1 PRE-START-UP/START-UP CHECKLIST CHILLED WATER SYSTEM NOTE: University s Representative must be notified and scheduled to witness test prior to any start up of equipment. A. Chilled Water Pumps 1. Submittal / Approvals Submittal. The Chilled Water System and any other associated equipment and systems are complete and ready for functional testing. The checklist items are complete and have been checked off only by parties having direct knowledge of the event, and by the. This pre-functional checklist is submitted for approval, subject to an attached list of outstanding items yet to be completed. A Statement of Correction will be submitted upon completion of any outstanding areas. None of the outstanding items preclude safe and reliable functional tests being performed. (Firm, Name, Title) (Signature) () (Firm, Name, Title) (Signature) () (Firm, Name, Title) (Signature) () Pre-Functional checklist items are to be completed as part of the functional testing. This checklist does not take the place of the manufacturer s recommended checkout and startup procedures or report. Items that do not apply shall be noted with the reasons on this form (N/A = not applicable, BO = by others). Sections that require attachments are designated with an asterisk (*). Approvals. This filled-out checklist has been reviewed in its entirety with those non-applicable items noted, and all required documentation attached. Its completion is approved with the exceptions noted below. University s Representative 2. Requested documentation submitted Check Equipment Tag AHU-4-1 Contractor Comments 1. Manufacturer s cut sheets 2. Performance data (fan curves, coil data, etc.) 3. Installation and startup manual and plan Documentation complete as per contract documents for given work YES NO 3. Nameplate Verification* Provide Digital Photos of Nameplate from Each CHW Pump B-1
2 The equipment installed matches the specifications for given work YES NO 4. Physical Installation Checks Check Equipment Tag P-1 P-2 P-3 Contractor University General Installation Label permanently affixed Pumps in place and properly grouted inertia base Vibration isolation devices installed and functional (springs for piping) Factory alignment appears correct Field alignment, if required, completed Seismic anchoring installed Temperature, pressure and flow gages and sensors installed Pump lubricated Pump case not subject to piping force Check drain line for each pump base to floor drain Piping (immediately around pump, see full piping checklist) Pipe fittings complete and pipes properly supported (not by pump) Pipes properly labeled Pipes properly insulated Strainers in place and clean Piping system properly flushed Valves properly tagged VFD VFD powered (wired to controlled equipment) VFD interlocked to control system (on/off signal, status/current switch, analog signals and communication) Drive location not subject to temperatures in excessive of 100 deg. F Drive location not subject to excessive moisture or dirt Drive size matches motor size Internal setting designating the model is correct Input of motor FLA represents 100% to 105% of motor FLA rating Appropriate Volts vs. Hz curve is being used Unit is programmed with full written programming record on site Acceleration and Deceleration Values Set > 30 Sec Actual Acceleration Actual Deceleration Lower Minimum Frequency Value Maximum Frequency (60Hz) Actual B-2
3 Check Equipment Tag P-1 P-2 P-3 Contractor University Filled Out Factory Start-up and Checkout Lists. Attach list of all parameters changed from the default values, showing register and altered value for each one. * Electrical and Controls Power disconnects in place and labeled All electric connections tight Proper grounding installed for components and unit Motor safeties in place and operable TAB Installation of system and balancing devices allowed balancing to be completed following specified NEBB or AABC procedures and Contract Documents* See voltage phase imbalance and full amp load checks in Operational Checks below The checklist items of Part 4 are all successfully completed for given work. YES NO 5. Operational Checks (These augment manufacturer s list. This is not the functional performance testing.) Check if Okay. Enter comment or note number if deficient Check Equipment Tag P-1 P-2 P-3 Note Contractor The HOA switch properly activates and deactivates the unit Pump rotation verified correct No unusual noise or vibration No leaking apparent around fittings Phase Imbalance (Must Be < 2 %) P1 % P2 % % Full Running Motor Amps /Full Rated Motor Amps P1 % P2 % The checklist items of Part 5 are all successfully completed for given work. YES NO B. Chilled Water Piping 1. Requested documentation submitted Check Y / N Contractor Manufacturer s cut sheets Performance data Flushing and cleaning plan, including staging of multiple floors B-3
4 Documentation complete as per contract documents for given work YES NO 2. Physical Installation Checks Check if Okay. Enter comment or note number if deficient. University Check Y / N Contractor Check Note Piping Pipe fittings complete and pipes properly supported Required seismic anchoring installed Pipes properly labeled Pipes properly insulated Strainers in place and clean Isolation valves and balancing valves installed Test ports (P/T) installed near all control sensors and as per Specification Flushing and cleaning plan submitted and approved (Minimum flushing velocity in all pipe sections is the greater of 4 ft. per second, or 1.5 times the velocity at design flow) Piping system properly flushed and cleaned and temporary piping removed (report attached) Ten percent of strainers and University-selected low-point drains opened and witnessed by University to be clean. (List points checked below). Piping pressure tested according to Contract Documents (report attached) Chemical treatment system or plan installed Water treatment report submitted according to contract documents No leaking apparent around fittings ASME pressure vessel data sheet or certification tag posted and inspection complete for each expansion tank Expansion tanks verified to not be air bound and system completely full of water. System purged of all air. Air vents and bleeds at high points of systems functional All instrumentation and devices (thermometers, gauges, sensors, check valves, etc.) match Specifications and placement per Contract Drawings Flowmeters Installed with Correct Up Stream/Down Stream diameters. Flowmeters installed to permit access and, if insertion type, removal. Loop Flowmeter and Temperature Sensors Connected to a Means to Record CHW Usage. All thermometers/ gauges reading within manufacturers allowances Exceptions Valves (Shutoff and Automatic) Valve labels permanently affixed Valves installed in proper direction No leaks B-4
5 Check if Okay. Enter comment or note number if deficient. University Check Y / N Contractor Check Note Valves that require a positive shut-off are verified to not be leaking when closed at normal operating pressure per Calibration and Leak-by Test Procedures document. List: The checklist items of Part 3 are all successfully completed for given work. YES NO Followed Manufacturers start up steps YES NO Summary of Documents to be Attached 1. Nameplate Information on CHW Pumps 2. VFD Startup and Checkout Forms including List of Default Parameter Changes 3. Prebalance Report B-5
Unit Substation Transformer Construction Checklist (under 500 kva)
Unit Substation Transformer Checklist (under 500 kva) Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.
More informationOAKDALE CHILLED WATER PLANT CAPACITY UPGRADES UI PROJECT INSTALL CHILLERS SECTION COMMISSIONING
PART I GENERAL 1.01 SECTION INCLUDES A. Commissioning objectives. B. Roles and responsibilities. C. Test Equipment. D. Systems to be commissioned. E. Construction Checklist requirements. SECTION 01 91
More informationLow Voltage Switchgear Construction Checklist (under 500 kva)
Low Voltage Switchgear Checklist (under 500 kva) Project: Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.
More informationSECTION COOLING TOWER
PART 1 GENERAL 1.1 SECTION INCLUDES A. Mechanical induced draft Cooling Tower B. Controls C. Ladder and handrails 1.2 REFERENCES SECTION 23 65 00 COOLING TOWER A. ANSI/AFBMA 9 - Load Rating and Fatigue
More informationB. ASHRAE 1991 HVAC Applications Handbook: Chapter 34--Testing, Adjusting and Balancing.
PART 1 GENERAL 1.1 RELATED DOCUMENTS SECTION 230593 TESTING, ADJUSTING, AND BALANCING A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification
More information1.07 SUPPLEMENTS PRODUCTS (NOT USED) EXECUTION (NOT USED) END OF SECTION
1.07 SUPPLEMENTS d. Complete using typewriter or electronic printing. 3. Include detailed lubrication instructions and diagrams showing points to be greased or oiled; recommend type, grade, and temperature
More informationSECTION HVAC INSTRUMENTATION AND CONTROLS INSTALLATION. (Applicable to IUPUI Only)
SECTION 15957 (Applicable to IUPUI Only) I. GENERAL A. NOTES 1. The University has a pre-purchase agreement (PPA) with Johnson Controls (JCI) and Siemens Building Technologies (SBT). The University will
More informationNEBBinar: Managing Building Performance through Commissioning. March 28, 2013
NEBBinar: Managing Building Performance through Commissioning March 28, 2013 0 Moderator Jim Huber, NEBB Vice President and President of Complete Commissioning Jim Huber is the President of Complete Commissioning.
More informationSPECIFICATIONS - DETAILED PROVISIONS Section Chlorination System (On-site Sodium Hypochlorite Generation System) C O N T E N T S
SPECIFICATIONS - DETAILED PROVISIONS Section 11241 - Chlorination System (On-site Sodium Hypochlorite Generation System) C O N T E N T S PART 1 - GENERAL... 1 1.01 Scope... 1 1.02 Scope of Work... 1 1.03
More informationSECTION INFLUENT EQUALIZATION TANK PUMPS
PART 1 GENERAL 1.01 SCOPE OF WORK A. The Contractor shall furnish and install all materials, labor and equipment to put into service the Influent Equalization Pumps in accordance with the Contract Drawings
More informationA. This Section includes exterior piping for vertical, direct-buried, ground-loop, heat-pump systems that operate between 23 and 104 deg F.
SECTION 23 21 16 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
More informationHEATMAX. Mechanical Installation and Commissioning Instructions HEATMAX
HEATMAX Mechanical Installation and Commissioning Instructions HEATMAX 1. General Safety Information 2. General Product Information 3. Installation 4. Commissioning 5. Maintenance -----------------------------------------
More informationSECTION ROTARY SCREW WATER CHILLERS
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:
More informationBanyan Air Service November 18, 2011 AVE Aviation and Commerce Center Building 1 Miami, FL
SECTION 01815 - HVAC COMMISSIONING REQUIREMENTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division
More informationFundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619
AABC Commissioning Group AIA Provider Number 50111116 Fundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619 Jim Hall, PE, TBE, CxA Systems Management & Balancing,
More informationInstallation Instructions
Installation Instructions AquaSnap 010-055 Chilled Water Storage Tank 50/60 Hz Part No: -900---001; -900---009; -900---010 CONTENTS INTRODUCTION.................................. 1 SAFETY CONSIDERATIONS......................
More informationSECTION PACKAGE BOOSTER PUMP STATIONS
SECTION 331223 PACKAGE BOOSTER PUMP STATIONS Scope: The Contractor shall install a pump station at two locations to be determined by the Owner. These pump stations shall be designed to deliver flow to
More informationSt. Monica Food Pantry Testing, Adjusting, & Balancing for HVAC sys-tek No
St. Monica Food Pantry 23 0593-1 HVAC WORK DIVISION 23 SECTION 230593 TESTING, ADJUSTING, & BALANCING FOR HVAC PART 1. GENERAL 1.1 DESCRIPTION OF WORK A. Air balancing of dedicated outside air systems
More informationB. System Design and Performance Requirements
15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes
More informationSECTION HVAC INSTRUMENTATION AND CONTROLS INSTALLATION
I. GENERAL A. NOTES SECTION 15957 (Applicable to IUPUI Only) 1. The University has a pre-purchase agreement (PPA) with Johnson Controls (JCI) and Siemens Building Technologies (SBT). The University will
More informationB. Shop Drawings: For air terminal units. Include plans, elevations, sections, details, and attachments to other work.
SECTION 233600 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fan-powered air terminal units. 2. Shutoff, single-duct air terminal units. 1.2 PERFORMANCE REQUIREMENTS A. Structural Performance:
More informationAMCOT COOLING TOWER CORPORATION LRC-H & LRC-LNS CROSS FLOW COOLING TOWER OPERATIONS AND MAINTAINENCE MANUAL
AMCOT COOLING TOWER CORPORATION LRC-H & LRC-LNS CROSS FLOW COOLING TOWER 1. Preface OPERATIONS AND MAINTAINENCE MANUAL 1-800-444-8693 Operation and Maintenance Manual For Amcot LRC-H Cooling Tower & LRC-LNS
More informationAttachment 1: RAE Corporation Technical Specification
Attachment 1: RAE Corporation Technical Specification RAE Corporation Phone: 918-825-7222, ext. 105 Steve Corbin Quote# XXXX Qty Customer Tag Technical Systems Model Number 1 ACC-4 10A0-162-S General Scope
More informationFACILITIES MANAGEMENT
FACILITIES MANAGEMENT Planning, Design & Construction March 7, 2013 Re: Request for Proposals- Commissioning Services Mayflower Hall Permanent Flood Recovery & Mitigation (UI# 0200201) University of Iowa
More informationSystem & Equipment Checkout Procedure Client Name Plant Location
System & Equipment Checkout Procedure Client Name Plant Location Procedure Title: Boiler Feed Water System Prepared By: Applied Performance Strategies 1 of 7 Approved By: Date: 01/11/08 Date: Purpose:
More informationNEBBinar: Technical Commissioning: The most effective commissioning process for new buildings. March 5, 2014
NEBBinar: Technical Commissioning: The most effective commissioning process for new buildings March 5, 2014 0 Moderator Jim Huber, NEBB President-Elect and President of Complete Commissioning Jim Huber
More informationSECTION VIBRATION ISOLATION FOR PLUMBING PIPING AND EQUIPMENT
SECTION 220550 - VIBRATION ISOLATION FOR PLUMBING PIPING AND EQUIPMENT PART 1 - GENERAL REQUIREMENTS 1.1 SUMMARY A. It is the intent of this specification to provide vibration isolation supports for Plumbing
More informationCONTROL OF HAZARDOUS ENERGY LOCKOUT/TAGOUT PROCEDURES (Revised 8/05)
CONTROL OF HAZARDOUS ENERGY LOCKOUT/TAGOUT PROCEDURES (Revised 8/05) 29CFR1910.147 Purpose Scope This policy establishes the requirements for energy control procedures, employee training and periodic inspections
More informationTYPICAL INSTALLATION INSTRUCTIONS
TYPICAL INSTALLATION INSTRUCTIONS Environment One Grinder Pump Feature Identification 1. Grinder Pump Basin High density polyethylene (HDPE) 2. Accessway Cover Painted Steel 3. Electrical Quick Disconnect
More informationField Accuracy of Temperature Measurements in TAB Work Andrew P. Nolfo, PE
Field Accuracy of Temperature Measurements in TAB Work Andrew P. Nolfo, PE The purpose of this article is to discuss the measuring and reporting of temperatures at heat transfer equipment during the Testing
More informationPreparation For an Official CTI Thermal Performance, Plume Abatement, Or Drift Emission Test
COOLING TECHNOLOGY INSTITUTE Preparation For an Official CTI Thermal Performance, Plume Abatement, Or Drift Emission Test February 2014 PTG-156 (14) FOREWORD This Cooling Technology Institute (CTI) publication
More informationB. Provide liquid-filled secondary substation transformers as indicated on drawings.
SECTION 26 12 13 PART 1 - GENERAL 1.01 WORK INCLUDED A. Comply with the provisions of Sections 26 05 00. B. Provide liquid-filled secondary substation transformers as indicated on drawings. 1.02 RELATED
More informationLegacy Environmental Process, LLC 1445 Ashville Road, Suite 103 Leeds, Alabama In USA Fax:
Legacy Environmental Process, LLC 1445 Ashville Road, Suite 103 Leeds, Alabama 35094 In USA 1-205-640-1035 Fax: 1-205-640-1039 www.legacyenvpro.com Pre-Plant Delivery And Installation Manual For Project
More informationSUGGESTED SPECIFICATIONS Pump Frames through 64132
TYPE HBB - HORIZONTAL SOLIDS-HANDLING WASTEWATER PUMPS Pump Frames 44081 through 64132 GENERAL Furnish and install Horizontal Flexible Coupled Dry Pit Pumping Units complete with all accessories and appurtenances
More informationLockout/Tagout. Company Policy
Company Policy Lockout/Tagout is dedicated to the protection of its employees from occupational injuries and illnesses. is responsible for providing a safe working environment and the employees have and
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 25 0800 - COMMISSIONING OF INTEGRATED AUTOMATION GENERAL 1.1 SUMMARY This section defines responsibilities of the Integrated Automation Contractor to facilitate the Commissioning process for the
More informationSECTION MEDIUM VOLTAGE TRANSFORMERS
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the
More informationA. This Section includes the following types of dry-type transformers rated 600 V and less, with capacities up to 1000 kva:
SECTION 16461 - LOW-VOLTAGE TRANSFORMERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationPSP Series Water Purification Systems
Operations and Maintenance Manual for PSP Series Water Purification Systems PSP-1000 PSP-1600 PSP-2700 Rev. 2 / 08/26/14 Compact Design, Self-Contained Water Processing Unit for Point-Of-Use or Point-Of-Entry
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-23 05 93 (November 2015) ----------------------------- Preparing Activity: NAVFAC Superseding UFGS-23 05 93 (August 2009) UNIFIED FACILITIES GUIDE SPECIFICATIONS References
More informationENVOY STATION FUEL SELF AUDIT CHECKLIST
A. GENERAL AND INSTRUCTIONS 1. Self-audits of jet fuel storage facilities, mobile refueling units and into-plane fueling operations are to be performed at all Company stations as described in this section.
More informationSECTION SLUDGE HOLDING TANK DECANTER PUMP
PART 1 GENERAL 1.01 SCOPE OF WORK A. The Contractor shall furnish and install all materials, labor and equipment to put into service the Sludge Holding Tank Decanter Pumping System in accordance with the
More informationSAN FRANCISCO PUBLIC UTILITIES COMMISSION INFRASTRUCTURE CONSTRUCTION MANAGEMENT PROCEDURES
SAN FRANCISCO PUBLIC UTILITIES COMMISSION INFRASTRUCTURE CONSTRUCTION MANAGEMENT PROCEDURES SECTION: SFPUC INFRASTRUCTURE CONSTRUCTION MANAGEMENT PROCEDURE NO: 018 TITLE: SYSTEM TESTING AND START-UP APPROVED:
More informationHUP. Performance Data. Wholesale Products Page: Section: Performance Data Dated: January RPM: 1550 Discharge: 1" Solids: 1/8" GPM: TDH:
Performance RPM: 1550 Discharge: 1" Solids: 1/8" Wholesale Products Page: 6660-1 Section: Performance The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower.
More informationSECTION SANITARY WASTE INTERCEPTORS
SECTION 22 13 23 SANITARY WASTE INTERCEPTORS PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable
More informationSmall Oil-Less Centrifugal Compressors: Bringing Energy Efficiency and Reduced Costs to Chiller Plants
Small Oil-Less Centrifugal Compressors: Bringing Energy Efficiency and Reduced Costs to Chiller Plants Ben Erpelding and Annika Moman, San Diego Regional Energy Office ABSTRACT According the U.S. Department
More informationExterior Cryogenic Fluid Vessels
Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA. 92602 www.ocfa.org 714-573-6100 Exterior Cryogenic Fluid Vessels Guideline G-13 Serving the Cities of
More informationSK75/100. Performance Data TOTAL HEAD IN FEET HEAD-METERS 6 SK100 SK Liters/Second Capacity-U.S. G.P.M.
Performance SK75/100 RPM: 1750 Discharge: 2" Solids: 2" Wholesale Products Page: 6300-1 Section: Performance 12 40 9 30 HEAD-METERS 6 3 TOTAL HEAD IN FEET 20 10 SK75 SK100 0 0 Capacity-U.S. G.P.M. 20 40
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 12 2113 - LOUVER BLINDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationPrecision Automatic Vacuum Control (PAVC+)
USER GUIDE UGE105-1216 www.conairgroup.com Precision Automatic Vacuum Control (PAVC+) Corporate Office: 724.584.5500 l Instant Access 24/7 (Parts and Service): 800.458.1960 l Parts and Service: 814.437.6861
More informationKnowledge is Power Belimo Energy Valve CHW DELTA T MITIGATION STUDY AHR Expo Innovation Award Winner in the Category of Building Automation
Knowledge is Power Belimo Energy Valve CHW DELTA T MITIGATION STUDY 2014 AHR Expo Innovation Award Winner in the Category of Building Automation The Belimo Energy Valve won the Technical Innovation of
More informationTGG, TBG, TEG, TUG, 3.9 TBS, Gene-Link series
Absorption Chillers TGG, TBG, TEG, TUG, 3.9 TBS, Gene-Link series Stable Chilled Water Outlet Temperature PID control is applied to maintain constant chilled water outlet temperature. When the cooling
More informationZehnder Carboline Radiant Heating and Cooling Ceiling Panels. Installation, Operation and Maintenance. Cooling Fresh Air Clean Air
Zehnder Carboline Radiant Heating and Cooling Ceiling Panels Installation, Operation and Maintenance Heating Cooling Fresh Air Clean Air ii General information 1 Safety considerations 1 Unpacking and preparation
More information2015 DW Module 1: General Overview VOLUME III Answer Key
2015 DW Module 1: General Overview VOLUME III Answer Key Unit 1 Unit 1 Exercise 1) Coliform bacteria make good indicator organisms because: a) They are always present when pathogens are present. b) The
More informationTABLE OF CONTENTS 1.0 SUMMARY SCOPE REGULATIONS AND POLICIES DEFINITIONS RESPONSIBILITIES... 2
The University of Iowa LOCKOUT / TAGOUT Control of Hazardous Energy Dates Revised: 10/20/06; 6/11/09 TABLE OF CONTENTS 1.0 SUMMARY.................................................... 1 2.0 SCOPE.......................................................
More informationSeries Sump and Sewage Systems
Series 000 Sump and Sewage Systems file no: 0. date: may 17, 13 supersedes: 0. date: march 29, 13 Series 000 Sump Series 0 & 2 Armstrong offers a complete range of high performance, easily maintained Column
More informationSt. Clair County Road Commission. For Turn Key Replacement of the Existing Chilled Water System Page 1 of 6
Page 1 of 6 NOTICE IS HEREBY GIVEN THAT SEALED PROPOSALS ARE SOUGHT AND REQUESTED FOR THE FOLLOWING: BID NAME: TURN KEY REPLACEMENT OF THE EXISTING CHILLED WATER SYSTEM BID OPENING: JANUARY 15, 2015 1:00
More informationQUALITY ASSURANCE SPECIFICATION WELDING HEAT TREATMENT PAGE 1 OF 6
QUALITY ASSURANCE SPECIFICATION REVISION: 0 DATE: 08/29/14 WELDING HEAT TREATMENT PAGE 1 OF 6 1.0 Purpose The purpose of this specification is to establish the minimum quality assurance requirements for
More informationSECTION MECHANICAL SPECIFICATION GRIT COLLECTION EQUIPMENT
SECTION 11322 MECHANICAL SPECIFICATION GRIT COLLECTION EQUIPMENT PART 1 GENERAL 1.01 SCOPE There shall be furnished ( ) Grit Separator Mechanism(s) suitable for installation in (a) concrete tank(s) -ft.
More informationHYDROMATIC W/D/V-A1 SUBMERSIBLE SUMP/EFFLUENT
PERFORMANCE DATA Wholesale Products Page: 6570-1 RPM: 1550 Discharge: 1 ½ Solids: ½ V-A1 W-A1 D-A1 Head, meters 8 4 Head, feet 30 20 10.3 HP 0 0 Capacity, US GPM 0 10 20 30 40 50 60 liters/second 0.0 1.0
More information1. Vertical reciprocating conveyor, Hydraulic straddle VRC.
PART 1: GENERAL 1.01 Section Includes: 1. Vertical reciprocating conveyor, Hydraulic straddle VRC. a. Machine, controller, platform, structural steel hoist frame. b. Wire mesh enclosure and gates. Related
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-26 29 23 (April 2006) -------------------------- Preparing Activity: NAVFAC Replacing without change UFGS-16261 (August 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationG2D Series Performance Data Discharge: 1-1/4 Solids: 1/4. Wholesale Products Page: JP10075SSD-1 Section: Performance Data Dated: January, 2011
100 Best Efficiency Point 90 80 70 TDH (ft) 60 50 40 30 20 10 The curve reflects maximum performance characteristics without exceeding full load (Nameplate) horsepower. Operation is recommended near the
More informationRetro-Commissioning for Existing Facilities
Retro-Commissioning for Existing Facilities Tom Meyer Director, Technical Programs National Environmental Balancing Bureau 8575 Grovemont Circle Gaithersburg, Maryland 20877 (301) 977-3698 www.nebb.org
More informationProperty Condition Assessment
Property Condition Assessment Pewaukee, WI 53072 Inspection Date: 1/6/15 Prepared For: Report Number: Prepared By: Shamrock Building Inspection Consultants LLC N29 W29951 Shel-Mar Dr. Pewaukee, WI 53072
More informationROUND LAKE AREA SCHOOLS DISTRICT 116: LIMITED COMMISSIONING GUIDELINES INTRODUCTION
INTRODUCTION Commissioning (Cx) is a quality assurance process that works to ensure the design intent of a building is fully realized. It requires a systematic approach to review, verify, and document
More informationTHE IMPORTANCE OF EQUIPMENT ACCESSIBILITY IN BUILDINGS
THE IMPORTANCE OF EQUIPMENT ACCESSIBILITY IN BUILDINGS Throughout the commissioning process, we often find issues with accessibility to equipment, whether it be a heat pump above a ceiling grid or an air
More informationACBC Floor Mounted Active Beam
Floor Mounted Active Beam The Price Floor Mounted Active Beam,, is designed for occupant comfort. It provides high cooling and heating capacities while simultaneously supplying ventilation air from a DOAS
More informationOil and Gas Contractor QA/QC Plan Sample Selected pages (not a complete plan)
Oil and Gas Contractor QA/QC Plan Sample Selected pages (not a complete plan) Part 1: Project Specific Quality Plan Part 2: Quality Manual Part 3: Submittal Forms Part 4: Inspection Checklist Forms Contact:
More informationThis guide can be used to prepare a specification for incorporating free standing jib cranes into a competitively bid construction project.
SECTION 14651 FREE STANDING JIB CRANE ***** Gorbel, Inc. manufacturers a broad range of material handling cranes including monorail, bridge, gantry, and jib cranes. Numerous work station and industrial
More informationSystems Commissioning Table of Contents
Systems Commissioning Table of Contents C NC NA I. General II. Commissioning III. Mechanical Systems A. Testing, Adjusting, and Balancing B. Piping IV. Electrical Systems A. Load Balancing B. Electrical
More informationBackflow Irrigation Control Station
At A Glance Backflow Irrigation Control Station BIC-1000 Watts.com Table of Contents Purpose 3 The Existing & Current Irrigation Design 3 The Backflow Irrigation Control Station 4 Backflow Irrigation Control
More informationMODEL SJ10. Installation Manual. SumpJet TM - Water Powered Backup System C IMPORTANT: MODEL SERIAL
Installation Manual 5824000C SumpJet TM - Water Powered Backup System MODEL SJ10 7000 Apple Tree Avenue, Bergen, NY 14416 Phone: (800) 543-2550 liberty@libertypumps.com website: www.libertypumps.com IMPORTANT:
More informationFOUR FOLD DOORS-WITH SINGLE OVERHEAD MTD OPERATOR
FOUR FOLD DOORS-WITH SINGLE OVERHEAD MTD OPERATOR Section 083713- Four Fold Doors- With Single Overhead Mounted Operator Part 1-General 1.1 Related Document: A. Drawing and general provisions of contract,
More informationSample Written Program. for. Control of Hazardous Energy (Lockout/Tagout) OSHCON
Sample Written Program for Control of Hazardous Energy (Lockout/Tagout) provided as a public service by OSHCON Occupational Safety and Health Consultation Program Publication No. HS02-011B(3-03) Revised
More informationSPECIFICATIONS - DETAILED PROVISIONS Section Horizontal Centrifugal Water Pumps C O N T E N T S
SPECIFICATIONS - DETAILED PROVISIONS Section 11931 - Horizontal Centrifugal Water Pumps C O N T E N T S PART 1 - GENERAL... 1 1.01 PUMP - GENERAL... 1 1.02 CERTIFIED PUMP CURVES... 1 1.03 NPSH REQUIREMENTS...
More informationTYP. SINGLE PLY ROOFING ROOF SHEETING BROAN VENT CAP #10 x 1" GASKETED SMS TYP. 4 SIDES 8" FRAMED CURB HVAC SYSTEMS "BASIS OF DESIGN" ROOF INSULATION R-19 WALL INSULATION R-13 LIGHTING EFFIECNCY PER STANDARDS
More informationF Series Flow Meter F300. User Manual
F Series Flow Meter F300 User Manual Contents 1. F300 Series Flow Meter ------------------------------------- 2 1.1 F300 Series Flow Meter Structure Drawing ---------------------------- 2 1.2 Introduction
More informationREQUEST FOR PROPOSAL. Commissioning Services College of Pharmacy Building Construct New Facility University of Iowa #
REQUEST FOR PROPOSAL Commissioning Services College of Pharmacy Building Construct New Facility University of Iowa # Addendum #1 Issued Wednesday, February 10, 2016 Changes: Item #01: Item #02: Section
More informationWATER-COOLED HELICAL ROTARY CHILLER
WATER-COOLED HELICAL ROTARY CHILLER 1.0 GENERAL REQUIREMENTS 1.1 Application. This technical specification applies to equipment and materials furnished and installation work performed by the Contractor.
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-23 71 19 (January 2008) Change 1-08/15 ---------------------------- Preparing Activity: USACE Superseding UFGS-23 71 19 (July 2007) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationNUCLEAR POWER CORPORATION OF INDIA LTD TECHNICAL SPECIFICATION ON SUBMERSIBLE PUMPS PAGE NO: 1 OF 4 REV NO : 0 DATA SHEET A
TECHNICAL SPECIFICATION ON SUBMERSIBLE PUMPS PAGE NO: 1 OF 4 DATA SHEET A ANNEXURE - A Sr. Item Description Sr. Item Description A. GENERAL DATA B. PUMP DUTY PARAMETERS 1. System Name 1. Rated capacity,
More informationSECTION HEAT TRACING FOR PLUMBING PIPING
SECTION 22 05 33 HEAT TRACING FOR PLUMBING PIPING PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between //----// if not applicable to project. Also delete any other item or paragraph not
More informationProduct Booklet Keen K-1000CS FCAW Wire Coil and TIG Filler Wire Storage Oven Floor Positioned
Product Booklet Keen K-1000CS FCAW Wire Coil and TIG Filler Wire Storage Oven Floor Positioned Purpose: To prevent moisture contamination in spooled welding wire and TIG filler rods Capacity: 8 / 10 lb
More informationSECTION DENTAL VACUUM AND EVACUATION EQUIPMENT
SECTION 22 62 19.74 DENTAL VACUUM AND EVACUATION EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTE: Delete between //----// if not applicable to project. Also delete any other item or paragraph
More informationFundamental Overview of an NGL Meter Station Design Tony Lockard Enterprise Products 1100 Louisiana Street, Houston, TX
Fundamental Overview of an NGL Meter Station Design Tony Lockard Enterprise Products 1100 Louisiana Street, Houston, TX 77002-5227 Overview In this paper I will attempt to give a fundamental overview of
More informationAgenda. Understanding the three basic piping systems. Low DeltaT Syndrome causes, effects, and solutions Design & Control Considerations (VPF)
Roy Hubbard Agenda Understanding the three basic piping systems Design and Off-design operation Advantages and Disadvantages Low DeltaT Syndrome causes, effects, and solutions Design & Control Considerations
More informationRolairtrol Air Separator For Hot and Chilled Water Systems
REMOVES ENTRAINED AIR To protect the system against damage To eliminate system noise TANGENTIAL FLOW PATTERN Increases air separation efficiency Allows use of smaller sizes than required with straight
More informationAnchor Load Cells Installation - considerations
Anchor Load Cells Installation - considerations This article outlines the main points to check during installation of load cells to control tensions while installing and service life, applied on bar and
More informationLARGE STORAGE TANK PROJECT
INTRODUCTION The Fairbanks Large Storage Tank is part of the Interior Energy Project (IEP) designed to expand natural gas distribution in Fairbanks and Interior Alaska. A tank with a capacity of 0.44 Bcf
More informationSanitary Sewer Extensions, Lift Stations, and Force Mains Engineering Report Form. I. General Information. 1. Name of Facility:
Oklahoma Department of Environmental Quality Water Quality Division Phone: 405-702-8100 Construction Permitting Section 707 N. Robinson, OKC, OK 73102-6010 P.O. Box 1677, OKC, OK 73101-1677 Sanitary Sewer
More informationDRIP EMITTER SYSTEM STUDY GUIDE
DRIP EMITTER SYSTEM STUDY GUIDE Minimum Criteria for Pressurized Subsurface Absorption Fields Utilizing Emitters. Subsurface systems utilizing emitters may be used in lieu of conventional or other alternative
More informationVariable Speed Waste Water Pumping
Variable Speed Waste Water Pumping Challenges & Opportunities Kristel Zaman Marketing & Business Development Manager Flygt Large Systems Xylem North America Background VFDs have become common during the
More informationHYDROMATIC SKV50 SEWAGE EJECTOR PERFORMANCE DATA SKV50. Wholesale Products Page: RPM: 1650 Discharge: 2 Solids: 2.
PERFORMANCE DATA Wholesale Products Page: 6280-1 RPM: 1650 Discharge: 2 Solids: 2 12 40 9 30 HEAD-METERS 6 HEAD-FEET 20 3 10 0 0 Capacity - U.S. G.P.M. 0 30 60 90 120 150 180 Liters/Second 0 2 4 6 8 10
More informationAJONES AIRWAYS, LLC CLEVELAND REGIONAL JETPORT Sliding Hangar Doors SBA SECTION SLIDING HANGAR DOORS
CLEVELAND REGIONAL JETPORT 08 3430-1 PART 1 - GENERAL 1.1 SUMMARY: SECTION 08 3430 SLIDING HANGAR DOORS A. Work of this section includes door leaves 19'-0" + wide by 28'-0" high, floating group door system,
More informationChemigation. in Georgia
Chemigation in Georgia Table of Contents Chemigation Terminology...3 The Benefits of Chemigation...3 General Principles of Chemigation Safety Considerations...3 Injection Methods...4 Determining Injection
More informationEssex County College - West Essex Campus Addition And Renovations Dib # / SECTION DOMESTIC WATER PIPING SPECIALTIES
Essex County College - West Essex Campus Addition And Renovations Dib # 54292 / 11-14 SECTION 221119 - DOMESTIC WATER PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions
More informationSECTION MOTORS AND PUMPS FOR PLUMBING SYSTEMS
PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including the General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related
More informationINCREASING LARGE RESIDENTIAL/LIGHT COMMERCIAL GEOTHERMAL SYSTEM EFFICIENCIES
INCREASING LARGE RESIDENTIAL/LIGHT COMMERCIAL GEOTHERMAL SYSTEM EFFICIENCIES Jeff Hammond Director of Business Development & Marke:ng rev. October 2014 Topics New Variable Speed Pumping ApplicaKons System
More information