SECTION MOTORS AND PUMPS FOR PLUMBING SYSTEMS

Size: px
Start display at page:

Download "SECTION MOTORS AND PUMPS FOR PLUMBING SYSTEMS"

Transcription

1 PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including the General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections: The following Sections contain requirements that relate to this Section: 1. Section "Motors" for pump motors. 2. Section "Domestic Water Piping" for piping not specified in this Section. 3. Division 16 Sections for power-supply wiring, field-installed disconnects, required electrical devices, and motor controllers. 1.2 SUMMARY A. This Section includes the following types of pumps for permanent installation in plumbing systems: 1. Sewage pumps. 2. Sump pumps. 3. Automatic, packaged pump units. 1.3 DEFINITIONS A. Automatic, Packaged Pump Units: Type suitable for automatically lifting waste water or sewage to a point of discharge. Unit is complete with pump, controls, valves, and basin. B. Permanent-Installation Pumps: Type suitable for fixed installation and connection to piping systems. C. Sewage Pumps: Type suitable for lifting sewage containing solids to point of discharge. Pumps are normally without strainer and have nonclog type impeller. Pumps include cutter- or grinder-type impeller when specified. This type includes wet-pit-mounted vertical sewage pumps and submersible sewage pumps. D. Submersible Pumps: Type that operates with motor submerged in water. E. Sump Pumps: Type suitable for lifting waste water not containing solids from a sump or wet location to a point of discharge. Pumps normally have strainer on inlet. This type includes wet-pit-mounted, vertical sump pumps and submersible sump pumps. F. Wet-Pit-Mounted, Vertical Pumps: Type that operates with pump volute in water and motor above basin. 1.4 PUMP PERFORMANCE REQUIREMENTS A. Pump Pressure Ratings: At least equal to maximum pump-operating pressure. 1.5 SUBMITTALS Page 1 of 16

2 A. General: Submit the following according to the Conditions of the Contract and Specification Sections. B. Product data including certified performance curves, weights (shipping, installed, and operating), furnished specialties, and accessories. Include startup instructions. C. Shop drawings showing layout and connections for pumps. Include setting drawings with templates, directions for installation of foundation and anchor bolts, and other anchorages. D. Wiring diagrams detailing wiring for power, signal, and control systems differentiating between manufacturer-installed wiring and field-installed wiring. E. Product certificates signed by pump manufacturers certifying accuracies under specified operating conditions and compliance with specified requirements. F. Maintenance data for each type and size pump specified to include in the "Operating and Maintenance Manual" specified in Section "Project Closeout." 1.6 QUALITY CONTROL A. Regulatory Requirements: Comply with provisions of the following: 1. ASME B31.9 "Building Services Piping" for piping materials and installation. 2. H.I. "Hydraulic Institute Standards for Centrifugal, Rotary and Reciprocating Pumps" for pump design, manufacture, and installation. 3. UL 778 "Standard for Motor Operated Water Pumps" for construction requirements. Include UL listing and labeling. 4. NEMA MG 1 "Standard for Motors and Generators" for electric motors. Include NEMA listing and labeling. 5. NFPA 70 "National Electrical Code" for electrical components and installation. B. Single-Source Responsibility: Obtain same type of pumps from a single manufacturer. C. Single-Source Responsibility: Obtain same type of pumps from a single manufacturer with pumps, components, and accessories from a single source. Include responsibility and accountability to answer and resolve problems regarding compatibility, installation, performance, and acceptance of pumps. D. Design Criteria: Drawings indicate sizes, profiles, connections, and dimensional requirements of pumps and are based on specific manufacturer types and models indicated. Pumps having equal performance characteristics by other manufacturers may be considered provided that deviations in dimensions and profiles do not change the design concept or intended performance as judged by the Architect. The burden of proof for equality of pumps is on the proposer. 1.7 DELIVERY, STORAGE, AND HANDLING A. Store pumps in a clean, dry location. B. Retain shipping flange protective covers and protective coatings during storage. Page 2 of 16

3 C. Protect bearings and couplings against damage from sand, grit, or other foreign matter. D. Extended Storage Greater Than 5 Days: Dry internal parts with hot air or a vacuumproducing device. After drying, coat internal parts with light oil, kerosene, or antifreeze. Dismantle bearings and couplings, dry and coat with an acid-free heavy oil, and tag and store in a dry location. E. Comply with pump manufacturer's rigging instructions for handling. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated in the Work include, but are not limited to, the following: B. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Wet-Pit-Mounted, Vertical Sewage Pumps: a. Aurora Pump, General Signal. b. Paco Pumps, Inc. c. Vertiflo Pump Div., Fluidpak, Inc. d. Weinman by AMW Industries. 2. Submersible Sewage Pumps: a. Aurora Pump, General Signal. b. Aurora/Hydromatic Pumps, Inc., General Signal. c. Paco Pumps, Inc. d. Weinman by AMW Industries. 3. Sewage Pump Reverse-Flow Attachment: a. Paco Pumps, Inc. b. Peerless Pump. c. Weil Pump Co. 4. Submersible, Cutter and Grinder Sewage Pumps: a. Aurora/Hydromatic Pumps, Inc., General Signal. b. Sta-Rite Industries, Inc. c. Weil Pump Co. 5. Wet-Pit-Mounted, Vertical Sump Pumps: a. Aurora Pump, General Signal. b. Paco Pumps, Inc. c. Peerless Pump Co., Sterling Fluid Products, Inc. d. Vertiflo Pump Div., Fluidpak, Inc. e. Weil Pump Co. 6. Submersible Sump Pumps: a. Aurora Pumps, General Signal. b. Grundfos Pumps Corp. c. Paco Pumps, Inc. d. Weil Pump Co. 7. Pump Basins: Page 3 of 16

4 2.2 PUMPS, GENERAL a. Federal Pump Corp. b. Peerless Pump Co., Sterling Fluid Products, Inc. c. Weil Pump Co. A. Plumbing Pumps: Factory assembled and tested, and of construction required for permanent installation. B. Motors: NEMA MG 1; single, multiple, or variable speed with type of enclosure and electrical characteristics indicated. Include built-in thermal-overload protection and grease-lubricated ball bearings. Motors are non-overloading within full range of pump performance curves. C. Finish: Manufacturer's standard paint applied to factory-assembled and -tested plumbing pump unit prior to shipping. D. Manufacturer's Preparation for Shipping: Clean flanges and exposed machined metal surfaces and treat with anticorrosion compound after assembly and testing. Protect flanges, pipe openings, and nozzles with wooden flange covers or with screwed-in plugs. 2.3 SEWAGE PUMPS A. General Description: Centrifugal, end-suction, single-stage sewage pump, with motor and operating controls. B. Impeller: ASTM A 48, Class No. 25 A or higher cast iron, statically and dynamically balanced, open or semi-open nonclog design except where otherwise indicated, overhung, single suction, keyed to shaft, and secured by locking capscrew. C. Impeller: ASTM B 584 cast bronze, statically and dynamically balanced, open or semiopen nonclog design except where otherwise indicated, overhung, single suction, keyed to shaft, and secured by locking capscrew. D. Impeller: ASTM A 532 (ASTM A 532M) abrasion-resistant cast iron, statically and dynamically balanced, open or semi-open nonclog design except where otherwise indicated, overhung, single suction, keyed to shaft, and secured by locking capscrew. E. Wet-Pit-Mounted, Vertical Sewage Pumps: Vertical, separately coupled, suspended type, with basin cover suitable for supporting pumps, motors, and controls. Include holes in cover as required. 1. Pump Arrangement: Duplex. 2. Casing: Cast iron, with open inlet. 3. Pump Shaft and Sleeve Bearings: Stainless-steel shaft with bronze sleeve bearings. Include oil-lubricated, intermediate sleeve bearings at 48 inches (1200 mm) maximum intervals where basin depth is greater than 48 inches (1200 mm), and grease-lubricated, ball-type thrust bearings. 4. Pump and Motor Shaft Coupling: Flexible, capable of absorbing torsional vibration and shaft misalignment. Page 4 of 16

5 5. Seals: Stuffing box, with a minimum of 4 graphite-impregnated braided-yarn rings, bronze lantern ring between center 2 graphite rings, and bronze packing gland. 6. Seals: Mechanical seals, with carbon-steel rotating ring, stainless-steel spring, ceramic seat, and flexible bellows and gasket. 7. Motor: Vertically mounted on cast-iron pedestal. 8. Pump Discharge Piping: Manufacturer's standard galvanized-steel or bronze pipe, except where specific material is indicated. 9. Controls: NEMA 250, Type 1 pedestal-mounted float switch, complete with floats, float rods, and rod buttons. Include automatic alternator to alternate operation of pump units on successive cycles and operate both units when 1 pump cannot handle the load. 10. Float Guide Pipe: Include guide pipe or other restraint for floats and rods in basins of depth greater than 60 inches (1500 mm) and where indicated. 11. High-Water Alarm: Cover-mounted compression-probe alarm with electric bell. Operation is 120 volts a.c., with transformer and contacts for remote alarm bell, except where battery operation is indicated. F. Submersible Sewage Pumps: Submersible direct-connected type, with a guide rail system and basin cover suitable for supporting controls when cover-mounted controls are specified. Include holes with seals in cover as required. 1. Pump Arrangement: Duplex. 2. Casing: Cast iron, with cast-iron legs that elevate pump to permit flow into impeller. Include discharge companion flange arranged to connect to guide-rail system discharge elbow fitting. 3. Pump and Motor Shaft: Stainless steel, with factory-sealed, grease-lubricated ball bearings. 4. Seals: Double mechanical seals. 5. Motor: Hermetically sealed capacitor-start type, with built-in overload protection. Include a lifting eye or lug, and a 3-conductor waterproof power cable of length required, but not less than 20 feet (6 m), with a grounding plug and cable-sealing assembly for connection at pump. 6. Moisture-Sensing Probe: Include an internal moisture sensor, a waterproof cable of length required but not less than 20 feet (6 m), with a cable-sealing assembly for connection at pump, and a moisture alarm. 7. Guide Rail System: Include the following: a. Guide Rails: 2 galvanized-steel or other corrosion-resisting vertical pipes or structural members, attached to base plate and basin side wall or cover. b. Base Plate: Corrosion-resisting metal plate, attached to basin floor, supporting guide rails and stationary elbow. c. Pump Yokes: Pump-motor- or casing-mounted yokes or other attachments for aligning pump during connection of flanges. d. Movable Elbow: Pump discharge elbow fitting with flange, seal, and positioning device. e. Stationary Elbow: Fixed discharge elbow fitting with flange that mates to movable-elbow flange and support attached to base plate. f. Lifting Cable: Stainless-steel cable attached to pump and basin cover at manhole. Page 5 of 16

6 8. Pump Discharge Piping: Factory or field fabricated, ASTM A 53, Schedule 40, galvanized-steel pipe, bronze pipe, or copper tube, except where specific material is indicated. 9. Controls: Wall mounted, except where pedestal mounting is indicated, in a NEMA 250, Type 1 enclosure. Controls consist of 3 micro-pressure switches in NEMA 250, Type 6 enclosures; mounting rod; and electric cables. Include an automatic alternator to alternate operation of pump units on successive cycles and operate both units when 1 pump cannot handle the load. 10. Controls: Wall mounted, except where pedestal mounting is indicated, in a NEMA 250, Type 1 enclosure. Controls consist of 3 mercury float switches in NEMA 250, Type 6 enclosures; mounting rod; and electric cables. Include an automatic alternator to alternate operation of pump units on successive cycles and operate both units when 1 pump cannot handle the load. 11. Controls: Pedestal-mounted float switch in a NEMA 250, Type 1 enclosure, complete with floats, float rods, and rod buttons. Include automatic alternator to alternate operation of pump units on successive cycles and operate both units when 1 pump cannot handle the load. 12. Float Guide Pipe: Include guide pipe or other restraint for floats and rods in basins of depth greater than 60 inches (1500 mm) and where indicated. 13. High-Water Alarm: Cover-mounted, compression-probe alarm, with electric bell. Operation is 120 volts a.c., with transformer and contacts for remote alarm bell, except where battery operation is indicated. 14. High-Water Alarm: Rod-mounted, NEMA 250, Type 6 micro-pressure-switch alarm matching the control, with electric bell. Operation is 120 volts a.c., with transformer and contacts for remote alarm bell, except where battery operation is indicated. 15. High-Water Alarm: Rod-mounted, NEMA 250, Type 6 mercury float switch alarm matching control, with electric bell. Operation is 120 volts a.c., with transformer and contacts for remote alarm bell, except where battery operation is indicated. G. Submersible Sewage Pumps: Submersible direct-connected type, with basin cover suitable for supporting controls when cover-mounted controls are specified. Include holes in cover as required. 1. Pump Arrangement: Duplex. 2. Casing: Cast iron, with cast-iron legs that elevate pump to permit flow into impeller. Include discharge companion flange arranged for vertical discharge and suitable for plain-end pipe connection. 3. Pump and Motor Shaft: Stainless steel, with factory-sealed, grease-lubricated ball bearings. 4. Seals: Double mechanical seals. 5. Motor: Hermetically sealed capacitor-start type, with built-in overload protection. Include a 3-conductor waterproof power cable of length required, but not less than 20 feet (6 m), with a grounding plug and cable-sealing assembly for connection at pump. 6. Moisture-Sensing Probe: Include an internal moisture sensor, a waterproof cable of length required, but not less than 20 feet (6 m), with a cable-sealing assembly for connection at pump, and a moisture alarm. 7. Pump Discharge Piping: Factory or field fabricated, ASTM A 53, Schedule 40, galvanized-steel pipe, bronze pipe, or copper tube, except where specific material is indicated. Page 6 of 16

7 8. Controls: Wall mounted, except where pedestal mounting is indicated, in a NEMA 250, Type 1 enclosure. Controls consist of 3 micro-pressure switches in NEMA 250, Type 6 enclosures; mounting rod; and electric cables. Include an automatic alternator to alternate operation of pump units on successive cycles and operate both units when 1 pump cannot handle the load. 9. Controls: Wall mounted, except where pedestal mounting is indicated, in a NEMA 250, Type 1 enclosure. Controls consist of 3 mercury float switches in NEMA 250, Type 6 enclosures; mounting rod; and electric cables. Include an automatic alternator to alternate operation of pump units on successive cycles and operate both units when 1 pump cannot handle the load. 10. Controls: Pedestal-mounted float switch in a NEMA 250, Type 1 enclosure, complete with floats, float rods, and rod buttons. Include automatic alternator to alternate operation of pump units on successive cycles and operate both units when 1 pump cannot handle the load. 11. Float Guide Pipe: Include guide pipe or other restraint for floats and rods in basins of depth greater than 60 inches (1500 mm) and where indicated. 12. High-Water Alarm: Cover-mounted, compression-probe alarm, with electric bell. Operation is 120 volts a.c., with transformer and contacts for remote alarm bell, except where battery operation is indicated. 13. High-Water Alarm: Rod-mounted, micro-pressure-switch alarm matching the control in a NEMA 250, Type 6 enclosure, with electric bell. Operation is 120 volts a.c., with transformer and contacts for remote alarm bell, except where battery operation is indicated. 14. High-Water Alarm: Rod-mounted, mercury-float-switch alarm matching the control in a NEMA 250, Type 6 enclosure, with electric bell. Operation is 120 volts a.c., with transformer and contacts for remote alarm bell, except where battery operation is indicated. H. Submersible, Cutter Sewage Pumps: Submersible direct-connected type, with quickdisconnect system and basin cover suitable for supporting controls when cover-mounted controls are specified. Include holes in cover as required. 1. Pump Arrangement: Duplex. 2. Casing: Cast iron, with cast-iron legs that elevate pump to permit flow into impeller. Include discharge companion flange arranged for connection to guiderail system-discharge elbow fitting. 3. Impeller: Bronze or stainless-steel impeller, with stainless-steel cutter assembly. 4. Pump and Motor Shaft: Stainless steel, with factory-sealed, grease-lubricated ball bearings. 5. Seals: Double mechanical seals. 6. Motor: Hermetically sealed capacitor-start type, with built-in overload protection. Include a 3-conductor waterproof power cable of length required, but not less than 20 feet (6 m), with a grounding plug and cable-sealing assembly for connection at pump. 7. Moisture-Sensing Probe: Include an internal moisture sensor, a waterproof cable of length required but not less than 15 feet (4.5 m), with a cable-sealing assembly for connection at pump, and a moisture alarm. 8. Quick-Disconnect System: Include the following: a. Guide Rails: 2 galvanized-steel or other corrosion-resisting vertical pipes or structural members attached to base plate and basin side wall or cover. Page 7 of 16

8 b. Base Plate: Corrosion-resisting metal plate attached to basin floor, supporting guide rails and stationary elbow. c. Pump Yokes: Pump motor- or casing-mounted yokes or other attachments for aligning pump during connection of flanges. d. Movable Elbow: Pump discharge elbow fitting with flange, seal, and positioning device. e. Stationary Elbow: Fixed discharge elbow fitting with flange that mates to movable-elbow flange and support attached to base plate. f. Lifting Cable: Stainless-steel cable attached to pump and basin cover at manhole. 9. Pump Discharge Piping: Factory or field fabricated, ASTM A 53, Schedule 40, galvanized-steel pipe, bronze pipe, or copper tube, except where specific material is indicated. 10. Controls: Wall mounted, except where pedestal mounting is indicated, in a NEMA 250, Type 1 enclosure. Controls consist of 3 mercury float switches in NEMA 250, Type 6 enclosures; mounting rod; and electric cables. Include an automatic alternator to alternate operation of pump units on successive cycles and operate both units when 1 pump cannot handle the load. 11. High-Water Alarm: Rod-mounted, mercury-float-switch alarm matching the control in a NEMA 250, Type 6 enclosure, with electric bell. Operation is 120 volts a.c., with transformer and contacts for remote alarm bell, except where battery operation is indicated. I. Submersible, Grinder Sewage Pumps: Submersible direct-connected type, with quickdisconnect system and basin cover suitable for supporting controls when cover-mounted controls are specified. Include holes in cover as required. 1. Pump Arrangement: Duplex. 2. Impeller: Bronze or stainless-steel impeller, with stainless-steel grinder assembly. 3. Pump and Motor Shaft: Stainless steel, with factory-sealed, grease-lubricated ball bearings. 4. Seals: Double mechanical seals. 5. Motor: Hermetically sealed capacitor-start type, with built-in overload protection. Include a 3-conductor waterproof power cable of length required, but not less than 20 feet (6 m), with a grounding plug and cable-sealing assembly for connection at pump. 6. Moisture-Sensing Probe: Include an internal moisture sensor, a waterproof cable of length required, but not less than 20 feet (6 m), with a cable-sealing assembly for connection at pump, and a moisture alarm. 7. Quick-Disconnect System: Include the following: a. Guide Rails: 2 galvanized-steel or other corrosion-resisting vertical pipes or structural members attached to base plate and basin side wall or cover. b. Base Plate: Corrosion-resisting metal plate attached to basin floor, supporting guide rails and stationary elbow. c. Pump Yokes: Pump motor- or casing-mounted yokes or other attachments for aligning pump during connection of flanges. d. Movable Elbow: Pump discharge elbow fitting with flange, seal, and positioning device. Page 8 of 16

9 e. Stationary Elbow: Fixed discharge elbow fitting with flange that mates to movable-elbow flange and support attached to base plate. f. Lifting Cable: Stainless-steel cable attached to pump and basin cover at manhole. 8. Pump Discharge Piping: Factory or field fabricated, ASTM A 53, Schedule 40, galvanized-steel pipe, bronze pipe, or copper tube, except where specific material is indicated. 9. Controls: Wall mounted, except where pedestal mounting is indicated, in a NEMA 250, Type 1 enclosures. Controls consist of 3 mercury float switches in NEMA 250, Type 6 enclosures; mounting rod; and electric cables. Include an automatic alternator to alternate operation of pump units on successive cycles and operate both units when 1 pump cannot handle the load. 10. High-Water Alarm: Rod-mounted, mercury-float-switch alarm matching the control in a NEMA 250, Type 6 enclosure, with electric bell. Operation is 120 volts a.c., with transformer and contacts for remote alarm bell, except where battery operation is indicated. 2.4 SEWAGE PUMP REVERSE-FLOW ATTACHMENT A. Description: Factory-fabricated reverse-flow pump attachment for factory or field installation in sewage pump basin. B. Inlet Fitting: 1 combination inlet-overflow strainer fitting. C. Valves: 2 shutoff valves and 2 check valves. D. Strainers: 2 strainer housings with reverse-flow, self-flushing strainers. E. Pipe and Fittings: Size and configuration required to connect to sewage pumps and piping. 2.5 SUMP PUMPS A. General Description: Centrifugal, end-suction, single-stage sump pump, with inlet strainer, motor, and operating controls. B. Impeller: ASTM B 584 cast bronze, statically and dynamically balanced, open or semiopen, overhung, single suction, keyed to shaft, and secured by locking capscrew. C. Wet-Pit-Mounted, Vertical Sump Pumps: Vertical, separately coupled, suspended type, with basin cover suitable for supporting pumps, motors, and controls. Include holes in cover as required. 1. Pump Arrangement: Duplex. 2. Casing: Cast iron, with integral cast-iron inlet strainer. 3. Pump Shaft and Sleeve Bearings: Stainless-steel shaft with bronze sleeve bearings. Include oil-lubricated, intermediate sleeve bearings at 48 inches (1200 mm) maximum intervals where basin depth is greater than 48 inches (1200 mm), and grease-lubricated, ball-type thrust bearings. 4. Pump and Motor Shaft Coupling: Flexible, capable of absorbing torsional vibration and shaft misalignment. Page 9 of 16

10 5. Seals: Stuffing box; with minimum of 4 graphite-impregnated, braided-yarn rings; bronze lantern ring between center 2 graphite rings; and bronze packing gland. 6. Seals: Mechanical seals; with carbon-steel rotating ring; stainless-steel spring; ceramic seat; and flexible bellows and gasket. 7. Motor: Vertically mounted on cast-iron pedestal. 8. Pump Discharge Piping: Manufacturer's standard galvanized-steel or bronze pipe, except where specific material is indicated. 9. Controls: Pedestal-mounted float switch in a NEMA 250, Type 1 enclosure, complete with floats, float rods, and rod buttons. Include automatic alternator to alternate operation of pump units on successive cycles and operate both units when 1 pump cannot handle the load. 10. Float Guide Pipe: Include guide pipe or other restraint for floats and rods in basins of depth greater than 60 inches (1500 mm), and where indicated. 11. High Water Alarm: Cover-mounted-compression-probe alarm with electric bell. Operation is 120 volts a.c., with transformer and contacts for remote alarm bell, except where battery operation is indicated. D. Submersible Sump Pumps: Submersible direct-connected type, with basin cover suitable for supporting controls when cover-mounted controls are specified. Include holes in cover as required. 1. Pump Arrangement: Duplex. 2. Casing: Cast iron with integral, cast-iron inlet strainer and legs that elevate pump to permit flow into impeller. Include discharge companion flange arranged for vertical discharge and suitable for plain-end pipe connection. 3. Pump and Motor Shaft: Stainless steel, with factory-sealed, grease-lubricated ball bearings. 4. Seals: Double mechanical seals. 5. Motor: Hermetically sealed, capacitor-start type, with built-in overload protection. Include a 3-conductor waterproof power cable of length required, but not less than 20 feet (6 m), with a grounding plug and cable-sealing assembly for connection at pump. 6. Moisture-Sensing Probe: Include an internal moisture sensor, a waterproof cable of length required, but not less than 20 feet (6 m), with a cable-sealing assembly for connection at pump, and a moisture alarm. 7. Pump Discharge Piping: Factory or field fabricated, ASTM A 53, Schedule 40, galvanized-steel pipe, bronze pipe, or copper tube, except where specific material is indicated. 8. Controls: Wall mounted, except where pedestal mounting is indicated, in a NEMA 250, Type 1 enclosure. Controls consist of 3 micro-pressure switches in NEMA 250, Type 6 enclosures; mounting rod; and electric cables. Include an automatic alternator to alternate operation of pump units on successive cycles and operate both units when 1 pump cannot handle the load. 9. Controls: Wall mounted, except where pedestal mounting is indicated, in a NEMA 250, Type 1 enclosure. Controls consist of 3 mercury float switches in NEMA 250, Type 6 enclosures; mounting rod; and electric cables. Include an automatic alternator to alternate operation of pump units on successive cycles and operate both units when 1 pump cannot handle the load. 10. Controls: Pedestal-mounted float switch in a NEMA 250, Type 1 enclosure, complete with floats, float rods, and rod buttons. Include automatic alternator to Page 10 of 16

11 alternate operation of pump units on successive cycles and operate both units when 1 pump cannot handle the load. 11. Float Guide Pipe: Include guide pipe or other restraint for floats and rods in basins of depth greater than 60 inches (1500 mm) and where indicated. 12. High-Water Alarm: Cover-mounted, compression-probe alarm, with electric bell. Operation is 120 volts a.c., with transformer and contacts for remote alarm bell, except where battery operation is indicated. 13. High-Water Alarm: Rod-mounted, micro-pressure-switch alarm matching the control in a NEMA 250, Type 6 enclosure, with electric bell. Operation is 120 volts a.c., with transformer and contacts for remote alarm bell, except where battery operation is indicated. 14. High-Water Alarm: Rod-mounted, mercury-float-switch alarm matching the control in a NEMA 250, Type 6 enclosure, with electric bell. Operation is 120 volts a.c., with transformer and contacts for remote alarm bell, except where battery operation is indicated. E. Submersible, Waste-Water Sump Pumps: Simplex, submersible, direct-connected type, with basin cover with holes with gaskets in cover as required. 1. Casing: Cast iron with integral, cast-iron inlet strainer. Include discharge companion flange arranged for vertical discharge and suitable for plain-end pipe connection. 2. Pump and Motor Shaft: Stainless steel, with factory-sealed, grease-lubricated ball bearings. 3. Seal: Mechanical seal. 4. Motor: Hermetically sealed capacitor-start type, with built-in overload protection. Include a 3-conductor waterproof power cable of length required, but not less than 10 feet (3 m), with a grounding plug and cable-sealing assembly for connection at pump. 5. Pump Discharge Piping: Factory or field fabricated, ASTM A 53, Schedule 40, galvanized-steel pipe, bronze pipe, or copper tube, except where specific material is indicated. 6. Controls: 120 volts a.c., NEMA 250, Type 6 micro-pressure or mercury float switches, mounted on discharge piping. 2.6 PUMP BASINS A. General: Basins are factory fabricated from metal, fiberglass, or other plastic as indicated. Include metal covers except where plastic covers or basins without covers are indicated. B. Sizes: Dimensions as indicated. C. Inlet and Outlets: Number, sizes, types, and locations indicated. D. Reinforcement: Include mounting plates at locations where pumps, fittings, rail systems, and accessories are installed. E. Covers for basins include openings with gaskets and seals for access, pumps, pump shafts, control rods, discharge piping, vent connections, and power cables where indicated. Page 11 of 16

12 1. Covers for sewage pump basins include gaskets, bushings, and seals that are required to make basin gas-tight when installed. 2. Covers for sump pump basins include gaskets, bushings, and seals that are required to make basin gastight when installed. 3. Covers for Installation in Foot Traffic Areas: Include steel or cast-iron reinforcing capable of supporting foot traffic. F. Sump Pump Basins: Fabricated from fiber glass. G. Sump Pump Basins: Fabricated from polyethylene. H. Sump Pump Basins: Fabricated from cast iron. I. Sump Pump Basin Covers: Fiber glass. J. Sump Pump Basin Covers: Polyethylene. K. Sump Pump Basin Covers: Steel, with bitumastic coating. L. Sump Pump Basin Covers: Cast iron. M. Sewage Pump Basins: Fabricated from fiber glass. N. Sewage Pump Basins: Fabricated from cast iron. O. Sewage Pump Basin Covers: Steel, with bitumastic coating. P. Sewage Pump Basin Covers: Cast iron. Q. Basin Anchor Flange: Flange cast in or attached to basin, in location and of size required to anchor basin in concrete slab. Include flange of same material as or compatible with basin. 2.7 PUMP PITS AND SUMPS A. General: Pits and sumps are constructed of cast-in-place concrete. Include steel curb frames and covers except where no cover is indicated. B. Sizes: Dimensions as indicated. C. Inlet and Outlets: Number, sizes, types, and locations indicated. D. Curb Frames: Galvanized steel or steel with bitumastic coating of dimension to fit cover. 1. Pattern: Angle-cross-section shape with flat top surface. 2. Pattern: Z-cross-section shape with raised outer rim of height matching cover for recessed mounting that will have installed cover flush with top of floor slab. E. Covers for sump-pump pits and sumps include openings with gaskets and seals for access, pumps, pump shafts, control rods, discharge piping, vent connections, and power cables where indicated. Page 12 of 16

13 1. Covers include gaskets, bushings, and seals that are required to make basins gas-tight when installed. 2. Covers for Installation in Foot Traffic Areas: Include steel or cast-iron reinforcing capable of supporting foot traffic. F. Sump Pump Basin Covers: Fiber glass. G. Sump Pump Basin Covers: Polyethylene. H. Sump Pump Basin Covers: Steel, with bitumastic coating. I. Sump Pump Basin Covers: Cast iron. 2.8 AUTOMATIC, PACKAGED PUMP UNITS A. General Description: Automatic, packaged pump units complete with pumps, basin, controls, and valves. B. Pump Seals: Mechanical type. C. Basin: Fabricated of material indicated, with inlet as indicated. Include gas-tight cover with vent and pump discharge connections. D. Controls: Automatic, with mercury float switches and 20-foot (6m), waterproof, electrical power cables, except where other controls are indicated. E. Pump Discharge Piping: ASTM A 53, Schedule 40, galvanized-steel pipe, except where other material is indicated. F. Pump Discharge Piping: Manufacturer's standard steel pipe, copper tube, or plastic pipe, except where specific material is indicated. G. Valves: Factory- or field-installed check and shutoff valves on each pump discharge. H. Automatic, Packaged Waste-Water Pump Units: Pedestal sump pump, with aluminum impeller, and welded-steel basin. Include motor-mounted float switch, float and rod, and 72-inches (1800-mm) minimum power cord and plug. I. Automatic, Packaged Waste-Water Pump Units: Submersible sump pump, with cast-iron body, brass impeller, and plastic basin. Include 72 inches (1800-mm) minimum power cable and plug. J. Automatic, Packaged Waste-Water Pump Units: Submersible sump pump, with plastic body, impeller, and basin. Include 72-inches (1800-mm) minimum power cable and plug. K. Automatic, Packaged Sewage Pump Units: Submersible sewage pump, with cast-iron body, brass non-clog impeller, and plastic basin. Include control panel, high-water-level alarm, and 20-foot (6m) minimum power cable. Page 13 of 16

14 L. Automatic, Packaged Sewage Pump Units: Duplex sewage pumps. Include 2 submersible sewage pumps with cast-iron bodies and brass non-clog impellers, control panel with alternator, plastic basin, high-water-level alarm, and 20-foot (6m) minimum power cable. M. Automatic, Packaged, Grinder Sewage Pump Units: Suspended-type submersible sewage pump, with cast-iron body, stainless-steel grinder-type impeller and shredding ring, and plastic basin. Include control panel and 20-foot (6m) minimum power cable. N. Automatic, Packaged, Grinder Sewage Pump Units: Duplex-arrangement sewage pumps. Include 2 suspended-type submersible sewage pumps, with cast-iron bodies, stainless-steel grinder-type impellers and shredding rings, control panel, 2-compartment plastic basin, and 20-foot (6m) minimum power cable. 2.9 GENERAL-DUTY VALVES A. Refer to Division 15 Section "Valves" for general-duty gate, ball, butterfly, globe, and check valves. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine areas, equipment foundations, and conditions with Installer present for compliance with requirements for installation and other conditions affecting performance of pumps. Do not proceed with installation until unsatisfactory conditions have been corrected. B. Examine roughing-in of plumbing piping systems to verify actual locations of piping connections prior to pump installation. 3.2 EARTHWORK A. Excavating, trenching, and backfilling are specified in Division 2 Section "Earthwork." 3.3 CONCRETE A. Install concrete bases of dimensions indicated for plumbing pumps. Refer to Division 3 Section "Cast-in-Place Concrete" and Division 15 Section "Basic Mechanical Materials and Methods." B. Construct concrete pits and sumps of shapes and dimensions indicated. C. Concrete for pits and sumps is specified in Division 3 Section "Cast-in-Place Concrete." 3.4 INSTALLATION A. General: Comply with pump manufacturer's written installation instructions. Page 14 of 16

15 B. Install pumps in locations indicated and arrange to provide access for periodic maintenance, including removal of motors, impellers, couplings, and accessories. C. Support piping so that weight of piping is not supported by pumps. D. Wet-Pit-Mounted, Vertical Sewage Pumps: Install wet-pit-mounted sewage pumps, suspended from basin covers, in basins. Make direct connections to sanitary drainage piping. E. Submersible, Sewage Pumps: Install submersible sewage pumps set on basin floor. Make direct connections to sanitary drainage piping. 1. Install guide rail systems anchored to bottom of basins and to basin sidewalls or covers. Install pumps so that pump and discharge pipe disconnecting flanges make positive seals when pumps are dropped into place. F. Wet-Pit-Mounted, Vertical Sump Pumps: Install wet-pit-mounted sump pumps, suspended from basin covers, in basins, pits, or sumps, as indicated. Make direct connections to storm drainage piping. G. Submersible Sump Pumps: Install submersible sump pumps, set on basin, pit, or sump floor. Make direct connections to storm drainage piping. H. Basins: Install manufactured basins in locations indicated and connect to drainage piping. Connect to vent piping when indicated. Brace interior of basins according to manufacturer's instructions to prevent distortion or collapse during concrete placement. Refer to Division 3 Section "Cast-in-Place Concrete" for concrete work. Set basin cover and fasten to basin top flange. Install so top surface of cover is flush with finished floor. I. Automatic, Packaged Pump Units: Install pump units in locations indicated for receiving of fixture waste. Make direct connections to drainage and vent piping. 3.5 CONNECTIONS A. General: Connect piping to pumps as indicated. Install valves that are same size as piping connecting to pumps. B. Install discharge pipe sizes equal to or greater than diameter of pump nozzles. C. Install check valve and gate or ball valve on each sewage and sump pump discharge. D. Install check valve and gate or ball valve on each automatic, packaged pump unit pump discharge. E. Install check valve and gate or ball valve on each automatic, condensate pump unit pump discharge that is connected to drainage piping. F. Install electrical connections for power, controls, and devices. G. Electrical power and control wiring and connections are specified in Division 16 Sections. Page 15 of 16

16 3.6 ADJUSTING A. Pump Controls: Set pump controls for automatic start, stop, and alarm operation as required for system application. 3.7 COMMISSIONING A. Final Checks Before Startup: Perform the following preventive maintenance operations and checks before startup: 1. Lubricate oil-lubricated-type bearings. 2. Remove grease-lubricated bearing covers and flush bearings with kerosene and thoroughly clean. Fill with new lubricant according to manufacturer's recommendations. 3. Disconnect couplings and check motors for proper rotation. Rotation shall match direction of rotation marked on pump casing. 4. Check that pumps are free to rotate by hand. Do not operate pump, if bound or even drags slightly, until cause of trouble is determined and corrected. 5. Check that pump controls are correct for required application. B. Starting procedure for pumps with shutoff power not exceeding safe motor power: 1. Start motors. 2. Open discharge valves slowly. 3. Observe leakage from stuffing boxes and adjust sealing liquid valves for proper flow to ensure lubrication of packing. Let packing "run in" before reducing leakage through stuffing boxes; then tighten glands. 4. Check general mechanical operation of pumps and motors. END OF SECTION Page 16 of 16

Series Sump and Sewage Systems

Series Sump and Sewage Systems Series 000 Sump and Sewage Systems file no: 0. date: may 17, 13 supersedes: 0. date: march 29, 13 Series 000 Sump Series 0 & 2 Armstrong offers a complete range of high performance, easily maintained Column

More information

C. ASSE 1013 Performance Requirements for Reduced Pressure Principle Backflow Preventers.

C. ASSE 1013 Performance Requirements for Reduced Pressure Principle Backflow Preventers. PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

PUMPS FOR INDUSTRY. The Vertical Pump Specialists CONTENTS: Introduction & User List. Product Overview. Vertical Process Pumps...

PUMPS FOR INDUSTRY. The Vertical Pump Specialists CONTENTS: Introduction & User List. Product Overview. Vertical Process Pumps... PUMPS FOR INDUSTRY CONTENTS: The Vertical Pump Specialists Introduction & User List Product Overview Vertical Process Pumps... Series 600 Vertical Sewage Pumps... Series 700 Vertical Sump Pumps... Vertical

More information

SUGGESTED SPECIFICATIONS Pump Frames through 64132

SUGGESTED SPECIFICATIONS Pump Frames through 64132 TYPE HBB - HORIZONTAL SOLIDS-HANDLING WASTEWATER PUMPS Pump Frames 44081 through 64132 GENERAL Furnish and install Horizontal Flexible Coupled Dry Pit Pumping Units complete with all accessories and appurtenances

More information

SECTION COOLING TOWER

SECTION COOLING TOWER PART 1 GENERAL 1.1 SECTION INCLUDES A. Mechanical induced draft Cooling Tower B. Controls C. Ladder and handrails 1.2 REFERENCES SECTION 23 65 00 COOLING TOWER A. ANSI/AFBMA 9 - Load Rating and Fatigue

More information

SECTION SLUDGE HOLDING TANK DECANTER PUMP

SECTION SLUDGE HOLDING TANK DECANTER PUMP PART 1 GENERAL 1.01 SCOPE OF WORK A. The Contractor shall furnish and install all materials, labor and equipment to put into service the Sludge Holding Tank Decanter Pumping System in accordance with the

More information

SECTION PACKAGE BOOSTER PUMP STATIONS

SECTION PACKAGE BOOSTER PUMP STATIONS SECTION 331223 PACKAGE BOOSTER PUMP STATIONS Scope: The Contractor shall install a pump station at two locations to be determined by the Owner. These pump stations shall be designed to deliver flow to

More information

HUP. Performance Data. Wholesale Products Page: Section: Performance Data Dated: January RPM: 1550 Discharge: 1" Solids: 1/8" GPM: TDH:

HUP. Performance Data. Wholesale Products Page: Section: Performance Data Dated: January RPM: 1550 Discharge: 1 Solids: 1/8 GPM: TDH: Performance RPM: 1550 Discharge: 1" Solids: 1/8" Wholesale Products Page: 6660-1 Section: Performance The curves reflect maximum performance characteristics without exceeding full load (Nameplate) horsepower.

More information

SK75/100. Performance Data TOTAL HEAD IN FEET HEAD-METERS 6 SK100 SK Liters/Second Capacity-U.S. G.P.M.

SK75/100. Performance Data TOTAL HEAD IN FEET HEAD-METERS 6 SK100 SK Liters/Second Capacity-U.S. G.P.M. Performance SK75/100 RPM: 1750 Discharge: 2" Solids: 2" Wholesale Products Page: 6300-1 Section: Performance 12 40 9 30 HEAD-METERS 6 3 TOTAL HEAD IN FEET 20 10 SK75 SK100 0 0 Capacity-U.S. G.P.M. 20 40

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 22 1316 - SANITARY WASTE AND VENT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

HYDROMATIC W/D/V-A1 SUBMERSIBLE SUMP/EFFLUENT

HYDROMATIC W/D/V-A1 SUBMERSIBLE SUMP/EFFLUENT PERFORMANCE DATA Wholesale Products Page: 6570-1 RPM: 1550 Discharge: 1 ½ Solids: ½ V-A1 W-A1 D-A1 Head, meters 8 4 Head, feet 30 20 10.3 HP 0 0 Capacity, US GPM 0 10 20 30 40 50 60 liters/second 0.0 1.0

More information

MANHOLES, VAULTS AND CATCH BASINS SECTION A. Section Soil and Aggregate Materials. C. Section Storm Drainage Systems

MANHOLES, VAULTS AND CATCH BASINS SECTION A. Section Soil and Aggregate Materials. C. Section Storm Drainage Systems SECTION 02607-1 1.0 GENERAL 1.1 SCOPE: A. This section covers the work necessary for the construction of sanitary and storm system manholes, catch basins, and miscellaneous concrete structures complete.

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING SECTION 221316 - SANITARY WASTE AND VENT PIPING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following soil and waste, sanitary drainage and vent piping inside the building: 1. Pipe, tube,

More information

Read Only Copy Not For Distribution. Chapter 17. Private Potable Water Supply Systems 17.1 GENERAL REGULATIONS 17.2 QUANTITY OF WATER REQUIRED

Read Only Copy Not For Distribution. Chapter 17. Private Potable Water Supply Systems 17.1 GENERAL REGULATIONS 17.2 QUANTITY OF WATER REQUIRED Chapter 17 Private Potable Water Supply Systems 17.1 GENERAL REGULATIONS 17.1.1 Applicability The regulations in this chapter apply to any private potable water supply system where plumbing fixtures are

More information

A. Product Data shall be provided for each type of product indicated.

A. Product Data shall be provided for each type of product indicated. 32 31 13 CHAIN LINK FENCES AND GATES SECTION 1 GENERAL 1.1 SUMMARY This Section includes the following: 1. Chain Link Fences 2. Gates for Chain Link Fences. See electrical specifications for electrical

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 22 1319 - SANITARY WASTE PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

1. Vertical reciprocating conveyor, Hydraulic straddle VRC.

1. Vertical reciprocating conveyor, Hydraulic straddle VRC. PART 1: GENERAL 1.01 Section Includes: 1. Vertical reciprocating conveyor, Hydraulic straddle VRC. a. Machine, controller, platform, structural steel hoist frame. b. Wire mesh enclosure and gates. Related

More information

University of Houston Master Construction Specifications Insert Project Name SECTION PLUMBING PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS:

University of Houston Master Construction Specifications Insert Project Name SECTION PLUMBING PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: SECTION 22 10 00 - PLUMBING PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01 00, "Mechanical

More information

SECTION ROTARY SCREW WATER CHILLERS

SECTION ROTARY SCREW WATER CHILLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

SECTION ALUMINUM GATES

SECTION ALUMINUM GATES P.O. Box 1058 370 South Athol Rd. Athol, Massachusetts 01331 Phone: (978) 249-7924 Fax: (978) 249-3072 SECTION ALUMINUM GATES PART 1 GENERAL 1.01 SCOPE OF WORK A. The CONTRACTOR shall furnish all labor,

More information

SECTION MANHOLES AND STRUCTURES. A. Section Includes: 1. Manholes for water, storm drain and sanitary sewer systems.

SECTION MANHOLES AND STRUCTURES. A. Section Includes: 1. Manholes for water, storm drain and sanitary sewer systems. SECTION 33 05 13 MANHOLES AND STRUCTURES PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Manholes for water, storm drain and sanitary sewer systems. B. Related Sections: 1. Section 03 20 00 - Concrete

More information

BEST ONE SUBMERSIBLE SUMP PUMPS EPA. Page Features & Applications 100 Exploded View 101 Pump & Motor Specifications 102 Selection Chart / Type key 103

BEST ONE SUBMERSIBLE SUMP PUMPS EPA. Page Features & Applications 100 Exploded View 101 Pump & Motor Specifications 102 Selection Chart / Type key 103 CONTENTS -SPECIFICATIONS Page Features & Applications 100 Exploded View 101 Pump & Motor Specifications 102 Selection Chart / Type key 103 -PERFORMANCE CURVES Performance Curve Best One 200 Performance

More information

SECTION SLUICE GATES

SECTION SLUICE GATES SECTION 11100 SLUICE GATES PART 1--GENERAL Fill in the blank with a short description of sluice gate usage, i.e., for isolation of wastewater, or for tank drainage, or for control of water surface. 1.01

More information

SECTION CHAIN-LINK FENCES AND GATES 02821/1

SECTION CHAIN-LINK FENCES AND GATES 02821/1 SECTION 02821 - CHAIN-LINK FENCES AND GATES 02821/1 PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Chain-Link Fences: 2. Gates: horizontal slide or swing. 3. Fences installed where

More information

SECTION SECTIONAL OVERHEAD DOORS 522 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS. Display hidden notes to specifier. (Don't know how?

SECTION SECTIONAL OVERHEAD DOORS 522 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS. Display hidden notes to specifier. (Don't know how? SECTION 08360 SECTIONAL OVERHEAD DOORS 522 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Glazed Aluminum

More information

Series - 1

Series - 1 SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word

More information

SECTION ROLLER GATES

SECTION ROLLER GATES GENERAL SUMMARY A. The Contractor shall provide all labor, materials, equipment, and incidentals required to furnish and install roller gates, complete and operational with all necessary accessories as

More information

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows: SECTION 16130 (Master Template Final-05) ELECTRICAL BOXES PART 1 GENERAL 1.01 SECTION INCLUDES A. Provide boxes for electrical equipment and wiring devices as follows: 1. Wall and ceiling outlet boxes.

More information

TYPICAL INSTALLATION INSTRUCTIONS

TYPICAL INSTALLATION INSTRUCTIONS TYPICAL INSTALLATION INSTRUCTIONS Environment One Grinder Pump Feature Identification 1. Grinder Pump Basin High density polyethylene (HDPE) 2. Accessway Cover Painted Steel 3. Electrical Quick Disconnect

More information

YEOMANS SUBMERSIBLE SOLIDS-HANDLING WASTEWATER PUMPS YEOMANS

YEOMANS SUBMERSIBLE SOLIDS-HANDLING WASTEWATER PUMPS YEOMANS YEOMANS SUBMERSIBLE SOLIDS-HANDLING WASTEWATER PUMPS YEOMANS SERIES 9100 - SUBMERSIBLE NON-CLOG PUMPS SERIES 9235 - DRY-PIT SUBMERSIBLE NON-CLOG PUMPS SERIES 9500 - STAINLESS STEEL SUBMERSIBLE NON-CLOG

More information

American Metal Specialties, Inc.

American Metal Specialties, Inc. American Metal Specialties, Inc. www.cablerailings.com (253) 272-9344 (253) 627-3843 Fax PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 05 73 00 STAINLESS STEEL ORNAMENTAL HANDRAILS AND RAILINGS For best

More information

RB WEIR GATES MODEL GENERAL DESCRIPTION DESIGN CONSTRUCTION

RB WEIR GATES MODEL GENERAL DESCRIPTION DESIGN CONSTRUCTION GENERAL DESCRIPTION The Orbinox model RB Weir Gate is designed for downward opening applications where a more accurate flow control is required. The water flows over the top of the slide permitting a constant

More information

SUGGESTED SPECIFICATIONS

SUGGESTED SPECIFICATIONS SOLIDS-HANDLING SUBMERSIBLE DRY-PIT PUMPS PART 1 GENERAL 1.1 DESCRIPTION Work Included: Under this section, the contractor shall provide all labor, equipment and material necessary to furnish, install,

More information

SECTION FACILITY SANITARY SEWERS

SECTION FACILITY SANITARY SEWERS SECTION 22 13 13 FACILITY SANITARY SEWERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

DIVISION 22 PLUMBING

DIVISION 22 PLUMBING DIVISION 22 PLUMBING This Article on Codes, Regulation and Standards shall apply to all Divisions of the Building Standards 1 Table of Contents SECTION 22 05 16 EXPANSION FITTINGS AND LOOPS FOR PLUMBING

More information

SECTION FIELD ERECTED INDUCED DRAFT COOLING TOWER

SECTION FIELD ERECTED INDUCED DRAFT COOLING TOWER PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the contract including general and supplementary conditions and specifications section apply to this section. B. Related Sections:

More information

ANSI/ ASME HST Performance Standard For Overhead Electric Wire Rope Hoists

ANSI/ ASME HST Performance Standard For Overhead Electric Wire Rope Hoists SECTION 412213- BRIDGE CRANES Part 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 12 2113 - LOUVER BLINDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

SINGLE STAGE END SUCTION PUMPS AURORA Series. Distributed By: Model 3804

SINGLE STAGE END SUCTION PUMPS AURORA Series.  Distributed By: Model 3804 Model 3804 AURORA 3800 Series SINGLE STAGE END SUCTION PUMPS Distributed By: Flow-Tech Industries 4601 South Pinemont, Suite 100 Houston, Texas 77041 Phone: 713.690.7474 Fax: 409.882.0254 sales@flow-tech.com

More information

W ARR A NTY FAIRBANKS NIJHUIS 1600 SERIES SINGLE STAGE END SUCTION PUMPS. Certified to NSF/ANSI 372.

W ARR A NTY FAIRBANKS NIJHUIS 1600 SERIES SINGLE STAGE END SUCTION PUMPS. Certified to NSF/ANSI 372. W ST IND TRY FIR US ARR A NTY FAIRBANKS NIJHUIS 1600 SERIES SINGLE STAGE END SUCTION PUMPS Certified to NSF/ANSI 372 www.fairbanksnijhuis.com FAIRBANKS NIJHUIS 1600 SERIES Single Stage End Suction Pumps

More information

SECTION ACOUSTICAL PANEL CEILINGS

SECTION ACOUSTICAL PANEL CEILINGS SECTION 095113 ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

PASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017

PASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017 SECTION 02630 - STORM DRAINAGE PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Simplex Fiberglass Lift Station: Hard Piped

Simplex Fiberglass Lift Station: Hard Piped www.cranepumps.com Simplex Fiberglass Lift Station: Hard Piped Pre-Packaged Fiberglass Systems Specifications: inches (mm) BASIN... Fiberglass w/ 3 (76) Ballast Support Flange DISCHARGE CONNECTION:...

More information

MODELS PH PH PH

MODELS PH PH PH WWW.BURCAM.COM 2190 Boul. Dagenais West TEL: 514.337.4415 LAVAL (QUEBEC) FAX: 514.337.4029 CANADA H7L 5X9 info@burcam.com Your pump has been carefully packaged at the factory to prevent damage during shipping.

More information

SECTION MECHANICAL SPECIFICATION GRIT COLLECTION EQUIPMENT

SECTION MECHANICAL SPECIFICATION GRIT COLLECTION EQUIPMENT SECTION 11322 MECHANICAL SPECIFICATION GRIT COLLECTION EQUIPMENT PART 1 GENERAL 1.01 SCOPE There shall be furnished ( ) Grit Separator Mechanism(s) suitable for installation in (a) concrete tank(s) -ft.

More information

This guide can be used to prepare a specification for incorporating free standing jib cranes into a competitively bid construction project.

This guide can be used to prepare a specification for incorporating free standing jib cranes into a competitively bid construction project. SECTION 14651 FREE STANDING JIB CRANE ***** Gorbel, Inc. manufacturers a broad range of material handling cranes including monorail, bridge, gantry, and jib cranes. Numerous work station and industrial

More information

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES SECTION 15420 DRAINAGE AND VENT SYSTEMS PART 1 DESIGN DIRECTIVES 1.1 DESIGN CRITERIA A. All cleanouts above finished (accessible and non-accessible) ceilings shall be extended to the floor above. B. Do

More information

A. Codes and Standards that are standard at the University. C. Coordinate cleanout locations with Architect.

A. Codes and Standards that are standard at the University. C. Coordinate cleanout locations with Architect. PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

Fiberglass Cooling Towers

Fiberglass Cooling Towers Fiberglass Cooling Towers Available in sizes from 100 to 240 tons. FC Series 700 Fiberglass Cooling Tower Available in sizes from 170 to 240 tons. No other fiberglass cooling tower comes with as many high-quality

More information

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT SECTION 230548 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Elastomeric Isolation pads. 2. Elastomeric Isolation mounts. 3. [Freestanding] [Restrained] [Freestanding and restrained]

More information

2000-SG STAINLESS STEEL SLIDE GATES

2000-SG STAINLESS STEEL SLIDE GATES 2000-SG STAINLESS STEEL SLIDE GATES 1. GENERAL CONDITIONS 1.1. SCOPE. This section covers Stainless Steel Flow Control Slide Gates and operators. 1.2. GENERAL. Slide gates, including actuation devices,

More information

SECTION FOUNTAINS

SECTION FOUNTAINS PART 1 - GENERAL SECTION 13121 FOUNTAINS 1.1 SUMMARY A. Section includes design and complete installation of decorative fountains complete as shown on Drawings and as specified, including: 1. Equipment

More information

Daytona Beach Pier Building Renovation Jun 2010

Daytona Beach Pier Building Renovation Jun 2010 SECTION 15150 - SANITARY WASTE AND VENT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Weir Specialty Pumps. WEMCO Torque-Flow

Weir Specialty Pumps. WEMCO Torque-Flow Weir Specialty Pumps WEMCO Torque-Flow HIGH LOW OIL LEVEL WEMCO Torque-Flow Model C WEMCO Torque-Flow Model C Materials of Construction Ni-Hard, High Chrome Configurations Horizontal Sealing Multiple options

More information

SECTION ORNAMENTAL ALUMINUM RAILING. ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products.

SECTION ORNAMENTAL ALUMINUM RAILING. ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products. SECTION 05720 ORNAMENTAL ALUMINUM RAILING ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products. This section is based on the products of Superior Aluminum Products,

More information

This guide can be used to prepare a specification for incorporating free standing jib cranes into a competitively bid construction project.

This guide can be used to prepare a specification for incorporating free standing jib cranes into a competitively bid construction project. GORBEL PRODUCT SPECIFICATIONS 2010 Gorbel, Inc., P.O., Box 593, Fisher, New York 14453-0593 PHONE: 800-821-0086, FAX: 585-924-6273; WEBSITE: www.gorbel.com November SECTION 41 22 31PRIVATE FREE STANDING

More information

SECTION SWIMMING POOLS STAINLESS, FULL TILE, OR TILE TRIM

SECTION SWIMMING POOLS STAINLESS, FULL TILE, OR TILE TRIM SECTION 13 1100 SWIMMING POOLS STAINLESS, FULL TILE, OR TILE TRIM This section includes editing notes to assist the user in editing the section to suit project requirements. These notes are included as

More information

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II SECTION 221313 - FACILITY SANITARY SEWERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SERVICE LINES, METERS AND APPURTENANCES

SERVICE LINES, METERS AND APPURTENANCES AUGUST02 SECTION 02646 SERVICE LINES, METERS AND APPURTENANCES PART 1 - GENERAL 1.1 DESCRIPTION A. This section concerns materials and installation of corporation stops, curb stops, service lines, meters,

More information

SECTION SECTIONAL OVERHEAD DOORS

SECTION SECTIONAL OVERHEAD DOORS SECTION 08360 SECTIONAL OVERHEAD DOORS PART 1 GENERAL 1.1 SECTION INCLUDES A. Aluminum Doors B. Track and Framing 1.2 RELATED SECTIONS A. Section 04810 - Unit Masonry Assemblies: Prepared opening in masonry.

More information

1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases.

1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases. SECTION 260529 - HANGERS AND SUPPORTS PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases. 1.2

More information

Storm Drainage

Storm Drainage University of New Hampshire University of New Hampshire Scholars' Repository Division 33 Utilities Chapter 5 Technical Construction and Renovation Standards 4-23-2015 334100 - Storm Drainage Sandra Hickey

More information

Cast Iron Sluice Gates Rugged Dependability in Demanding Applications

Cast Iron Sluice Gates Rugged Dependability in Demanding Applications Cast Iron Sluice Gates Rugged Dependability in Demanding Applications A Proud Tradition Since 1840, the team at Rodney Hunt has pioneered safe and reliable flow control systems to help communities and

More information

SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS SECTION 08 32 20 CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS Page 1 of 6 USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS PANEL PARTITIONS. SECTION INCLUDES OVERHEAD TRACK ASSEMBLY,

More information

SEPTIC TANK CONSTRUCTION GUIDELINES

SEPTIC TANK CONSTRUCTION GUIDELINES SEPTIC TANK CONSTRUCTION GUIDELINES Septic tank for this airport will be designed/ built by the general contractor of the building facilities. At the time of the project design, availability of a septic

More information

FAIRBANKS NIJHUIS SUBMERSIBLE SOLIDS HANDLING PUMPS.

FAIRBANKS NIJHUIS SUBMERSIBLE SOLIDS HANDLING PUMPS. FAIRBANKS NIJHUIS SUBMERSIBLE SOLIDS HANDLING PUMPS www.fairbanksnijhuis.com FAIRBANKS NIJHUIS Introduction Fairbanks Nijhuis manufactures a complete line of submersible pumps for municipal and industrial

More information

SECTION TURBINE VENTILATORS

SECTION TURBINE VENTILATORS SECTION 07 72 00 TURBINE VENTILATORS **This is a CSI Three-Part Specification using CSI MasterFormat 2004-2010 Section Numbers and Titles. This specification must be edited to suit your particular project.

More information

- CONSTRUCTIONS 300 SECTIONAL VIEW 300 SECTIONAL TABLE 301 QUANTITY FOR MODEL 302 MECHANICAL SEAL 303 BEARINGS 304

- CONSTRUCTIONS 300 SECTIONAL VIEW 300 SECTIONAL TABLE 301 QUANTITY FOR MODEL 302 MECHANICAL SEAL 303 BEARINGS 304 CONTENTS Page - SPECIFICATIONS 200 PERFORMANCE RANGE and SELECTION CHART 201 TYPE KEY and CURVE SPECIFICATIONS 202 PERFORMANCE CURVE 40 203 PERFORMANCE CURVE 80 204 - CONSTRUCTIONS 300 SECTIONAL VIEW 300

More information

ADDENDUM NO. 1. Mallory Valley Utility District Technical Specifications & Design Criteria for Water Supply & Distribution Facilities

ADDENDUM NO. 1. Mallory Valley Utility District Technical Specifications & Design Criteria for Water Supply & Distribution Facilities ADDENDUM NO. TO Mallory Valley Utility District Technical Specifications & Design Criteria for Water Supply & Distribution Facilities Date of Addendum: December, 00 Hethcoat & Davis, Inc. 78 Franklin Road,

More information

SECTION PLUMBING PIPING SYSTEMS

SECTION PLUMBING PIPING SYSTEMS SECTION 15300 PLUMBING PIPING SYSTEMS PART 1 - GENERAL 1.01 SPECIAL NOTICE A. Each contractor shall read all relevant documents, become familiar with the job, the scope of work, type of general construction,

More information

SECTION VI Duplex Lift Station with Above Grade Valve Pit

SECTION VI Duplex Lift Station with Above Grade Valve Pit SECTION VI Duplex Lift Station with Above Grade Valve Pit DESCRIPTION The contractor shall furnish and install one submersible sewage lift station with concrete wet well, pumps, piping, and factory built

More information

HIGH MAST CAMERA POLE ASSEMBLY GENERAL

HIGH MAST CAMERA POLE ASSEMBLY GENERAL 10-3.24 HIGH MAST CAMERA POLE ASSEMBLY GENERAL The Contractor must furnish and install the following equipment for high mast camera pole assembly as described herein and as shown on the plans: 1. Camera

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS 2190 Dagenais Blvd.West Laval (Quebec) Canada H7L 5X9 Tel. : 514.337.4415 Fax : 514.337.4029 info@burcam.com see us at www.burcam.com VERSION Z MODELS 300500 SUMP PUMPS Your pump

More information

SECTION STORM UTILITY DRAINAGE PIPING PART 1 - GENERAL 1.1 SUMMARY 1.2 SUBMITTALS 1.3 PROJECT CONDITIONS

SECTION STORM UTILITY DRAINAGE PIPING PART 1 - GENERAL 1.1 SUMMARY 1.2 SUBMITTALS 1.3 PROJECT CONDITIONS SECTION 334100 - STORM UTILITY DRAINAGE PIPING PART 1 - GENERAL 1.1 SUMMARY Section Includes: 1. Pipe and fittings. 2. Drain Basin. 3. De-chlorination tablet feeder. 4. Non-pressure transition couplings.

More information

B. Polyethylene samples shall be submitted for Owner approval of color and quality.

B. Polyethylene samples shall be submitted for Owner approval of color and quality. Glass Rail ENGINEERED DASHERBOARD SPECIFICATIONS PART 1 - GENERAL 1.01 PROJECT SCOPE A. Contractor shall furnish and install one complete set of steel framed dasherboards as indicated on the drawings and

More information

Aluminum Component Pipe Railings

Aluminum Component Pipe Railings 1 SECTION 05 7360 ALUMINUM COMPONENT PIPE RAILINGS PART 1 GENERAL 1.01 SECTION INCLUDES A. Aluminum component pipe handrails and railings. 1.02 RELATED REQUIREMENTS A. Section 02 9000: Landscaping: Installation

More information

SECTION UTILITY MANHOLES AND STRUCTURES

SECTION UTILITY MANHOLES AND STRUCTURES SECTION 33 05 14 UTILITY MANHOLES AND STRUCTURES PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Precast reinforced concrete manholes and structures with tongue-and-groove joints with masonry transition

More information

SECTION ENTRANCE FLOOR GRILLES STAINLESS STEEL GRATING

SECTION ENTRANCE FLOOR GRILLES STAINLESS STEEL GRATING 7160 Krick Rd., Walton Hills, OH 44146 800-321-3827 - Tel 440-439-8650 - Fax 440-439-6889 SECTION 12 48 16 ENTRANCE FLOOR GRILLES STAINLESS STEEL GRATING PART 1. GENERAL 1.01 SUMMARY: This section includes

More information

Northpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017

Northpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017 SECTION 055213 - PIPE AND TUBE RAILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION C1 DUCTILE IRON PIPE AND FITTINGS GENERAL

SECTION C1 DUCTILE IRON PIPE AND FITTINGS GENERAL SECTION C1 DUCTILE IRON PIPE AND FITTINGS GENERAL This section covers the furnishing and installation of ductile iron water pipe, fittings, thrust restraint and pipe disinfection. Ductile Iron Pipe MATERIALS

More information

D-1 FIRE PROTECTION PRODUCTS TAPPING VALVE. MUELLER Tapping Valves. MUELLER Tapping Sleeves and Crosses. MUELLER Stainless Steel Tapping Sleeves

D-1 FIRE PROTECTION PRODUCTS TAPPING VALVE. MUELLER Tapping Valves. MUELLER Tapping Sleeves and Crosses. MUELLER Stainless Steel Tapping Sleeves TAPPING VALVE MUELLER Tapping Sleeves and Crosses Full range of Tapping Sleeves and Crosses to fit most types of pipe including cast iron, ductile iron, A-C, and cast iron O.D. PVC--Also outlet sealed

More information

SECTION FACILITY STORM DRAINAGE

SECTION FACILITY STORM DRAINAGE PART 1 - GENERAL 1.1 DESCRIPTION SECTION 22 14 00 Storm drainage systems, including piping and all necessary accessories as designated in this section. 1.2 RELATED WORK A. Penetrations in rated enclosures:

More information

4 1 /2 MARK 73-5 AMERICAN FLOW CONTROL. It s What We Know. AMERICAN-DARLING FIRE HYDRANT AMERICAN-DARLING 4 1 /2 MARK 73-5 FIRE HYDRANT

4 1 /2 MARK 73-5 AMERICAN FLOW CONTROL. It s What We Know. AMERICAN-DARLING FIRE HYDRANT AMERICAN-DARLING 4 1 /2 MARK 73-5 FIRE HYDRANT AMERICAN-DARLING FIRE HYDRANT AMERICAN-DARLING FIRE HYDRANT AMERICAN FLOW CONTROL It s What We Know. CONSTRUCTION AMERICAN-DARLING FIRE HYDRANT OPERATING NUT Cast one-piece bronze operating nut. Design

More information

SECTION HYDRAULIC DRIVE MACHINE ROOM (MR) RESIDENTIAL ELEVATORS

SECTION HYDRAULIC DRIVE MACHINE ROOM (MR) RESIDENTIAL ELEVATORS SECTION 14 20 10 HYDRAULIC DRIVE MACHINE ROOM (MR) RESIDENTIAL ELEVATORS PART 1 - GENERAL 1.1 CONDITIONS AND REQUIREMENTS A. The General Conditions, Supplementary Conditions, and Division 01 General Requirements

More information

SECTION DRAINAGE AND VENT SYSTEMS CONSTRUCTION STANDARD

SECTION DRAINAGE AND VENT SYSTEMS CONSTRUCTION STANDARD PART 1: GENERAL 1.01 The design guidelines contained herein include the requirements for drainage and vent systems utilized at The University of Texas at Austin. It is the intention of this document to

More information

SECTION EXPANSION CONTROL

SECTION EXPANSION CONTROL SECTION 07 95 00 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Diffused Aeration Piping Equipment

Diffused Aeration Piping Equipment 1.0 General 1.1. The specifications in this section include all components of the Diffused Aeration System with the exception of the individual diffuser units. Refer to additional specification sections

More information

A. Codes and Standards that are Standards at the University. A. Provide floor drains in all toilet rooms, janitor closets, and mechanical rooms.

A. Codes and Standards that are Standards at the University. A. Provide floor drains in all toilet rooms, janitor closets, and mechanical rooms. PART 1: GENERAL 1.01 Purpose A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

AUGUST 2017 Tulpehocken Station Utility Improvements ADDENDUM 3 SECTION SEWAGE EJECTOR PUMPING STATION

AUGUST 2017 Tulpehocken Station Utility Improvements ADDENDUM 3 SECTION SEWAGE EJECTOR PUMPING STATION SECTION 15141 SEWAGE EJECTOR PUMPING STATION PART 1 GENERAL 1.01 DESCRIPTION A. Provide all labor, materials, tools, equipment and services required to furnish, deliver and install all work as required

More information

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection SECTION 13090 RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13090-1 LOW INTENSITY RADIATION PROTECTION

More information

Flygt C-pumps Submersible waste and raw water pumps

Flygt C-pumps Submersible waste and raw water pumps Flygt C-pumps 3068 3800 Submersible waste and raw water pumps Flygt submersible pumps for a variety of applications Submersibles Flygt pumps operate directly in the liquid being pumped, which means they

More information

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS SECTION 26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals as shown, specified, and

More information

SECTION ORNAMENTAL ALUMINUM RAILING. ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products.

SECTION ORNAMENTAL ALUMINUM RAILING. ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products. SECTION 05720 ORNAMENTAL ALUMINUM RAILING ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products. This section is based on the products of Superior Aluminum Products,

More information

SECTION PIPE AND TUBE RAILINGS PART 1- GENERAL 1.1 RELATED DOCUMENTS 1.2 SUMMARY 1.3 PERFORMANCE REQUIREMENTS

SECTION PIPE AND TUBE RAILINGS PART 1- GENERAL 1.1 RELATED DOCUMENTS 1.2 SUMMARY 1.3 PERFORMANCE REQUIREMENTS SECTION 055213- PIPE AND TUBE RAILINGS PART 1- GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

FOUR FOLD DOORS-WITH SINGLE OVERHEAD MTD OPERATOR

FOUR FOLD DOORS-WITH SINGLE OVERHEAD MTD OPERATOR FOUR FOLD DOORS-WITH SINGLE OVERHEAD MTD OPERATOR Section 083713- Four Fold Doors- With Single Overhead Mounted Operator Part 1-General 1.1 Related Document: A. Drawing and general provisions of contract,

More information

DBI-SALA Uni 8 Overhead Horizontal Lifeline Cable System SECTION HORIZONTAL FALL PROTECTION - OVERHEAD CABLE

DBI-SALA Uni 8 Overhead Horizontal Lifeline Cable System SECTION HORIZONTAL FALL PROTECTION - OVERHEAD CABLE SECTION 112429.18 - HORIZONTAL FALL PROTECTION - OVERHEAD CABLE PART 1 - GENERAL 1.1 SECTION INCLUDES A. Provide overhead horizontal cable fall protection system, including end anchors, energy absorbers,

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

***************************************************************************************************************

*************************************************************************************************************** 02720 STORM DRAINAGE SYSTEM *************************************************************************************************************** SPECIFIER: CSI MasterFormat 2004 number 33 40 00. ***************************************************************************************************************

More information