SL175 is a integral snap-lock standing seam roofing panel used on commercial and residential applications. The panel is factory formed in continuous lengths up to 60-0 long. Attachment to either
More informationMetal Roof Certification & Listing Program
Certification Report 145 Limekiln Road, Suite 100B Issue Dated: 1/22/2018 New Cumberland, PA 17070 Revision Date: 1/27/2018 www.keystonecerts.com Expiration Date: 1/22/2023 Construction Specifications
More informationD. Provide UL-approved assemblies for pipes and ducts passing through fire-rated floors, walls, or partitions as required.
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationSECTION (07200) - THERMAL PROTECTION
PART 1 GENERAL 1.01 SUMMARY A. Section Includes: SECTION 07 20 00 (07200) - THERMAL PROTECTION 1. Batt Insulation a. Unfaced b. Faced 2. Sound Attenuation Insulation a. Mineral Fiber b. Slag-Wool-Fiber/Rock-Wool-Fiber
More informationSECTION THERMAL INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS
SECTION 072100 - THERMAL INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More information