Not to be distributed outside of FM Approvals and its affiliates except by Customer

Size: px
Start display at page:

Download "Not to be distributed outside of FM Approvals and its affiliates except by Customer"

Transcription

1 Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT APPROVAL EXAMINATION ZEE-LOCK DOUBLE LOCK SYSTEM OVER FM APPROVED STEEL DECK PER FM 4471 Prepared for: Berridge Manufacturing Company 1720 Maury Houston, TX Project ID: Class: 4471 Date of Approval: 4/26/2013 Authorized by: Cynthia Frank, Group Manager, FM Approvals FM Approvals 1151 Boston Providence Turnpike P.O. Box 9102 Norwood, MA Page 1 of 7

2 APPROVAL EXAMINATION ZEE-LOCK DOUBLE LOCK SYSTEM OVER FM APPROVED INSULATED STEEL DECK PER FM 4471 from Berridge Manufacturing Company 1720 Maury Houston, TX I INTRODUCTION 1.1 Berridge Manufacturing Company submitted for Approval their ZEE-Lock Double Lock metal panel roof system for increased wind uplift rating for Approval over FM Approved Insulated Steel Deck per the Approval Standard listed below. 1.2 Previous tests have been conducted on the currently Approved Berridge Manufacturing Company metal panel roof system per FM Approval Standard See Report 2Y5A1.AM for details. 1.3 This Report may be reproduced only in its entirety and without modification. 1.4 Standard: Title Class Number Date Approval Standard for Class 1 Panel Roofs 4471 March Examination included simulated wind uplift pressure tests and ASTM E108 testing. 1.6 Tests show that the Berridge Manufacturing Company ZEE-Lock Double Lock metal panel roof system over FM Approved Class 1 steel deck, as tested, meet the FM Approval requirements of the FM 4471 Approval Standard as outlined in the CONCLUSIONS. 1.7 Listings: The tested constructions meet the Approval criteria of FM Approvals when installed as specified in the CONCLUSIONS of this report and will be listed in RoofNav. II DESCRIPTIONS All products are as described in RoofNav. Proprietary formulations, specifications and drawings are on file at FM Approvals. III EXAMINATIONS AND TESTS 3.1 Samples were submitted for examination and testing as outlined below Tests conducted were as required by the FM 4471 Approval Standard. Hail damage and Foot Traffic testing was waived due to satisfactory performance of these panels in Project I.D.# Page 2 of 7

3 2Y5A1.AM. Calorimeter testing for the H-Shield was waived due to satisfactory performance of a more critical construction in Project I.D.# , , and , sponsored by Hunter Panels LLC. This information was released to Berridge Manufacturing for the purpose of this Approval program. Calorimeter testing for the ACFoam-II was waived due to satisfactory performance of a more critical construction in Project I.D.# & , sponsored by Atlas Roofing Corp and released to Berridge Manufacturing for the purpose of this Approval program. Approval Requirement Wind Uplift Testing Internal Fire Testing ASTM E108 Testing Hail Testing Foot Traffic Testing Included/Waived Included Waived completed by insulation manufacturers see above Included in this program Waived see Project ID# 2Y5A1.AM Waived see Project ID# 2Y5A1.AM All test samples were produced under the FM Approvals Surveillance Audit program as indicated by FM Approvals labels. All samples were considered to be representative of standard production and were examined and tested as indicated below All components incorporated into test samples were selected by FM Approvals personnel. Test samples were prepared by, or under the supervision of, FM Approvals personnel All data is on file at FM Approvals under Project I.D. # along with other documents and correspondence applicable to this program. 3.2 FM Approvals 12x24 ft (3.7x7.3 m) Simulated Wind Uplift Pressure Tests Tests were conducted using the FM Approvals Uplift Pressure Test Apparatus to evaluate the ability of the above deck components of the roofing system to resist a minimum simulated wind uplift pressure of 60 psf (2.9 kpa) without failure of the assemblies The simulated wind uplift pressure tests utilized a 24 ft. (7.3 m) long by 12 ft. (3.7 m) wide by 2 in. (51 mm) deep steel pressure vessel arranged to apply air pressure at pre-established standard rates to the underside of the test sample which formed the top of the pressure vessel. The vessel was pressurized with compressed air A net pressure of 30 psf (1.4 kpa) was applied to each test sample and maintained for 1 minute before the net pressure was reduced to 0 psf (0 kpa) and the test panels were inspected. The pressure was increased to 45 psf (2.2 kpa) and held for 1 minute, reduced to 0 psf (0 kpa) and the test panels were inspected. The pressure was increased in increments of 15 psf (0.7 kpa), held at each increment for 1 minute, reduced to 0 psf (kpa) and the test panels were inspected after each increment until failure occurred Two 12 by 24 ft. (3.7 by 7.3 m) test samples were prepared. The components, sequence of installation and test results were as follows: Sample #1 SSR: Insulation: Zee-Lock Double Lock and Zee-Rib Clips at a rate of 18 in (457 mm) o.c. with Triangle Concealer Fasteners. Seams were crimped using seamer tool. two layers of 3.0 in (76 mm) thick H-Shield and one layer of 0.5 in (13 mm) FM Page 3 of 7

4 Deck: Approved polyisocyanurate insulation, loose laid (this layer added to meet test frame height only) Steel deck, FM Approved 22 ga. Grade 33 Steel Deck secured to the ¼ in (6 mm) thick steel deck supports spaced 6 ft (1.8 m) o.c. with one, Traxx/5 fasteners spaced 6 in. (152 mm) o.c.. The deck side laps secured with one ICH Traxx/1 fastener spaced 24 in (610 mm) o.c. Perimeter securements spaced 6 in. (152 mm) o.c. along the 24 ft (7.3 m) length and 6 in. (152 mm) o.c. along the 12 ft (3.7 m) length using Traxx/5 fasteners Test results #1: The sample met the 120 psf (5.7 kpa) minimum FM Approvals requirement for Class windstorm classification. The sample failed on the increase to the next pressure level. The failure mode was fastener pull out from the deck. Sample #2 SSR: Insulation: Deck: Zee-Lock Double Lock and Zee-Rib Clips at a rate of 12 in (305 mm) o.c. with Triangle Concealer Fasteners. Seams were crimped using seamer tool. two layers of 3.0 in (76 mm) thick H-Shield and one layer of 0.5 in (13 mm) FM Approved polyisocyanurate insulation, loose laid (this layer added to meet test frame height only) Steel deck, FM Approved 22 ga. Grade 33 Steel Deck secured to the ¼ in (6 mm) thick steel deck supports spaced 6 ft (1.8 m) o.c. with one, Traxx/5 fasteners spaced 6 in. (152 mm) o.c.. The deck side laps secured with one ICH Traxx/1 fastener spaced 24 in (610 mm) o.c. Perimeter securements spaced 6 in. (152 mm) o.c. along the 24 ft (7.3 m) length and 6 in. (152 mm) o.c. along the 12 ft (3.7 m) length using Traxx/5 fasteners Test results #2: The sample met the 150 psf (7.2 kpa) minimum FM Approvals requirement for Class windstorm classification. The sample failed after 53 seconds at the next pressure level. The failure mode was fastener pull out from the deck. 3.3 ASTM E108 Spread of Flame Tests The fire tests from above the roof cover were conducted in accordance with ASTM E Spread of Flame Tests Sample size was 3-1/3 by 8 ft (1.0 by 2.4 m) The wind velocity over the top of the standard panel was adjusted to 12±0.5 mph (5.3±0.2 m/s) Flame exposure: The flame was adjusted to 1400±50 o F (760±28 o C) for Class A tests. The flame temperature was measured by a thermocouple located 1 in (25.4 mm) above the surface of the standard panel and 1/2 in (13 mm) toward the flame source from the lower edge of the standard panel. The flame was applied to each test panel for 10 minutes During and after the application of the flame, each panel was observed for the distance of maximum flame spread, glowing brands and other damage Three 3-1/3 by 8 ft (1.0 by 2.4 m) test samples were prepared. The components and sequence of installation were as follows: Page 4 of 7

5 Sample #1 & 3: Roof Cover: Cee-Lock panel* and Cee-Rib Clips* mechanically fastened at a rate of 18 in (457 mm) o.c. Insulation: 3.0 in (76 mm) thick H-Shield, pre-secured Deck: plywood * This product was removed from Approval program at customer s request. ASTM E108 samples are included here as the more critical metal panel used for the external fire tests Sample #2: Roof Cover: Cee-Lock panel* and Cee-Rib Clips* mechanically fastened at a rate of 18 in (454 mm) o.c. Insulation: 1.5 in (38 mm) thick ACFoam II, pre-secured Deck: plywood * This product was removed from Approval program at customer s request. ASTM E108 samples are included here as the more critical metal panel used for the external fire tests Results: Sample No. Slope Class Tested Max. Flame Spread Class Passed 1 5 in 12 A 26 in (0.66 m) A 2 5 in 12 A 23 in (0.58 m) A 3 5 in 12 A 25 in (0.64 m) A + + Confirmation sample for both Deck exposure, flying brands and significant lateral flame spread were not observed during the tests. IV MARKING 4.1 The manufacturer shall mark each product or packaging with the manufacturer's name and product trade name. In addition, the product or packaging must be marked with the Approval Mark of FM Approvals. 4.2 Markings denoting Approval by FM Approvals shall by applied by the manufacturer only within and on the premises of manufacturing locations under the FM Approvals Facilities and Procedures Audit program. 4.3 The manufacturer agrees that use of the FM Approvals name or Approval Mark is subject to the conditions and limitations of the Approval by FM Approvals. Such conditions and limitations must be included in all references to Approval by FM Approvals. V REMARKS 5.1 The securement of the roof system must be enhanced at the building corners and perimeter as outlined in FM Global Property Loss Prevention Data Sheets 1-29 and The roof cover must be installed using a roof perimeter flashing system Approved by FM Approvals. Refer to RoofNav. Page 5 of 7

6 VI SURVEILLANCE AUDITS Berridge Manufacturing Company manufacturing location in Seguin, TX is subject to periodic audit inspections to determine that the quality and uniformity of the materials have been maintained and will provide the same level of performance as originally Approved. The facilities and quality control procedures in place have been found to be satisfactory to manufacture product identical to that examined and tested as described in this report. VII MANUFACTURER'S RESPONSIBILITIES 7.1 To assure compliance with his procedures in the field, the manufacturer shall supply to the installer such necessary instruction or assistance required to produce the desired performance achieved in the tests. 7.2 The manufacturer shall notify FM Approvals of any planned change in the Approved products, prior to general sale or distribution, using Form 797, Approved Product Revision Report. VIII DOCUMENTATION No new audit documents were created as a results of this Approval program. IX CONCLUSIONS 9.1 The results from this and previous programs sponsored by Berridge Manufacturing Company indicate that the ZEE-Lock Double Lock metal panel roof system over FM Approved Class 1 steel deck meets the FM Approval requirements of the FM 4471 Approval Standard as outlined below SSR: Zee-Lock Double Lock and Zee-Rib Clips at a rate of 18 in (457 mm) o.c. with Triangle Concealer Fasteners Insulation: Optional Minimum 1.5 in (38 mm) thick H-Shield or ACFoam-II, loose laid Deck: Steel deck, FM Approved minimum 22 ga. Steel Deck secured to the ¼ in (6 mm) thick steel deck supports spaced maximum 6 ft (1.8 m) o.c. with one, Traxx/5 fasteners spaced 6 in. (152 mm) o.c.. The deck side laps secured with one ICH Traxx/1 fastener spaced 24 in (610 mm) o.c. Perimeter securements spaced 6 in. (152 mm) o.c. along the 24 ft (7.3 m) length and 6 in. (152 mm) o.c. along the 12 ft (3.7 m) length using Traxx/5 fasteners ASTM E108: Meets Class 5 in 12 slope Wind: Meets Class SSR: Zee-Lock Double Lock and Zee-Rib Clips at a rate of 12 in (305 mm) o.c. with Triangle Concealer Fasteners Insulation: same as Insulation in Deck: same as deck in ASTM E108: Meets Class 5 in 12 slope Page 6 of 7

7 Wind: Meets Class Consult Roofnav for hail ratings and details of all assemblies. 9.3 Tests show that the tested roof constructions in and of themselves would not create a need for automatic sprinklers. 9.4 Since a duly signed Master Agreement is on file for this customer, Approval is effective as of the date of this report. 9.5 Continued Approval will depend upon satisfactory field experience and periodic Facilities and Procedures Audits. TESTING SUPERVISED BY: Joanna M. Blaney PROJECT DATA RECORD: ORIGINAL TEST DATA: 2Y5A1.AM, , , , , and ATTACHMENTS: REPORT BY: None REPORT REVIEWED BY:.. Joanna M. Blaney Phillip J. Smith, P.E. Advanced Engineer - Materials Group AVP/Technical Team Manager - Materials Group Page 7 of 7

EXPLORATORY SIMULATED WIND UPLIFT PRESSURE TESTING OF PANELCRAFTTM STANDING SEAM METAL ROOF SYSTEMS

EXPLORATORY SIMULATED WIND UPLIFT PRESSURE TESTING OF PANELCRAFTTM STANDING SEAM METAL ROOF SYSTEMS ,... ) RESEARCH REPORT EXPLORATORY SIMULATED WIND UPLIFT PRESSURE TESTING OF PANELCRAFTTM STANDING SEAM METAL ROOF SYSTEMS Prepared For: BUILDING RESEARCH SYSTEMS INC. 247 N. BROADWAY SUITE 203 EDMOND,

More information

CBUCK Engineering. Evaluation Report Cee Lock Panel Metal Roof Assembly

CBUCK Engineering. Evaluation Report Cee Lock Panel Metal Roof Assembly Specialty Structural Engineering CBUCK, Inc. Certificate of Authorization #8064 Prepared by: James L. Buckner, P.E., S.E.C.B. Florida Professional Engineer # 31242 Florida Evaluation ANE ID: 1916 Project

More information

Force Engineering & Testing Inc Ramblewood Drive. Humble,TX Product Evaluation Report SENTRIGARD METAL ROOFING SYSTEMS

Force Engineering & Testing Inc Ramblewood Drive. Humble,TX Product Evaluation Report SENTRIGARD METAL ROOFING SYSTEMS Force Engineering & Testing Inc. Product Evaluation Report SENTRIGARD METAL ROOFING SYSTEMS Sentrigard ML 200 24 Ga. 18 7/8" Wide Roof Panel over open framing Florida Product Approval # 9864.2 R4 Florida

More information

CBUCK Engineering. Product: Zee-Lock Roof Panel Material: Steel Panel Thickness: 24 gauge Panel Width: 16 Support: Wood Deck

CBUCK Engineering. Product: Zee-Lock Roof Panel Material: Steel Panel Thickness: 24 gauge Panel Width: 16 Support: Wood Deck Evaluation Report Zee-Lock With Continous Zee-Rib Clip Metal Roof Assembly Manufacturer: 1720 Maury Road Houston, TX 77026 (800) 231-8127 2333 for Florida Product Approval HVHZ # FL 15471.1 Florida Building

More information

FLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC.

FLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. 26 Ga. GulfRib Roof Panel over 15/32 Plywood Florida Product Approval #11651.22 R3 Florida Building Code 2017 Per Rule 61G20-3 Method:

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

Residential, 26 Ga. Roof Panel over 15/32 Plywood. Florida Product Approval # R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D

Residential, 26 Ga. Roof Panel over 15/32 Plywood. Florida Product Approval # R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D Product Evaluation Report REED S METAL, INC. Residential, 26 Ga. Roof Panel over 15/32 Plywood Florida Product Approval # 12725.2 R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D Category: Roofing

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

Florida Product Approval # R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D

Florida Product Approval # R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D Product Evaluation Report REED S METALS, INC. Perma-Lok, 26 Ga. 16 Coverage Roof Panel over 15/32 Plywood Florida Product Approval # 12725.1 R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D Category:

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 NOTICE OF ACCEPTANCE

More information

FLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC.

FLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. 26 Ga. GulfRib Roof Panel over 15/32 Plywood Florida Product Approval #11651.23 R3 Florida Building Code 2017 Per Rule 61G20-3 Method:

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590

More information

FM APPROVALS Boston Providence Turnpike, Norwood, MA Phone: (781) Fax: (781) E mail:

FM APPROVALS Boston Providence Turnpike, Norwood, MA Phone: (781) Fax: (781) E mail: THE DEVELOPMENT OF FM APPROVAL STANDARDS FOR CLASS ONE STEEP ROOF COVERS, FLEXIBLE PHOTOVOLTAIC MODULES, AND VEGETATIVE ROOF SYSTEMS BY DAVID L. ALVES FM APPROVALS 1151 Boston Providence Turnpike, Norwood,

More information

Wood Decks Testing Reveals Best Wood Roof Deck Systems to Resist Wind-Uplift by Fulton Desler, senior engineer, APA The Engineered Wood Association

Wood Decks Testing Reveals Best Wood Roof Deck Systems to Resist Wind-Uplift by Fulton Desler, senior engineer, APA The Engineered Wood Association This article was originally published in Western Roofing January/February 2007 Wood Decks Testing Reveals Best Wood Roof Deck Systems to Resist Wind-Uplift by Fulton Desler, senior engineer, APA The Engineered

More information

Approval Standard for Class 1 Insulated Steel Deck Roofs

Approval Standard for Class 1 Insulated Steel Deck Roofs Approval Standard for Class 1 Insulated Steel Deck Roofs Class Number 4450 February 1989 2002 FM Approvals LLC. All rights reserved. Foreword The FM Approvals certification mark is intended to verify that

More information

Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT

Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT Project No: 3046488 Class: 2511 Product Designation: Name of Listing Company: AquaFence Perimeter Flood

More information

Recommended Fastening Patterns for Rmax Insulation in Low Slope Roofing Applications

Recommended Fastening Patterns for Rmax Insulation in Low Slope Roofing Applications Recommended Fastening Patterns for Rmax Insulation in Low Slope Roofing Applications INTRODUCTION Rmax recommends that any insulation which is laid over a steel or wood roof deck be attached with mechanical

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS REPORT HOLDER: METAL SALES MANUFACTURING CORPORATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS REPORT HOLDER: METAL SALES MANUFACTURING CORPORATION 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (0) 3-87 (562) 699-03 www.icc-es.org ESR-23 Reissued 08/2017 This report is subject to renewal 08/2019. DIVISION: 07 00 00 THERMAL

More information

CBUCK Engineering. Florida Product Approval # FL R2

CBUCK Engineering. Florida Product Approval # FL R2 Specialty Structural Engineering CBUCK, Inc. Certificate of Authorization #8064 Prepared by: James L. Buckner, P.E., SECB Florida Professional Engineer # 31242 Florida Evaluation ANE ID: 1916 Project Manager:

More information

SHEET METAL ROOF TEST REPORT

SHEET METAL ROOF TEST REPORT SHEET METAL ROOF TEST REPORT Introduction The time tested performance of the double lock standing seam and batten seam metal roofing is demonstrated by thousands of squares successfully installed by SMACNA

More information

CITY OF RICHMOND PINE CAMP COMMUNITY CENTER ROOF REPLACEMENT PROJECT RCS PROJECT NO

CITY OF RICHMOND PINE CAMP COMMUNITY CENTER ROOF REPLACEMENT PROJECT RCS PROJECT NO SECTION 07220 - ROOF INSULATION PART 1 - GENERAL 1.01 DESCRIPTION A. Work included: The Roofing Contractor will provide all polyisocyanurate insulation and high density wood fiber roof insulation (tapered

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COATED FOAM ROOFING REPORT HOLDER: LAPOLLA INDUSTRIES, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COATED FOAM ROOFING REPORT HOLDER: LAPOLLA INDUSTRIES, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3916 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 07 00

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786)315-2590

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: POLYVINYL CHLORIDE ROOFING REPORT HOLDER: IB ROOF SYSTEMS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: POLYVINYL CHLORIDE ROOFING REPORT HOLDER: IB ROOF SYSTEMS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 28 Reissued 02/2018 This report is subject to renewal 02/2019. DIVISION: 07 00 00

More information

CBUCK Engineering. Evaluation Report Englert Series 500 Metal Roof Assembly Manufacturer: Englert, Inc Amboy Avenue Perth Amboy, NJ

CBUCK Engineering. Evaluation Report Englert Series 500 Metal Roof Assembly Manufacturer: Englert, Inc Amboy Avenue Perth Amboy, NJ Evaluation Report Englert Series 500 Metal Roof Assembly Manufacturer: 1200 Amboy Avenue Perth Amboy, NJ 08862 for Florida Product Approval # FL 11698.2 R3 Florida Building Code 5th Edition (2014) Method:

More information

Specifications. When specifying metal panel roof systems, roof. system designers and specifiers need to be aware

Specifications. When specifying metal panel roof systems, roof. system designers and specifiers need to be aware 32 www.professionalroofing.net OCTOBER 2012 When specifying metal panel roof systems, roof system designers and specifiers need to be aware of specific standards. Sometimes, the standards applicable to

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COATED FOAM ROOFING REPORT HOLDER: COVESTRO, LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COATED FOAM ROOFING REPORT HOLDER: COVESTRO, LLC 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1221 Reissued 12/2017 This report is subject to renewal 12/2018. DIVISION: 07 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3909 Issued 07/2017 This report is subject to renewal 07/2018. DIVISION: 07 00 00

More information

Originally Issued: 09/19/2014 Revised: 10/17/2017 Valid Through: 11/15/2017

Originally Issued: 09/19/2014 Revised: 10/17/2017 Valid Through: 11/15/2017 EVALUATION SUBJECT: QUALITY EDGE MATTERHORN METAL ING REPORT HOLDER: Quality Edge, Inc. 2712 Walkent Drive Walker, MI 49544 (888) 784-0878 www.quality-edge.com CSI Division: 07 THERMAL AND MOISTURE PROTECTION

More information

Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT. Expansion Shields

Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT. Expansion Shields Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT Project No: 0003053725 Class: 1952 Product Name: Product Type: Pipe Hanger Components for Automatic Sprinkler

More information

LEGACY REPORT DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FLUID APPLIED ROOFING REPORT HOLDER: CONKLIN COMPANY INC.

LEGACY REPORT DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FLUID APPLIED ROOFING REPORT HOLDER: CONKLIN COMPANY INC. 0 Most Widely Accepted and Trusted ICC ES Legacy Report ICC ES 000 (800) 42 6587 (562) 699 054 www.icc es.org ER 520 Reissued 09/2017 This report is subject to renewal 09/2018. DIVISION: 07 00 00 THERMAL

More information

SL175 Panel Technical Data Guide

SL175 Panel Technical Data Guide Description SL175 is a integral snap-lock standing seam roofing panel used on commercial and residential applications. The panel is factory formed in continuous lengths up to 60-0 long. Attachment to either

More information

Addendum No. 1. ITB for Emergency Management/Utilities Administration Building Renovation Addendum Release Date April 06, 2017

Addendum No. 1. ITB for Emergency Management/Utilities Administration Building Renovation Addendum Release Date April 06, 2017 City of Wilton Manors Finance Department 2020 Wilton Drive Wilton Manors, FL 33305 Phone (954) 390-2171 Fax (954)390-2199 www.wiltonmanors.com Addendum No. 1 ITB # 2016-16 ITB for Emergency Management/Utilities

More information

Understanding Wind Uplift Ratings

Understanding Wind Uplift Ratings Page 1 of 5 Home Understanding Wind Uplift Ratings By Stan Choiniere September 1, 2006 What is an FM Approvals wind test, and what do the various wind uplift ratings mean? This question is frequently asked,

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

Evaluation Report. Die Formed Skirt Ridge Ventilator. "12 Inch Throat" Manufacturer. Metallic Products Corporation Hollister Road

Evaluation Report. Die Formed Skirt Ridge Ventilator. 12 Inch Throat Manufacturer. Metallic Products Corporation Hollister Road Specialtu Structural Engineering CBUCK, Inc. Certificate of Authorization #864 Evaluation Report Die Formed Skirt Ridge Ventilator "12 Inch Throat" Manufacturer Metallic Products Corporation 7777 Hollister

More information

ANSI/FM Approvals March FM Approvals LLC. All rights reserved.

ANSI/FM Approvals March FM Approvals LLC. All rights reserved. American National Standard for Evaluating the Simulated Wind Uplift Resistance of Roof Assemblies Using Static Positive and/or Negative Differential Pressures ANSI/FM Approvals 4474 March 2004 2004 FM

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

Approval Standard. for. Flammable and Combustible Liquid Storage Buildings

Approval Standard. for. Flammable and Combustible Liquid Storage Buildings Approval Standard for Flammable and Combustible Liquid Storage Buildings Class Number 6049 August 1991 (Effective Date: August 1, 1992) 2002 FM Global Technologies LLC. All rights reserved. Foreword FM

More information

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street Oxford, CT PHONE: (203) FAX: (203)

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street Oxford, CT PHONE: (203) FAX: (203) EVALUATION REPORT Mule-Hide Products Co., Inc. 1195 Prince Hall Drive Beloit, WI 53511 EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization #9503 353 Christian Street Oxford, CT 06478 PHONE: (203)

More information

Through-Fastener Panel UL Listing documentation

Through-Fastener Panel UL Listing documentation Through-Fastener Panel UL Listing documentation Class-4 Impact Rating Class-90 Fire Rating Tensile Strength: Grade 80/E Coil Thickness Range for 29 ga.: 0.0142 0.015 Coil Thickness Range for 26 ga.: 0.0182

More information

SECTION STRUCTURAL RETROFIT ROOF SUB-FRAMING SYSTEM

SECTION STRUCTURAL RETROFIT ROOF SUB-FRAMING SYSTEM SECTION 13 34 21 - STRUCTURAL RETROFIT ROOF SUB-FRAMING SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION A. The structural retrofit roof sub-framing system will provide support for a new metal roofing system constructed

More information

ROOFING APPLICATION STANDARD (TAS) No. 102(A)-95

ROOFING APPLICATION STANDARD (TAS) No. 102(A)-95 ROOFING APPLICATION STANDARD (TAS) No. 102(A)-95 TEST PROCEDURE FOR STATIC UPLIFT RESISTANCE OF MECHANICALLY ATTACHED, CLIPPED, RIGID, ROOF SYSTEMS (For Methods of Mechanical Attachment Excluding Clips,

More information

2010 FLORIDA BUILDING CODE TEST PROTOCOLS HVHZ (TAS)

2010 FLORIDA BUILDING CODE TEST PROTOCOLS HVHZ (TAS) TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE FOR FIELD UPLIFT RESISTANCE OF EXISTING MEMBRANE ROOF SYSTEMS AND IN SITU TESTING FOR REROOF AND NEW CONSTRUCTION APPLICATIONS 1. Scope: 1.1 This

More information

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET Environmental Protection and Growth Management Department BUILDING CODE SERVICES DIVISION 1 N. University Drive, Box #302 Plantation, Florida 33324 954-765-4400 Broward.org/Building APPLICATION INFORMATION

More information

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi STRUCTURAL NOTES MATERIAL STRENGTHS Structural Steel Reinforcing Steel Concrete Masonry Structural Lumber Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel

More information

EVALUATION REPORT ICP Adhesives and Sealants, Inc NW 44 th Street Coral Springs, FL 33065

EVALUATION REPORT ICP Adhesives and Sealants, Inc NW 44 th Street Coral Springs, FL 33065 EVALUATION REPORT ICP Adhesives and Sealants, Inc. 12505 NW 44 th Street Coral Springs, FL 33065 EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization #9503 353 CHRISTIAN STREET, UNIT 13 OXFORD,

More information

Exterior Research & Design, L.L.C. Building Science and Envelope Consultants

Exterior Research & Design, L.L.C. Building Science and Envelope Consultants Exterior Research &, L.L.C. Building Science and Envelope Consultants Certificate of Authorization #9503 Evaluation Report 00256.09.06 Evaluation of Roofing s for Florida Product Approval #FL7508 Prepared

More information

Thermoplastic Single Ply & Multi-Ply Roofing Systems

Thermoplastic Single Ply & Multi-Ply Roofing Systems Thermoplastic Single Ply & Multi-Ply Roofing Systems COMMERCIAL INDUSTRIAL INSTITUTIONAL RESIDENTIAL Specializing in Roof Solutions for over 25 years FlexRoofingSystems.com Thermoplastic Single Ply Roof

More information

Exterior Research & Design, L.L.C. Building Science and Envelope Consultants

Exterior Research & Design, L.L.C. Building Science and Envelope Consultants Exterior Research & Design, L.L.C. Building Science and Envelope Consultants Certificate of Evaluation Report 3520.03.04-R2 Evaluation of Roof s for Florida Product Approval #FL2533-R2 Prepared for: CertainTeed

More information

NUCOR VR 16 II STANDING SEAM ROOF SYSTEM TABLE OF CONTENTS

NUCOR VR 16 II STANDING SEAM ROOF SYSTEM TABLE OF CONTENTS NUCOR VR 16 II STANDING SEAM ROOF SYSTEM TABLE OF CONTENTS Nucor VR16 II Vertical Rib Standing Seam Roof System...2 Nucor VR16 II Property and Span Tables...3 Standard Details...5 ED3010PE - Gutter...5

More information

ML150 Guide Specification

ML150 Guide Specification ML150 Guide Specification This specification is a guide recommendation for many metal roofing projects. It is available for downloading in both Microsoft WORD and.pdf format for your ease of use. Revise

More information

ESR-2894 Reissued April 2014 This report is subject to renewal April 1, 2016.

ESR-2894 Reissued April 2014 This report is subject to renewal April 1, 2016. ICC-ES Evaluation Report ESR-894 Reissued April 04 This report is subject to renewal April, 0. www.icc-es.org (800) 4-87 () 99-04 A Subsidiary of the International Code Council DIVISION: 07 00 00 THERMAL

More information

Code Compliance Research Report CCRR-0228

Code Compliance Research Report CCRR-0228 Code Compliance Research Report CCRR-0228 Issue Date: 05-09-2017 Renewal Date: 05-11-2018 Revision Date: 06-23-2017 DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION Section: 07 40 00 Roofing and Siding

More information

ROOF MITIGATION STRUCTURE EVALUATION FORM. For Single Family Residential Re-Roof Effective October 1, 2007 (Revised February 2, 2018)

ROOF MITIGATION STRUCTURE EVALUATION FORM. For Single Family Residential Re-Roof Effective October 1, 2007 (Revised February 2, 2018) ROOF MITIGATION STRUCTURE EVALUATION FORM For Single Family Residential Re-Roof Effective October 1, 2007 (Revised February 2, 2018) Check One Value of home does not exceed $300,000 based on insured value

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COATED FOAM ROOFING REPORT HOLDER: NCFI POLYURETHANES

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COATED FOAM ROOFING REPORT HOLDER: NCFI POLYURETHANES 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3392 Reissued 06/2017 This report is subject to renewal 06/2018. DIVISION: 07 00

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY AFFAIRS (PERA) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474

More information

TECHNICAL INFORMATION

TECHNICAL INFORMATION TECHNICAL INFORMATION SECTION 07320 TWO-PIECE TAPERED MISSION CLAY ROOFING TILE PART 1 GENERAL 1.01 SECTION INCLUDES A. Formed clay roofing tiles, complete with components and other required accessories

More information

UL Evaluation Report UL ER Issued: July 25, UL Category Code: ULFB. CSI MasterFormat

UL Evaluation Report UL ER Issued: July 25, UL Category Code: ULFB. CSI MasterFormat UL Evaluation Report UL ER10167-01 Issued: July 25, 2014 Visit UL s On-Line Certifications Directory: www.ul.com/erdirectory for current status of Report. UL Category Code: ULFB CSI MasterFormat DIVISION:

More information

1 Firestone EPDM Roofing Systems

1 Firestone EPDM Roofing Systems 1 Firestone 1. Firestone EPDM Systems To ensure a long-lasting, trouble-free roof today, it is not sufficient to manufacture high quality roofing membranes. Experience learned that roofing membranes need

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ETHYLENE PROPYLENE DIENE MONOMER ROOFING REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ETHYLENE PROPYLENE DIENE MONOMER ROOFING REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Rept ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.g ESR 3026 Reissued 04/207 This rept is subject to renewal 04/208. DIVISION: 07 00 00 THERMAL

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786)315-2590

More information

ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) PREFACE

ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) AC191 Approved May 2008 Effective June 1, 2008 Previously approved February 2008, October 2007,

More information

Originally Issued: 03/27/2015 Revised: 10/17/2017 Valid Through: 03/31/2018

Originally Issued: 03/27/2015 Revised: 10/17/2017 Valid Through: 03/31/2018 EVALUATION SUBJECT: CERTAINTEED MATTERHORN AND PRESIDIO METAL ING REPORT HOLDER: CertainTeed Corporation 20 Moores Road Malvern, PA 19355 (610) 893-5400 www.certainteed.com CSI Division: 07 THERMAL AND

More information

TRIAD CORRUGATED METAL, INC.

TRIAD CORRUGATED METAL, INC. TRIAD CORRUGATED METAL, INC. C O M M E R C I A L R E S I D E N T I A L A G R I C U L T U R A L Snap Loc Panel Guide Snap Loc metal panels are a perfect fit for residential, architectural and commercial

More information

: Plan Review and Project Services

: Plan Review and Project Services 01 34 10: Plan Review and Project Services November 7th, 2014 Contact Information Tony Schifiliti, Consultant Engineer Office: 781-440-8630 Cell: 617-771-2350 Anthony.Schifiliti@fmglobal.com George Schork,

More information

TESTING APPLICATION STANDARD (TAS) No TEST PROCEDURE FOR STATIC UPLIFT RESISTANCE OF MORTAR OR ADHESIVE SET TILE SYSTEMS

TESTING APPLICATION STANDARD (TAS) No TEST PROCEDURE FOR STATIC UPLIFT RESISTANCE OF MORTAR OR ADHESIVE SET TILE SYSTEMS TESTING APPLICATION STANDARD (TAS) No. 101-95 TEST PROCEDURE FOR STATIC UPLIFT RESISTANCE OF MORTAR OR ADHESIVE SET TILE SYSTEMS 1. Scope 2. Referenced Documents 1.1 This Protocol covers the determination

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 4 6587 (562) 699 0543 www.icc es.org ESR 3152 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 07 00 00

More information

TESTING APPLICATION STANDARD (TAS) No TEST PROCEDURE FOR WIND AND WIND DRIVEN RAIN RESISTANCE OF DISCONTINUOUS ROOF SYSTEMS

TESTING APPLICATION STANDARD (TAS) No TEST PROCEDURE FOR WIND AND WIND DRIVEN RAIN RESISTANCE OF DISCONTINUOUS ROOF SYSTEMS TESTING APPLICATION STANDARD (TAS) No. 100-95 TEST PROCEDURE FOR WIND AND WIND DRIVEN RAIN RESISTANCE OF DISCONTINUOUS ROOF SYSTEMS 1. 2. Scope 1.1 This Protocol covers the determination of the water infiltration

More information

SAM HOUSTON STATE UNIVERSITY DIVISION 07 THERMAL & MOISTURE PROTECTION SECTION ROOFING SYSTEMS DESIGN AND CONSTRUCTION STANDARDS February 2016

SAM HOUSTON STATE UNIVERSITY DIVISION 07 THERMAL & MOISTURE PROTECTION SECTION ROOFING SYSTEMS DESIGN AND CONSTRUCTION STANDARDS February 2016 PART 1: GENERAL 1.01 Scope Of Standard 1.02 Reference Standards 1.03 Quality Control A. This standard provides general guidance concerning the specific preferences of the Sam Houston State University for

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

SECTION 07530CP EPDM MEMBRANE ROOFING

SECTION 07530CP EPDM MEMBRANE ROOFING PART 1 GENERAL 1.1 SUMMARY SECTION 07530CP EPDM MEMBRANE ROOFING A. Section includes: 1. Adhered membrane roofing and flashing 2. Mechanically fastened roof insulation 3. Walkway pads 1.2 ARCHITECTURAL

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: CLAY ROOF TILES REPORT HOLDER: BORAL ROOFING LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: CLAY ROOF TILES REPORT HOLDER: BORAL ROOFING LLC 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 07 Reissued 0/207 This report is subject to renewal 2/207. DIVISION: 07 00 00 THERMAL

More information

SECTION METAL ROOF PANELS

SECTION METAL ROOF PANELS SECTION 07 41 13 PART 1 GENERAL 1.1 SECTION INCLUDES A. Standing-seam roof panels. B. Metal roofing accessories. 1.2 RELATED SECTIONS A. Section 07 62 00 - Sheet Metal Flashing. B. Section 07 72 00 - Roof

More information

Sure-Weld (TPO) Adhered Roofing Systems Code Approval Guide January, Table of Contents

Sure-Weld (TPO) Adhered Roofing Systems Code Approval Guide January, Table of Contents (TPO) Adhered Roofing Systems Code Approval Guide January, 2017 Introduction... ii Guidelines... Mechanically Fastened or Induction Welding Roofing Systems UL Approvals NonCombustible ANSI UL Class A...

More information

INSTALLATION INSTRUCTIONS for MP-RC1 TWO PIECE CONSTRUCTION TO BE INSTALLED ON COMPLETED ROOF DECK

INSTALLATION INSTRUCTIONS for MP-RC1 TWO PIECE CONSTRUCTION TO BE INSTALLED ON COMPLETED ROOF DECK INSTALLATION INSTRUCTIONS for MP-RC1 TWO PIECE CONSTRUCTION TO BE INSTALLED ON COMPLETED ROOF DECK A. 1. Using curb ribs as a guide, layout and mark roof openings on completed roof deck as outside curb

More information

ESR-2015P* Reissued April 2014 This report is subject to renewal April 1, 2015.

ESR-2015P* Reissued April 2014 This report is subject to renewal April 1, 2015. ICC-ES Evaluation Report ESR-2015P* Reissued April 2014 This report is subject to renewal April 1, 2015. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council DIVISION:

More information

FOAMULAR Commercial Roofing

FOAMULAR Commercial Roofing Low Slope Insulated Roof Systems Roofing Systems Single-ply roofing s are flexible sheets of compounded synthetic materials that are manufactured in a factory. Single ply roof systems provide strength,

More information

SECTION LIGHTWEIGHT INSULATING CONCRETE

SECTION LIGHTWEIGHT INSULATING CONCRETE SECTION 03342 LIGHTWEIGHT INSULATING CONCRETE PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 03300 - Cast-In-Place Concrete. 2. 05310 - Steel Deck. 3. 07511 - Multi-Ply Mineral Surfaced Built-Up Roofing

More information

HALIFAX HUMANE SOCIETY BOARDING AND GROOMING FACILITY SECTION STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS

HALIFAX HUMANE SOCIETY BOARDING AND GROOMING FACILITY SECTION STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS SECTION 075216 - PART 1 - GENERAL 1.1 SUMMARY A. Section includes styrene-butadiene-styrene (SBS) modified bituminous membrane roofing. 1.2 DEFINITIONS A. Hot Roofing Asphalt: Roofing asphalt heated to

More information

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street, Unit 13 Oxford, CT (203)

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street, Unit 13 Oxford, CT (203) EVALUATION REPORT Duro-Last Roofing, Inc. 525 Morley Drive Saginaw, MI 48601 (800) 248-0280 EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization #9503 353 Christian Street, Unit 13 Oxford, CT

More information

Colorado Chapter of the International Conference of Building Officials. Building Guide. The Colorado Chapter of the International

Colorado Chapter of the International Conference of Building Officials. Building Guide. The Colorado Chapter of the International Building Guide Colorado Chapter of the International Conference of Building Officials Colorado Building Chapter of the International Guide Code Council Single Family Residential One Story Detached Garage

More information

NAILABLE INSULATION GUIDE

NAILABLE INSULATION GUIDE NAILABLE INSULATION GUIDE NAILABLE INSULATION, FASTENERS & ENGINEERED VENTILATION SOLUTIONS. DELIVERED.TM 2 INTRODUCTION In May 1982, Atlas Roofing Corporation began operations as a single roofing manufacturing

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL SHINGLES REPORT HOLDER: TEFUTE BUILDING MATERIALS COMPANY, LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL SHINGLES REPORT HOLDER: TEFUTE BUILDING MATERIALS COMPANY, LLC 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 4036 Reissued 05/2018 This report is subject to renewal 05/2019. DIVISION: 07 00

More information

ASTM C 1363 Thermal Performance Test Report

ASTM C 1363 Thermal Performance Test Report ASTM C 1363 Thermal Performance Test Report Test Number: 2010-50 Sponsor: Butler Research Center Liner System R-25 + R-11 Membrane liner system, R-25 fiberglass insulation between the purlins, R-11 fiberglass

More information

UPLIFT RESISTANCE OF EXISTING ROOF DECKS: RECOMMENDATIONS FOR ENHANCED ATTACHMENT DURING REROOFING WORK

UPLIFT RESISTANCE OF EXISTING ROOF DECKS: RECOMMENDATIONS FOR ENHANCED ATTACHMENT DURING REROOFING WORK UPLIFT RESISTANCE OF EXISTING ROOF DECKS: RECOMMENDATIONS FOR ENHANCED ATTACHMENT DURING REROOFING WORK By Thomas L. Smith, AIA, RRC Abstract The uplift resistance of roof decks on many buildings in the

More information

Metal Roof Panels

Metal Roof Panels University of New Hampshire University of New Hampshire Scholars' Repository Division 07 Thermal and Moisture Protection Chapter 5 Technical Construction and Renovation Standards 1-25-2013 074113 - Metal

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: KINGSPAN INSULATED PANELS, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: KINGSPAN INSULATED PANELS, INC. 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1143 Reissued 04/2017 This report is subject to renewal 04/2018. DIVISION: 07 00 00 THERMAL

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

EVALUATION REPORT Boral Roofing 7575 Irvine Center Drive Suite 100 Irvine, CA

EVALUATION REPORT Boral Roofing 7575 Irvine Center Drive Suite 100 Irvine, CA EVALUATION REPORT Boral Roofing 7575 Irvine Center Drive Suite 100 Irvine, CA. 92618 EXTERIOR RESEARCH & DESIGN, LLC. 353 CHRISTIAN STREET, UNIT #13 OXFORD, CT 06478 PHONE: (203) 262-9245 FAX: (203) 262-9243

More information

ACFoam-II HCFC Free "Green" Polyiso Specification

ACFoam-II HCFC Free Green Polyiso Specification ACFoam-II HCFC Free "Green" Polyiso Specification To help owners and specifiers, the following specification strategies are offered as they relate to product performance when including HCFC FREE Green

More information

UL Evaluation Report UL ER Issued: December 19, 2014 Revised: August 14, UL Category Code: ULFB. CSI MasterFormat

UL Evaluation Report UL ER Issued: December 19, 2014 Revised: August 14, UL Category Code: ULFB. CSI MasterFormat UL Evaluation Report UL ER9516-02 Issued: December 19, 2014 Revised: August 14, 2015 Visit UL s On-Line Certifications Directory: www.ul.com/erdirectory for current status of Report. UL Category Code:

More information

GAF Cornell ThermaCal Nail Base Roof Insulation Panels (RESGN421) Updated: 2/15

GAF Cornell ThermaCal Nail Base Roof Insulation Panels (RESGN421) Updated: 2/15 GAF Cornell ThermaCal Nail Base Roof Insulation Panels (RESGN421) Updated: 2/15 Perfect for cathedral ceilings, glue lam, post & beam structures, and conditioned attic spaces Helps reduce heat drive into

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER: POLYGLASS USA, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER: POLYGLASS USA, INC. 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2018 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 07 00

More information

CS-100 Guide Specifications

CS-100 Guide Specifications MANUFACTURER CUSTOM-BILT METALS 1333 Corporate Drive, Suite 103 Irving, Texas 75038-2520 (800) 826-7813 or info@custombiltmetals.com www.custombiltmetals.com CS-100 Guide Specifications This Guide Specification

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 2 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (78) 315-2590

More information

Originally Issued: 11/04/2016 Revised: 11/28/2017 Valid Through: 11/30/2018

Originally Issued: 11/04/2016 Revised: 11/28/2017 Valid Through: 11/30/2018 HUBER ENGINEERED WOODS ZIP SYSTEM R-SHEATHING CSI Section: 06 12 00 Structural Panels 06 16 00 Sheathing 1.0 RECOGNITION ZIP System R-Sheathing panels, manufactured by Huber Engineered Woods, LLC, were

More information