1 EVALUATION REPORT Johns Manville Corporation P.O. Box 5108 Denver, CO EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street Oxford, CT PHONE: (203) FAX: (203) Evaluation Report J R9 FL2948-R10 Date of Issuance: 03/28/2008 Revision 9: 08/28/2015 SCOPE: This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for compliance with the 5 th Edition (2014) Florida Building Code sections noted herein. DESCRIPTION: Johns Manville SBS Modified Bitumen Roof Systems LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product changes or the referenced Quality Assurance documentation changes. Trinity ERD requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words Trinity ERD Evaluated may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 6, plus a 48-page Appendix. Prepared by: Robert J.M. Nieminen, P.E. Florida Registration 59166, Florida DCA ANE1983 The facsimile seal appearing was authorized by Robert Nieminen, P.E. on 08/28/2015. This does not serve as an electronically signed document. Signed, sealed hardcopies have been transmitted to the Product Approval Administrator and to the named client CERTIFICATION OF INDEPENDENCE: 1. Exterior Research & Design, LLC. d/b/a Trinity ERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or distributing products it evaluates. 2. Exterior Research & Design, LLC. d/b/a Trinity ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for which the evaluation reports are being issued. 4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the product. 5. This is a building code evaluation. Neither Trinity ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose.

2 ROOFING SYSTEMS EVALUATION: 1. SCOPE: Product Category: Roofing Sub-Category: Modified Bitumen Roof Systems Compliance Statement: Johns Manville SBS Modified Bitumen Roof Systems, as produced by Johns Manville Corporation, have demonstrated compliance with the following sections of the Florida Building Code through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. 2. SNDARDS: Section Property Standard Year Wind FM Wind UL Impact FM Physical Properties ASTM D Physical Properties ASTM D Physical Properties ASTM D Physical Properties ASTM D Wind S REFERENCES: Entity Examination Reference Date ACRC (TST4671) S /30/2003 ACRC (TST4671) S /30/2003 ACRC (TST4671) S /04/2003 ACRC (TST4671) S /27/2006 ACRC (TST4671) S /27/2006 ACRC (TST4671) S /28/2006 ACRC (TST4671) S /18/2007 ERD (TST6049) Physical Properties /17/2005 ERD (TST6049) S /07/2007 ERD (TST6049) Physical Properties J /03/2007 ERD (TST6049) Physical Properties J /16/2009 ERD (TST6049) Physical Properties J /11/2010 ERD (TST6049) Physical Properties J /11/2010 ERD (TST6049) FM 4470/4474 J /16/2010 ERD (TST6049) FM 4470/4474 J /04/2011 FM Approvals (TST1867) FM 4470/4474 JM-SC /13/2014 FM Approvals (TST1867) FM 4470/4474 JM-SC /16/2015 FM Approvals (TST1867) FM 4470/4474 RAS-SC /16/2015 FM Approvals (TST1867) FM Q6A4.AM 12/11/1990 FM Approvals (TST1867) FM /11/1998 FM Approvals (TST1867) FM /11/1998 FM Approvals (TST1867) FM /10/1998 FM Approvals (TST1867) FM /01/1999 FM Approvals (TST1867) FM /02/2000 FM Approvals (TST1867) FM /19/2000 FM Approvals (TST1867) FM /13/2000 FM Approvals (TST1867) FM /15/2000 FM Approvals (TST1867) FM /04/2001 FM Approvals (TST1867) FM /10/2001 FM Approvals (TST1867) FM /04/2002 FM Approvals (TST1867) FM /04/2002 FM Approvals (TST1867) FM /03/2002 FM Approvals (TST1867) FM /25/2002 FM Approvals (TST1867) FM /05/2002 FM Approvals (TST1867) FM /02/2002 FM Approvals (TST1867) FM /21/2003 FM Approvals (TST1867) FM /05/2004 FM Approvals (TST1867) FM /09/2004 FM Approvals (TST1867) FM /30/2004 Exterior Research and Design, LLC. Certificate of Authorization #9503 Evaluation Report J R9 FL2948-R10 Revision 9: 08/28/2015 Page 2 of 6

3 Entity Examination Reference Date FM Approvals (TST1867) FM 4470/ /29/2004 FM Approvals (TST1867) FM 4470/ /21/2005 FM Approvals (TST1867) FM 4470/ /26/2006 FM Approvals (TST1867) FM 4470/ /18/2006 FM Approvals (TST1867) FM 4470/ /04/2006 FM Approvals (TST1867) FM 4470/ /15/2006 FM Approvals (TST1867) FM 4470/ /01/2006 FM Approvals (TST1867) FM 4470/ /22/2006 FM Approvals (TST1867) FM 4470/ /09/2007 FM Approvals (TST1867) FM 4470/ /21/2007 FM Approvals (TST1867) FM 4470/ /20/2009 FM Approvals (TST1867) FM 4470/ /10/2009 FM Approvals (TST1867) FM 4470/ /02/2009 FM Approvals (TST1867) FM 4470/ /02/2009 FM Approvals (TST1867) FM 4470/ /18/2011 FM Approvals (TST1867) FM 4470/ /23/2011 FM Approvals (TST1867) FM 4470/ /06/2012 FM Approvals (TST1867) FM 4470/ /04/2012 FM Approvals (TST1867) FM 4470/ /19/2012 FM Approvals (TST1867) FM 4470/ /03/2013 FM Approvals (TST1867) FM /04/2015 Madinah C&TC (TST9199) S 114 MCTC /02/2010 Madinah C&TC (TST9199) S 114 MCTC /12/2010 PRI (TST5878) Physical Properties JMC /15/2013 PRI (TST5878) FM 4470/4474 JMC /16/2013 PRI (TST5878) FM 4470/4474 JMC /16/2013 PRI (TST5878) FM 4470/4474 JMC /16/2013 PRI (TST5878) FM 4470/4474 JMC /16/2013 PRI (TST5878) Physical Properties JMC /17/2013 PRI (TST5878) FM 4470/4474 JMC /17/2013 PRI (TST5878) FM 4470/4474 JMC /17/2013 PRI (TST5878) FM 4470/4474 JMC /17/2013 PRI (TST5878) FM 4470/4474 JMC /19/2013 PRI (TST5878) FM 4470/4474 JMC /19/2013 PRI (TST5878) FM 4470/4474 JMC /13/2013 PRI (TST5878) FM 4470/4474 JMC /26/2015 PRI (TST5878) FM 4470/4474 JMC /22/2015 PRI (TST5878) UL 1897 JMC (A) 04/22/2015 PRI (TST5878) FM 4470/4474 JMC /14/2015 Miami-Dade (CER1592) S 114 Various NOAs Current UL, LLC (QUA9625) Quality Assurance Service Confirmation, R10167 Exp. 10/22/ PRODUCT DESCRIPTION: This Evaluation Report covers Johns Manville Modified Bitumen Roof Systems installed in accordance with Johns Manville published installation instructions and the Limitations / Conditions of Use herein. The following Johns Manville products make up the subject systems. Type Base / Ply Sheets BLE 1: ROLL-GOODS FOR JOHNS MANVILLE MODIFIED BITUMEN ROOF SYSTEMS Product Specification Reference Grade Type GlasPly IV ASTM D2178 N/A IV GlasPly Premier ASTM D2178 N/A VI GlasBase Plus ASTM D4601 N/A II PermaPly 28 ASTM D4601 N/A II JMCleanBond SBS Base ASTM D4601 N/A II JM BaseGrip SD/SA ASTM D4601 N/A II Ventsulation Felt ASTM D4897 N/A II Pro Proprietary N/A N/A Exterior Research and Design, LLC. Certificate of Authorization #9503 Evaluation Report J R9 FL2948-R10 Revision 9: 08/28/2015 Page 3 of 6

4 Type Smooth-Surfaced SBS Granule-Surfaced SBS Foil-Surfaced SBS BLE 1 (CONTINUED): ROLL-GOODS FOR JOHNS MANVILLE MODIFIED BITUMEN ROOF SYSTEMS Product Specification Reference Grade Type DynaPly T1 ASTM D6162 S I DynaBase ASTM D6163 S I DynaBase HW ASTM D6163 S I DynaWeld Base ASTM D6163 S I DynaBase XT ASTM D6163 S I DynaBase PR ASTM D6164 S I DynaFast 180 HW ASTM D6164 S I DynaFast 180 S ASTM D6164 S I DynaLastic 180 S ASTM D6164 S I DynaWeld 180 S ASTM D6164 S I DynaFast 250 HW ASTM D6164 S II DynaLastic 250 S ASTM D6164 S II DynaLastic 250 FR S ASTM D6164 S II DynaGrip Base SA/SD Proprietary N/A N/A DynaGrip Base SD/SA Proprietary N/A N/A DynaGrip Base SA/SA Proprietary N/A N/A DynaKap T1 ASTM D6162 G I DynaKap FR T1 ASTM D6162 G I DynaKap FR T1 CR ASTM D6162 G I DynaKap FR T1 CR G ASTM D6162 G I DynaMax FR ASTM D6162 G III DynaMax FR CR ASTM D6162 G III DynaMax FR CR G ASTM D6162 G III DynaGlas ASTM D6163 G I DynaGlas 30 FR ASTM D6163 G I DynaGlas 30 FR CR ASTM D6163 G I DynaGlas FR ASTM D6163 G I DynaGlas FR CR ASTM D6163 G I DynaGlas FR CR G ASTM D6163 G I DynaWeld Cap FR ASTM D6163 G I DynaWeld Cap FR CR ASTM D6163 G I DynaWeld Cap FR CR G ASTM D6163 G I DynaGlas 30 FR XT ASTM D6163 G I DynaGlas FR XT ASTM D6163 G I DynaGlas FR XT CR ASTM D6163 G I DynaGlas FR XT CR G ASTM D6163 G I JMCleanBond SBS Cap ASTM D6163 G I DynaLastic 180 ASTM D6164 G I DynaLastic 180 FR ASTM D6164 G I DynaLastic 180 FR CR ASTM D6164 G I DynaLastic 180 FR CR G ASTM D6164 G I DynaWeld Cap 180 ASTM D6164 G I DynaWeld Cap 180 CR ASTM D6164 G I DynaWeld Cap 180 FR ASTM D6164 G I DynaWeld Cap 180 FR CR ASTM D6164 G I DynaWeld Cap 180 FR CR G ASTM D6164 G I DynaLastic 250 ASTM D6164 G II DynaLastic 250 FR ASTM D6164 G II DynaLastic 250 FR CR ASTM D6164 G II DynaLastic 250 FR CR G ASTM D6164 G II DynaWeld Cap 250 ASTM D6164 G II DynaWeld Cap 250 CR ASTM D6164 G II DynaWeld Cap 250 FR ASTM D6164 G II DynaWeld Cap 250 FR CR ASTM D6164 G II DynaWeld Cap 250 FR CR G ASTM D6164 G II DynaGrip Cap Proprietary N/A N/A DynaClad ASTM D6298 N/A N/A DynaClad Copper ASTM D6298 N/A N/A Exterior Research and Design, LLC. Certificate of Authorization #9503 Evaluation Report J R9 FL2948-R10 Revision 9: 08/28/2015 Page 4 of 6

5 5. LIMITIONS: 5.1 This is a building code evaluation. Neither Trinity ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report is not for use in HVHZ. 5.3 Refer to a current Roofing Materials Directory for fire ratings of this product. 5.4 For steel deck installations, foam plastic insulation shall be separated from the building interior in accordance with FBC unless the exceptions stated in FBC and apply. 5.5 The roof system evaluation herein pertains to above-deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the AHJ. Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation. 5.6 For recover installations, the existing roof shall be examined in accordance with FBC For mechanically attached insulation or membrane or strip-bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC Chapter 16. Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are RAS 117, FM LPDS 1-29 and ANSI/SPRI WD-1. Assemblies marked with an asterisk* carry the limitations set forth in Section (a) of FM LPDS 1-29 for Zone 2/3 enhancements. 5.8 For fully-adhered insulation, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16. No rational analysis is permitted for these systems 5.9 For mechanically attached insulation or membrane over existing roof decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum requirements for the system. Testing and analysis shall be in accordance with S 105 or ANSI/SPRI FX For bonded insulation or membrane over existing substrates in a re-roof (tear off) or recover installation, the existing deck or existing roof surface shall be examined for compatibility with the adhesive to be installed. If any surface conditions exist that bring system performance into question, field uplift testing in accordance with ASTM E907, FM LPDS 1-52, ANSI/SPRI IA-1 or S 124 shall be conducted on mock-ups of the proposed new roof assembly For bonded insulation or membrane over existing substrates in a recover installation, the existing roof system shall be capable of resisting project design pressures on its own merit to the satisfaction of the AHJ, as documented through field uplift testing in accordance with ASTM E907, FM LPDS 1-52 or S Metal edge attachment (except gutters), shall be designed and installed for wind loads in accordance with FBC Chapter 16 and tested for resistance in accordance with ANSI/SPRI ES-1 or RAS 111, except the basic wind speed shall be determined from FBC Figure All products in the roof assembly shall have quality assurance audit in accordance with the FBC and F.A.C. Rule 61G INSLLATION: 6.1 Johns Manville SBS Modified Bitumen roof systems shall be installed in accordance with Johns Manville published installation instructions, subject to the Limitations / Conditions of Use noted below. 6.2 System attachment requirements for wind load resistance are set forth in Appendix 1. MDP = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC has already been applied). Refer to FBC 1609 for determination of design wind loads. Exterior Research and Design, LLC. Certificate of Authorization #9503 Evaluation Report J R9 FL2948-R10 Revision 9: 08/28/2015 Page 5 of 6

6 7. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product. 8. MANUFACTURING PLANTS: Contact the named QA entity for information on plants covered under F.A.C. Rule 61G20-3 QA requirements. 9. QUALITY ASSURANCE ENTITY: UL, LLC QUA9625; (414) ; - THE 48-PAGES TT FOLLOW FORM PART OF THIS EVALUATION REPORT - Exterior Research and Design, LLC. Certificate of Authorization #9503 Evaluation Report J R9 FL2948-R10 Revision 9: 08/28/2015 Page 6 of 6

7 APPENDIX 1: ATCHMENT REQUIREMENTS FOR WIND UPLIFT RESISNCE Table Application Type Description Page 1A-1 Wood New or Reroof (Tear-Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 4 1A-2 Wood New, Reroof (Tear-Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 4 1B Wood New, Reroof (Tear-Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 5 1C Wood New, Reroof (Tear-Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 5 1D Wood New, Reroof (Tear-Off) or Recover D Prelim. Attached Insulation, Mech. Attached Base Sheet, Bonded Roof Cover 6 1E-1 Wood New, Reroof (Tear-Off) E Non-Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 7 1E-2 Wood New, Reroof (Tear-Off) or Recover E Non-Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 7 2A Steel or Conc. New, Reroof (Tear-Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover B Steel or Conc. New, Reroof (Tear-Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover C Steel or Conc. New, Reroof (Tear-Off) or Recover D Prelim. Attached Insulation, Mech. Attached Base Sheet, Bonded Roof Cover A-1 New or Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover A-2 New or Reroof (Tear-Off) A-1 Bonded Temporary Roof, Bonded Insulation, Bonded Roof Cover 25 3B-1 New or Reroof (Tear-Off) F Non-Insulated, Bonded Roof Cover 26 3B-2 New or Reroof (Tear-Off) F Non-Insulated, Bonded Roof Cover, Paver System Overburden 26 4A-1 LWIC New or Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover A-2 LWIC New or Reroof (Tear-Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 30 4B LWIC New, Reroof (Tear-Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 31 4C-1 LWIC New or Reroof (Tear-Off) E Non-Insulated, Mech. Attached Base Sheet, Bonded Roof Cover C-2 LWIC New, Reroof (Tear-Off) or Recover E Mech. Attached Base Sheet, Bonded Roof Cover 36 4D-1 LWIC New or Reroof (Tear-Off) F Non-Insulated, Bonded Roof Cover 37 4D-2 LWIC New or Reroof (Tear-Off) F Non-Insulated, Bonded Roof Cover, Paver System Overburden 37 5A-1 CWF New or Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover 38 5A-2 CWF New, Reroof (Tear-Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 39 5B CWF New, Reroof (Tear-Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 39 5C CWF New, Reroof (Tear-Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 40 5D CWF New, Reroof (Tear-Off) or Recover E Non-Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 40 6A-1 Gypsum New or Reroof (Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover 41 6A-2 Gypsum New, Reroof (Tear-Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover B Gypsum New, Reroof (Tear-Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 43 6C Gypsum New, Reroof (Tear-Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 44 6D Gypsum New, Reroof (Tear-Off) or Recover E Non-Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 44 7 Various Recover A-1 Bonded Insulation, Bonded Roof Cover Various Summary of FBC EHPA Systems per SSTD The following notes apply to the systems outlined herein: 1. The evaluation herein pertains to above-deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the AHJ. Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation. 2. Unless otherwise noted, fasteners and stress plates for insulation attachment shall be as follows. Fasteners shall be of sufficient length for the following engagements: Wood : UltraFast Fasteners or All Purpose Fasteners with UltraFast Metal Plates. Minimum 0.75-inch plywood penetration or minimum 1-inch wood plank embedment. Steel : UltraFast Fasteners or All Purpose Fasteners with UltraFast Metal Plates. Minimum 0.75-inch steel penetration and engage the top flute of the steel deck. : All Purpose Fasteners with UltraFast Metal Plates or Structural Fasteners with UltraFast Metal Plates (flat bottom only). Minimum 1-inch embedment. Fasteners installed with a pilot hole in accordance with the fastener manufacturer s published installation instructions. Prepared by: Robert Nieminen, PE Appendix 1, Page 1 of 48

8 3. Unless otherwise noted, insulation may be any one layer or combination of polyisocyanurate, polystyrene, wood fiberboard, perlite, gypsum-based roof board, that meets the QA requirements of F.A.C. Rule -3 and is documented as meeting FBC and, for foam plastic, FBC Chapter 26, when installed with the roof cover. 4. Minimum 200 psi, minimum 2-inch thick lightweight insulating concrete may be substituted for rigid insulation board for System Type D (mechanically attached base sheet, bonded roof cover), whereby the base sheet fasteners are installed through the LWIC to engage the structural steel or concrete deck. The structural deck shall be of equal or greater configuration to the steel and concrete deck listings. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the AHJ. Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation. 5. Unless otherwise noted, insulation adhesive application rates are as follows. Ribbon or bead width is at the time of application; the ribbons/beads shall expand as noted in the manufacturer s published instructions. Hot asphalt (): Full coverage at lbs/square JM MBR Bonding Adhesive (MBR-BA): Continuous 0.75-inch wide ribbons, 12-inch o.c. or full coverage at 2.0 gal/square JM Two-Part Urethane Insulation Adhesive (): Continuous 0.75-inch wide ribbons, 12-inch o.c. Note: JM Green Two-Part Urethane Insulation Adhesive may be used where is referenced. JM Roofing System Urethane Adhesive (RSUA): Continuous 0.5 to 0.75-inch wide ribbons, 12-inch o.c. 3M : Continuous 2.5 to 3.5-inch ribbons, 12-inch o.c. Note: When multiple layers(s) of insulation and/or coverboard are installed in ribbon-applied adhesive, adhesive ribbons shall be staggered from layer-to-layer a distance of one-half the ribbon spacing. Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one-half the specified ribbons spacing 6. Unless otherwise noted, all insulations are flat stock or taper board of the minimum thickness noted. Tapered polyisocyanurate at the following thickness limitations may be substituted with the following Maximum Design Pressure (MDP) limitations. In no case shall these values be used to increase the MDP listings in the tables; rather if MDP listing below meets or exceeds that listed for a particular system in the tables, then the thinner board listed below may be used as a drop-in for the equivalent thicker material listed in the table: JM Two-Part Urethane Insulation Adhesive (): MDP psf (Min. 0.5-inch thick) JM Roofing System Urethane Adhesive (RSUA): MDP psf (Min. 0.5-inch thick) 3M : MDP psf (Min. 1.0-inch thick) 7. Bonded polyisocyanurate insulation boards shall be maximum 4 x 4 ft. 8. For mechanically attached components or partially bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC Chapter 16, and Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are RAS 117 and FM LPDS Assemblies marked with an asterisk* carry the limitations set forth in Section (a) of FM LPDS 1-29 for Zone 2/3 enhancements. 9. For fully bonded assemblies, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16, and no rational analysis is permitted. 10. For mechanically attached components over existing decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum requirements for the system. Testing and analysis shall be in accordance with S 105 or ANSI/SPRI FX For existing substrates in a bonded recover installation, the existing roof surface shall be examined for compatibility and bond performance with the selected adhesive, and the existing roof system shall be capable of resisting project design pressures on its own merit to the satisfaction of the AHJ, as documented through field uplift testing in accordance with ASTM E907, FM LPDS 1-52, ANSI/SPRI IA-1 or S For Recover Applications using System Type D, the insulation is optional; however, the existing roof system shall be suitable for a recover application. 13. LWIC shall be cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWIC is referenced, refer to current LWIC Product Approval for specific deck construction and limitations. For systems where specific LWIC is not referenced, the minimum design mix shall be 300 psi. In all cases, the minimum top-coat thickness is 2-inches. For LWIC over, reference is made to FBC Section , Point Unless otherwise noted, refer to the following references for bonded base, ply or cap sheet applications. JOHNS MANVILLE ROOF COVERS Reference Layer Material Application BP-AA (Base and Ply sheets, Asphalt-Applied) BP-CA1 (Base and Ply sheets, Cold-Applied, 1-part) Base GlasBase Plus, PermaPly 28 Ply GlasPly IV, GlasPly Premier, GlasBase Plus, PermaPly 28 Base or Ply GlasBase Plus, PermaPly 28 Hot asphalt at lbs/square JM MBR Cold Application Adhesive at 1.5 to 2.0 gal/square Prepared by: Robert Nieminen, PE Appendix 1, Page 2 of 48

9 JOHNS MANVILLE ROOF COVERS (CONTINUED) Reference Layer Material Application BP- (Base and Ply sheets, Cold-Applied, 2-part) BP- (Base and Ply sheets, Cold-Applied, 1-part) SBS-AA (SBS, Asphalt-Applied) SBS-CA1 (SBS, Cold-Applied, 1- part) SBS- (SBS, Cold-Applied, 2- part) SBS- (SBS, Cold-Applied, 1- part) (SBS, Torch-Applied) SBS-SA (SBS, self-adhering) Base or Ply GlasBase Plus, PermaPly 28 Base or Ply Base or Ply: Cap Base or Ply: Cap Base or Ply: Cap Note: Base or Ply: Cap Base or Ply: Cap Base or Ply: Cap GlasBase Plus, PermaPly 28, GlasPly IV, GlasPly Premier DynaPly T1, DynaBase, DynaBase XT, DynaBase PR, DynaLastic 180 S, DynaLastic 250 S, DynaLastic 250 FR S DynaPly T1, DynaKap T1, DynaKap FR T1, DynaKap FR T1 CR, DynaKap FR T1 CR G, DynaGlas, DynaGlas FR, DynaGlas FR XT, DynaGlas FR XT CR, DynaGlas FR XT CR G, DynaGlas FR CR, DynaGlas FR CR G, DynaGlas 30 FR, DynaGlas 30 FR CR, DynaGlas 30 FR, DynaGlas 30 FR CR XT, DynaLastic 180 S, DynaLastic 250 S, DynaLastic 250 FR S, DynaLastic 180, DynaLastic 180 FR, DynaLastic 180 FR CR, DynaLastic 180 FR CR G, DynaLastic 250, DynaLastic 250 FR, DynaLastic 250 FR CR, DynaLastic 250 FR CR G, DynaMax FR, DynaMax FR CR, DynaMax FR CR G DynaPly T1, DynaBase, DynaBase XT, DynaBase PR, DynaLastic 180 S, DynaLastic 250 S, DynaLastic 250 FR S DynaPly T1, DynaKap T1, DynaKap FR T1, DynaKap FR T1 CR, DynaKap FR T1 CR G, DynaGlas, DynaGlas FR, DynaGlas FR XT, DynaGlas FR XT CR, DynaGlas FR XT CR G, DynaGlas FR CR, DynaGlas FR CR G, DynaGlas 30 FR, DynaGlas 30 FR CR, DynaGlas 30 FR, DynaGlas 30 FR CR XT, DynaLastic 180 S, DynaLastic 250 S, DynaLastic 250 FR S, DynaLastic 180, DynaLastic 180 FR, DynaLastic 180 FR CR, DynaLastic 180 FR CR G, DynaLastic 250, DynaLastic 250 FR, DynaLastic 250 FR CR, DynaLastic 250 FR CR G, DynaMax FR, DynaMax FR CR, DynaMax FR CR G DynaPly T1, DynaBase, DynaBase XT, DynaBase PR, DynaLastic 180 S, DynaLastic 250 S, DynaLastic 250 FR S DynaPly T1, DynaKap T1, DynaKap FR T1, DynaKap FR T1 CR, DynaKap FR T1 CR G, DynaGlas, DynaGlas FR, DynaGlas FR XT, DynaGlas FR XT CR, DynaGlas FR XT CR G, DynaGlas FR CR, DynaGlas FR CR G, DynaGlas 30 FR, DynaGlas 30 FR CR, DynaGlas 30 FR, DynaGlas 30 FR CR XT, DynaLastic 180 S, DynaLastic 250 S, DynaLastic 250 FR S, DynaLastic 180, DynaLastic 180 FR, DynaLastic 180 FR CR, DynaLastic 180 FR CR G, DynaLastic 250, DynaLastic 250 FR, DynaLastic 250 FR CR, DynaLastic 250 FR CR G, DynaMax FR, DynaMax FR CR, DynaMax FR CR G SBS- applications shall not be mixed with SBS-AA applications DynaPly T1, DynaBase, DynaBase XT, DynaBase PR, DynaLastic 180 S, DynaLastic 250 S, DynaLastic 250 FR S DynaPly T1, DynaKap T1, DynaKap FR T1, DynaKap FR T1 CR, DynaKap FR T1 CR G, DynaGlas, DynaGlas FR, DynaGlas FR XT, DynaGlas FR XT CR, DynaGlas FR XT CR G, DynaGlas FR CR, DynaGlas FR CR G, DynaGlas 30 FR, DynaGlas 30 FR CR, DynaGlas 30 FR, DynaGlas 30 FR CR XT, DynaLastic 180 S, DynaLastic 250 S, DynaLastic 250 FR S, DynaLastic 180, DynaLastic 180 FR, DynaLastic 180 FR CR, DynaLastic 180 FR CR G, DynaLastic 250, DynaLastic 250 FR, DynaLastic 250 FR CR, DynaLastic 250 FR CR G, DynaMax FR, DynaMax FR CR, DynaMax FR CR G DynaBase HW, DynaWeld Base, DynaWeld 180 S DynaWeld Cap FR, DynaWeld Cap FR CR, DynaWeld Cap FR CR G, DynaWeld Cap 180, DynaWeld Cap 180 CR, DynaWeld Cap 180 FR, DynaWeld Cap 180 FR CR, DynaWeld Cap 180 FR CR G, DynaWeld Cap 250, DynaWeld Cap 250 CR, DynaWeld Cap 250 FR, DynaWeld Cap 250 FR CR, DynaWeld Cap 250 FR CR G, DynaClad, DynaClad Copper DynaGrip Base SD/SA, DynaGrip Base SA/SA, JMCleanBond SBS Base Sheet DynaGrip Cap, JMCleanBond SBS Cap Sheet 15. MDP = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for determination of design wind loads. JM MBR Bonding Adhesive at 1.5 to 2.0 gal/square JM Premium Cold App at 1.5 to 2.0 gal/square Hot asphalt at lbs/square JM MBR Cold Application Adhesive at 1.5 to 2.0 gal/square JM MBR Bonding Adhesive at 1.5 to 2.0 gal/square JM Premium Cold App at 1.5 to 2.0 gal/square Torch-Applied Self-Adhering Prepared by: Robert Nieminen, PE Appendix 1, Page 3 of 48

10 W-1 W-2 W-3 Min. 15/32-inch plywood at max. 24-inch spans Min. 15/32-inch plywood at max. 24-inch spans Min. 19/32-inch plywood at max. 24-inch spans BLE 1A-1: WOOD DECKS NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE A-2: MECNICALLY ATCHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER Anchor Sheet Base Insulation Top Insulation Roof Cover MDP Type Fasteners Attach Type Attach Type Attach Base Ply Cap PermaPly 28, DynaBase, GlasBase Plus or Ventsulation Two plies of PermaPly 28, DynaBase, GlasBase Plus or Ventsulation GlasPly Premier, PermaPly 28 or Ventsulation 32 ga., 1-5/8- inch diameter tin caps with 11 ga. annular ring shank nails 32 ga., 1-5/8- inch diameter tin caps with 11 ga. annular ring shank nails 32 ga., 1-5/8- inch diameter tin caps with 11 ga. annular ring shank nails 9-inch o.c. in 4- inch lap and 12- inch o.c. in three, equally spaced, staggered center rows 9-inch o.c. in 4- inch lap and 12- inch o.c. in two, equally spaced, staggered center rows 9-inch o.c. in 4- inch lap and 9- inch o.c. in two, equally spaced, staggered center rows (Optional) Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25 PSI AGF or CGF, ValuTherm AGF or CGF, ValuTherm 25 PSI AGF or CGF (Optional) Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25 PSI AGF or CGF, ValuTherm AGF or CGF, ValuTherm 25 PSI AGF or CGF (Optional) Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25 PSI AGF or CGF, ValuTherm AGF or CGF, ValuTherm 25 PSI AGF or CGF Min inch Fesco Board, min. 0.5-inch Retro-Fit Board, RetroPlus Board or DuraBoard or min. 1.5-inch Fesco Foam or DuraFoam Min inch Fesco Board, min. 0.5-inch Retro-Fit Board, RetroPlus Board or DuraBoard or min. 1.5-inch Fesco Foam or DuraFoam Min inch Fesco Board, min. 0.5-inch Retro-Fit Board, RetroPlus Board or DuraBoard or min. 1.5-inch Fesco Foam or DuraFoam, SBS- AA or SBS-, SBS- AA or SBS-, SBS- AA or SBS- (Optional) SBS-AA or (Optional) SBS- or (Optional) SBS- or SBS- or SBS- or SBS- or System W-4 Min. 19/32-inch plywood at max. 24-inch spans BLE 1A-2: WOOD DECKS NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE A-2: MECNICALLY ATCHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER Anchor Sheet Base Insulation Top Insulation Roof Cover MDP Type Fasteners Attach Type Attach Type Attach Base Ply Cap GlasPly Premier, PermaPly 28 or Ventsulation 8-inch o.c. in 4- inch lap and 8- inch o.c. in three, equally spaced, staggered center rows (Optional) Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25 PSI AGF or CGF, ValuTherm AGF or CGF, ValuTherm 25 PSI AGF or CGF Min inch Fesco Board, min. 0.5-inch Retro-Fit Board, RetroPlus Board or DuraBoard or min. 1.5-inch Fesco Foam or DuraFoam, SBS- AA or SBS- (Optional) SBS- or SBS- or Prepared by: Robert Nieminen, PE Appendix 1, Page 4 of 48

11 BLE 1B: WOOD DECKS NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE B: MECNICALLY ATCHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER System W-5 W-6 W-7 Min. 19/32-inch plywood at max. 24-inch spans Min. 19/32-inch plywood at max. 24-inch spans Min. 19/32-inch plywood at max. 24-inch spans Base Insulation Layer Top Insulation Layer Roof Cover MDP Type Fasteners Attach Type Attach Base Ply Cap Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, 1 per 2 Min inch Fesco Board, min. 0.5-inch Retro-Fit Board, RetroPlus Board or min. 1.5-inch Fesco Foam 2 Min. 0.5-inch 1 per 2 ft DuraBoard 1 per 1.33 Min. 0.5-inch DuraBoard or MBR-BA full coverage, SBS-AA or SBS-, SBS-AA or SBS- AA, BP- or (Optional) SBS- AA, BP- or SBS- or SBS- or BLE 1C: WOOD DECKS NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C: MECNICALLY ATCHED INSULATION, BONDED ROOF COVER System Base Insulation Layer Top Insulation Layer Roof Cover MDP Type Fasteners Attach Base Ply Cap W-8 Min. 19/32-inch plywood at max. 24-inch spans Min. 0.5-inch Retro-Fit Board, RetroPlus Board or DuraBoard, min inch Fesco Board or min inch Fesco Foam or DuraFoam 1 per 2 SBS-AA or SBS-, BP- SBS- or or W-9 Min. 19/32-inch plywood at max. 24-inch spans Min. 0.5-inch DuraBoard 1 per 2 (Optional) W-10 Min. 19/32-inch plywood at max. 24-inch spans Min inch DuraBoard 1 per 1.33, SBS- or SBS-, Prepared by: Robert Nieminen, PE Appendix 1, Page 5 of 48

12 BLE 1D: WOOD DECKS NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE D: PRELIMINARILY ATCHED INSULATION, MECNICALLY ATCHED BASE SHEET, BONDED ROOF COVER System (See Note ) Slip Sheet Insulation Layer(s) Base Sheet Roof Cover MDP Type Attach Base Fasteners Attach Ply Cap W-11 Min. 19/32-inch plywood at max. 24- inch spans (Optional) One or more layers PermaPly 28, loose laid below or above insulation One or more layers, any combination Looselaid DynaBase High Load Fasteners through 1-inch wide JM Polymer Membrane Batten 9-inch o.c. within the min. 4-inch wide, heat-welded side laps. (Optional) SBS- AA or SBS-AA or -37.5* W-12 Min. 15/32-inch plywood at max. 24- inch spans (Optional) One or more layers PermaPly 28, loose laid below or above insulation One or more layers, any combination Looselaid DynaFast 180 HW or DynaFast 250 HW High Load Fasteners and JM APB Plates or High Load Plates 18-inch o.c. within the min. 4-inch wide, heatwelded side laps. (Optional) SBS- W-13 Min. 19/32-inch plywood at max. 24- inch spans (Optional) One or more layers PermaPly 28, loose laid below or above insulation One or more layers, any combination Prelim Attach GlasPly Premier, PermaPly 28 or Ventsulation 8-inch o.c. at min. 4-inch lap and 8-inch o.c. at three, equally spaced, staggered center rows AA, BP- SBS- AA, SBS- or or SBS W-14 Min. 15/32-inch plywood at max. 24- inch spans (Optional) One or more layers PermaPly 28, loose laid below or above insulation One or more layers, min. 1-inch, any combination Looselaid DynaFast 180 HW or DynaFast 250 HW High Load Fasteners and JM APB Plates or High Load Plates 9-inch o.c. within the min. 4-inch wide, heat-welded side laps. (Optional) SBS W-15 Min. 15/32-inch plywood at max. 24- inch spans (Optional) One or more layers PermaPly 28, loose laid below or above insulation One or more layers, min. 1-inch, any combination Looselaid DynaFast 180 HW or DynaFast 250 HW High Load LH through 1- inch wide JM Polymer Membrane Batten 6-inch o.c. within the min. 4-inch wide, heat-welded side laps. (Optional) SBS Prepared by: Robert Nieminen, PE Appendix 1, Page 6 of 48

13 W-16 W-17 Min. 19/32-inch plywood at max. 24-inch spans Min. 19/32-inch plywood at max. 24-inch spans BLE 1E-1: WOOD DECKS NEW CONSTRUCTION OR REROOF (TEAR-OFF) SYSTEM TYPE E: NON-INSULATED, MECNICALLY ATCHED BASE SHEET, BONDED ROOF COVER Two plies of PermaPly 28, DynaBase, GlasBase Plus or Ventsulation Base Sheet Roof Cover MDP Base Fasteners Attach Ply Cap GlasPly Premier, PermaPly 28 or Ventsulation 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 32 ga., 1-5/8-inch diameter tin caps with 11 ga. annular ring shank nails 9-inch o.c. in 4-inch lap and 12- inch o.c. in two, equally 9-inch o.c. in 4-inch lap and 9- inch o.c. in two, equally BP- or BP- or or or BLE 1E-2: WOOD DECKS NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE E: NON-INSULATED, MECNICALLY ATCHED BASE SHEET, BONDED ROOF COVER System Slip Sheet Base Sheet Roof Cover MDP Base Fasteners Attach Ply Cap W-18 Min. 19/32-inch plywood at max. 24-inch spans (Optional) One or more layers PermaPly 28, loose laid DynaBase High Load Fasteners through 1-inch wide JM Polymer Membrane Batten 9-inch o.c. within the min. 4- inch wide, heat-welded side laps. (Optional) SBS-AA or SBS-AA or SBS * W-19 Min. 15/32-inch plywood at max. 24-inch spans (Optional) One or more layers PermaPly 28, loose laid DynaFast 180 HW or DynaFast 250 HW High Load Fasteners and JM APB Plates or High Load Plates 18-inch o.c. within the min. min. 4-inch wide, heat-welded side laps. (Optional) W-20 Min. 19/32-inch plywood at max. 24-inch spans (Optional) One or more layers PermaPly 28, loose laid GlasPly Premier, PermaPly 28 or Ventsulation 8-inch o.c. in 4-inch lap and 8- inch o.c. in three, equally BP- or or Prepared by: Robert Nieminen, PE Appendix 1, Page 7 of 48

14 S-1 S-2 S-3 S-4 S-5 S-6 S-7 BLE 2A: STEEL OR CONCRETE DECKS NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE B: MECNICALLY ATCHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER Base Insulation Layer Top Insulation Layer Roof Cover MDP Type Fasten Attach Type Attach Base Ply Cap Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, Min. 1.5-inch ENRGY 3, ValuTherm. Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, 1 per Min. 0.5-inch RetroPlus 5.33 Board 1 per Min. 0.5-inch RetroPlus 5.33 Board 1 per Min. 0.5-inch SECUROCK 5.33 or MBR-BA, full coverage 1 per 2 2 Min. 0.5-inch DuraBoard MBR-BA ft 1 per 2 1 per 2 1 per 2 One or more layers base insulation followed by min. 0.5-inch DuraBoard or min. 0.5-inch DuraBoard MBR-BA CA1, BP-, BP-, CA1, SBS-, SBS- CA1, BP-, BP-, CA1, SBS-, SBS- CA1, BP-, BP-, CA1, SBS-, SBS- BP-CA1, BP-, BP-, SBS- CA1, SBS- or SBS- BP-CA1, BP-, BP-, SBS- CA1, SBS- or SBS- BP-CA1, BP-, BP-, SBS-CA1, SBS-, SBS- BP-CA1, BP-, BP-, SBS-CA1, SBS-, SBS- BP-CA1, BP-, BP-, SBS-CA1, SBS-, SBS- CA1, BP-, BP-, SBS-CA1, SBS- or SBS- CA1, BP-, BP-, SBS-CA1, SBS- or SBS- CA1, SBS-, SBS- CA1, SBS-, SBS- CA1, SBS-, SBS-, SBS-CA1, SBS- or SBS-CA-3 SBS-CA1, SBS- or SBS-CA * -37.5* -37.5* (Optional) RSUA (Optional) Prepared by: Robert Nieminen, PE Appendix 1, Page 8 of 48

15 S-8 S-9 S-10 S-11 S-12 S-13 S-14 BLE 2A: STEEL OR CONCRETE DECKS NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE B: MECNICALLY ATCHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER Base Insulation Layer Top Insulation Layer Roof Cover MDP Type Fasten Attach Type Attach Base Ply Cap Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, Min. 1.5-inch ENRGY 3, ValuTherm. Min. 2-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, Min. 2-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, 1 per 2 Min inch Invinsa Roof Board or min. 1.5-inch Invinsa Foam or RSUA DynaGrip SD/SA (Optional) 1 per 2 2 Min. 0.5-inch DuraBoard (Optional) ft 1 per 4 1 per 4 1 per 4 Min. 0.5-inch RetroPlus Board Min. 0.5-inch RetroPlus Board Min. 0.5-inch SECUROCK 1 per Min. 0.5-inch RetroPlus 5.33 Board 1 per Min. 0.5-inch RetroPlus 5.33 Board or MBR-BA, full coverage or MBR-BA, full coverage CA1, BP-, BP-, CA1, SBS-, SBS- CA1, BP-, BP-, CA1, SBS-, SBS- CA1, BP-, BP-, CA1, SBS-, SBS- CA1, BP-, BP-, CA1, SBS-, SBS- CA1, BP-, BP-, CA1, SBS-, SBS- BP-CA1, BP-, BP-, SBS-CA1, SBS-, SBS- BP-CA1, BP-, BP-, SBS-CA1, SBS-, SBS- BP-CA1, BP-, BP-, SBS-CA1, SBS-, SBS- BP-CA1, BP-, BP-, SBS-CA1, SBS-, SBS- BP-CA1, BP-, BP-, SBS-CA1, SBS-, SBS- CA1, SBS-, SBS- CA1, SBS-, SBS- CA1, SBS-, SBS-, CA1, SBS-, SBS- CA1, SBS-, SBS- Prepared by: Robert Nieminen, PE Appendix 1, Page 9 of 48

16 S-15 S-16 S-17 S-18 S-19 S-20 S-21 BLE 2A: STEEL OR CONCRETE DECKS NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE B: MECNICALLY ATCHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER Base Insulation Layer Top Insulation Layer Roof Cover MDP Type Fasten Attach Type Attach Base Ply Cap Min. 2-inch ENRGY 3, ValuTherm. Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25,, Fesco Foam or DuraFoam Min. 1.5-inch ENRGY 3, ValuTherm. Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25,, Fesco Foam or DuraFoam Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, Min. 2-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, 1 per Min. 0.5-inch SECUROCK per 2 Min. 0.5-inch Retro-Fit Board, RetroPlus Board or DuraBoard, min inch Fesco Board (flat or tapered) or min. 1.5-inch Fesco Foam or DuraFoam 1 per Min. 0.5-inch SECUROCK per 1.78 Min. 0.5-inch Retro-Fit Board, RetroPlus Board or DuraBoard or min. 1.5-inch Fesco Foam or DuraFoam 1 per Min. 0.5-inch RetroPlus 1.78 Board 1 per Min. 0.5-inch RetroPlus 1.78 Board 1 per 2 Min. 3/8-inch SECUROCK or MBR-BA, full coverage or CA1, BP-, BP-, CA1, SBS-, SBS-, SBS-AA or SBS- CA1, BP-, BP-, CA1, SBS-, SBS-, SBS-AA or SBS- CA1, BP-, BP-, CA1, SBS-, SBS- CA1, BP-, BP-, CA1, SBS-, SBS-, SBS-SA or BP-CA1, BP-, BP-, SBS-CA1, SBS-, SBS- or BP-CA1, BP-, BP-, SBS-CA1, SBS-, SBS- or BP-CA1, BP-, BP-, SBS-CA1, SBS-, SBS- BP-CA1, BP-, BP-, SBS-CA1, SBS-, SBS-, BP-AA,, SBS-SA or SBS- CA1, SBS-, SBS-,,, CA1, SBS-, SBS-, or SBS- CA1, SBS-, SBS- CA1, SBS-, SBS- SBS-,, SBS-SA or Prepared by: Robert Nieminen, PE Appendix 1, Page 10 of 48

17 S-22 S-23 S-24 S-25 S-26 S-27 S-28 BLE 2A: STEEL OR CONCRETE DECKS NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE B: MECNICALLY ATCHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER Base Insulation Layer Top Insulation Layer Roof Cover MDP Type Fasten Attach Type Attach Base Ply Cap Min. 2-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, Min. 1.5-inch ENRGY 3, ValuTherm. Min. 2-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25,, Fesco Foam or DuraFoam Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, 1 per 2 Min. 3/8-inch SECUROCK 1 per Min. 0.5-inch RetroPlus 1.33 Board 1 per Min. 0.5-inch RetroPlus 1.33 Board 1 per Min. 0.5-inch SECUROCK per per 1 1 per 1 Min. 0.5-inch Retro-Fit Board, RetroPlus Board or DuraBoard or min. 1.5-inch Fesco Foam or DuraFoam Min. 0.5-inch RetroPlus Board Min. 0.5-inch RetroPlus Board RSUA, 6- inch o.c. or MBR-BA, full coverage or MBR-BA, full coverage, SBS-SA or CA1, BP-, BP-, CA1, SBS-, SBS- CA1, BP-, BP-, CA1, SBS-, SBS- CA1, BP-, BP-, CA1, SBS-, SBS-, SBS-AA or SBS- CA1, BP-, BP-, CA1, SBS-, SBS- CA1, BP-, BP-, CA1, SBS-, SBS-, BP-AA,, SBS-SA or SBS- BP-CA1, BP-, BP-, SBS-CA1, SBS-, SBS- BP-CA1, BP-, BP-, SBS-CA1, SBS-, SBS- BP-CA1, BP-, BP-, SBS-CA1, SBS-, SBS- BP- SBS- or BP-CA1, BP-, BP-, SBS-CA1, SBS-, SBS- BP-CA1, BP-, BP-, SBS-CA1, SBS-, SBS- SBS-,, SBS-SA or CA1, SBS-, SBS- CA1, SBS-, SBS- CA1, SBS-, SBS-, or SBS- CA1, SBS-, SBS- CA1, SBS-, SBS Prepared by: Robert Nieminen, PE Appendix 1, Page 11 of 48

18 S-29 S-30 S-31 S-32 BLE 2A: STEEL OR CONCRETE DECKS NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE B: MECNICALLY ATCHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER Base Insulation Layer Top Insulation Layer Roof Cover MDP Type Fasten Attach Type Attach Base Ply Cap Min. 1.5-inch ENRGY 3, ValuTherm. Min. 2-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, Min. 2-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, Min. 2-inch ENRGY 3, ValuTherm. 1 per 1 Min. 0.5-inch SECUROCK 1 per Min. 0.5-inch RetroPlus 1.45 Board 1 per Min. 0.5-inch RetroPlus 1.45 Board 1 per Min. 0.5-inch SECUROCK inch o.c. or MBR-BA, full coverage 4-inch o.c. CA1, BP-, BP-, CA1, SBS-, SBS- CA1, BP-, BP-, CA1, SBS-, SBS- CA1, BP-, BP-, CA1, SBS-, SBS- CA1, BP-, BP-, CA1, SBS-, SBS- BP-CA1, BP-, BP-, SBS-CA1, SBS-, SBS- BP-CA1, BP-, BP-, SBS-CA1, SBS-, SBS- BP-CA1, BP-, BP-, SBS-CA1, SBS-, SBS- BP-CA1, BP-, BP-, SBS-CA1, SBS-, SBS- CA1, SBS-, SBS-, CA1, SBS-, SBS- CA1, SBS-, SBS- CA1, SBS-, SBS-, -90.0* * Prepared by: Robert Nieminen, PE Appendix 1, Page 12 of 48

19 BLE 2B: STEEL OR CONCRETE DECKS NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C: MECNICALLY ATCHED INSULATION, BONDED ROOF COVER System Base Insulation Layer Top Insulation Layer Roof Cover MDP Type Fasteners Attach Base Ply Cap S-33 Grade 33 steel or Min inch Invinsa Roof Board UltraFast (steel only) or All Purpose with UltraFast Metal (round) Plates 2 BP- or SBS- 1 per 2 ft or SBS- SBS * S-34 Grade 33 steel or (Optional) One or more layers, any Min inch Invinsa Foam UltraFast (steel only) or All Purpose with UltraFast Metal (round) Plates 2 BP- or SBS- 1 per 2 ft or SBS- SBS * S-35 Grade 33 steel or Gypsum- Fiber Roof Board (square plates) 1 per 2.67 DynaGrip Base SD/SA or (Optional) -37.5* S-36 Grade 33 steel or Gypsum- Fiber Roof Board (square plates) 1 per 2.67 CA1, BP-, BP-CA-3 CA1, SBS-, SBS- BP- CA1, BP-, BP-CA- 3 CA1, SBS-, SBS- SBS-CA1, SBS-, SBS * S-37 Grade 33 steel or Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25 PSI AGF or CGF, ValuTherm AGF or CGF, ValuTherm 25 UltraFast (steel only) or All Purpose with UltraFast Metal (round) Plates 1 per 2 BP- orsbs- or SBS- SBS- S-38 Grade 33 steel or Min. 0.5-inch DuraBoard 1 per 2 BP-, SBS-CA1, SBS- or SBS- BP-CA1, BP-, CA1, BP-, BP-, SBS- CA1, SBS- or SBS- SBS-CA1, SBS- or SBS- CA-3 S-39 Grade 33 steel or Min. 0.5-inch DuraBoard 1 per 2 (Optional) S-40 Grade 33 steel or (Optional) One or more layers, any Min. 2-inch ENRGY 3 Foil Face or min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, or FescoFoam (perlite side down) 1 per 2 SBS-SA (Optional) SBS-SA or SBS-SA or Prepared by: Robert Nieminen, PE Appendix 1, Page 13 of 48

20 BLE 2B: STEEL OR CONCRETE DECKS NEW CONSTRUCTION, REROOF (TEAR-OFF) OR RECOVER SYSTEM TYPE C: MECNICALLY ATCHED INSULATION, BONDED ROOF COVER System Base Insulation Layer Top Insulation Layer Roof Cover MDP Type Fasteners Attach Base Ply Cap S-41 Grade 33 steel or (Optional) One or more layers, any Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI 2 JM BaseGrip 1 per 2 ft SD/SA (Optional) S-42 Grade 33 steel or (Optional) One or more layers, any Min. 2-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25, 1 per 4 DynaGrip SD/SA (Optional) S-43 Grade 33 steel or Min inch Invinsa Roof Board UltraFast (steel only) or All Purpose with UltraFast Plastic Plates 1 per 2 SBS-SA (Optional) S-44 Grade 33 steel or (Optional) One or more layers, any Min inch Invinsa Foam UltraFast (steel only) or All Purpose with UltraFast Plastic Plates 1 per 2 SBS-SA (Optional) S-45 Grade 33 steel or Min inch SECUROCK Gypsum- Fiber Roof Board (square plates) 1 per 2.67 DynaGrip Base SD/SA or (Optional) S-46 Grade 33 steel or Min inch SECUROCK Gypsum- Fiber Roof Board (square plates) 1 per 2.67 CA1, BP-, BP-CA-3 CA1, SBS-, SBS- BP- CA1, BP-, BP-CA- 3 CA1, SBS-, SBS- SBS-CA1, SBS-, SBS- S-47 Grade 33 steel or Min. 0.5-inch Retro-Fit Board or DuraBoard, min inch Fesco Board or min. 1.5-inch Fesco Foam or DuraFoam 2 BP-AA, SBS-AA or 1 per 2 ft SBS- or SBS-,SBS-, S-48 Grade 33 steel or Min 2inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25,, UltraFast (steel only) 1 per 1.78 SBS-SA (Optional) SBS-SA or S-49 Grade 33 steel or (Optional) One or more layers, any Min. 1.5-inch ENRGY 3, R-Panel, ENRGY 3 25 PSI, R-Panel 25 PSI, ENRGY 3 AGF or CGF, ENRGY 3 25 PSI AGF or CGF, ValuTherm AGF or CGF, ValuTherm 25 1 per 1.33 BP- or SBS- or SBS- SBS Prepared by: Robert Nieminen, PE Appendix 1, Page 14 of 48

EVALUATION REPORT ICP Adhesives and Sealants, Inc NW 44 th Street Coral Springs, FL 33065

EVALUATION REPORT ICP Adhesives and Sealants, Inc NW 44 th Street Coral Springs, FL 33065 EVALUATION REPORT ICP Adhesives and Sealants, Inc. 12505 NW 44 th Street Coral Springs, FL 33065 EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization #9503 353 CHRISTIAN STREET, UNIT 13 OXFORD,

More information

Exterior Research & Design, L.L.C. Building Science and Envelope Consultants

Exterior Research & Design, L.L.C. Building Science and Envelope Consultants Exterior Research & Design, L.L.C. Building Science and Envelope Consultants Certificate of Evaluation Report 3520.03.04-R2 Evaluation of Roof s for Florida Product Approval #FL2533-R2 Prepared for: CertainTeed

More information

CREEK Technical Services, LLC

CREEK Technical Services, LLC a CREEK Certificate of Authization 29824 17520 Edinburgh Drive Tampa, FL 33647 (813) 480-3421 EVALUATION REPORT FLORIDA BUILDING CODE 5 TH EDITION (2014) Manufacturer: JOHNS MANVILLE CORPORATION Issued

More information

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street Oxford, CT PHONE: (203) FAX: (203)

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street Oxford, CT PHONE: (203) FAX: (203) EVALUATION REPORT Carlisle SynTec Systems P.O. Box 7000 Carlisle, PA 17013 (717) 245-7264 EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization #9503 353 Christian Street Oxford, CT 06478 PHONE:

More information

UL Evaluation Report UL ER Issued: July 25, UL Category Code: ULFB. CSI MasterFormat

UL Evaluation Report UL ER Issued: July 25, UL Category Code: ULFB. CSI MasterFormat UL Evaluation Report UL ER10167-01 Issued: July 25, 2014 Visit UL s On-Line Certifications Directory: www.ul.com/erdirectory for current status of Report. UL Category Code: ULFB CSI MasterFormat DIVISION:

More information

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street Oxford, CT PHONE: (203) FAX: (203)

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street Oxford, CT PHONE: (203) FAX: (203) EVALUATION REPORT Mule-Hide Products Co., Inc. 1195 Prince Hall Drive Beloit, WI 53511 EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization #9503 353 Christian Street Oxford, CT 06478 PHONE: (203)

More information

Florida Building Code Online Page 1 of 2 BCIS Home Log In User Registration Hot Topics Submit Surcharge Stats & Facts Publications FBC Staff BCIS Site Map Links Search Product Approval USER: Public User

More information

technical bulletin ROOFING CORPORATION

technical bulletin ROOFING CORPORATION ROOFING CORPORATION technical bulletin TO: All Region Managers, Plant Managers, National Account Managers, Sales Representatives, Account Executives, and Atlanta Sales FROM: Ed Todd, Director, Product

More information

JM PVC Fleece Backed 50 mil, JM PVC Fleece Backed 60 mil, JM PVC Fleece Backed 80 mil

JM PVC Fleece Backed 50 mil, JM PVC Fleece Backed 60 mil, JM PVC Fleece Backed 80 mil UL Evaluation Report UL ER10167-02 Issued: August 8, 2016 Revised: November 3, 2016 Visit UL s On-Line Certifications Directory: www.ul.com/erdirectory for current status of Report. UL Category Code: ULFB

More information

EVALUATION REPORT Soprema, Inc. 310 Quadral Drive Wadsworth, OH 44281

EVALUATION REPORT Soprema, Inc. 310 Quadral Drive Wadsworth, OH 44281 EVALUATION REPORT Soprema, Inc. 310 Quadral Drive Wadsworth, OH 44281 EXTERIOR RESEARCH & DESIGN, LLC. 353 CHRISTIAN STREET OXFORD, CT 06478 PHONE: (203) 262-9245 FAX: (203) 262-9243 Date of Issuance:

More information

technical bulletin ROOFING CORPORATION

technical bulletin ROOFING CORPORATION ROOFING CORPORATION technical bulletin TO: All Region Managers, Plant Managers, National Account Managers, Sales Representatives, Account Executives, and Atlanta Sales FROM: Ed Todd, Director, Product

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

UL Evaluation Report UL ER Issued: December 9, Revised: September 29, UL Category Code: ULFB. CSI MasterFormat

UL Evaluation Report UL ER Issued: December 9, Revised: September 29, UL Category Code: ULFB. CSI MasterFormat UL Evaluation Report UL ER9516-01 Issued: December 9, 2013 Revised: September 29, 2017 Visit UL s On-Line Certifications Directory: www.ul.com/erdirectory for current status of Report. UL Category Code:

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

UL Listing: EPDM Roofing Systems

UL Listing: EPDM Roofing Systems Commercial/Industrial Roofing Systems UL Listing: EPDM Roofing Systems SINGLE PLY MEMBRANE ROOFING SYSTEMS In the fully adhered and mechanically fastened systems described below, the ".045 EPDM" membrane

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 NOTICE OF ACCEPTANCE

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3909 Issued 07/2017 This report is subject to renewal 07/2018. DIVISION: 07 00 00

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY AFFAIRS (PERA) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

statement: "Miami-Dade County Product Control Approved", unless otherwise noted herein.

statement: Miami-Dade County Product Control Approved, unless otherwise noted herein. MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: POLYVINYL CHLORIDE ROOFING REPORT HOLDER: IB ROOF SYSTEMS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: POLYVINYL CHLORIDE ROOFING REPORT HOLDER: IB ROOF SYSTEMS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 28 Reissued 02/2018 This report is subject to renewal 02/2019. DIVISION: 07 00 00

More information

Table of Contents. Dedicated to Service and Support

Table of Contents. Dedicated to Service and Support A Roofing Resource for More Than a Century and a Half, Look to Johns Manville for Superior Service and Comprehensive Solutions That Perform for the Long Term. 2 Table of Contents Introduction 2 Modified

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER: POLYGLASS USA, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER: POLYGLASS USA, INC. 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2018 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 07 00

More information

HALIFAX HUMANE SOCIETY BOARDING AND GROOMING FACILITY SECTION STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS

HALIFAX HUMANE SOCIETY BOARDING AND GROOMING FACILITY SECTION STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS SECTION 075216 - PART 1 - GENERAL 1.1 SUMMARY A. Section includes styrene-butadiene-styrene (SBS) modified bituminous membrane roofing. 1.2 DEFINITIONS A. Hot Roofing Asphalt: Roofing asphalt heated to

More information

REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC 250 WEST 96 TH STREET INDIANAPOLIS, INDIANA EVALUATION SUBJECT:

REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC 250 WEST 96 TH STREET INDIANAPOLIS, INDIANA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2831 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 07 00

More information

Sure-Weld (TPO) Adhered Roofing Systems Code Approval Guide January, Table of Contents

Sure-Weld (TPO) Adhered Roofing Systems Code Approval Guide January, Table of Contents (TPO) Adhered Roofing Systems Code Approval Guide January, 2017 Introduction... ii Guidelines... Mechanically Fastened or Induction Welding Roofing Systems UL Approvals NonCombustible ANSI UL Class A...

More information

Addendum No. 1. ITB for Emergency Management/Utilities Administration Building Renovation Addendum Release Date April 06, 2017

Addendum No. 1. ITB for Emergency Management/Utilities Administration Building Renovation Addendum Release Date April 06, 2017 City of Wilton Manors Finance Department 2020 Wilton Drive Wilton Manors, FL 33305 Phone (954) 390-2171 Fax (954)390-2199 www.wiltonmanors.com Addendum No. 1 ITB # 2016-16 ITB for Emergency Management/Utilities

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER: CERTAINTEED CORPORATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER: CERTAINTEED CORPORATION 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1388 Reissued 05/2017 This report is subject to renewal 05/2018. DIVISION: 07 00 00 THERMAL

More information

Department of Environmental Protection August 22, 2014 Attn: Katie Parrish 3900 Commonwealth Blvd MS520 Tallahassee, FL 32399

Department of Environmental Protection August 22, 2014 Attn: Katie Parrish 3900 Commonwealth Blvd MS520 Tallahassee, FL 32399 Department of Environmental Protection August 22, 2014 Attn: Katie Parrish 3900 Commonwealth Blvd MS520 Tallahassee, FL 32399 Re: San Marcos de Apalache Historic State Park, Museum and Roof Repairs Tallahassee,

More information

Florida Building Code Product Approval

Florida Building Code Product Approval Florida Building Code Product Approval Updated 4/7/10 Your Best and Safest Choice Quality You Can Trust Since 1886! Florida Building Code Online http://floridabuilding.org/pr/pr_app_dtl.aspx?param=wgevxqwtdquqvxydmpwxq0d...

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786)315-2590

More information

CBUCK Engineering. Evaluation Report Englert Series 500 Metal Roof Assembly Manufacturer: Englert, Inc Amboy Avenue Perth Amboy, NJ

CBUCK Engineering. Evaluation Report Englert Series 500 Metal Roof Assembly Manufacturer: Englert, Inc Amboy Avenue Perth Amboy, NJ Evaluation Report Englert Series 500 Metal Roof Assembly Manufacturer: 1200 Amboy Avenue Perth Amboy, NJ 08862 for Florida Product Approval # FL 11698.2 R3 Florida Building Code 5th Edition (2014) Method:

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ETHYLENE PROPYLENE DIENE MONOMER ROOFING REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ETHYLENE PROPYLENE DIENE MONOMER ROOFING REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Rept ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.g ESR 3026 Reissued 04/207 This rept is subject to renewal 04/208. DIVISION: 07 00 00 THERMAL

More information

Roof Replacement. Notes: T-1 (Title Sheet) Roof Key Plan Russell House Student Union 1400 Greene Street Columbia, South Carolina 29208

Roof Replacement. Notes: T-1 (Title Sheet) Roof Key Plan Russell House Student Union 1400 Greene Street Columbia, South Carolina 29208 Notes: Drawing Index T-1 Title R-1 Roof Plan - Existing Conditions R-2 Roof Plan - New D-1 Roof Details D-2 Roof Details D-3 Roof Details M-1 Mechanical - Roof Plan M-2 Mechanical - Details Roof Key Plan

More information

Residential, 26 Ga. Roof Panel over 15/32 Plywood. Florida Product Approval # R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D

Residential, 26 Ga. Roof Panel over 15/32 Plywood. Florida Product Approval # R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D Product Evaluation Report REED S METAL, INC. Residential, 26 Ga. Roof Panel over 15/32 Plywood Florida Product Approval # 12725.2 R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D Category: Roofing

More information

CBUCK Engineering. Evaluation Report Cee Lock Panel Metal Roof Assembly

CBUCK Engineering. Evaluation Report Cee Lock Panel Metal Roof Assembly Specialty Structural Engineering CBUCK, Inc. Certificate of Authorization #8064 Prepared by: James L. Buckner, P.E., S.E.C.B. Florida Professional Engineer # 31242 Florida Evaluation ANE ID: 1916 Project

More information

SPECIFICATION SUBMITTAL

SPECIFICATION SUBMITTAL 101C AWAPLAN PREMIUM INSULATED DECK TAMKO BASE PLY INSULATION 1/2 m = 50 cm = 19-11/16 inches 1 m = 100 cm = 39-3/8 inches Material Requirements TAMKO GLASS-BASE, TAM-GLASS PREMIUM, TAM- PLY IV, or BASE-N-PLY

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590

More information

2010 FLORIDA BUILDING CODE TEST PROTOCOLS HVHZ (TAS)

2010 FLORIDA BUILDING CODE TEST PROTOCOLS HVHZ (TAS) TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE FOR FIELD UPLIFT RESISTANCE OF EXISTING MEMBRANE ROOF SYSTEMS AND IN SITU TESTING FOR REROOF AND NEW CONSTRUCTION APPLICATIONS 1. Scope: 1.1 This

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590

More information

CBUCK Engineering. Product: Zee-Lock Roof Panel Material: Steel Panel Thickness: 24 gauge Panel Width: 16 Support: Wood Deck

CBUCK Engineering. Product: Zee-Lock Roof Panel Material: Steel Panel Thickness: 24 gauge Panel Width: 16 Support: Wood Deck Evaluation Report Zee-Lock With Continous Zee-Rib Clip Metal Roof Assembly Manufacturer: 1720 Maury Road Houston, TX 77026 (800) 231-8127 2333 for Florida Product Approval HVHZ # FL 15471.1 Florida Building

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590

More information

CBUCK Engineering. Florida Product Approval # FL R2

CBUCK Engineering. Florida Product Approval # FL R2 Specialty Structural Engineering CBUCK, Inc. Certificate of Authorization #8064 Prepared by: James L. Buckner, P.E., SECB Florida Professional Engineer # 31242 Florida Evaluation ANE ID: 1916 Project Manager:

More information

CITY OF RICHMOND PINE CAMP COMMUNITY CENTER ROOF REPLACEMENT PROJECT RCS PROJECT NO

CITY OF RICHMOND PINE CAMP COMMUNITY CENTER ROOF REPLACEMENT PROJECT RCS PROJECT NO SECTION 07220 - ROOF INSULATION PART 1 - GENERAL 1.01 DESCRIPTION A. Work included: The Roofing Contractor will provide all polyisocyanurate insulation and high density wood fiber roof insulation (tapered

More information

DRAFT NOTICE OF ACCEPTANCE (NOA)

DRAFT NOTICE OF ACCEPTANCE (NOA) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590

More information

1. SUBJECT: DURO-LAST, DURO-TUFF, DURO-FLEECE, and DURO-FLEECE PLUS ROOFING MEMBRANES

1. SUBJECT: DURO-LAST, DURO-TUFF, DURO-FLEECE, and DURO-FLEECE PLUS ROOFING MEMBRANES UL Evaluation Report UL ER10128-01 Issued: January 22, 2016 Revised: September 30, 2017 Visit UL s On-Line Certifications Directory: www.ul.com/erdirectory for current status of Report. UL Category Code:

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER: CERTAINTEED CORPORATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER: CERTAINTEED CORPORATION 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1388 Reissued 05/2017 This report is subject to renewal 05/2018. DIVISION: 07 00

More information

SECTION PREPARATION FOR RE-ROOFING

SECTION PREPARATION FOR RE-ROOFING SECTION 07 01 50.19 PREPARATION FOR RE-ROOFING SPEC WRITER NOTES: 1. Delete text between // // not applicable to project. Edit remaining text to suit project. 2. Edit Summary article below after establishing

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

COMMERCIAL WINDSTORM MITIGATION INSPECTION REPORT Prepared for: Boca Vista Condominium Association, Inc th Avenue Madeira Beach, FL 33708

COMMERCIAL WINDSTORM MITIGATION INSPECTION REPORT Prepared for: Boca Vista Condominium Association, Inc th Avenue Madeira Beach, FL 33708 Insurance Appraisals Reserve Studies Wind Mitigation COMMERCIAL WINDSTORM MITIGATION INSPECTION REPORT Prepared for: Boca Vista Condominium Association, Inc. 401 150th Avenue Madeira Beach, FL 33708 As

More information

SL175 Panel Technical Data Guide

SL175 Panel Technical Data Guide Description SL175 is a integral snap-lock standing seam roofing panel used on commercial and residential applications. The panel is factory formed in continuous lengths up to 60-0 long. Attachment to either

More information

SECTION STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS MEMBRANE ROOFING

SECTION STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS MEMBRANE ROOFING SECTION 075216 - STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS MEMBRANE ROOFING PART 1 - GENERAL 1.1 SUMMARY A. Section includes styrene-butadiene-styrene (SBS) modified bituminous membrane roofing.

More information

LEGACY REPORT DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FLUID APPLIED ROOFING REPORT HOLDER: CONKLIN COMPANY INC.

LEGACY REPORT DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FLUID APPLIED ROOFING REPORT HOLDER: CONKLIN COMPANY INC. 0 Most Widely Accepted and Trusted ICC ES Legacy Report ICC ES 000 (800) 42 6587 (562) 699 054 www.icc es.org ER 520 Reissued 09/2017 This report is subject to renewal 09/2018. DIVISION: 07 00 00 THERMAL

More information

Thermoplastic Single Ply & Multi-Ply Roofing Systems

Thermoplastic Single Ply & Multi-Ply Roofing Systems Thermoplastic Single Ply & Multi-Ply Roofing Systems COMMERCIAL INDUSTRIAL INSTITUTIONAL RESIDENTIAL Specializing in Roof Solutions for over 25 years FlexRoofingSystems.com Thermoplastic Single Ply Roof

More information

Florida Product Approval # R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D

Florida Product Approval # R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D Product Evaluation Report REED S METALS, INC. Perma-Lok, 26 Ga. 16 Coverage Roof Panel over 15/32 Plywood Florida Product Approval # 12725.1 R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D Category:

More information

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 075423 - THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Division 00 Bidding Requirements and other Division

More information

SECTION CLAY BARREL TILE ROOFING. A. American Society for Testing and Materials (ASTM):

SECTION CLAY BARREL TILE ROOFING. A. American Society for Testing and Materials (ASTM): SECTION 07320 CLAY BARREL TILE ROOFING PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 02072 - Removals. 2. 07600 - Flashing and Sheet Metal. 1.02 REFERENCES A. American Society for Testing and Materials

More information

Re-Roof Permit Checklist

Re-Roof Permit Checklist Re-Roof Permit Checklist The following items are required with submission of your building permit application: 2 copies of completed Re-Roof permit application Roof Pressure Sheet completed as applicable

More information

ACFoam-II HCFC Free "Green" Polyiso Specification

ACFoam-II HCFC Free Green Polyiso Specification ACFoam-II HCFC Free "Green" Polyiso Specification To help owners and specifiers, the following specification strategies are offered as they relate to product performance when including HCFC FREE Green

More information

COMMERCIAL ROOFING SYSTEMS

COMMERCIAL ROOFING SYSTEMS Flex Membrane International Corp. 2670 Leiscz s Bridge Road, Suite 400, Leesport, PA 19533 Tel: 610-916-9500 Fax: 610-916-9501 COMMERCIAL ROOFING SYSTEMS FLEX FB (Fleece Backed) ELVALOY, FLEX MF/R (Smooth

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

Recommended Fastening Patterns for Rmax Insulation in Low Slope Roofing Applications

Recommended Fastening Patterns for Rmax Insulation in Low Slope Roofing Applications Recommended Fastening Patterns for Rmax Insulation in Low Slope Roofing Applications INTRODUCTION Rmax recommends that any insulation which is laid over a steel or wood roof deck be attached with mechanical

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

SBS Modified Bitumen Specifications

SBS Modified Bitumen Specifications 7A.1 General Information 7A.1.1 This section provides application information, and outlines specifications currently available from JM Roofing Systems, for SBS (Styrene-Butadiene-Styrene) Modified Bitumen

More information

ROOFING APPLICATION STANDARD (TAS) No. 102(A)-95

ROOFING APPLICATION STANDARD (TAS) No. 102(A)-95 ROOFING APPLICATION STANDARD (TAS) No. 102(A)-95 TEST PROCEDURE FOR STATIC UPLIFT RESISTANCE OF MECHANICALLY ATTACHED, CLIPPED, RIGID, ROOF SYSTEMS (For Methods of Mechanical Attachment Excluding Clips,

More information

COMMERCIAL WINDSTORM MITIGATION INSPECTION REPORT

COMMERCIAL WINDSTORM MITIGATION INSPECTION REPORT Insurance Appraisals - Reserve Studies - Windstorm Mitigation Reports COMMERCIAL WINDSTORM MITIGATION INSPECTION REPORT Prepared for Harbour Hill Condominium Apartment Association, Inc. This report contains

More information

Firestone Polyiso Boards

Firestone Polyiso Boards Firestone Polyiso Boards Superior energy efficiency. Superior protection. Firestone Polyiso Boards POLISOBROUK10.indd 1 1/04/10 14:26 Firestone Polyiso Boards Firestone total roofing systems Since Firestone

More information

REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3275 Reissued 09/2017 This report is subject to renewal 09/2018. DIVISION: 03 00

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 2 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (78) 315-2590

More information

Uniform Mitigation Verification Inspection Form Maintain a copy of this form with insurance policy

Uniform Mitigation Verification Inspection Form Maintain a copy of this form with insurance policy Uniform Mitigation Verification Inspection Form Maintain a copy of this form with insurance policy Inspection Date: 08/12/2011 Owner Information Owner Name: Steve Owner Contact Person: Joe Contact Address:

More information

1 Firestone EPDM Roofing Systems

1 Firestone EPDM Roofing Systems 1 Firestone 1. Firestone EPDM Systems To ensure a long-lasting, trouble-free roof today, it is not sufficient to manufacture high quality roofing membranes. Experience learned that roofing membranes need

More information

COMMERCIAL BUILDING APPLICATIONS

COMMERCIAL BUILDING APPLICATIONS EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that

More information

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1663 Reissued 03/2017 This report is subject to renewal 03/2019. DIVISION: 03 00 00 CONCRETE

More information

1.2 DEFINITIONS, REFERENCES, AND OVERALL STANDARDS Follow 07500

1.2 DEFINITIONS, REFERENCES, AND OVERALL STANDARDS Follow 07500 07503 ROOF ASSEMBLY LIGHTWEIGHT INSULATING CONCRETE (LWIC) ************************************************************************************************************* SPECIFIER: All roof-related items

More information

LOW SLOPE ROOFING INSTALLATION

LOW SLOPE ROOFING INSTALLATION 4.1 STORAGE & HANDLING The following is a list of Malarkey basic requirements for handling and storing roof insulations, roofing products, and construction materials. Unload, handle and store all roofi

More information

Product Evaluation Report of. JELD-WEN, inc. Energy Saver/Contour Wood Edge Opaque Steel Outswing Door w/ or w/o Sidelites

Product Evaluation Report of. JELD-WEN, inc. Energy Saver/Contour Wood Edge Opaque Steel Outswing Door w/ or w/o Sidelites 127 W. Fairbanks Ave. Suite 438 Winter Park, FL 32789 407.644.6957 PH 407.644.2366 FX contact@buildingdrops.com Product Evaluation Report of Energy Saver/Contour Wood Edge Opaque Steel Outswing Door w/

More information

ROOFING CONTRACTORS GENERAL TRADE KNOWLEDGE EXAMINATION CONTENT INFORMATION

ROOFING CONTRACTORS GENERAL TRADE KNOWLEDGE EXAMINATION CONTENT INFORMATION ROOFING CONTRACTORS GENERAL TRADE KNOWLEDGE EXAMINATION CONTENT INFORMATION Revised September 14 The General Trade Knowledge portion of the examination is administered daily in Computer Based Testing (CBT)

More information

Evaluation Report SkylightTube Tubular Daylight Device

Evaluation Report SkylightTube Tubular Daylight Device Evaluation Report SkylightTube Tubular Daylight Device Manufacturer U.S. Sunlight Corporation 5625 B Brisa Street Livermore, CA 94550 925 271 7614 for Florida Product Approval # FL 14564.1 Florida Building

More information

Evaluation Report. Die Formed Skirt Ridge Ventilator. "12 Inch Throat" Manufacturer. Metallic Products Corporation Hollister Road

Evaluation Report. Die Formed Skirt Ridge Ventilator. 12 Inch Throat Manufacturer. Metallic Products Corporation Hollister Road Specialtu Structural Engineering CBUCK, Inc. Certificate of Authorization #864 Evaluation Report Die Formed Skirt Ridge Ventilator "12 Inch Throat" Manufacturer Metallic Products Corporation 7777 Hollister

More information

ANSI/FM Approvals March FM Approvals LLC. All rights reserved.

ANSI/FM Approvals March FM Approvals LLC. All rights reserved. American National Standard for Evaluating the Simulated Wind Uplift Resistance of Roof Assemblies Using Static Positive and/or Negative Differential Pressures ANSI/FM Approvals 4474 March 2004 2004 FM

More information

TEST PROCEDURE FOR AIR PERMEABILITY TESTING OF RIGID, DISCONTINUOUS ROOF SYSTEMS

TEST PROCEDURE FOR AIR PERMEABILITY TESTING OF RIGID, DISCONTINUOUS ROOF SYSTEMS TESTING APPLICATION STANDARD (TAS) 116-95 TEST PROCEDURE FOR AIR PERMEABILITY TESTING OF RIGID, DISCONTINUOUS ROOF SYSTEMS Scope 1.1 This Protocol covers the determination of the air permeability characteristics

More information

ROOFING APPLICATION STANDARD (RAS) No. 120 MORTAR AND ADHESIVE SET TILE APPLICATION

ROOFING APPLICATION STANDARD (RAS) No. 120 MORTAR AND ADHESIVE SET TILE APPLICATION ROOFING APPLICATION STANDARD (RAS) No. 120 MORTAR AND ADHESIVE SET TILE APPLICATION 1. Scope This application standard covers the procedures for installation of mortar or adhesive set roof tile systems.

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786)315-2590

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590

More information

Code Compliance Research Report CCRR-0194

Code Compliance Research Report CCRR-0194 Code Compliance Research Report CCRR-0194 Issued: 09-16-2013 Renewal Due: 09-16-2018 Revised: 10-12-2017 DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES Section: 06 05 23 Wood, Plastic, and Composite

More information

APPLICATION SAFETY TOOLS REQUIRED

APPLICATION SAFETY TOOLS REQUIRED Revised April 2007 Product Technical Bulletin SFM-3.5H-FR BITUMEN-POLYMER WATERPROOFING MEMBRANE, MADE FROM SELECT SBS AND DISTILLED BITUMEN, REINFORCED WITH HIGH-STRENGTH FIBERGLASS MAT UL CLASS A FIRE-RATED

More information

American National Standard Standard Field Test Procedure for Determining the Withdrawal Resistance of Roofing Fasteners

American National Standard Standard Field Test Procedure for Determining the Withdrawal Resistance of Roofing Fasteners ANSI/SPRI FX-1 American National Standard Standard Field Test Procedure for Determining the Withdrawal Resistance of Roofing Fasteners Table of Contents 1.0 Purpose................................................

More information

GOWANDA, NEW YORK SEPTEMBER 18, 2008 ARCH PROJECT NO

GOWANDA, NEW YORK SEPTEMBER 18, 2008 ARCH PROJECT NO SECTION 07210 BUILDING INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

REPORT HOLDER: PAREX USA, INC EAST LA PALMA AVENUE, SUITE 250 ANAHEIM, CALIFORNIA EVALUATION SUBJECT:

REPORT HOLDER: PAREX USA, INC EAST LA PALMA AVENUE, SUITE 250 ANAHEIM, CALIFORNIA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 689 Reissued 07/206 This report is subject to renewal 07/208. DIVISION: 07 00 00

More information

Force Engineering & Testing Inc Ramblewood Drive. Humble,TX Product Evaluation Report SENTRIGARD METAL ROOFING SYSTEMS

Force Engineering & Testing Inc Ramblewood Drive. Humble,TX Product Evaluation Report SENTRIGARD METAL ROOFING SYSTEMS Force Engineering & Testing Inc. Product Evaluation Report SENTRIGARD METAL ROOFING SYSTEMS Sentrigard ML 200 24 Ga. 18 7/8" Wide Roof Panel over open framing Florida Product Approval # 9864.2 R4 Florida

More information

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT:

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2184 Reissued 06/2017 This report is subject to renewal 06/2019. DIVISION: 03 00

More information

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET Environmental Protection and Growth Management Department BUILDING CODE SERVICES DIVISION 1 N. University Drive, Box #302 Plantation, Florida 33324 954-765-4400 Broward.org/Building APPLICATION INFORMATION

More information

Roofing. Carrier Membrane SA. Self-adhesive Carrier Membrane. Product Description. Tests. Product Data. Form. Storage

Roofing. Carrier Membrane SA. Self-adhesive Carrier Membrane. Product Description. Tests. Product Data. Form. Storage Carrier Membrane SA Self-adhesive Carrier Membrane Product Description Carrier Membrane SA is a multi-layer self-adhesive membrane made of polymer modified bitumen with an aluminium foil/random fibre top

More information

ESR-1365 Reissued March 2014 This report is subject to renewal April 1, 2015.

ESR-1365 Reissued March 2014 This report is subject to renewal April 1, 2015. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-1365 Reissued March 2014 This report is subject to renewal April 1, 2015. A Subsidiary of the International Code Council DIVISION:

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COATED FOAM ROOFING REPORT HOLDER: LAPOLLA INDUSTRIES, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COATED FOAM ROOFING REPORT HOLDER: LAPOLLA INDUSTRIES, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3916 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 07 00

More information

Design No. P922 September 26, Restrained Assembly Rating 1, 1-1/2 or 2 Hr (See Items 6, 7) Unrestrained Assembly Rating 0 Hr (See Item 6)

Design No. P922 September 26, Restrained Assembly Rating 1, 1-1/2 or 2 Hr (See Items 6, 7) Unrestrained Assembly Rating 0 Hr (See Item 6) Design No. P922 September 26, 2003 Restrained Assembly Rating 1, 1-1/2 or 2 Hr (See Items 6, 7) Unrestrained Assembly Rating 0 Hr (See Item 6) Unrestrained Beam Rating 1, 1-1/2 or 2 Hr (See Item 7) 1.

More information