1 Efectis Nederland BV Efectis Nederland report 2010EfectisR1091 Reaction to fire testing of Arundo Reed a.k.a. Thai Coconut Thatch tiles, polyvinylchloride (PVC) reed roof covering. External fire exposure to roofs according to ENV 1187: A1:2005; Test 1 Efectis Nederland BV Centre for Fire Safety Lange Kleiweg 5 P.O. Box CB Rijswijk The Netherlands T fire safety ( ) F E nederland@efectis.com Date November 2010 Author(s) W. Scheffer B.Be. C.C.M. Steinhage B.Sc. Sponsor Waalbandijk 9192 NL6669 ME DODEWAARD The Netherlands Project number Number of pages 8 All rights reserved. No part of this publications may be reproduced and/or published by print, photoprint, microfilm or any others means without the previous written consent of Efectis. In case this report was drafted on instructions, the rights and obligations of contracting parties are subject to either the Standard Conditions for Research Instructions given to TNO, or the relevant agreement concluded between the contracting parties. Submitting the report for inspection to parties who have a direct interest is permitted Efectis Nederland BV: a TNO company This report is issued by Efectis Nederland BV (previously TNO Centre for Fire Research). Efectis Nederland BV and her sister company Efectis France are full subsidiaries of Efectis Holding SAS since 1 st January 2008, in which the Dutch TNO and the French CTICM participate. The activities of the TNO Centre for Fire Research were privatised in Efectis Nederland BV since 1 st July This is in response to international developments and requests by customers. In order to be able to give a better answer to the customer s request and offer a more comprehensive service of high quality and a wider range of facilities, the international collaboration has been further expanded. This is done with highly experienced partners in fire safety in Norway (SintefNBL), Spain (AfitiLicof), Germany (IFT), USA (South West Research Institute) and China (TFRI). Further information can be found at our website.
2 Efectis Nederland report 2010EfectisR1091 November / 8 Product identification: Arundo Reed outside Europe also known as Thai Coconut Thatch tiles, polyvinylchloride (PVC) reed roof covering, further referred to as the product. Abstract: Determination of the reaction to fire by exposure to external fire to roofs according to ENV 1187: A1:2005; Test 1: Method with burning brands, with the objective to obtain the reaction to fire classification according to EN : A1:2009. Intended application: The product will be used as a roof covering. Product description: According to the sponsor the product is composed of: Plywood; the reed thatch tiles are attached to plywood with a thickness of 18 mm. Silisto Max Plus; on the plywood Silisto Max Plus roof covering is attached; 1 layer of fire retardant polypropylene (PP) laminate with a thickness of 0.5 mm and a weight of 150 ±8 g/m 2. PVC Reed thatch tiles; on the plywood and the roof covering the polyvinylchloride (PVC) thatch tiles are attached. The product has a weight of 0.5 kg/tile and a square meter of roof contains approx. 16 tiles. Samples: Sampling procedure: Age: Date of receipt: Conditioning: The specimens were prepared and submitted by the sponsor. Efectis did not exercise any supervision during specimen fabrication. At the time of receipt: no information received. October 14, 2010 (1 st specimen) and October 26, 2010 (2 nd, 3 rd, 4 th specimen) Prior to the examinations, the specimens were conditioned over a period of one or two weeks at a temperature of (23 ± 2) ºC and a relative humidity of (50 ± 5) % according to 4.1 of EN 13238:2010. Specimen preparation: Actions taken by the laboratory Non taken to prevent flames passing the edges: Testconditions: Test Method: Test 1: Method with burning brands Roof pitch: 45 Ambient temperature at start approx. 20 C
3 Efectis Nederland report 2010EfectisR1091 November / 8 Examination: Number of tests: A total of four tests were carried out according to ENV Deviations from the test method: None Date of examination: October 21, 2010 (1 st test) and November 8, 2010 (2 nd, 3 rd and 4 th test) The results are given in Table 1. Table 1: External fire exposure to roof classification parameter results Parameter Test result Classification parameter Test number Flame spread 1 ): Internal, upwards [m:s] 10 cm 30 cm 50 cm 70 cm External, upwards [m:s] 10 cm 30 cm 50 cm 70 cm Internal, downwards [m:s] 10 cm 30 cm 50 cm 60 cm External, downwards [m:s] 10 cm 30 cm 50 cm 60 cm Maximum burned length: Internal: < 80 cm [cm] External: < 80 cm [cm] 13:30 Not reached Not reached Not reached Not reached Compliant Compliant Lateral flame spread to edges 2 )(m:s) [Y/N] N N N N Not reached Burning droplets/debris falling from exposed side [Y/N] N N N N N Burning/glowing particles Penetrating the roof [Y/N] N N N N N Size of through openings: one single opening: < 25 mm 2 [mm 2 ] sum of all openings: < 4500 mm 2 [mm 2 ] 1 ) Spread of flame measured from the edges of the projection of the ignition source 2 ) Edge of the measuring zone Compliant Compliant
4 Efectis Nederland report 2010EfectisR1091 November / 8 Table 2: Observations of physical behaviour of the test specimen: Parameter Test number Time since start test [m:s] Burning of wood wool 4:30 4:00 3:00 4:00 Glowing of wood wool 15:00 12:00 13:00 11:00 Burning of roof 13:00 30:00 Glowing/smoking of roof 17:00 30:00 12:00 30:00 Termination of test 60:00 60:00 60:00 60:00 Internal inspection of specimen 60:00 60:00 60:00 60:00 Conclusions: A formal classification is to be assessed in accordance with EN , Fire classification of construction products and building elements Part 5: Classification using data from external fire exposure to roof tests. Remarks: The test results relate to the behaviour of the test specimens of a product under the particular conditions of the test; they are not intended to be the sole criterion for assessing the potential fire hazard of the product in use. W. Scheffer B.Be. C.C.M. Steinhage B.Sc. This report is issued by Efectis Nederland BV (previously TNO Centre for Fire Research). Efectis Nederland BV and her sister company Efectis France are full subsidiaries of Efectis Holding SAS since 1 st January 2008, in which the Dutch TNO and the French CTICM participate. The activities of the TNO Centre for Fire Research were privatised in Efectis Nederland BV since 1 st July This is in response to international developments and requests by customers. In order to be able to give a better answer to the customer s request and offer a more comprehensive service of high quality and a wider range of facilities, the international collaboration has been further expanded. This is done with highly experienced partners in fire safety in Norway (SintefNBL), Spain (AfitiLicof), Germany (IFT), USA (South West Research Institute) and China (TFRI). Further information can be found at our website.
5 Efectis Nederland report 2010EfectisR1091 November / 8 Representative photographs of the tests performed Test 1 Efectis Nederland BV 2010
6 Efectis Nederland report 2010EfectisR1091 November / 8 Test 2 Efectis Nederland BV 2010
7 Efectis Nederland report 2010EfectisR1091 November / 8 Test 3 Efectis Nederland BV 2010
8 Efectis Nederland report 2010EfectisR1091 November / 8 Test 4 Efectis Nederland BV 2010
Rockwool / Rockfon BV Industrieweg JG ROERMOND Postbus KD ROERMOND The Netherlands
Efectis Nederland BV Efectis Nederland report 2009-Efectis-R0539[Rev.1] Determination of the fire resistance according to EN 1365-2: 1999 of a suspended ceiling system of CMC with Rockfon Sonar db44 Dznl/A
More informationRockwool / Rockfon BV Industrieweg JG ROERMOND Postbus KD ROERMOND The Netherlands
Efectis Nederland BV Efectis Nederland report 2009-Efectis-R0541[Rev.2] Determination of the fire resistance according to EN 1365-2 1999 of a suspended ceiling system of CMC with Rockfon Sonar db44 A24
More informationRockwool / Rockfon BV Industrieweg JG Roermond Postbus KD Roermond The Netherlands
Efectis Nederland BV Efectis Nederland-report 2007-Efectis-R0009[Rev.1] Determination of the fire resistance according to EN 1365-2:1999 of a suspended ceiling system of CMC with Rockfon Sonar D 900 x
More informationCLASSIFICATION OF FIRE RESISTANCE OF AN ALUMINIUM CURTAIN WALL STRUCTURE, TYPE CW50-FP, ACCORDING TO EN :2007+A1: 2009
CLASSIFICATION OF FIRE RESISTANCE OF AN ALUMINIUM CURTAIN WALL STRUCTURE, TYPE CW50-FP, ACCORDING TO EN 13501-2:2007+A1: 2009 Sponsors: Reynaers Aluminium NV/SA Oude Liersebaan 266 B-2570 Duffel Belgium
More informationCLASSIFICATION OF FIRE RESISTANCE PERFORMANCE IN ACCORDANCE WITH EN : 2007
CLASSIFICATION OF FIRE RESISTANCE PERFORMANCE IN ACCORDANCE WITH EN 13501-2: 2007 Sponsor: Reynaers Aluminium NV/SA Oude Liersebaan 266 B-2570 Duffel BELGIUM Prepared by: Efectis Nederland B.V. Centre
More informationP.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com DETERMINATION OF THE FIRE RESISTANCE ACCORDING TO EN 1364-1:2015 OF A NON-LOAD
More informationP.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk
P.O. Box 554-2665 ZN Bleiswijk Brandpuntlaan Zuid 16-2665 NZ Bleiswijk 088 3473 723 nederland@efectis.com Product 110 Envirograf Firoblock 110V15 penetration seal in a standard flexible supporting construction
More informationFire resistance according to EN :2008 of a Sectional door set, type Metacon OHD EI(1)-60
P.O. Box 554-2665 ZN Bleiswijk Brandpuntlaan Zuid 16-2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com Fire resistance according to EN 1634-1:2008 of a Sectional door set, type Metacon
More informationDD CEN/TS 1187: 2012 Test 4
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com DD CEN/TS 1187: 2012 Test 4 Incorporating
More informationENV 1187: 2002 Test 4
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com ENV 1187: 2002 Test 4 Incorporating Amendment
More informationCLASSIFICATION OF FIRE RESISTANCE ACCORDING TO EN : 2007+A1:2009 OF A LOAD BEARING THERMAL INSULATED CONCRETE FLOOR; REPPEL OP-DECK
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com OF FIRE RESISTANCE ACCORDING TO EN 13501-2: 2007+A1:2009 OF A LOAD BEARING THERMAL
More informationP.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com Determination of the fire resistance according to EN 1364-1:1999 and FprEN 1364-1:2014
More informationP.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com Determination of the fire resistance according to EN 1364-1:1999 and FprEN 1364-1:2014
More informationP.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com Determination of the fire resistance according to EN 1364-1:1999 and FprEN 1364-1:2014
More informationBankstraat 2 B-9770 Kruishoutem BELGIUM. Fire resistant THEUMA door set in RVS frame with three 3-D Argenta Invisible ARGENT ALU hinges
CLASSIFICATION OF THE FIRE RESISTANCE ACCORDING TO EN 13501-2: 2007 + A1:2009 OF A THEUMA DOOR SET WITH THREE 3-D ARGENTA ALU INVISIBLE HINGES AND BUILT IN DOOR CLOSER IN A TWO PIECE STAINLESS STEEL FRAME
More informationDD CEN/TS 1187: 2012 Test 4
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com DD CEN/TS 1187: 2012 Test 4 Incorporating
More informationP.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com Classification of the fire resistance according to EN 13501-2:2007+ A1:2009
More informationTNO Institute of Environmental and Energy Technology
TNO Institute of Environmental and Energy Technology Laan van Westenenk 51 P.O. Box 342 73 AH Apeldoorn The Netherlands Telex 39395 tnoap nl Phone +31 55 49 34 93 Fax +31 55 41 98 37 TNO-report Removal
More informationTest report. Mr. M.A.A.M. Schets, B.Sc. Páfrány forduló 14 H-1221 Budapest Hungary.
TÜV Rheinland Nederland B.V. Test report Test report relating to a glass product according to European standard EN 1279-4; MVTR, gas permeation rate and tensile strength testing concerning the product
More informationSPECIMEN. Fire Test Certificate Specimen. Fabric: Cotton Cyclorama Canvas Type: BS5867 Part 2 Type B 0000-M-FC U02
Type: BS5867 Part 2 Type B 0000-M-FC-0025-01-U02 Type: BS5867 Part 2 Type B 0000-M-FC-0025-01-U02 Type: BS5867 Part 2 Type B 0000-M-FC-0025-01-U02 Fire Test Certificate Specimen Fabric: Cotton Cyclorama
More informationBS 476 Part 3: External Fire Exposure Roof Test. A Report To: Light Weight Tiles Limited. Document Reference: Date: 16 th March 2015
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS 476 Part 3: 2004 External Fire Exposure
More informationBRE Global Test Report
BRE Global Test Report BS 476: Part 3: 2004 External fire exposure to roofs test on Flexitec 2020 on 9mm Masterboard calcium silicate base Prepared for: Res-Tec Ltd Date: 03 November 2017 Report Number:
More informationSoaSA Technology International Ltd. EN Pendulum Test-Impact test method and classification for flat glass SaoSA Resin Laminated Glass (4-1-4)
TNO report TC-RAP-06-22618/rie. EN 12600-Pendulum Test-Impact test method and classification for flat glass SaoSA Resin Laminated Glass (4-1-4) De Rondom 1 P.O. Box 6235 The Netherlands www.tno.nl T +31
More informationeuropean fire standards and national legislation
1 european fire standards and national legislation An Introduction Current testing and standards In the past, manufacturers, designers and specifiers in the Internal Market had to cope with a lack of meaningful
More informationBRE Global Classification Report
BRE Global ification Report ification report for roofs/roof coverings exposed to external fire in accordance with EN 13501-5: 2005 + A1:2009 on Sarnafil G410-12 EL membrane over SarnaTherm G/TR27 on a
More informationREQUESTED BY : Atlas Roofing and Flooring PO Box Queenswood CONTRACT No : FTC12/088. AUTHOR(S) : K. van Dyk. DATE : 13 September 2012
TITLE : Report on the small-scale fire properties of a Structural Insulated Panel System (SIPS) product when used as a roofing material and exposed to a fire originating inside the structure REQUESTED
More informationBRE Global Test Report
BRE Global Test Report CEN/TS 1187: 2012 Test 4 External fire exposure to roofs test on Sarnafil G410-12 EL membrane over SarnaTherm G/TR27 on a Plywood deck Prepared for: Sika Limited Date: 05 January
More informationDetermination of the influence of the SpeedComfort fan system affixed on a plate radiator.
TNO report TNO 2016 R11745 Determination of the influence of the SpeedComfort fan system affixed on a plate radiator. Technical Sciences Leeghwaterstraat 44 2628 CA Delft P.O. Box 6012 2600 JA Delft The
More informationThe Effect of Moisture on the Compressive Strength and Walkability of Roofing Insulation By Nico A. Hendriks
Paper presented at the 5 th Global Insulation Conference, London, 4 th and 5 th of October 2010 The Effect of Moisture on the Compressive Strength and Walkability of Roofing Insulation By Nico A. Hendriks
More informationClassification report for roofs/roof coverings exposed to external fire in accordance with BS EN : 2005+A1:2009
ification report for roofs/roof coverings exposed to external fire in accordance with BS EN 13501-5: 2005+A1:2009 Prepared for: Flex-R Ltd Unit 5 Central Park Bellfield Road High Wycombe Bucks HP13 5HG
More informationClassification report for roofs/roof coverings exposed to external fire No D
ification report for roofs/roof coverings exposed to external fire No. 16261D Owner of the classification report IKO Insulations bv Wielewaalweg 3 4791 PD Klundert/Moerdijk The Netherlands Introduction
More informationTesting in Accordance with SFM Standard 12-7A-1: Fire Resistive Standard for Exterior Wall Siding and Sheathing
Testing in Accordance with SFM Standard 12-7A-1: Fire Resistive Standard for Exterior Wall Siding and Sheathing LP FlameBlock Fire-Rated OSB Sheathing (7/16 Minimum Nominal Thickness) with Various Claddings:
More informationEvidence of Performance
Evidence of Performance Air permeability, Watertightness and wind load Test Report No. 15-003209-PR02 (PB-F01-02-en-01) Client Product Designation Performance-relevant product details Overall dimensions
More informationTitle: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1: Notified Body No: 0833 Product Name:
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: CLASSIFICATION OF REACTION TO
More informationNot to be distributed outside of FM Approvals and its affiliates except by Customer
Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT APPROVAL EXAMINATION ZEE-LOCK DOUBLE LOCK SYSTEM OVER FM APPROVED STEEL DECK PER FM 4471 Prepared for:
More informationEvaluation Report. for. Empire West, Inc Graton Road Post Office Box 511 Graton, California 95444
for Empire West, Inc. 9270 Graton Road Post Office Box 511 Graton, California 95444 CertMark International Pty Ltd (CMI) has awarded this Certification to the company named above for the Product/system
More informationThe experimental programme for this stage of the project has been undertaken in three phases:
Annex A Floor Voids General In order to investigate the potential for unseen fire spread to occur through voids in suspended floor systems, a series of experiments have been undertaken utilising a commercially
More informationBS 476: Part 7: Method For Classification Of The Surface Spread Of Flame Of Products. A Report To: Geaves Surface Solutions Ltd
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS 476: Part 7: 1997 Method For Classification
More informationWFRC TEST REPORT NO BS 476: Part 7: 1997 Method For Classification Of The Surface Spread Of Flame Of Products.
WFRC TEST REPORT NO 142605 BS 476: Part 7: 1997 Method For Classification Of The Surface Spread Of Flame Of Products Sponsored By Mactac UK Limited 4-6 The Britannia Trade Centre Ryehill Close Lodge Farm
More informationAn Effective Pool Fire Mitigation Concept
An Effective Pool Fire Mitigation Concept D. (Dave) van Vliet, J.F.M. (Jos) Wessels, W.H.A. (Willy) Peelen and G.J. (Gert-Jan) Meijer TNO, the Netherlands V.J.A. (Victor) Meeussen Efectis, the Netherlands
More informationReport on Spread of Flame and Burning Brand Performance of Generic Installations
Report on Spread of Flame and Burning Brand Performance of Generic Installations Date: January 23, 2014 Revised March 20, 2014 Bob Backstrom Research Engineer, Fire Group, Corporate Research Chad Fisher
More informationRainfall and impact noise measurements on metal roof tiles
Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research TNO report DGT-RPT-040015 Rainfall and impact noise measurements on metal
More informationCORRELATION BETWEEN 8-FOOT TUNNEL FURNACES
U.S. DEPARTMENT OF AGRICULTURE FOREST SERVICE FOREST PRODUCTS LABORATORY MADISON, WIS. U.S. FOREST SERVICE RESEARCH NOTE FPL - 058 August 1964 CORRELATION BETWEEN 8-FOOT TUNNEL FURNACES Abstract Flammability
More informationWORLD S 2 MM SOLAR GLASS
WORLD S FIRST MM HIGH PERFORMANCE FULLY TEMPERED SOLAR GLASS ONE TECHNOLOGY MANY ADVANTAGES Bi-facial modules deliver upto 3% more power Increased module life upto 4 years Higher reliability - reduced
More informationREPORT NUMBER: SAT-001 ORIGINAL ISSUE DATE: March 23, 2010 REVISED DATE: NA
TEST REPORT REPORT NUMBER:3195900SAT-001 ORIGINAL ISSUE DATE: March 23, 2010 REVISED DATE: NA EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Road Elmendorf, TX 78112 RENDERED TO
More informationNew Test Method To Assess The Walkability Of Roof Insulation Boards. Nico A. Hendriks
New Test Method To Assess The Walkability Of Roof Insulation Boards Nico A. Hendriks KEY WORDS: Insulation boards, roofing, walkability, test method and dynamic loading ABSTRACT For many years problems
More informationcombustibility behaviour of insulation products
1 combustibility behaviour of insulation products Smouldering and continuous glowing Smouldering and continuous glowing are slow internal combustion processes that can lead to fires breaking out some distance
More informationTitle: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN : 2007 Notified Body No: 0833 Product Name:
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: CLASSIFICATION OF REACTION TO
More informationBRE Global Test Report
BRE Global Test Report BS 476: Part 3: 2004 + A1: 2006 + A2: 2007 External fire exposure to roofs test on Sarnafil G410-12 EL membrane over SarnaTherm G/TR27 on a Plywood deck Prepared for: Sika Limited
More informationRainfall and impact noise measurements on metal roof tiles
Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research TNO report DGT-RPT-040015 Rainfall and impact noise measurements on metal
More informationCeiling Tiles C200B - Specification
Ceiling Tiles C200B - Specification SECTION 09510 ACOUSTICAL CEILING TILES PART 1 GENERAL 1.00 GENERAL A. Sound Quality Acoustical Ceiling Tiles by Sound Seal, 50 H.P. Almgren Drive, Agawam, MA 01001;
More informationBS 476: Part 7: Method For Classification Of The Surface Spread Of Flame Of Products. A Report To: Contra Vision. Document Reference:
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Method For Classification Of The Surface
More informationTitle: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN : 2002 Notified Body No: 0833 Product Name: Mix Report No:
Title: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1: 2002 Notified Body No: 0833 Product Name: Mix Report No: 155547 Issue No: 1 Prepared for: Tessera Carpet Tiles, Unit
More informationPhenolic foam thermal insulation products for buildings and building services end use applications
BS xxxx-1:2010 Phenolic foam thermal insulation products for buildings and building services end use applications Part 1 - Specification for phenolic foam (PF) products for use as thermal insulation for
More informationNFP Epiradiateur Test. WF Report Number: (Issue 2) Test Sponsor: Fiba Tech Industries Limited. Date of original report:
NFP 92-501 Epiradiateur Test WF Report Number: 145349 Test Sponsor: Fiba Tech Industries Limited Date of original report: 15 th March 2005 Date of issue 2: 18 th March 2005 Page 2 of 9 Warringtonfire Test
More informationA NEW APPARATUS FOR FLAME SPREAD EXPERIMENTS
th International Conference on Structural Mechanics in Reactor Technology (SMiRT ) - A NEW APPARATUS FOR FLAME SPREAD EXPERIMENTS Johan Mangs VTT Technical Research Centre of Finland, Espoo, Finland ABSTRACT
More informationClass 0 Summary Report
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Class 0 Summary Report Including Opinion
More informationBRE Global Test Report
BRE Global Test Report BS 476: Part 3: 2004 + A1: 2006 + A2: 2007 External fire exposure to roofs test on SolFit Top Loader. Prepared for: SolFiT Ltd Date: 19 November 2016 Report Number: P105772-1000
More informationJune 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON REFLECTIVE FOIL INSULATION
June 1, 2010 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON REFLECTIVE FOIL INSULATION SUBJECT: Proposed Revisions to the Acceptance Criteria for Reflective Foil Insulation, Subject AC02-0610-R1 (LS/RB)
More informationEuropean Technical Assessment. ETA 17/0154 of 27/03/2017. ALSAN Flashing quadro. Liquid applied roof waterproofing kit on the basis of plyurethane
Member of Kiwa Nederland B.V. Sir Winston Churchilllaan 273 2288 EA Rijswijk The Netherlands www.kiwa.nl www.eota.eu European Technical Assessment ETA 17/0154 of 27/03/2017 General Part Technical Assessment
More informationCrystalTM Tapis Coton
CrystalTM Tapis Coton #10 black/white #30 brown #70 anthracite Les tapis coton CrystalTM empêchent la poussière et l humidité de se disperser dans des bâtiments. Ces tapis en coton absorbent la poussière
More informationBS 476: Part 7: Method For Classification Of The Surface Spread Of Flame Of Products. A Report To: Thermaflex International Holding B.V.
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS 476: Part 7: 1997 Method For Classification
More informationThis document is a preview generated by EVS
INTERNATIONAL STANDARD ISO 3850 First edition 2004-04-01 Resilient floor coverings Determination of apparent density of composition cork Revêtements de sol résilients Détermination de la masse volumique
More informationEuropean Architectural Barometer
European Architectural Barometer Survey and Reports Economical part Today s main issues Development of the order book Turnover development Impact of the economic situation Opportunities and threats Predictions
More informationBS :2005 test on a Kingspan Benchmark External Wall Insulation System
BS 8414-2:2005 test on a Kingspan Benchmark External Wall Insulation Prepared for: Kingspan Ltd. Carrickmacross Road Kingscourt County Cavan Ireland 7 September 2011 0578 Page 1 of 30 Prepared on behalf
More informationCREATING A FIRE ADAPTED HOME
THE IBHS GUIDE TO CREATING A FIRE ADAPTED HOME What Does it Take to Protect Your Home from Wildfire? Protecting your home from wildfire damage requires limiting the amount of fuel that could bring flames
More informationHIGH PERFORMANCE PIR INSULATION
HIGH PERFORMANCE PIR INSULATION FOR RESIDENTIAL, INDUSTRIAL AND AGRICULTURAL APPLICATIONS Export Delivery Programme Lambda 0.022 from 20 mm up to 200 mm www.unilininsulation.com UNILIN, division insulation
More informationDIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS/WEATHER BARRIERS
0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1504 Reissued 03/2017 This report is subject to renewal 03/2018. DIVISION: 07 00
More informationJuly 23, 2010 PARTIES INTERESTED IN REFLECTIVE FOIL INSULATION
July 23, 2010 TO: SUBJECT: PARTIES INTERESTED IN REFLECTIVE FOIL INSULATION Revisions to the Acceptance Criteria for Reflective Foil Insulation, Subject AC02-0610-R1 (LS/RB) Dear Madam or Sir: In June
More informationTitle: EXTENDED APPLICATION REPORT IN ACCORDANCE WITH EN/TS Notified Body No: 0833 Product Name:
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: EXTENDED APPLICATION REPORT IN
More information1 st August Title: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1: 2009.
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: CLASSIFICATION OF REACTION TO
More informationBS 476: Part 7: Method For Classification Of The Surface Spread Of Flame Of Products. WF Report Number: Test Sponsor:
BS 476: Part 7: 1997 Method For Classification Of The Surface Spread Of Flame Of Products WF Report Number: 146240 Test Sponsor: Wilhelm Kaimann GmbH & Co. KG Date: 13 th April 2005 Page 2 of 11 Warringtonfire
More informationWe create links in the world of chemical and mineral specialities.
We create links in the world of chemical and mineral specialities. Our business model: trading, distribution and production under one roof Global procurement market Worldwide sourcing Development and production
More informationCONSTRUCTION MATERIALS
CONSTRUCTION MATERIALS T E C H N O L O G I E S WATER PONDING EVALUATION OF THE EDGE TM VENT (PROJECT NO. AVIG-004-02-01) For AIR VENT, INC. 4117 PINNACLE POINT DRIVE, SUITE 200 DALLAS, TX 75211 JUNE 20,
More informationKiwa Castor Gaea Manual
Manual K15012 January 2016 Kiwa Castor Gaea Manual Classification of Circular Economy aspects of products and or processes. Kiwa Nederland B.V. Sir Winston Churchilllaan 273 Postbus 70 2280 AB RIJSWIJK
More informationIMO Resolution MSC 307(88): Annex 1: Part 5
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com IMO Resolution MSC 307(88): Annex 1: Part
More informationBS 476: Part 6: Method Of Test For Fire Propagation For Products. WF Additional Report Number: Date: 18 th February 2008.
BS 476: Part 6: 1989 Method Of Test For Fire Propagation For Products WF Additional Report Number: 170998 Date: 18 th February 2008 Test Sponsor: Lindab Limited 0249 Page 2 of 15 Bodycote warringtonfire
More informationBS EN ISO : 1999
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN ISO 4589-2: 1999 Determination of
More informationEN 356 Glass in Building-Security glazing-testing and classification of resistance against manual attack SaoSA Resin Laminated Glass (4-1.
TNO report TC-RAP-06-22617/rie EN 356 Glass in Building-Security glazing-testing and classification of resistance against manual attack SaoSA Resin Laminated De Rondom 1 P.O. Box 6235 The Netherlands www.tno.nl
More informationTitle: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009 Notified Body No: 0833 Product Name: Type II
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: CLASSIFICATION OF REACTION TO
More informationDecember 3, 2012 PARTIES INTERESTED IN INTUMESCENT FIRE-RESISTANT COATINGS FIELD-APPLIED TO PREFABRICATED WOOD I-JOISTS
December 3, 2012 TO: PARTIES INTERESTED IN INTUMESCENT FIRE-RESISTANT COATINGS FIELD-APPLIED TO PREFABRICATED WOOD I-JOISTS SUBJECT: Proposed Acceptance Criteria for Intumescent Fire-resistant Coatings
More informationSOUTH AFRICAN NATIONAL STANDARD
ISBN 978-0-626-29899-9 Edition 1 ASTM E 108:2011 Edition 13 SOUTH AFRICAN NATIONAL STANDARD Fire testing of materials, components and elements used in buildings Part 12: Test methods for fire tests of
More informationSection SoundPly RF M25 Acoustic Wall Panels
Section 097714 Acoustic Wall Panels PART 1 GENERAL 1.1 RELATED DOCUMENTS 1.2 SUMMARY A. Drawings and general conditions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationBS 476: Part 3: 2004 test on SureSeal EPDM 1.2mm on a plywood deck
BS 476: Part 3: 2004 test on SureSeal EPDM 1.2mm on a plywood deck Prepared for: Flex-R Ltd Unit 5 Central Park Bellfield Road High Wycombe Bucks HP13 5HG 5 th December 2012 Test report number 281504B
More informationProfessional Adhesives and Sealants
Professional Adhesives and Sealants PERFECTLY MATCHING YOUR NEEDS www.hardcast.nl More than 1,600 Possible Specifications HARDCAST Sealing Diversity for Roofs and Façades WIDTH: HARDCAST tapes can be produced
More informationEN : A1:2015
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com EN 45545-2: 2013 + A1:2015 Summary Test
More informationALPOLIC /fr for External Cladding
ALPOLIC /fr for External Cladding Mitsubishi Chemical Functional Products, Inc. JUL 2002 Contents Outline of ALPOLIC /fr 1 1. Material composition 2 2. Production process 2 3. Features 3 4. Rigidity 3
More informationAPPLICATION: Roof insulation warm pitched roof
138 APPLICATION: Product: Jabroof Premium panel Jabroof Premium panel is specially designed to be incorporated into warm pitched-roof constructions to provide a high level of insulation to meet the current
More informationSummary Investigation concerning the long-term behaviour of Polygum roofs in practice Order No.: 00-B-0111 Ref.: AFVDH/JB
Summary Investigation concerning the long-term behaviour of Polygum roofs in practice Order No.: 00-B-0111 Ref.: AFVDH/JB Client: Contact person: Project: ATAB NV / SA d Herbouvillekaai 80 B-2020 Antwerp
More informationASTM E 648 Test Method. 5/8" Walnut Engineered Wood Flooring
FIRE RATINGS Walnut Report On Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source As Determined By ASTM E 648 Test Method PREPARED FOR: DuChateau Floors San Diego,CA TEST
More informationDICKSON COATINGS FIRE TEST REPORT
DICKSON COATINGS FIRE TEST REPORT SCOPE OF WORK ASTM E84-17a TESTING ON JET TEX WALL REPORT NUMBER 103427765SAT-001B TEST DATE(S) 2/28/18 ISSUE DATE 2/28/18 PAGES 10 DOCUMENT CONTROL NUMBER RT-R-AMER-Test-2780
More informationFISSIC FIRE PROOF COATING GAS TIGHT SURFACE, NO WATER ABSORPTION SALT WATER RESISTANT
SAFETY WE CARE FISSIC FIRE PROOF COATING GAS TIGHT SURFACE, NO WATER ABSORPTION SALT WATER RESISTANT TECHNOLOGY DEVELOPED BY BEELE ENGINEERING BV COMPOUNDING AND PRODUCTION IN THE ULTRA-MODERN MANUFACTURING
More informationAgrément Certificate 2009/367
Agrément Certificate 2009/367 Copyright Agrément South Africa, November 2009 The master copy of this document appears on the website: http://www.agrement.co.za Validity Users of any Agrément certificate
More informationBRE Global Test Report
BRE Global Test Report Classification of reaction to fire performance in accordance with EN 13501-1: 2007 + A1: 2009 on Multi-Pro, Multi-Pro XS and Render Pro Prepared for: Resistant Building Products
More informationFIRE RATINGS. European Oak
FIRE RATINGS European Oak Report On Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source As Determined By ASTM E 648 Test Method PREPARED FOR: DuChateau Floors San Diego,
More informationOverview of Exolit Flame retardants in thermoset applications
Overview of Exolit Flame retardants in thermoset applications Dr. Frank Osterod TM & Development BL Flame Retardants 02.05.2013 2 Applications for thermosets and composites 3 Product groups and chemistry
More informationCSIRO Materials Science and Engineering 14 Julius Avenue, Riverside Corporate Park, North Ryde NSW 2113 Ph: Fax:
Test on palm fibre and MgO composite board at 50-kW/m² irradiance in accordance with AS/NZS 3837:1998 Report number FNK 10294 CSIRO job number NK6432 Date of Issue: 27 October 2011 Client PalmEco Tech
More informationTried, Tested and Trusted Fire Protection
September 2017 NON-COM Exterior Fire Protection SPECIFIER S GUIDE EXTERIOR 1 IN LINE WITH NHBC STANDARDS 2 Tried, Tested and Trusted Fire Protection 3 Fire can devastate buildings and lives in a matter
More informationDICKSON COATINGS FIRE TEST REPORT
DICKSON COATINGS FIRE TEST REPORT SCOPE OF WORK ASTM E84-17a TESTING ON JET UP BC REPORT NUMBER 103427765SAT-001A TEST DATE(S) 2/27/18 ISSUE DATE 2/28/18 PAGES 10 DOCUMENT CONTROL NUMBER RT-R-AMER-Test-2780
More informationCLASSIFICATION REPORT
IJ LNE -~~. ~{~11 Le progrès, une passion eipartager LABORATOIRE DE TRAPPES 29 avenue Roger Hennequin - 78197 Trappes Cedex Tél. : 01 30691000 - Fax: 01 30691234 File F110743-Document CEMATE/53 -Page 1/5
More information