INSPECTION GUIDELINES: JOIST AND UNDERFLOOR COMBO

Size: px
Start display at page:

Download "INSPECTION GUIDELINES: JOIST AND UNDERFLOOR COMBO"

Transcription

1 Joist and Underfloor Combo Page 1 of 7 Revision Date: 10/02/2017 DEVELOPMENT SERVICES BUILDING INSPECTION INSPECTION GUIDELINES: JOIST AND UNDERFLOOR COMBO INSPECTION CODE: 212, 213 SCOPE: RESIDENTIAL CODES ENFORCED: 2016 CBC, CRC, CPC, CMC, CEC, CALGreen, CEnC, and PAMC The information provided in this document is general and intended as a guide only. Each project is unique and additional requirements may be enforced as deemed appropriate. IMPORTANT Failure to complete the items below prior to the City of Palo Alto (CPA) inspection will result in a reinspection fee. Gas and electric utilities will be removed if found to be unsafe at time of inspection. (CBC ) All structures require joist inspection prior to installation of subfloor including buildings with a crawl space, basement, and joist installed directly on floor/sleepers. DO NOT install the subfloor prior to the joist inspection NO EXCEPTIONS. Contractor is subject to a Stop Work Order and a $ re-inspection fee when covering work or joists without inspection. The contractor will be required to provide equipment (i.e., scaffolding) and lighting to do the joist inspection if this step is skipped. INSPECTION BUILDINGS IN FLOOD ZONE AREAS When in a flood zone, contact Public Works Inspector Denis Huegle at to schedule an inspection; make sure that you have met all their requirements before scheduling the inspection. Public Works must sign the card before Building Inspectors can verify the work. All structural material and members below base flood elevation (BFE) shall be water resistant concrete or pressure treated lumber type. (CRC R322) All metal below the BFE shall be corrosion resistant/galvanized, including gas piping. (CRC R )

2 Joist and Underfloor Combo Page 2 of 7 Revision Date: 10/02/2017 Mechanical, plumbing, and electrical systems shall be located at or above the BFE. (CRC R ) This includes any insulation being used. o Exceptions: Although not recommended, in unavoidable situations duct systems exposed to flood water must be 20 gage spiral duct, sealed to prevent water entry, and braced for buoyancy effects. They shall have a minimum 4 clearance to grade and shall not block access to underfloor opening(s). The insulation on the duct must be bubble-wrap-type, secured, and sealed with waterproof tape. Plumbing systems and gas piping are permitted below the BFE provided that the systems are rigidly supported to resist buoyancy during the occurrence of flooding (see Figure CPA 030). (CPC 301.4) Figure CPA 030 Plumbing below BFE Where under floor crawl space is less than 18, or if the underfloor area is not accessible or below BFE in a flood zone, all floor materials shall be pressure treated (e.g., joists, girders, plywood). (CBC ) FRAMING Access openings: Min. 18 x 24. Underfloor access openings and crawl area shall not be blocked by duct work or plumbing. See Mechanical below. (CRC R408.4) Provide solid blocking or squash blocks under all hold-downs in raised floor installations. Verify all foundation attachments are per the structural plans and details (e.g., anchor bolts, clips, blocking, screws, nailing, and hold-downs). The size of sill plate washers shall be a minimum of 3 x 3 x 1/4. The hole in the washer may be slotted provided a standard cut washer is placed between the plate washer and the nut. (CBC , CRC R )

3 Joist and Underfloor Combo Page 3 of 7 Revision Date: 10/02/2017 Verify sill plate is sized per plan specifications and sealant, adhesive or gasket is installed between slab/foundation and sill plate to limit infiltration and exfiltration. (CEC 110.7) Install a minimum of two anchor bolts per sill plate. The minimum distance from end of sill should be 4 and a maximum distance from sill edge 12. (CBC ) Hardware and fasteners in contact with pressure-treated wood shall be of approved corrosion resistant material. (CRC R317.3) Verify that all forms, stakes, wood debris, Sonotube forms have been removed from under-floor area. (CRC R408.5) Air vent openings shall not be located in or below shear walls or at hold-down locations. (Vent openings are typically located under windows and non-shearwall areas.) (CRC R408) Post to girder and beam connections shall be closely fitted and positive connections with approved hardware at footing to post, post to girder/beam and girder/beam joints. Wooden stakes are not allowed at any foundation inspection when embedded in concrete. (PAMC ) Wood to earth: Wood framing shall be 8 minimum from exposed ground unless pressure treater. (CRC R317.1) I-joist installation: install web stiffeners/backer blocks where hangers are not full height and when I- joist is used as a header. Install squash blocks a min. of 1/16 above I-joist at bearing walls. Install per manufacturer is installation instructions. Joist closer than 18 to ground and girders closer than 12 to ground shall be preservative treated (PT) or naturally durable wood, including post and sub-floor. (CRC R317.1) Cripple walls with stud height less than 14 shall be sheathed on at least one side with a wood structural panel that is fastened to both the top and bottom plates. Foundation cripple walls shall be framed of studs not smaller than the studs above. (CRC R602.9) Verify protection of exposed wood and insulation at foundation and flood vents from water intrusion. Install insulation baffles, apply copper green or automotive undercoat or install non-operable louvered vents to protect structure. (CEC)

4 Joist and Underfloor Combo Page 4 of 7 Revision Date: 10/02/2017 PLUMBING Protect all piping systems within 1-1/2 from top of joist including copper pipes with nail plates 1-1/2 from top of joist. (CPC ) Horizontal drain and waste piping systems shall have a minimum 1/4" per foot slope toward the point of disposal. Piping systems less than 1/4 slope needs to be pre-approved. (CPC 708.1) Under floor cleanouts shall not be located more than 5 from an access door. (CPC 707.9) Maintain an 18 clearance in front of clean out for piping 2 or less. Maintain a 24 clearance in front of the cleanout for piping larger than 2. (CPC 707.9) Cleanouts shall extend to or above the finished floor or be extended to the outside of the building where there is less than 18 vertical clearance (allowing for obstructions such as ducts, beams, and piping) and 30 horizontal clearance from the means of access to the cleanout. (CPC 707.9) A water test shall be applied to the drainage and vent systems with not less than a 10 head of water; the water shall be kept in the system for not less than 15 minutes. Alternatively, an air test can be done at a pressure of 5 psi for not less than 15 minutes. (CPC 712.2, CPC 712.3) Piping support: Per CPC Table (see the page that follows). GAS Gas piping systems shall be pressure tested not less than 10 psi for at least 15 minutes with not perceptible drop in pressure. (CPC ) (NOTE: A whole-house gas test will be required at Final Inspection.) Gas piping supports shall be per Table

5 Joist and Underfloor Combo Page 5 of 7 Revision Date: 10/02/2017 MECHANICAL Air ducts installed under a floor in a crawl space shall be installed per the following (CMC 603.2): o Shall not prevent access to an area of the crawl space o Where it is required to move under ducts for access to areas of the crawl space, a vertical clearance of not less than 18 shall be provided Ducts shall have at least a 4 clearance to the earth. (CMC 603.3) Wrap boots with insulation.

6 Joist and Underfloor Combo Page 6 of 7 Revision Date: 10/02/2017 Joints and seams and reinforcements for rigid air ducts shall be listed in accordance with UL 181A; for flexible ducts it shall be in accordance with UL 181B. (CMC ) Installers shall provide the manufacturer s installation instructions showing the support requirements and/or per SMACNA HVAC Duct Construction Standards Metal and Flexible. In no case shall flex duct supports be spaced more than 5 and max sag 2-1/2 or ½ max. per foot (see Figure CPA 032). (CMC 603.8) Figure CPA 032 Correctly Supported Flex Duct VENTILATION Louvered vents are required when vent openings are above floor. (CEnC) The minimum net area of underfloor ventilation openings shall not be less than 1 square foot of each 150 square feet of underfloor area. (CRC R408.1) One ventilation opening shall be within 3 feet of each corner of the building. (CRC R408.1). Openings for underfloor ventilation shall be not less than 1-1/2 square feet for each 25 linear feet of exterior wall.

7 Joist and Underfloor Combo Page 7 of 7 Revision Date: 10/02/2017 Openings shall be placed so as to provide cross ventilation (and not under shear-walls). o Exception: At the discretion of the Building Official and when impractical due to structural features or the arrangement of the structure, the following three exceptions may be used as an alternative to the 1/150 rule as stated above. (CRC R408.2, Exception) 1. Ventilation openings may be reduced to 1 square feet of each 1,500 square feet of underfloor area where the ground surface is treated with a CPA approved vapor retarder material and required openings are placed so as to provide cross ventilation of the space. The installation of operable louvers shall not be prohibited. 2. Provide continuously operated mechanical ventilation and ground surface covered with CPA approved vapor retarder. 3. CPA approved vapor retarder, perimeter walls are insulated, and the space is conditioned in accordance with the California Energy Code, Title 24, Part 6. CPA Approved Vapor Retarders: Stego Wrap or Moistop; 6mill or 10 mill Visqueen plastic sheeting is not permitted because it does not comply with a permeability rating, lacks the puncture resistance, and deteriorates over time. RODENT PROTECTION Tub waste openings in framed construction to crawl spaces shall be protected from rodent intrusion with no openings greater than 1/2". See FIGURE A-3 for an approved method of protection/access. (CPC ) Figure CPA 031 Rodent Protection at Crawl Space Bath/Shower Plumbing Access Locations

INSPECTION REQUIREMENTS: FOUNDATIONS

INSPECTION REQUIREMENTS: FOUNDATIONS Foundations Page 1 of 9 Revision Date: 1/2/2018 DEVELOPMENT SERVICES BUILDING INSPECTION INSPECTION REQUIREMENTS: FOUNDATIONS INSPECTION CODE: 204 SCOPE: RESIDENTIAL APPLICABLE CODES: 2016 CBC, CRC, CPC,

More information

INSPECTION GUIDELINES: STRUCTURAL INSULATED PANELS (SIPs)

INSPECTION GUIDELINES: STRUCTURAL INSULATED PANELS (SIPs) Structural Insulated Panels Page 1 of 7 Revision Date: 05/22/2017 DEVELOPMENT SERVICES BUILDING INSPECTION INSPECTION GUIDELINES: STRUCTURAL INSULATED PANELS (SIPs) INSPECTION CODE: 111, 204, 216 SCOPE:

More information

INSPECTION GUIDELINES: ROOF/EXTERIOR SHEATHING/STRUCTURAL FRAME

INSPECTION GUIDELINES: ROOF/EXTERIOR SHEATHING/STRUCTURAL FRAME Roof/Exterior Sheathing/Structural Framing Page 1 of 24 Revision Date: 10/02/2017 DEVELOPMENT SERVICES BUILDING INSPECTION INSPECTION GUIDELINES: ROOF/EXTERIOR SHEATHING/STRUCTURAL FRAME INSPECTION CODE:

More information

FIELD COPY ATTACHMENT

FIELD COPY ATTACHMENT FIELD COPY ATTACHMENT The released plans for the project must be on site and available to the inspectors at all times. No inspection will be done without the released field plans. If you have any questions,

More information

FEMA P-593 STEP-BY STEP PRESCRIPTIVE RETROFIT FOR CRIPPLE WALL BRACING & ANCHORAGE TO FOUNDATION

FEMA P-593 STEP-BY STEP PRESCRIPTIVE RETROFIT FOR CRIPPLE WALL BRACING & ANCHORAGE TO FOUNDATION INTRODUCTION Objective of provisions: The provisions of IEBC Appendix Chapter A3 are intended to reduce hazard of earthquake-induced damage (IEBC A301.1). These provisions are not intended to eliminate

More information

Lonsdale Building Inspections Department 415 Central Street W. PO Box 357 Lonsdale, MN (507) fax (507)

Lonsdale Building Inspections Department 415 Central Street W. PO Box 357 Lonsdale, MN (507) fax (507) Lonsdale Building Inspections Department 415 Central Street W. PO Box 357 Lonsdale, MN 55046 (507) 744-2327 fax (507) 744-5554 2006 RESIDENTIAL CONSTRUCTION CHECKLIST The following checklist has been designed

More information

Garage/Accessory Structures

Garage/Accessory Structures Garage/Accessory Structures City of New Prague Building Inspections Department 118 Central Ave N New Prague, MN 56071 (952) 758-4401 Fax (952) 758-1149 Requirements for submitted Building Plans Signed

More information

INSPECTION GUIDELINES: SPECIAL INSPECTION REQUIREMENTS

INSPECTION GUIDELINES: SPECIAL INSPECTION REQUIREMENTS Special Inspection Requirements Page 1 of 8 Revision Date: 08/07/2018 DEVELOPMENT SERVICES BUILDING INSPECTION INSPECTION GUIDELINES: SPECIAL INSPECTION REQUIREMENTS INSPECTION CODE: N/A SCOPE: RESIDENTIAL

More information

March 30, 2017 MKM File #

March 30, 2017 MKM File # MKM File # 170161 Paul Jeschke 77 Starbuck Drive Muir Beach, CA Re: Muir Beach Community Building 19 Seacape Drive Muir Beach, CA Dear Paul, At your request, MKM & Associates visited the above referenced

More information

Administrative Changes

Administrative Changes Revised 11/29/06 Knox County Residential Building Codes Significant Changes From The 1995 CABO One And Two Family Dwelling Code To The 2006 International Residential Code All one and two family dwellings

More information

Minimum Residential Plan Submittal Requirements

Minimum Residential Plan Submittal Requirements Minimum Residential Plan Submittal Requirements BI-24 CRC 2016 In order to make your permit application and the plan review process go as smooth as possible it is important to have a general understanding

More information

BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018)

BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018) BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018) PERMIT SUBMITTAL CHECKLIST: Signed and completed Building Permit application form. A separate Electrical permit is required from

More information

Building Division Informational Handout

Building Division Informational Handout CITY OF SAN JOSÉ, CALIFORNIA Building Division Informational Handout Conventional Light Frame Construction Design Provisions 2007 CBC Handout No. 2-21 Published: 1/1/08 Page 1 of 3 This document summarizes

More information

Project Name: Enforcement Agency: Permit Number:

Project Name: Enforcement Agency: Permit Number: Installation (Page 1 of 4) If more than one person has responsibility for installation of the items on this certificate, each person shall prepare and sign a certificate applicable to the portion of construction

More information

Left Elevation. Front Elevation. Back Elevation. Right Elevation CEDAR RIDGE H O M E S. Total Sq Ft = 1,842. Scale : 1/4" = 1'

Left Elevation. Front Elevation. Back Elevation. Right Elevation CEDAR RIDGE H O M E S. Total Sq Ft = 1,842. Scale : 1/4 = 1' Plan Name 4 4" Window and door trim. (Street facing facades) 4" Corner Boards 4" Vertical Cedar Siding Left Elevation Lap siding over approved building wrap over 1 2" OSB sheathing. Front Elevation Stone

More information

1 AND 2 FAMILY DWELLING REQUIREMENTS

1 AND 2 FAMILY DWELLING REQUIREMENTS PLAN REQUIREMENTS: 1 AND 2 FAMILY DWELLING REQUIREMENTS All residential plans including additions and attached garages shall be designed to the current edition of the International Residential Code. Plans

More information

One and Two Family Additions

One and Two Family Additions One and Two Family Additions An addition to a house, duplex, garage, or an accessory structure requires a building permit prior to performing any construction. Building Department & Permit Office Mon-Fri

More information

Section 22A. Lead Paint Risk Factor NONE-HIGH FLOOR INSULATION FOR CONVENTIONAL HOMES TABLE OF CONTENTS

Section 22A. Lead Paint Risk Factor NONE-HIGH FLOOR INSULATION FOR CONVENTIONAL HOMES TABLE OF CONTENTS FLOOR INSULATION FOR CONVENTIONAL HOMES Lead Paint Risk Factor NONE-HIGH TABLE OF CONTENTS PART 1: INSTALLATION REQUIREMENTS FOR CONVENTIONAL HOMES... 1 FLOOR INSULATION REPAIR... 1 Not applicable to this

More information

Module number 3 provides an on-line, self-paced training seminar on chapter 4, foundations and chapter 5, floors from the residential code of ohio.

Module number 3 provides an on-line, self-paced training seminar on chapter 4, foundations and chapter 5, floors from the residential code of ohio. Module number 3 provides an on-line, self-paced training seminar on chapter 4, foundations and chapter 5, floors from the residential code of ohio. 1 This chapter sets forth the prescriptive requirements

More information

HILLSBOROUGH TOWNSHIP CODE ENFORCEMENT

HILLSBOROUGH TOWNSHIP CODE ENFORCEMENT HILLSBOROUGH TOWNSHIP CODE ENFORCEMENT SAMPLE GUIDE FOR RESIDENTIAL DECKS revised 7 16 Call before you dig! 1 800 272 1000 New Jersey One Call. Utility Mark Out. THIS GENERIC GUIDE IS NOT ALL INCLUSIVE

More information

BUILDING PERMIT REQUIREMENTS FOR: RESIDENTIAL DECKS CITY OF ESCONDIDO BUILDING DIVISION 201 N. BROADWAY, ESCONDIDO, CA (760)

BUILDING PERMIT REQUIREMENTS FOR: RESIDENTIAL DECKS CITY OF ESCONDIDO BUILDING DIVISION 201 N. BROADWAY, ESCONDIDO, CA (760) BUILDING PERMIT REQUIREMENTS FOR: RESIDENTIAL DECKS INFORMATION GUIDELINE 9 January 2017 CITY OF ESCONDIDO BUILDING DIVISION 201 N. BROADWAY, ESCONDIDO, CA 92025 (760) 839-4647 This information bulletin

More information

Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2014 LARC)

Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2014 LARC) Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2014 LARC) Plan Check Submittal Date: Plan Check #: Permit App.# Job Address: Applicant: Phone: ( ) Plan Check Engineer:

More information

RUNNERS (Required to convert to real property)

RUNNERS (Required to convert to real property) HUMBOLDT COUNTY BUILDING DEPARTMENT MANUFACTURED HOUSE/MOBILE HOME RUNNERS & PERIMETER FOUNDATION These requirements apply to the construction of permanent foundations necessary to convert to real property.

More information

Chapter 14 - Air Sealing

Chapter 14 - Air Sealing Chapter 14 - Air Sealing Contents Chapter 14 - Air Sealing... 14-1 Pre-Mechanicals Activities... 14-3 Insulate Bathtub Enclosures... 14-3 Insulate Double Walls and Chases... 14-3 Pre-Inspection Checklist...

More information

Typical Deck. CONSTRUCTION TIP SHEET 5 Basic Decks w/ 60 psf Live Loading

Typical Deck. CONSTRUCTION TIP SHEET 5 Basic Decks w/ 60 psf Live Loading CONSTRUCTION TIP SHEET 5 Basic Decks w/ 60 psf Live Loading April 1, 2017 This Tip Sheet reflects code requirements of the 2015 International Residential Code (IRC) with Washington State Amendments which

More information

GENERAL BUILDING CODE AND ZONING REQUIREMENTS: Post and spread footings shall be designed and constructed below the minimum frost depth of 42 inches

GENERAL BUILDING CODE AND ZONING REQUIREMENTS: Post and spread footings shall be designed and constructed below the minimum frost depth of 42 inches GENERAL BUILDING CODE AND ZONING REQUIREMENTS: Post and spread footings shall be designed and constructed below the minimum frost depth of 42 inches and shall be sized to carry the applicable roof and

More information

Typical Deck. CONSTRUCTION TIP SHEET 5 Basic Decks w/ 60 lb Live Loading

Typical Deck. CONSTRUCTION TIP SHEET 5 Basic Decks w/ 60 lb Live Loading CONSTRUCTION TIP SHEET 5 w/ 60 lb Live Loading April 1, 2017 This Tip Sheet reflects code requirements of the 2015 International Residential Code (IRC) with Washington State Amendments which update the

More information

Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2011 LARC)

Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2011 LARC) Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2011 LARC) Plan Check Submittal Date: Plan Check #: Permit App.# Job Address: Applicant: Phone: ( ) P.C. Engineer: Phone:

More information

ADDITIONS BUILDING AND ZONING REQUIREMENTS (REVISED 4/22/2008)

ADDITIONS BUILDING AND ZONING REQUIREMENTS (REVISED 4/22/2008) ADDITIONS BUILDING AND ZONING REQUIREMENTS (REVISED 4/22/2008) PERMIT SUBMITTAL CHECKLIST: Signed completed Building Permit application form. Two (2) Copies of a Certificate of Survey. Draw to scale the

More information

ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings

ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings Building Safety Department 400-2 nd Street South St. Cloud, MN 56301 (320) 255-7239 A building permit is required for any accessory

More information

SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE:

SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE: IRC CODE UPDATES TO: RESIDENTIAL BUILDING CONTRACTORS FROM: GARY STABER, BUILDING OFFICIAL SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE: 6/1/2003 INTERNATIONAL RESIDENTIAL CODE (IRC) APPLICABILITY:

More information

RESIDENTIAL CONSTRUCTION New Dwellings and Additions

RESIDENTIAL CONSTRUCTION New Dwellings and Additions How to Obtain a Building Permit For RESIDENTIAL CONSTRUCTION New Dwellings and Additions MIAMI COUNTY, KANSAS CODE SERVICES DEPARTMENT 201 South Pearl Street, Suite 201 Paola, Kansas 66071-1777 Phone:

More information

THE FLORIDA BUILDING CODE

THE FLORIDA BUILDING CODE THE FLORIDA BUILDING CODE 1. According to the Florida Building Code, spiral stairway treads must all be identical and rise must be sufficient enough to provide a headroom of minimum. A. 6'- 4" B. 6'- 6"

More information

4 EXTREME FOUNDATION PANELS

4 EXTREME FOUNDATION PANELS 4 EXTREME FOUNDATION PANELS For House Crawl Space On Concrete Footings 1. The type of soil is a factor in determining foundation construction details such as footing design, backfill, and drainage provisions.

More information

1 & 2 Family Garage/Shed Permits City of Oshkosh Inspection Services Division

1 & 2 Family Garage/Shed Permits City of Oshkosh Inspection Services Division This handout will help guide you through the permit application process. Following the steps below will help to expedite the issuance of your building permit. Please plan ahead and pick one of the following

More information

SECTION WOOD FRAMING. A. Includes But Not Limited To 1. Furnish and install wood framing and blocking as described in Contract Documents.

SECTION WOOD FRAMING. A. Includes But Not Limited To 1. Furnish and install wood framing and blocking as described in Contract Documents. SECTION 06110 WOOD FRAMING PART 1 GENERAL 1.1 SUMMARY A. Includes But Not Limited To 1. Furnish and install wood framing and blocking as described in Contract Documents. B. Products Installed But Not Supplied

More information

WeatherSmart Air Barrier Installation Guide

WeatherSmart Air Barrier Installation Guide WeatherSmart Air Barrier Installation Guide 1 The intent of this document is to provide a guide for the installation of WeatherSmart as both a Weather Resistive Barrier (W.R.B.) and an Air Barrier Material

More information

Elevations. Front Elevation. Left Elevation. Back Elevation. Right Elevation CEDAR RIDGE H O M E S. Total Sq Ft = 1,647.

Elevations. Front Elevation. Left Elevation. Back Elevation. Right Elevation CEDAR RIDGE H O M E S. Total Sq Ft = 1,647. 10" Belly Band Cement board shake siding Cement board siding 7" Lap Decorative Corbels Cement board siding 7" Lap 4" Corner boards Stone Veneer on Garage wings 48" high 4" Window and Door Trim (Street

More information

CODE COMPLIANCE GUIDELINE GENERAL BUILDING

CODE COMPLIANCE GUIDELINE GENERAL BUILDING CODE COMPLIANCE GUIDELINE This guideline has been prepared by The Calhoun County Building Department to assist Homebuilders, General Contractors, and Owner/Builders during the construction process. The

More information

Elevations. Front Elevation. Left Elevation. Back Elevation. Right Elevation CEDAR RIDGE H O M E S. Total Sq Ft = 1,647.

Elevations. Front Elevation. Left Elevation. Back Elevation. Right Elevation CEDAR RIDGE H O M E S. Total Sq Ft = 1,647. 4 12 Pitch Cement board siding 7" Lap 4" Corner boards Vertical Cedar T&G Siding 4" Window and Door Trim (Street facing facade) P.T. 6x6 : Wrapped & collared with cement board Trim. Stone Veneer on Garage

More information

Residential Patio Cover Specifications

Residential Patio Cover Specifications Residential Patio Cover Specifications This information bulletin describes the minimum requirements for obtaining patio cover permits for residential buildings using the City of Vista standard plan or

More information

Typical Deck Details Based on the 2009 International Residential Code (Designed and Printed August 2010)

Typical Deck Details Based on the 2009 International Residential Code (Designed and Printed August 2010) 1307 West Lehigh Street Bethlehem, PA 18018 610-866-9663 Office info@keycodes.net www.keycodes.net Typical Deck Details Based on the 2009 International Residential Code (Designed and Printed August 2010)

More information

The better way to build TM. Installation Manual FOUNDATION SIPs & FROST WALLS SIPs

The better way to build TM. Installation Manual FOUNDATION SIPs & FROST WALLS SIPs The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs November 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements....................................

More information

PICK YOUR POISON AND HOW TO GET THERE. Presented By Robby Schwarz

PICK YOUR POISON AND HOW TO GET THERE. Presented By Robby Schwarz PICK YOUR POISON AND HOW TO GET THERE Presented By Robby Schwarz Code Adoption Cycle 2012 International Energy Conservation code The code that got peoples attention Adoption and development are out of

More information

Contractor/Owner initials are verification that items #1 and #2 and items (a) thru (g) above are included in the submitted plan/drawing.

Contractor/Owner initials are verification that items #1 and #2 and items (a) thru (g) above are included in the submitted plan/drawing. FINISH BASEMENT/ADDITION/REMODEL PLAN CORRECTIONS LIST (Based on the current Editions of the International Codes and National Electrical Code) PLAN CHECKED BY: LOT/SUBDIVISION/ADDRESS: CONTRACTOR OR OWNER/BUILDER:

More information

HOLDOWN & STRAP SCHEDULE

HOLDOWN & STRAP SCHEDULE SHEAR WALL SCHEDULE STRUCTURAL DESIGN CRITERIA GOVERNING CODE SOIL BEARING PRESSURE HOLDOWN & STRAP SCHEDULE MARK SHEATHING SHEATH BOTH SIDES NAILS EDGE SPACING NOTES MARK SW 7/" OSB NO 8d " OC - A SW

More information

BUILDING DIVISION 120 Malabar Road, S.E., Palm Bay, FL Phone: (321) Fax: (321)

BUILDING DIVISION 120 Malabar Road, S.E., Palm Bay, FL Phone: (321) Fax: (321) BUILDING DIVISION 120 Malabar Road, S.E., Palm Bay, FL 32907 Phone: (321) 953-8924 Fax: (321) 953-8925 CUSTOMER SERVICE INFORMATION ON RESIDENTIAL PLAN REVIEW REQUIRED DOCUMENTS MUST BE SUBMITTED AT TIME

More information

Proud of its Heritage, Preparing for its Future

Proud of its Heritage, Preparing for its Future TUSTIN Proud of its Heritage, Preparing for its Future Revised August 2013 USER GUIDE FOR THE INSTALLATION OF RESIDENTIAL ROOM ADDITIONS OR ALTERATIONS PURPOSE This guide describes the City of Tustin s

More information

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi STRUCTURAL NOTES MATERIAL STRENGTHS Structural Steel Reinforcing Steel Concrete Masonry Structural Lumber Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel

More information

A.ENVELOPE AIR SEALING

A.ENVELOPE AIR SEALING (Page 1 of 4) Note: The Energy Efficiency Standards Section 110.7 requires that all joints, penetrations and other openings in the building envelope that are potential sources of air leakage shall be caulked,

More information

GARAGE MAIN FLOOR PLAN

GARAGE MAIN FLOOR PLAN BUILDING CONTRACTOR/HOME OWNER TO REVIEW AND VERIFY ALL DIMENSIONS, SPECS, AND CONNECTIONS BEFORE CONSTRUCTION BEGINS. SHED TO BE BUILT AS PER IRC, UBC OR CURRENT LOCAL CODE To the best of my knowledge

More information

Attachment A. USG Minimum Design and Construction Requirements for Wood Framed Structures

Attachment A. USG Minimum Design and Construction Requirements for Wood Framed Structures Attachment A USG Minimum Design and Construction Requirements for Wood Framed Structures 1. General Design Criteria 1.1. Per Adopted Georgia State Minimum Standard Building Code 1.2. Minimum Live Loads

More information

Table Air Barrier and Insulation Inspection Component Criteria

Table Air Barrier and Insulation Inspection Component Criteria Table 40.4. Air Barrier and Insulation Inspection Component Criteria NUMBER COMPONENT CRITERIA Air barrier and thermal barrier Exterior thermal envelope insulation for framed walls is installed in substantial

More information

Inspection of New One- and Two- Family Dwellings

Inspection of New One- and Two- Family Dwellings Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: permitservices@opkansas.org Inspection of New One- and Two- Family Dwellings Planning and Development

More information

Section numbers refer to the 2018 International Residential Code (IRC), as modified, unless otherwise noted. Revised Effective Sept.

Section numbers refer to the 2018 International Residential Code (IRC), as modified, unless otherwise noted. Revised Effective Sept. Residential Plan Check Addendum Page 2 of 5 Building Permit # Section numbers refer to the 2018 International Residential Code (IRC), as modified, unless otherwise noted. Revised Effective Sept. 5 th,

More information

CARROLL COUNTY BUREAU OF PERMITS AND INSPECTIONS RESIDENTIAL CODE COMPLIANCE GUIDELINES FOR DECKS

CARROLL COUNTY BUREAU OF PERMITS AND INSPECTIONS RESIDENTIAL CODE COMPLIANCE GUIDELINES FOR DECKS CARROLL COUNTY BUREAU OF PERMITS AND INSPECTIONS RESIDENTIAL CODE COMPLIANCE GUIDELINES FOR DECKS Code Reference: Chapter 97, Code of Public Local Laws and Ordinances of Carroll County and The International

More information

10 EXTREME BASEMENT PANELS

10 EXTREME BASEMENT PANELS 10 EXTREME BASEMENT PANELS On Granular Footings 1. The type of soil is a factor in determining foundation construction details such as footing design, backfill, and drainage provisions. Soils are classified

More information

STANDARD RESIDENTIAL DECK DETAILS

STANDARD RESIDENTIAL DECK DETAILS STANDARD RESIDENTIAL DECK DETAILS GUARD DECKING FLASHING OVER LEDGER BOARD EXISTING HOUSE FLOOR CONSTRUCTION GUARD POST ATTACHEMENT LEDGER BOARD ATTACHMENT TO HOUSE RIM JOIST JOIST BEAM FOOTING JOIST TO

More information

DESIGNING SAFE ROOMS AND SAFE HOMES WITH LOGIX.

DESIGNING SAFE ROOMS AND SAFE HOMES WITH LOGIX. . Actual ICF-Built Home That Survived Katrina Table of Contents Section Page Overview Logix Wind Resistance Advantages...3 Logix Wall Engineering To 300 MPH Wind Rating...6 Fema-Compliant Design Specifications

More information

CRAWL-SPACE CONSTRUCTION

CRAWL-SPACE CONSTRUCTION CRAWL-SPACE CONSTRUCTION Many basementless houses are built over a crawl space- that is, the grade-level floor is over an excavation which is deep enough to allow a man to gain access to the underfloor

More information

Residential Building Plans

Residential Building Plans Residential Building Plans 1. Building Site Plan indicating: a. Location of Proposed and Existing Buildings b. Location of Property Lines c. Building Setback Dimensions d. Location and Depth of Building

More information

INSTALLING WATER-RESISTIVE BARRIERS & FLASHING

INSTALLING WATER-RESISTIVE BARRIERS & FLASHING INSTALLING WATER-RESISTIVE BARRIERS & FLASHING IN A TWO-LAYER STUCCO APPLICATION Fortifiber Building Systems Group provides this guide to assist installers by demonstrating a two-layer installation of

More information

City of Hughson Building Safety Division 7018 Pine Street Hughson, CA (209)

City of Hughson Building Safety Division 7018 Pine Street Hughson, CA (209) City of Hughson Building Safety Division 7018 Pine Street Hughson, CA 95326 (209) 883-4054 RESIDENTIAL ATTACHED PATIO COVERS Patio covers are one story roofed structures not more than 12 feet above grade,

More information

Basic Information for Obtaining Permits, Submitting Plans, Scheduling Inspections, etc.

Basic Information for Obtaining Permits, Submitting Plans, Scheduling Inspections, etc. Basic Information for Obtaining Permits, Submitting Plans, Scheduling Inspections, etc. Franklin County Septic & Zoning permit application: A septic and zoning permit is required for residential or commercial

More information

KITCHEN REMODELS CITY OF MISSION VIEJO BUILDING SERVICES DIVISON 200 CIVIC CENTER, MISSION VIEJO, CA (949)

KITCHEN REMODELS CITY OF MISSION VIEJO BUILDING SERVICES DIVISON 200 CIVIC CENTER, MISSION VIEJO, CA (949) CITY OF MISSION VIEJO BUILDING SERVICES DIVISON 200 CIVIC CENTER, MISSION VIEJO, CA 92691 (949) 470-3054 KITCHEN REMODELS A permit is required for kitchen remodels that include removal and replacement

More information

Framing Methods Structural Components

Framing Methods Structural Components Framing Methods Structural Components Balloon Framing *Balloon framing or Eastern framing the exterior studs run from the top of the foundation to the top of the highest level. Benefits of this type of

More information

APPLICATION FOR FINISHED BASEMENT PERMIT

APPLICATION FOR FINISHED BASEMENT PERMIT APPLICATION FOR FINISHED BASEMENT PERMIT REAL ESTATE TAX I.D. #: - - _ - _ 7607 W College Drive Ph: (708) 361-1804 Fax: (708) 923-7112 building@palosheights.org APPLICANTS: COMPLETE ALL ITEMS AND SUBMIT

More information

Residential Building Inspections

Residential Building Inspections Residential Building Inspections Foundations, Grade Beams, Pile Caps, Foundation Pads 1. All trenches or excavations and formwork shall be in accordance with the size(s) and configuration(s) as per approved

More information

Hardin County Planning and Development Commission

Hardin County Planning and Development Commission Location by Climate Zone: Hardin County (per Table N1101.2), and the entire state of Kentucky is located in Climate Zone 4, the HDD is 4000 to 4999. Building Requirements; Building Thermal Envelope The

More information

ADDENDUM A CONSTRUCTION SPECIFICATIONS

ADDENDUM A CONSTRUCTION SPECIFICATIONS ADDENDUM A Description of Improvements: CONSTRUCTION SPECIFICATIONS The Improvements shall consist of constructing an approximate square foot single-family residence including car garage on the real property

More information

RESIDENTIALFOUNDATION GUIDELINE

RESIDENTIALFOUNDATION GUIDELINE Department of Community Development 04/01/2019 RESIDENTIALFOUNDATION GUIDELINE Johnson County Building Officials Association Residential Foundation Guideline This document is provided through endorsement

More information

Residential Deck Guide

Residential Deck Guide Residential Deck Guide The text and illustrations included in this guide represent opinions of the Borough of Mechanicsburg Codes and Zoning Department. This guide is for educational and information purposes

More information

Presented by: Stephen Carr Regional Building Science Manager (386)

Presented by: Stephen Carr Regional Building Science Manager (386) Presented by: Stephen Carr Regional Building Science Manager (386) 846-9155 stephen.carr@topbuild.com Understanding the Energy Code 2015 IECC CZ 1 CZ 2 CZ 3 CZ 4 CZ 5 CZ 6 CZ 7&8 Ceiling 30 38 38 49 49

More information

GAF EnergyGuard Polyiso Wall Sheathing

GAF EnergyGuard Polyiso Wall Sheathing From: Technical Services May 15, 2013 GAF EnergyGuard Polyiso Wall Sheathing GAF s EnergyGuard Polyiso Wall Sheathing is intended to be installed on residential construction only. Application types include:

More information

2003 International Residential Building Code

2003 International Residential Building Code 2003 International Residential Building Code Section R305 Ceiling Height Habitable rooms, hallways, corridors, bathrooms, toilet rooms, laundry rooms and basements shall have a ceiling height of not less

More information

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE - 268-5161 Residential Accessory Structures This information has been compiled for the benefit of any person

More information

UCC Permit Application Procedures

UCC Permit Application Procedures How do I apply for a permit? UCC Permit Application Procedures 1. Please complete the CodeMaster Pan Review Application 2. Please provide the scope of work description and/or construction documents/plans.

More information

Carroll County Bureau of Permits and Inspection Residential Code Compliance Guidelines Detached Garage

Carroll County Bureau of Permits and Inspection Residential Code Compliance Guidelines Detached Garage Carroll County Bureau of Permits and Inspection Residential Code Compliance Guidelines Detached Garage The following list of code requirements is intended to assist you in complying with the Code of Public

More information

PLYWOOD FLOATING FLOOR

PLYWOOD FLOATING FLOOR PLYWOOD FLOATING FLOOR Read First These suggestions represent generally accepted procedures for successful installation of Enka Building Products. These instructions may be followed, modified, or rejected

More information

Campbell County Building Inspection Division Guideline to 2018 IRC Residential Construction for Decks

Campbell County Building Inspection Division Guideline to 2018 IRC Residential Construction for Decks Campbell County Building Inspection Division Guideline to 2018 IRC Residential Construction for Decks The following information is intended to assist you in complying with the code requirements adopted

More information

Air Sealing for 5 ACH 50

Air Sealing for 5 ACH 50 November 13th, 2018 Christopher Hine Air Sealing for 5 ACH 50 www.phrc.psu.edu Provider # 60114115 PPP ID: 1562 November 13th, 2018 Christopher Hine Air Sealing for 5 ACH 50 www.phrc.psu.edu Provider #

More information

City of Rohnert Park Building Department Inspection Descriptions

City of Rohnert Park Building Department Inspection Descriptions 200 SITE REVIEW: Prior to a permit being issued the Fire / Building Department is authorized to examine existing buildings, structures, and site for which an application has been filed. 201 PRECONSTRUCTION

More information

A Closer Look Inspection Service 2015 IECC Residential DFW area handout

A Closer Look Inspection Service 2015 IECC Residential DFW area handout 103.2 Information required on construction documents 1. Designation of the Thermal Building Envelope on the plans 2. Insulation Material and their R Value 3. Fenestration U and SHGC values 4. Area weighted

More information

Manufactured decking (composite) may be used when approved by the building department

Manufactured decking (composite) may be used when approved by the building department DO YOU THINK YOU MIGHT ENCLOSE YOUR DECK IN THE FUTURE? Deck plans are approved based on the assumption that the deck will be used only as a deck for the life of the structure. Because there are so many

More information

Feature Zone IECC 2009 IECC

Feature Zone IECC 2009 IECC Feature Zone 3 2006 IECC 2009 IECC Window U factor 0.65 0.50 Skylight U factor 0.65 0.65 Window SHGC 0.40 0.30 Ceiling R value 30 30 Wood frame R value 13 13 Mass wall R value 1 5 5/8 Floor R value 19

More information

The Inspection Process. Waxhaw N.C.

The Inspection Process. Waxhaw N.C. The Inspection Process In Waxhaw N.C. This information is provided by the Waxhaw Enforcement Division to assist you in the progression of your project. Nothing in this document should be considered "Code"

More information

Plan Check No. Checked by: An Appointment Is Required for Verification

Plan Check No. Checked by: An Appointment Is Required for Verification SUPPLEMENTAL CORRECTION SHEET UNREINFORCED MASONRY (URM) RETROFIT ( 2002 LABC ) Plan Check No. Checked by: Permit Appl. # An Appointment Is Required for Verification Job Address: For appt. call: APPLICATION

More information

Quality Insulation Installation (QII) Insulation Installation (Page 1 of 4)

Quality Insulation Installation (QII) Insulation Installation (Page 1 of 4) Quality Insulation Installation (QII) Insulation Installation (Page 1 of 4) A. QUALITY (QII) PREPARATION FOR INSULATION 01 Air barrier installation and preparation for insulation was done and verified

More information

MAIN FLOOR PLAN. #G x 14 x 8 Shed - Chicken Coop By SDS-CAD Specialized Design Systems 10'-0" 3'-0" 1'-0" 14'-0" 14'-0" 1'-0" 6'-0" 3'-0"

MAIN FLOOR PLAN. #G x 14 x 8 Shed - Chicken Coop By SDS-CAD Specialized Design Systems 10'-0 3'-0 1'-0 14'-0 14'-0 1'-0 6'-0 3'-0 10'-0" BUILDING CONTRACTOR/HOME OWNER TO REVIEW AND VERIFY ALL DIMENSIONS, SPECS, AND CONNECTIONS BEFORE CONSTRUCTION BEGINS. BARN TO BE BUILT AS PER LOCAL CODE REQUIREMENTS 14'-0" BWP BWP BWP ABWP 101

More information

Presented by: Stephen Carr Regional Building Science Manager (386)

Presented by: Stephen Carr Regional Building Science Manager (386) Presented by: Stephen Carr Regional Building Science Manager (386) 846-9155 stephen.carr@topbuild.com Understanding the Energy Code 2015 IECC CZ 1 CZ 2 CZ 3 CZ 4 CZ 5 CZ 6 CZ 7&8 Ceiling 30 38 38 49 49

More information

CITY OF OCEANSIDE. Electrical Lines, Plumbing and Mechanical Burial & Support Requirements. Informational Bulletin

CITY OF OCEANSIDE. Electrical Lines, Plumbing and Mechanical Burial & Support Requirements. Informational Bulletin Electrical Lines, Plumbing and Mechanical Burial & Support Requirements Informational Bulletin MINIMUM BURIAL DEPTH REQUIREMENTS 2016 CALIFORNIA ELECTRICAL CODE (CEC) Burial depth shall be per Table 300.5,

More information

SECTION WOOD FRAMING. A. Includes But Not Limited To: 1. Furnish and install wood framing and blocking as described in Contract Documents.

SECTION WOOD FRAMING. A. Includes But Not Limited To: 1. Furnish and install wood framing and blocking as described in Contract Documents. SECTION 06 1100 WOOD FRAMING PART 1 - GENERAL 1.1 SUMMARY A. Includes But Not Limited To: 1. Furnish and install wood framing and blocking as described in Contract Documents. B. Products Installed But

More information

ARTICLE 12 INTERNATIONAL RESIDENTIAL CODE 2012 International Residential Code Modification Summary (Statutory Authority: 1976 Code Section )

ARTICLE 12 INTERNATIONAL RESIDENTIAL CODE 2012 International Residential Code Modification Summary (Statutory Authority: 1976 Code Section ) 8-1200. International Residential Code. ARTICLE 12 INTERNATIONAL RESIDENTIAL CODE 2012 International Residential Code Modification Summary (Statutory Authority: 1976 Code Section 6-9-40) NOTE-This article

More information

GARAGE MAIN FLOOR PLAN

GARAGE MAIN FLOOR PLAN BUILDING CONTRACTOR/HOME OWNER TO REVIEW AND VERIFY ALL DIMENSIONS, SPECS, AND CONNECTIONS BEFORE CONSTRUCTION BEGINS. SHED TO BE BUILT AS PER IRC, UBC OR CURRENT LOCAL CODE To the best of my knowledge

More information

TOWN OF PERINTON 1350 TURK HILL ROAD. FAIRPORT, NEW YORK (585) , Fax: (585) ,

TOWN OF PERINTON 1350 TURK HILL ROAD. FAIRPORT, NEW YORK (585) , Fax: (585) , BUILDING PERMIT REQUIREMENTS FOR BASEMENT REMODELING 1. Provide two copies of a detailed floor plan and elevation drawing, see sample drawings on page 9 and 10. Include materials, sizes, supports, heating,

More information

GARAGE MAIN FLOOR PLAN

GARAGE MAIN FLOOR PLAN 12'-0" 4'-6" 3'-0" 4'-6" 3040 14'-0" LADDER LT LINE BUNK CABIN 11'-4" x 13'-4" 14'-0" BUILDING CONTRACTOR/HOME OWNER TO REVIEW AND VERIFY ALL DIMENSIONS, SPECS, AND CONNECTIONS BEFORE CONSTRUCTION BEGINS.

More information

RESIDENTIAL DETACHED ACCESSORY STRUCTURES

RESIDENTIAL DETACHED ACCESSORY STRUCTURES RESIDENTIAL DETACHED ACCESSORY STRUCTURES *A Building permit is required for any alteration or addition to any existing building or structure. MN State Building Code Section 1300.0120 Subpart 1 Permit

More information

General Residential Code Requirements

General Residential Code Requirements General Residential Code Requirements Residential building code review will be based on compliance with the requirements of the Louisiana State Uniform Construction code in accordance with ACT 12 of the

More information

* RESIDENTIAL PLAN REVIEW *

* RESIDENTIAL PLAN REVIEW * CITY OF DES MOINES, IOWA COMMUNITY DEVELOPMENT DEPARTMENT PERMIT AND DEVELOPMENT CENTER 602 Robert D. Ray Drive DES MOINES, IOWA 50309 Phone: 515.283.4200 Facsimile: 515.283.4270 Based on the scope of

More information

SLAB ON GRADE Insul-Joint or Expansion Joint Material as Required by A/E Specifications AquaCheck Liquid Coating 400 (Waterproofing Membrane) with Aqu

SLAB ON GRADE Insul-Joint or Expansion Joint Material as Required by A/E Specifications AquaCheck Liquid Coating 400 (Waterproofing Membrane) with Aqu INSTALLATION INSTRUCTIONS Note: The following installation instructions are based off of ASTM E 1643 (Standard Practice for Installation of Water Vapor Retarders Used in Contact with Earth or Granular

More information