C L I M A +: An Early Design Natural Ventilation Prediction Method

Size: px
Start display at page:

Download "C L I M A +: An Early Design Natural Ventilation Prediction Method"

Transcription

1 C L I M A +: An Early Design Natural Ventilation Prediction Method by Alpha Yacob Arsano Bachelor of Science in Architecture Ethiopian Institute of Architecture, Building Construction and City Development, 2013 Submitted to the Department of Architecture in Partial Fulfillment of the Requirements for the Degree of Master of Science in Architecture Studies at the Massachusetts Institute of Technology June Massachusetts Institute of Technology. All rights reserved. Signature of Author: Department of Architecture May 25, 2016 Certified by: Christoph Reinhart Associate Professor of Building Technology Thesis Supervisor Accepted by: Sheila Kennedy Professor of Architecture Chair of the Department Committee on Graduate Students 1

2 THIS PAGE INTENTIONALLY LEFT BLANK 2

3 Committee Thesis Supervisor: Christoph Reinhart Associate Professor of Building Technology Thesis Readers: Brandon Clifford Assistant Professor in Architecture Erik Olson CEO, Transsolar Inc 3

4 C L I M A +: An Early Design Natural Ventilation Prediction Method by Alpha Yacob Arsano Submitted to the Department of Architecture on May 25, 2016 in Partial Fulfillment of the Requirements for the Degree of Master of Science in Architecture Studies Abstract One of the most widely discussed passive building design strategies is using natural ventilation for cooling. In addition to providing fresh air, which enhances occupant productivity and comfort, strategic implementation of natural ventilation in buildings reduces the energy needed for cooling. And this reduction in energy consumption significantly reduces carbon dioxide emissions. During the initial design phase, designers routinely use climate-file based analysis to evaluate the potential for comfort ventilation against other passive building strategies. Following this initial screening, it is customary to conduct detailed simulations to further develop design ideas. At this point, inconsistencies can arise between the early climate-file based analysis and later-stage simulations. Major differences arise from limitations of climate-file based analysis to account for influences of construction assemblies, building program, and occupant comfort preferences. This manuscript presents a building performance-based climate analysis method where quick, single-zone simulations are run in EnergyPlus. The ventilation cooling potential for a site and a building program is calculated using a series of Python scripts. Thesis Supervisor: Christoph Reinhart Title: Associate Professor of Building Technology 4

5 Acknowledgments Thank you to Christoph Reinhart for your infectious excitement and uninterrupted support for the past two years. You are indeed a wonderful mentor. Thank you to Brandon Clifford and Erik Olsen for taking the time to share critical ideas during my research. Thank you to Salmaan Craig, the learning from the lectures and the discussions in the Thermal Tectonics course helped shape the effort in this work. Thank you to Carlos Cerezo, you have been very inspiring with your meticulous and beautiful work. It is a pleasure working with you. A special thank you to Bradley Tran. You have always been by my side from the hectic work seasons to the most crazy-fun nights. Thank you for editing this document with your precise and sharp eyes. Thank you to Francesca, Renaud, and Pierre. You have made spending endless number of hours in the BT lab enjoyable. I will never forget the special home cuisines and your culinary skills. I am grateful to my Allston family, to Joan and Laura. I love you dearly. We will finally go for hiking after a year of planning. A very special thank you to Saba Moges and Yacob Arsano for nurturing me with your parental but friendly advices in spite of the large geographical separation. I always feel your presence. A very special gratitude to Lulit and Yosef for letting me make your home my home. The delicious Buna with the hilarious Saturday late night chats ware the recipe for recuperation. A special thank you to my sister Yodit for being my sunshine. Although your most missed voice comes through the skype line only occasionally, you are always in my heart. A special thank you to my brother Iskinder, also known as Isku the Great, for being a listener and an advisor on multiple personal and academic endeavors. Thank you for offering your proficiency and love for writing to groom this manuscript. A special thank you to my sister Gelila, and to Nigus, for keeping me up to speed with Addis jocks. Thanks a lot for always looking out for me big sister. I am very grateful for the funding sources for this work: MIT-Portugal Program, and the Massachusetts Institute of Technology. Last, but by no means least, thank you for all students and faculty in the Building Technology lab. Thank you to Kathleen Rose for always making resources accessible and getting us together in the events you organize. 5

6 THIS PAGE INTENTIONALLY LEFT BLANK 6

7 Contents Acknowledgements 5 List of Figures 9 Nomenclature Introduction Research Motivation and Objective What Can Go Wrong in the Design Process of Naturally Ventilated Building? Background Thermal Comfort, Natural Ventilation, and Thermal Mass Existing Tools, and Methods for Early Design Decision C L I M A Method for Natural Ventilation Potential Prediction Phase I- Using Climate Analysis Phase II- Using Climate Box Simulation User Interaction and Integration with Design Process Results and Discussion Mapping Natural Ventilation Globally Concluding Remarks Future Work 59 Appendix 61 A. Thermal Climate Zone Definition 61 B. Temporal Charts of the Selected 20 Climates 62 References 64 7

8 THIS PAGE INTENTIONALLY LEFT BLANK 8

9 List of Figures Figure 1 A medium-sized reference commercial building Figure 2 Comparison of predictions on overheated hours Figure 3 Important dates in the development of thermal comfort guidelines and standards Figure 4 Acceptable operative temperature ranges for naturally conditioned spaces Figure 5 Increases in acceptable operative temperature limits Figure 6 Applications of Natural ventilation Figure 7 Coupling of building insulation and thermal mass Figure 8 Comparison of thermal mass buffering Figure 9 Internal thermal mass Figure 10 Natural ventilation integration with climate Figure 11 Comparison of U-Values Figure 12 The description of thermal comfort models Figure 13 Climate Consultant s Bioclimatic Chart Figure 14 Components of the building bioclimatic chart of Climate Consultant Figure 15 CBE Thermal Comfort Tool Figure 16 The effect of the rate of natural ventilation on thermal mass buffering Figure 17 The components of CLIMA+ natural ventilation prediction method Figure 18 The coupling of natural ventilation and thermal mass Figure 19 Phase I study for Phoenix Figure 20 Potential application of different natural ventilation methods in Figure 21 compared for 20 selected climates Figure 22 The components of CLIMA+ natural ventilation prediction method Figure 23 The nine thermal climate zones defined by ASHRAE Figure 24 Single zone thermal zone Figure 25 CLIMA+ user inputs Figure 26 Occupancy schedules used for office and residence templates Figure 27 Thermal model settings Figure 28 Building constructions Figure 29 Building and occupant preferences Figure 30 Temporal chart for a residence in Phoenix Figure 32 CLIMA+ interface Figure 31 CLIMA+ interface Figure 33 Workflow of CLIMA+ with a 3D CAD design environment Figure 34 A comparison of predicted overheated hours Figure 35 Office and residence occupied hours Figure 36 A comparison of number of discomfort hours Figure 37 Effect of thermal mass Figure 38 The comparisons of temporal graphs Figure 39 Global maps showing natural ventilation predictions

10 Nomenclature Adaptive Comfort Standard (ACS) American Society of Heating and Air-Conditioning Engineers (ASHRAE) Chartered Institution of Building Services Engineers (CIBSE) Intermediate Data Format (IDF) American Society of Heating and Ventilating Engineers (ASHVE) EnergyPlus Weather Data (EPW) The US Department of Energy (DOE) Climate zone (CZ) Thermal mass (TM) Mean outdoor air temperature (T rm(out) ) Temperature, Kelvin (K) Temperature, Celsius ( 0 C) High ventilation- provides sufficient air change rates resulting in indoor air temperature following outdoor air temperature. Thermal mass buffering of indoor air temperature is restricted. Low ventilation- provides low air change rates sufficient for fresh air, but indoor air temperature will remain higher than outdoor air temperature due to internal heat gains. Climate or weather data- hourly, site-specific values of representative meteorological data, such as temperature, wind direction and speed, solar radiation, and relative humidity. For locations where climate data are not available, the designer shall select available weather or meteorological data that best represents the climate at the building site (ASHRAE ). Adaptive model- a model that relates indoor design temperatures or acceptable temperature ranges to outdoor meteorological or climatological parameters. It is the method for determining acceptable thermal conditions in occupant-controlled, naturally conditioned spaces (ASHRAE ). Thermal comfort- condition of mind that expresses satisfaction with the thermal environment and is assessed by subjective evaluation (ASHRAE ). Acceptable thermal environment- a thermal environment that a substantial majority (more than 80%) of the occupants find thermally acceptable (ASHRAE ). Operative temperature- the uniform temperature of an imaginary black enclosure and the air within it in which an occupant would exchange the same amount of heat by radiation and convection, as in the actual nonuniform environment. It is calculated in accordance with Normative Appendix A of ASHRAE

11 THIS PAGE INTENTIONALLY LEFT BLANK 11

12 1 Introduction 1.1 Research Motivation and Objective Thermal comfort is one of the fundamental aspects of indoor environmental quality that is strongly related to occupant satisfaction and energy use in buildings (Schiavon et al 2014). Many building science textbooks for designers and architects promote an hourly climate-file based analysis in order to understand whether natural ventilation is a valid design strategy to enhance thermal comfort. The analysis yields the number of comfort hours natural ventilation could add to a space over the course of the year using bioclimatic charts. These methods were first developed during the 1950s and have been implemented into digital design tools such as Climate Consultant and Ecotect Weather Tool. Victor Olgyay was an important pioneer of thermal comfort representations. He used the concept of an Effective Temperature (ET) as the basis of his comfort diagram, the Bioclimatic Chart (Schiavon et al 2014). This chart assumes the criterion that the perimeter of the comfort zone outlines the conditions in which an average person will not experience discomfort and it applies to moderate climate zones (Olgyay 1963). Givoni, author of Building Bioclimatic Chart, extended Olgyay s representation to the psychrometric chart and added rules about passive heating and cooling strategies. The Building Bioclimatic Chart, which is implemented in Climate Consultant, is a widely used climate-file based tool that uses two components: thermal comfort area and boundaries of climatic conditions within which various building design strategies and natural cooling systems can provide comfort (Givoni 1992). Climate Consultant allows users to upload the standardized EPW format climate data, which are made available online by the US Department of Energy (Climate Consultant 6.0 Documentation). 12

13 All hours of the year are then plotted on the Building Bioclimatic Chart, where different design strategies are compared. However, it does not allow users to adjust the level of air movement and does not include Standard 55 s model for elevated air speed. The thermal comfort area reported in the Bioclimatic Chart is not consistent with ASHRAE 55 thermal comfort areas (Schiavon et al 2014). Furthermore, the underlying principle for Climate Consultant s comfort ventilation calculates only for psychological cooling, and clearly states that ventilation does not reduce the dry bulb temperature (Climate Consultant 6.0 Documentation). On the contrary, thermal simulation tools such as EnergyPlus and CoolVent perform detailed building analysis to predict zone temperatures and airflow rates in naturally ventilated buildings, but they neglect psychological cooling effects due to indoor air movements. Designers and their consultants interested in designing high-performance buildings tend to start their conceptual design with a quick, climate-file based analysis. If the required know-how is present within the team, they later switch to more detailed, whole-building simulation tools that can further evaluate the hourly indoor thermal comfort conditions for a particular building design. Based on the observations discussed above, this thesis carefully reviews the assumptions underlying these two analysis steps, evaluates their applicability to a variety of building types and climates, and proposes an improved workflow for design teams to use. The objective is to allow a design team to easily transition between an early climate-file based analysis to a detailed building design analysis without conflicting results. 13

14 Figure 1 A medium-sized reference commercial building selected for analysis among the 16 building types that represent approximately 70% of the commercial buildings in the U.S., according to the report published by the National Renewable Energy Laboratory titled U.S. Department of Energy Commercial Reference Building Models of the National Building Stock (Energy.Gov). 1.2 What Can Go Wrong in the Design Process of Naturally Ventilated Building? An expert in an international climate-engineering firm shared a story about one particular encounter with a client. The goal of the collaboration was to develop deeply integrated comfort and energy concepts for a project located in New England. The climate engineer presented highperformance building strategies that successfully eliminated mechanical cooling systems. However, the client countered the climate engineer s proposal about eliminating the active cooling system by quoting the results from a building bioclimatic analysis method implemented in one of the most widely used tools called Climate Consultant. This story illustrates how an inconsistency between a quick climate-file based study and a thorough building performance analysis could arise and consequently result in design process challenges. The authors repeated the steps discussed in the story of the climate engineer using a medium-sized office reference building by the US Department of Energy (DOE) located in Phoenix. The DOE, in conjunction with three of its national laboratories, developed commercial reference buildings, formerly known as commercial building benchmark models. These modules provide a consistent baseline of comparison and improve the value of computer energy simulations using software such as EnergyPlus (Energy.Gov 2017). 14

15 Figure 2 Comparison of predictions on overheated hours by Climate Consultant's building bioclimatic chart and building performance simulation using energy plus for a naturally ventilated building. The bioclimatic chart reported 1550 overheated hours while on the other hand post analysis of building simulation showed it is possible to achieve 100% comfort. The adaptive comfort model is used in both cases. The prediction of the number of overheated hours by Climate Consultant s bioclimatic chart is compared with the number of overheated hours calculated using building simulation of the reference office building (see figure above). The prediction of overheated hours by the building bioclimatic chart considers cooling ventilation and thermal mass strategies. The energy simulation study showed that overheated hours can be reduced to zero with the application of ASHRAE 55 Adaptive Comfort Standard while Climate Consultant s optimized result showed over 1,500 overheated hours. The underlying principles and models used in Climate Consultant s bioclimatic chart are discussed in detail in the background section. Additional overview is included on the CBE online tool that is written by the Center for the Built Environment at UC Berkeley. Advantages and limitations of these tools are then compared with the proposed method with CLIMA+. 15

16 2 Background A tree doesn t need a support system it is a system. The shelter of the future will embody energy. Michael Reynolds Comfort in Any Climate,

17 Figure 3 Important dates in the development of thermal comfort guidelines and standards. 17

18 2.1 Thermal Comfort, Natural Ventilation and Thermal Mass Thermal comfort and natural ventilation have a long history in the built environment. Around 400 BC, Socrates had some thoughts on the climatic suitability of houses and on how to build to ensure thermal comfort. Vitruvius (1st century BC) also wrote about the need to consider climate in building design for reasons of health and comfort. This, however, had very little influence on the practice of architecture (Auliciems et Svokolay 2007). Mechanical cooling became a possibility early 20th century (Auliciems et Svokolay 2007), and comfort became a 'product' produced by machines that ran on cheap energy (Nicole et al 2012). The result has contributed to a trend in buildings with increasing use of mechanical systems and related energy consumption. In the early 1920s, Houghten and Yagloglou (1923) at the ASHVE (American Society of Heating and Ventilating Engineers) laboratories attempted to define the comfort zone. In England the motivation came from industrial hygiene: the limits of environmental conditions for work. Vernon and Warner (1932) and later Bedford (1936) carried out empirical studies among factory workers. Analytical work started in the US in the mid-1930s, where Winslow, Herrington and Gagge (1937) made a significant contribution. During and after World War 2, research activity increased and many disciplines became involved besides engineering, from physiology and medicine to geography and climatology. In architecture, Victor Olgyay (1963) was the first to collect findings from the various disciplines and interpret them for practical, architectural purposes (Auliciems et Svokolay 2007). Good passive design can minimize the periods during which mechanical cooling may be needed and can also substantially reduce the size of the required cooling equipment, perhaps restricting its use to only critical locations (CIBSI 2015). A growing international consensus now calls for lowenergy buildings. This means designers must first produce robust, passive structures that provide occupants with many opportunities to make changes to suit their environmental needs. Ventilation should be most preferred strategy and mechanical conditioning only used when the climate demands it (Nicole et al 2012). Recent studies have started recognizing the effects of air pollution and urban heat island on natural ventilation potential. Tong et al (2016) have shown that the energy savings and environmental benefits are affected greatly by ambient air pollution in China. In addition, the urban heat island effect can reduce the opportunities for night cooling in urban areas (CIBSI 2015). 18

19 Figure 4 Acceptable operative temperature ranges for naturally conditioned spaces The allowable operative temperature limits may not be extrapolated to outdoor temperatures above and below the end points of the curves in this figure. If the prevailing mean outdoor temperature is less than 10 C or greater than 33.5 C, this option may not be used (ASHRAE in Figure 5.4.2). The Adaptive Comfort Model promotes use of the comfort evaluation method using adaptive temperatures. Recent standards (European Standard EN 15251, ASHRAE 55) and guidelines (CIBSE) advise that comfort temperatures vary through the year as people adapt to changes in outside temperatures. Adaptive comfort temperatures are most appropriate to "free running" buildings where occupants have control over themselves and their environment. As comfort temperatures vary, heating and cooling set-points should be adjusted to maintain optimum comfort. This is in keeping with most peoples experience a building at 24 C will feel cool in summer but hot during cooler periods of the year (Low Carbon Comfort 2014). Adaptive comfort equations are provided in EN1525, CIBSE and ASHRAE Standards. The adaptive comfort temperatures are based on outside temperatures during the preceding few days. The allowable indoor operative temperatures shall be determined from the figure above using 80% acceptability limits or the following equations as provided in ASHRAE Upper 80% acceptability limit ( C) = 0.31 Trm(out) Lower 80% acceptability limit ( C) = 0.31 Trm(out) The prevailing mean outdoor air temperature (T rm(out) ) shall be based on no fewer than seven and no more than 30 sequential days prior to the day in question. It shall be a simple arithmetic mean of all of the mean daily outdoor air temperatures of all days in the considered period. 19

20 ASHRAE permits weighting methods if the weighting curve continually decreases towards the more distant days such that the weight applied to a day is between 0.6 and 0.9 of that applied to the subsequent day. For this option, the upper limit on the number of days in the sequence does not apply. A weighted running mean of outdoor temperatures, Trm, is calculated based on the following equation given in CIBSI Guide A: Environmental Design: Trm(out)= (1 - αrm) [Te(d-1) + αrm Te(d-2) + αrm 2 Te(d-3)...] where αrm is a constant between 0 and 1 which defines the speed at which the running mean responds to outdoor temperature, Te(d-1) is the daily mean outdoor temperature ( C) for the previous day, Te(d-2) is the daily mean outdoor temperature ( C) for the day before that, and so on. The recommended value of αrm is 0.8 (CIBSI A: Environmental Design). If operative temperature is greater than 25 C, then increasing the upper acceptability temperature limits in Figure 4 by the corresponding change in temperatures is permitted. The following table is adopted from ASHRAE (Table ). Average Air Speed (Va) 0.6 m/s Average Air Speed (Va) 0.9 m/s Average Air Speed (Va) 1.2 m/s 1.2 C 1.8 C 2.2 C Figure 5 Increases in acceptable operative temperature limits in occupant-controlled, naturally conditioned spaces resulting from increasing air speed above 0.3 m/s. 20

21 Figure 6 Applications of Natural ventilation Natural ventilation has two benefits: for fresh air supply and comfort cooling. Comfort cooling with natural ventilation can take place during daytime or night time. In buildings with operable windows and similar ventilation devices, free precooling can be used when outside air temperatures are below inside temperatures. In air-conditioned buildings, the use of natural ventilation can dramatically reduce the energy required to mechanically cool the space. In buildings with heating only, natural ventilation can significantly reduce peak indoor summer temperatures. (Low Carbon Comfort 2014). On cool days, free cooling can meet all the cooling load. The space is ventilated to maintain a comfortable indoor operative temperature. On hot days, there may be limited free cooling available in the morning and no opportunity for pre-cooling earlier in the day. It may be possible to pre-cool during the preceding night (often referred to as night cooling), though this will often be ruled out on practical grounds due to security risks. Pre-cooling restricted to the morning-occupied period will still have a major energy benefit during warm weather and can typically be expected to reduce cooling energy by 30% (Low Carbon Comfort 2014). Very often, peak temperatures in standard buildings will exceed the outdoor peak temperature by three or more degrees. At best, peak indoor temperature can be maintained at a degree or so below the peak outdoor temperature but this is only possible by means of night cooling combined with thermal mass (CIBSI 2015). Climatic conditions such as the diurnal temperature swings influence the effectiveness of night cooling. Additional discussion on the application of thermal mass to improve thermal comfort is presented in the third section of this document, CLIMA+ Phase I. 21

22 Figure 7 Coupling of building insulation and thermal mass Michael Reynolds (2001) in his book Comfort in Any Climate illustrated the coupling of building insulation and thermal mass to enhance heating and cooling strategies. The air temperature inside a building depends on many factors, including the outdoor temperature, building geometry and internal heat gains from occupants, equipment and lighting (Holford et Woods 2006). Thermal mass in buildings plays a great role in buffering internal temperature from outdoor environmental fluctuations and building design can benefit from exploiting the potential of thermal mass to enhance thermal comfort. The specific role of effective thermal mass specifically in naturally ventilated buildings is explained in detail by Holford and Woods. They have shown that the effective thermal mass, which is in good thermal contact with the air is limited by the diffusion distance into the thermal mass over one diurnal temperature cycle. They have also shown the great applicability of thermal mass models using lumped methods and numerical integration of thermal diffusion for exact solutions. 22

23 Figure 8 Comparison of thermal mass buffering of a 10 cm thick concrete structure with other constructions having different thermal mass thickness and volumetric heat capacity. 23

24 Figure 9 Internal thermal mass Michael Reynolds (2001) illustrates deep and shallow room layouts of naturally ventilated spaces to regulate exposure to solar gain. The thermal mass thickness within an interior space can be adjusted based on climatic conditions of the building s location. The geometry of the room and integration of thermal mass in the interior surfaces can be designed to optimize heat energy storage by increasing solar gain in cold climates. On the contrary, thermal mass in a deep space that is shaded from solar radiation will be kept cooler than outdoor temperatures in hot climates. 24

25 Figure 10 Natural ventilation integration with climate Michael Reynolds (2001) illustrates various passive strategies for naturally ventilated spaces in different climates in his book Comfort in Any Climate. The climatic forces of wind (wind effect) and temperature (stack effect) drive natural ventilation. For this reason, natural ventilation is highly variable since, at any instant, both the pattern of airflow and the rate of ventilation will depend on the prevailing weather conditions (CIBSI 2015). A strategic design of buildings that integrates the methods such as natural ventilation, thermal mass, envelope insulation, and solar heat gain, will improve comfort in any climate. 25

26 CZ8 CZ7 CZ6 CZ5 CZ4 CZ3 CZ2 CZ1 CZ WOOD STEEL METAL MASS Above Grade Wall, Assembly Maximum Transmittance (U-Value) ASHRAE 90.1 (2016) Figure 11 Comparison of U-Values The nine Climate Zones defined by ASHRAE Building energy standards provide insulation requirements for different types of constructions and climate zones. Insulation requirements for mass construction is relatively lower than the requirements for steel, metal and wood constructions in all climate zones defined in ASHRAE 90.1 (see figure above). Such variation in the minimum required U-values indicates that the building construction standards accounted the potential benefit of thermal mass in meeting comfort requirements and reducing space conditioning energy loads. 26

27 2.2 Existing Tools and Methods for Early Design Decision Figure 12 The description of thermal comfort models used in the architectural design strategies book Sun, Wind and Light, Climate Consultant, Ecotect, ASHRAE Thermal Comfort Tool and CBE Thermal Comfort Tool. 27

28 Figure 13 Climate Consultant s Bioclimatic Chart is shown for the climate of Phoenix. The number of comfortable hours are calculated and selected strategies are highlighted at the top left corner of the figure. Figure 14 Components of the building bioclimatic chart of Climate Consultant Climate Consultant is a simple to use, graphic-based computer program that helps users create more energy efficient and sustainable buildings (Milne 2009). It is extensively used in academic and professional work at an earlier design phase to better understand a given climate. A summary of design strategies as a function of ambient conditions (climate) are reported based on Pschrometric-Bioclimatic Chart by Baruch Givoni and Murray Milne. The concept of a building bioclimatic chart combines Victor Olgyay s bioclimatic chart (Olgyay 1993), the psychrometric chart, and passive heating and cooling rules. 28

29 Climate Consultant s Psychrometric chart ventilation-cooling strategy is only attributed to physiological cooling effects achieved by air movement, which increase sweat evaporation from the skin, and it is clearly stated that the strategy does not reduce air temperature. This ventilation cooling potential prediction method only takes wind speed as a measure of effectiveness, and the approach does not fully represent the process that takes place in a naturally ventilated building. It assumes an ideal ventilation situation where the indoor temperature follows the outdoor. The temperature difference between the indoor and outdoor that drives buoyancy is neglected resulting in an underestimation of natural ventilation potential. Furthermore, the benefit of coupling natural ventilation and thermal mass is not sufficiently incorporated. Rather, thermal mass is calculated independently as a passive cooling strategy. Its effectiveness is defined with maximum dry bulb temperature difference that is as much as 16.7 C above the comfort high and the dew point temperature limits at the top and bottom of the comfort zone (Climate Consultant ). Climate-file based analysis methods calculate ventilation cooling potential by estimating indoor air movement for direct physiological cooling. Results are shown on psychrometric charts where temperature and humidity values of analyzed hours are plotted. In the case of Climate Consultant, this method accounts for hours where there is sufficient indoor air velocity and zone of effectiveness is defined by a minimum air velocity to affect comfort, usually at least 0.2 m/s (Climate Consultant 6.0 Documentation). The underlying assumption is that with effective daytime cross-ventilation, the indoor air temperature tends to track the outdoor level along with higher indoor airspeed. Therefore, the temperature limit of comfort ventilation applicability is the comfort limit at the enhanced airspeed at any region or season (Givoni 1998). The quantitative effect of convective cooling was studied extensively by Givoni at the Institute for Desert Research of Ben Gurion University in Israel and at the University of California, Los Angeles (Givoni 1992). There are two important limitations of this method that could cause errors on cooling ventilation predictions. First, the comfort zone defined in Bioclimatic-based analysis do not align with comfort zones defined in ASHRAE Standards 55. Hence, when users switch to detailed studies using simulation tools and comfort standards, there is a high probability that the dynamic simulation results are inconsistent with design concepts developed during early stages. Second, extended comfort zones by the design strategies including cooling ventilation and thermal mass are shown to improve comfort in all instances. The influence of the different strategies on each other when implemented at the same time is not well explained. A very good example is the internal heat gain zone that is defined only by a balance point temperature below which heating is needed. This approach neglects the effects of internal heat gain during hours of high temperature when mechanical cooling is required. Furthermore, ventilation heat loss, which results in effective temperature reduction, is not considered with physiological cooling in the ventilation cooling strategy. Therefore, identifying comfort ventilation potential for building programs with different internal gains and envelope performances becomes challenging when using climate-file based analysis. 29

30 Figure 15: CBE Thermal Comfort Tool. For the ASHRAE Standard Adaptive Comfort model (de Dear and Brager 1998), the comfort zone is represented with indoor operative temperature as ordinate and prevailing mean outdoor temperature as abscissa. The CBE Thermal Comfort Tool for ASHRAE-55 (see figure above) is an application that provides a good alternative for cooling ventilation potential calculation. Designers can use this application during the programming and schematic design phases to assess different thermal control strategies including natural ventilation and elevated air speed (Schiavon et al 2014). However, users can only calculate results for a single point in time by defining indoor air temperature, mean radiant temperature, prevailing mean outdoor temperature and air speed. This requires users to know indoor and outdoor conditions before conducting the analysis, and users cannot run annual analysis in contrast to commonly used climate-file and simulation based methods. 30

31 3 C L I M A + CLIMA+ is an integrated method proposed for predicting potential of natural ventilation that is quick to use in comparison to detailed energy-performance simulation methods that are undertaken by experts. It provides users with reliable recommendations by incorporating comprehensive evaluations of comfort conditions based on current standards and studies. The analytical computations in CLIMA+ are in two phases: using climate file and climate box simulation. The two methods consider the coupling of natural ventilation and thermal mass. 31

32 Figure 16 The effect of the rate of natural ventilation on thermal mass buffering The result of thermal mass and natural ventilation coupling is regulated by the amount of natural ventilation rate permitted. 3.1 Method for Natural Ventilation Potential Prediction CLIMA+ promotes two analysis phases. In the first phase, a quick climate data based natural ventilation prediction is reported based on selected parameters to represent natural ventilation and thermal mass coupling. In the second phase, an additional step with a quick simulation of a singlezone thermal model is used to predict overheated hours. These two phases are discussed in length in the following sub-sections. 32

33 Figure 17 The components of CLIMA+ natural ventilation prediction method. The highlighted section of the figure is showing Phase I Phase I- Using Climate Analysis Climate-file based analysis is commonly used in the development of building strategies and prediction of building performance. The method is promoted largely in standards related to buildings and environment. ASHRAE 169: Climate Data for Building Design Standards provides recognized climatic data for use in buildings and related equipment standards (ASHRAE ). This standard provides a normative appendix that contains data for 5,564 U.S, Canadian, and international locations that can be used for climatic design and definition of climatic zones (ASHRAE ). Another standard CIBSI Guide A: Environmental Design provides the basic weather and solar data required for manual calculations of heating and cooling loads in the UK and Europe. In addition, CIBSI Guide A and ASHRAE 55 present comfort requirements using both the PMV/PPD method and the adaptive comfort approach for free-running buildings. However, these provisions do not layout a comprehensive methodology for predicting natural ventilation potential using a climate data. The author developed a simplified numerical calculation method on outdoor hourly temperature and humidity to predict the potential of thermal mass and natural ventilation in improving thermal comfort. Four main parameters to approximate ventilation scenarios and thermal mass coupling are defined. These are the parameters to predict direct natural ventilation with physiological cooling, buoyancy ventilation, thermal mass buffering with high and low ventilation rates. A comparison of 20 different climates using the four parameters showed significant variations among different climatic conditions. The method is repeated for 2,450 cities and the natural ventilation potential predictions are mapped globally. The resulting interactive global map is hosted on the web for public access. Please visit 33

34 Figure 18 The coupling of natural ventilation and thermal mass The two charts illustrate the coupling of natural ventilation and thermal mass based on the work of Holford and Woods. Coupling Natural Ventilation and Thermal Mass Holford and Woods (2006) had identified the following three important constituents and they are used in this manuscript to discuss the proposed methodology. The time for the heat exchange between the effective thermal mass and the air, the time for the natural ventilation to replace the air in the space with air from the environment and the period of the diurnal oscillations of the environment. Depending on the ventilation rate, the difference between the indoor and outdoor temperature can be calculated. The indoor air temperature becomes very close to the outdoor air temperature when high ventilation is permitted because internal heat loads are continuously removed and thermal mass buffering effect is reduced. On the other hand, when ventilation rate is 34

35 low, indoor air temperature will be mainly affected by internal heat gains and the interaction with the thermal mass. The illustration in Figure 18 shows the coupling effect of natural ventilation and thermal mass using the tool written by Salmaan Craig with the Cumulative Distribution Function (CDF) based on the study presented by Holford and Woods. It is worth noting that Holford and Woods have neglected internal thermal gains in the main simplification of the work in order to derive insight into the principles of heat exchange in the building design. The extended Adaptive Comfort Standard sets acceptable boundary conditions for thermal comfort taking into account effects of elevated air speed. Acceptable humidity level is defined based on the literature and standards review that is presented in section 2.1. The comfort conditions for multiple climates are then predicted using a python-script routine. The physical considerations underlying the four natural ventilation and thermal mass potential-prediction parameters are discussed in the following subsection. Direct natural ventilation potential and physiological cooling The outdoor hourly air temperatures are evaluated if they are within the upper and lower limits of the adaptive comfort range as provided in ASHRAE 55 s Adaptive Comfort Standard. Similarly, the hourly relative humidity (RH) values are evaluated if they are below 85%. This parameter assumes that the indoor air temperature closely follows the outdoor air temperature because high ventilation rate is promoted. The comfort hours by physiological cooling that are affected by elevated air speed are added in the direct natural ventilation potential predicted. ASHRAE permits the acceptable adaptive comfort range upper limit to be increased by 2.2 C when the average air speed is 1.2 m/s for occupant-controlled, naturally conditioned spaces (ASHRAE ). Buoyancy ventilation potential The buoyancy ventilation potential is calculated based on the assumption that the indoor air temperature shall be kept at least 2k higher than the outdoor air temperature to maintain a minimum temperature difference that drives outdoor air to flow into the space. Hence, the 80% upper and lower acceptability limits given for indoor operative temperatures in the Adaptive Comfort Standard are reduced by 2 K. The adjusted acceptability limits are then used to evaluate whether the hourly outdoor air temperatures are within the expected temperature range so that buoyancy ventilation is enhanced. This parameter considers the hourly indoor operative temperature to remain above the outdoor air temperature. The natural ventilation air-change rate is regulated so that it removes only part of the heat gained due to internal loads and solar radiation. Thermal mass buffering An ideal thermal mass buffering would result in indoor air temperature following closely the mean outdoor temperature (Figure 18). The outdoor running mean temperature is considered as the predicted indoor operative temperature as a result of thermal mass buffering. This outdoor running mean temperature is also used in the Adaptive Comfort Standard and it is the average temperature of the past 7 to 30 days. A detailed calculation method for the outdoor running mean is provided in the ASHRAE and CIBSI standards and it is discussed in Section

36 Temperature in 0 C Holford and Woods have shown that temperature attenuation achieved with moderate and heavy constructions in naturally ventilated buildings would range between 6.7 and 26 hours for convection to affect mass temperature. This time lag caused by thermal mass is considered by representing the predicted indoor operative temperature by the outdoor running mean temperature rather than the mean temperature of a single day. This works for construction systems that have insulation as required by building energy standards such as ASHRAE The internal thermal mass is exposed to the interior air temperature and is affected by outdoor air only during natural ventilation. The parameter to predict the effectiveness of thermal mass buffering is defined as the number of hours where the predicted indoor operative temperature is within adaptive comfort range as a result of thermal mass buffering in the naturally ventilated building. Predicted indoor temperature With low ventilation rate Predicted indoor temperature With high ventilation rate Outdoor temperature Adaptive comfort range Figure 19 Phase I study for Phoenix. Outdoor air temperature from climatic data is evaluated based on the adaptive comfort standards requirements. Thermal mass passive heating and cooling potential When outdoor temperature is above or below acceptable thermal comfort limits, thermal mass can be used to condition indoor air by convection and radiation. In a given climate where outdoor dry bulb temperature goes lower than 10 C, which is the lowest threshold defined by ASHRAE 55 s Adaptive Comfort Standard, thermal mass can be used to store solar energy or heat from other heat 36

37 Temperature in 0 C sources. Designing thermal mass for solar exposure in cold climates would help reduce heating energy loads and this potential is calculated by adding all hours where the outdoor running mean falls below the lower limit of adaptive comfort standard s 80% acceptability range. Applying similar calculation method but for overheated hours, the potential of pre-cooled thermal mass is calculated by adding hours which are above the upper limit of adaptive comfort standard s 80% acceptability range Potential extension of the adaptive comfort range Predicted ideal time for a different ventilation method Outdoor temperature Adaptive comfort range Figure 20 Potential application of different natural ventilation methods in for different times of a year based on outdoor temperature for the climate of Phoenix. Parts 1 and 5 have cold hours limiting potential ventilation hours. On the other hand, parts 2 and 4 have better potential for direct ventilation because of the hours of temperature within the adaptive comfort range. Limitation of CLIMA+ Phase I The current model for climate file based prediction of natural ventilation considers the high or the low ventilation assumptions that are applied for all hours of the year. However most climates could have optimized solutions by combining both high and low ventilation rates depending on outdoor conditions of each hour or day. The four modes of coupling natural ventilation and thermal mass discussed in the section above will be studied further to optimize their integration in a given climate. 37

38 Vancouver SanFrancisco Salem Albuquerque Boise Los Angeles Minot Duluth Burlington Boston Lisbon El Paso Chicago Tel Aviv Phoenix Houston Miami Mumbai Riyadh Kuwait Vancouver SanFrancisco Salem Albuquerque Boise Los Angeles Minot Duluth Burlington Boston Lisbon El Paso Chicago Tel Aviv Phoenix Houston Miami Mumbai Riyadh Kuwait Vancouver SanFrancisco Salem Albuquerque Boise Los Angeles Minot Duluth Burlington Boston Lisbon El Paso Chicago Tel Aviv Phoenix Houston Miami Mumbai Riyadh Kuwait TM Buffering (Low Ventilation) TM Buffering (High Ventilation) Direct Ventilation with Physiological Cooling Buoyancy Humidity TM Passive Cooling Potential TM Passive Heating Potential Figure 21 compared for 20 selected climates. Direct ventilation, buoyancy ventilation and thermal mass buffering potentials Natural Ventilation Potential for 20 Selected Climates The 20 different climates that are used to study the natural ventilation prediction parameters are selected from the commercial and residential reference buildings provided by the US Department of Energy (DOE). They represent climates ranging from extreme cold to extreme hot. The predicted direct ventilation, buoyancy ventilation and thermal mass buffering for high and low ventilation scenarios are compared for the 20 selected climates. Direct ventilation and physiological cooling improve comfort in humid climates such as Miami and Mumbai where the diurnal temperature fluctuation is relatively small and most of hourly temperatures are within the adaptive comfort range. In this case, the indoor air temperature is considered to closely follow the outdoor temperature where by internal heat gain is continuously removed with free running ventilation. Temporal plots of the 20 climates are shown in Figure 19. For the case of buoyancy ventilation, the primary driving force for air change rates is temperature difference of at least 2 K and such a difference is maintained by restricting natural ventilation rate. Temperate and cold climates such as Lisbon and San Francisco have better potential for buoyancy ventilation than direct ventilation. 38

39 Physiological cooling adds about 500 or more comfort hours in the hot to warm climates such as Riyadh, Mumbai, Miami, Houston and Phoenix. For climates where there are high daily temperature changes thermal mass buffers indoor air from the outdoor air fluctuations above and below the adaptive comfort range and increases number of comfortable hours. Thermal mass adds about a thousand comfortable hours in Albuquerque where significant number of hours with outdoor temperatures that are outside of the adaptive comfort limits. Thermal mass buffering has different results when combined with high and low natural ventilation rates. In the case of Mumbai and Miami thermal mass buffering is effective when natural ventilation is not restricted. Annual temporal maps for these climates as illustrated in Figure 19 show that thermal mass buffering is the preferred strategy when indoor air temperature is close to the outdoor running mean temperature. On the other hand, in the colder and the temperate climates such as Lisbon and Albuquerque thermal mass buffering is effective with limited ventilation rate. In this case indoor air temperature is higher than outdoor air temperature and hence it is within the adaptive comfort range. In hot climates such as Riyadh and Kuwait, that have cold winter seasons with temperatures below the adaptive comfort lower limit, thermal mass has the potential to reduce both heating and cooling energy loads. On the other hand, for predominantly hot to warm climates of Mumbai and Miami, thermal mass can be cooled to attenuate indoor air temperature and increase comfort hours. Cold and temperate climates benefit greatly from thermal mass by storing solar energy or other form of heat energy. 39

40 Figure 22 The components of CLIMA+ natural ventilation prediction method. The highlighted section of the figure is showing Phase II Phase II- Using Climate Box Simulation This section presents an integrated method where a simplified simulation of a climate box is performed to calculate operative temperature for a generic well-ventilated single zone building. The predicted number of overheated hours for the climate zone is calculated based on the Adaptive Comfort Standard. An additional comfort improvement that is achieved with elevated air speed is also considered and it is termed as physiological cooling effect. The climate box (simulation thermal zone), the assumptions for the simulation and output results of the method are discussed in detail in the following subsections. 40

41 Figure 23 The nine thermal climate zones defined by ASHRAE Non-geometric building template library All non-geometric building information for construction, occupancy, internal heat loads, and conditioning are compiled in each template based on programmatic and climatic differences. A library that is populated with residence and office building templates is then created for the second phase of CLIMA+. The construction requirements for both residence and office are different in the different climate zones that are defined in ASHRAE Appendix B is a table with the number of heating and cooling degree-day limits given by the standard to define each thermal climate zone. Templates for the nine thermal climate zones are prepared to represent most climates based on the constructions specified in ASHRAE: Energy Standard for Buildings Except Low-Rise Residential Buildings (ANSI/ASHRAE/IES Standard ). The non-geometric building template is a JSON file format that is created using Archsim which is a Grasshopper plugin that uses the EnergyPlus engine in the 3D CAD working environment called Rhinoceros (Rhino, Archsim 2017). The template files are integrated with a geometric information that defines a thermal zone and intermediate data files (IDF) are created to run building performance simulation. The geometric abstraction implemented this phase of CLIMA+ is presented in the following subsection. 41

42 Figure 24 Single zone thermal zone is used with program and climate zone based building templates. Climate box: best-case thermal energy model As a first step, it is assumed that a user selects a specific climate file (same as for Climate Consultant) along with a program type such as office, residential etc. Information for the latter such as envelope materials and construction, conditioning schedules, internal loads, and ventilation ware stored in a template library and applied to a single-zone EnergyPlus model (Figure 4). This model is supposed to represent a climate box, i.e. the abstraction of a building rather than an actual architectural design. The climate box is 10m by 10m open plan with 3m floor to ceiling height and 30% window to wall ratio. Operable area ratio is 30% of opening area and discharge coefficient is 0.65 giving a net area of 1.8m2 for air exchange. Ventilation Air Change Rate (ACH) of the zone is calculated using simple wind and stack equations implemented in Archsim based on EnergyPlus Input Output Reference ( The upper setpoint is 33.5 o C as the Adaptive Comfort Standard works if the mean monthly outdoor temperature is between 10 o C and 33.5 o C (ANSI/ASHRAE Standard ). The lower natural ventilation setting is adjusted to 23 o C outdoor air temperature. Indoor air speed can not be more than 0.2 m/s for temperatures lower than 23 o C (ANSI/ASHRAE Standard ). Physiological cooling of elevated air speed can be implemented for temperatures above 23 o C where air speeds can go up to 0.8 m/s for office spaces and 1.2 m/s for less sedentary activity spaces such as residence (ANSI/ASHRAE Addendum g 2016). In addition to calculated ventilation and physiological cooling, a constant infiltration rate of 0.6 ACH is considered based on the base reference given in PNNL document prepared for the U.S Department of Energy (PNNL ). This infiltration rate is equivalent to 50 lit/sec and sufficient to provide required fresh air supply for a maximum of 5 people with 10 lit/sec/person base standard. The climate box, being a small and very open space, is supposed to yield the maximum ventilation cooling potential for a given program type and climate. Cross ventilation based on wind and buoyancy ventilation are both supported. Further study is being conducted to optimize physical definition of the climate-box and possibilities of providing user control on building parameters such as occupancy schedules while maintaining the simplicity of the method. 42

43 Weather File Building Program Design strategies and annual results Figure 25 CLIMA+ user inputs Users select the building program and upload weather file before running EnergyPlus thermal simulation. Figure 26 Occupancy schedules used for office and residence templates Thermal simulation From a building physics standpoint, direct natural ventilation effects on comfort can be classified into two different phenomena: cooling ventilation by lowering operative temperature and cooling ventilation effected by moving air near an occupant inside a building. Cooling ventilation by lowering operative temperature This approach measures how much operative temperatures during overheated hours are reduced with cooling ventilation where indoor warmer air is replaced with outdoor cooler air. Air displacement calculation methods that naturally exchange inside air with outside air lead to comfort improvements if outside air is cooler than inside air. In the case of buoyancy driven ventilation, this temperature difference between inside and outside is required to initiate the air exchange in the first place. Once the temperature difference drops below 3 K the sensible cooling effect becomes quite small, even if air change rates as high as 5ACH can be maintained (CIBSI AM 10). Transient thermal simulation programs such as EnergyPlus consider temperature and air change rates. Effective reduction in overheating hours achieved by ventilation can be measured by comparing simulation results from low and high ventilation scenarios. Cooling ventilation by the effect of moving air (physiological cooling) Moving air has long been used to provide comfort in warm environments. Provision for indoor air movement was one of the wellsprings of traditional architectural design in warm regions, affecting building form, components, and equipment over millennia (Arens et al 2009). 43

44 Residence Office Occupancy (no of people) p/m p/m2 Equipment 5 W/m2 14 W/m2 Lighting set point 200 lx 500 lx Electrical lighting load 1W/m2 8 W/m2 Heating set point 20 o C 20 o C Ventilation Buoyance and wind Buoyance and wind Figure 27 Thermal model settings Residence and Office single zone thermal model settings for internal loads, conditioning and ventilation defined in simulation input files. Cold Average Hot External Facade U U U Glazing Triple-Pane Double-Pane Double-Pane Glass Coating Low-E Low-E Low-E Shading Internal External External Slab Adiabatic Adiabatic Adiabatic Ceiling/roof Adiabatic Adiabatic Adiabatic Figure 28 Building constructions for three different envelope performance options Envelope and thermal mass properties ASHRAE 90.1 defines construction types based on energy performance requirements and the standard presented for the different climate zones applies for all building types except low-rise residential building. The envelope performances for all templates are defined by U-values as provided in ASHRAE Among the four construction types in the ASHRAE Energy Standard; mass, metal buildings, steel structures and wood framed; at the current stage of the method only envelope performance value of steel structure is used for the single zone model. The U-values range between (climate zone 0) and (climate zone 8). For each of the functions, residence and office, 18 variants of single zone energy plus intermediate data files, IDFs are created. Envelope performance and thermal mass of the building highly influence the effectiveness of cooling ventilation. Consequently, the 18 variants presented are based on the 9 different envelope performances that are defined for each thermal climatic zone. For each of the 18 templates, four different thermal mass integration options that range from high mass (10 cm thickness) to low mass (without additional mass) are provided. The additional thermal mass is applied on the internal surface of the climate zone s floor. For high thermal mass conditions, the additional 10 cm thermal mass has a volumetric heat capacity of 50 x 10 6 J/K. 44

45 Building Preference Envelope Thermal Mass Occupant Preference Indoor air speed Humidity Figure 29 Building and occupant preferences Designers can select building envelopes, thermal mass and indoor air speeds from provided options. Post processing of simulation results Simulated results are evaluated based on the ASHRAE 55 s Adaptive Comfort Model and Elevated Air Speed standards to calculated number of hours that fall outside of the comfort limit (ANSI/ASHRAE/IES Standard ). In addition, indoor air humidity levels which are less than 20% and higher than 85% RH (relative humidity percentage) are counted towards hours of discomfort. User inputs and strategy selection To achieve sufficient simplicity while guaranteeing consideration of critical building parameters, all the zone input settings are predefined for the climate box as discussed in the above section. The user is able to run all prototypes that are defined in the IDF simulation files by selecting the program and uploading EnergyPlus weather data for the project s location. As mentioned above, there are two main categories of user inputs: building preferences and occupant preferences (Figure 6). Building preferences are given for envelope performance where three options are provided: cold, temperate and hot climates. Furthermore, these options can be used with base construction option for thermal mass or can be combined with high thermal mass option where additional construction layer is introduced to augment thermal capacity of the zone. Occupant preferences are defined for physiological cooling effects with elevated air speed and indoor humidity levels. Under the Graphical Elevated Air Speed Method (ANSI/ASHRAE Standard ), the required air speed for light, primarily sedentary activities may not be higher than 0.8 m/s although higher air speeds are acceptable when using the SET Method (ANSI/ASHRAE Standard , Section ). In contexts where occupants are engaged in non-sedentary activities, most commonly in residences, have a wider tolerance for higher elevated air speed of a 1.2 m/s maximum threshold. 45

46 Overheated hours and comfort rating Adaptive comfort range Indoor operative temperature Outdoor temperature Temperature bar: shows hours outside of comfort Humidity bar: shows hours outside of comfort Figure 30 Temporal chart for a residence in Phoenix Most overheated hours are from May to September. Indoor humidity levels remain below 85% all year round. User interface and visualization of results Once all the six simulations are completed for the selected program and climate data, the interface displays a temporal graph for the typology with the least number of overheated hours, giving a summary of selected envelope, thermal mass definition and indoor air speed. The number of overheated hours are shown in bold at the top-right corner of the chart. A comfort level rating highlighting the number with green, yellow or red marks the range from comfortable to very hot. Analysis result for the chosen set of building parameters is shown in a comprehensive time-based chart (Figure 28). The main graph in the upper section of the interface displays operative temperatures of all hours in dark dotted marks. Outdoor dry bulb temperature is shown in a light grey color shade at the background to give a good sense of outdoor condition in contrast to the indoor operative temperatures. The grey band going across all hours represents the adaptive comfort range as defined by the ASHRAE standard 55 s adaptive comfort model. The comfort band clearly shows when in the year thermal comfort is achieved with natural ventilation and when it is too hot. The two horizontal bands in the lower part of the graph summarize comfortable hours and relative humidity levels as shown in Figure

47 Figure 31 CLIMA+ interface 1 showing natural ventilation prediction in the first phase using climate data. Figure 32 CLIMA+ interface 2 showing natural ventilation prediction in the first phase using climate data. 47

48 3.2 Integration with Design Process The optimized template using CLIMA+ can be imported to Grasshopper by using Archsim s Zone component. This optimized template can then be integrated with a new design geometry. The designer has the option to re-evaluate the performance of the design during the design process using CLIMA+. One of the buttons in the top left corner of the interface that has a CSV file icon is designed to import such type of EnergyPlus simulation result files (see Figures 30 and 31). The Building Performance Simulation (BPS) engine that is used by Archsim is EnergyPlus (Crawley et al., 2000). The journal paper by ANSI/ASHRAE (2011) has stated that EnergyPlus has been thoroughly validated and tested in practice so that whole buildings can be modeled reliably and in great detail (Archsim Primer). The first generation of BPS engines emerged in the eighties and nineties to overcome limitations of the until then common steady-state single room heat balance models. The purpose of dynamic models using computational heat transfer methods such as response functions or finite-difference methods was to model transient thermal-mass effects (Clarke, 2000). Archsim Energy Modeling is a plugin that brings fully featured EnergyPlus simulations to Rhino/Grasshopper and thus links the EnergyPlus simulation engine with a powerful parametric design and CAD modeling environment. Archsim allows you to create complex multi-zone energy models, simulate them and visualize results all within the Rhino/Grasshopper environment. Archsim supports advanced daylighting and shading controls, ventilation modules such as wind and stack natural ventilation, airflow-networks, simple HVAC, photovoltaics and phase changing materials. It is typically used for rapid early design exploration where building shape, window to wall ratios, facade and glazing systems and passive approaches such as shading and natural ventilation potential are tested for their impact on the building environmental performance and comfort (Archsim Primer). 48

49 Workflow with 3D CAD Design Environment C L I M A + Figure 33 Workflow of CLIMA+ with a 3D CAD design environment. 49

50 Climate Consultant and CLIMA+ Vancouver SanFrancisco Salem Alburquerque Boise LosAngeles Minot Duluth Burlington Boston Lisbon ElPaso Chicago TelAviv Phoenix Houston Miami Mumbai Riyadh Kuwait Climate Consultant Best Residence Figure 34 A comparison of predicted overheated hours by Climate Consultants Psychrometric chart and the proposed method with CLIMA+ 3.3 Results and Discussion The authors have closely studied the cooling ventilation calculation methods used by climate-file based bioclimatic charts and simulation based calculations to predict potential of natural ventilation in a particular climate to achieve thermal comfort. The 20 different climates that are used to study the natural ventilation prediction parameters presented in the first phase of CLIMA+ are used in this section to compare results in the second phase. Hours of discomfort calculations are based on the extended Adaptive Comfort Model (CBE Thermal Comfort Tool) where physiological cooling effect with elevated air speed is incorporated to the Adaptive Comfort Model. In addition, the authors have accounted discomfort in naturally ventilated zone caused due to high humidity where indoor air relative humidity is higher than 85%. 50

51 CLIMA + overheated occupied hours Vancouver SanFrancisco Salem Alburquerque Boise LosAngeles Minot Duluth Burlington Boston Lisbon ElPaso Chicago TelAviv Phoenix Houston Miami Mumbai Riyadh Kuwait Office Occ Best Residence Occ Best Figure 35 Office and residence occupied hours A comparison of overheated hours predicted by CLIMA+ Figure 34 compares Climate Consultant s report on overheated hours and calculated results using the proposed method for 20 different climates. Results from Climate Consultant, best residence and office scenarios consider high thermal mass strategy and cooling ventilation. The locations are selected mainly from the list of DOE s prototypes for different climates ranging from Climatic Zone 1 (hot) to Climatic Zone 8 (cold) as referenced in ASHRAE s construction standards. A few more climates including Kuwait and Mumbai are added to represent wider variety of climatic conditions. Climate consultant considers the effect of comfort ventilation where by indoor air is completely replaced with outdoor temperature hence indoor air temperature follows outdoor air temperature. The underlying logic behind this climate-based analysis assumes that 100% heat and mass transfer has taken place between indoor air and incoming outdoor air. In addition, it accounts for Physiological cooling effect by evaluating wind speed from weather data and translating it into indoor air speed according to the guidelines given in ASHRAE Fundamentals 2005 (Climate Consultant Documentation: Natural Ventilation Cooling). This results in a perceived temperature reduction of 2.5 o C for air velocity of 0.82 m/s and 3.7 o C for air velocity of 1.60 m/s (Climate 51

52 Consultant 6.0 Documentation). As a result, climate consultant s comfort prediction during warm to hot seasons is calculated mainly based on outdoor conditions of air temperature, humidity and wind speed. Effects of internal gain and solar gain are only accounted during hours of low temperatures. Climate Consultant considers thermal mass as a cooling design strategy independent from the comfort ventilation. Maximum and minimum dry bulb temperatures above and below comfort thresholds are used to evaluate each hour of each day rather than diurnal cycles. As a result, comparison of proposed method and climate consultant shows that the latter tends to estimate higher number of discomfort hours from overheating than simulated thermal zones with thermal mass (See Figure 34). The evaluation shown in Figure 35 clearly indicated that making functional distinctions is crucial when predicting potential of ventilation cooling. In addition, it is very critical to analyze occupied hours of the respective programs to estimate hours of discomfort. In all prototypes, the goal is to provide maximum ventilation cooling as discussed in the methodology section. One limitation of Climate Consultant is the absence of occupancy schedule definition except the general filtering to select months, dates and hours of the year. At the current stage of the study presented in this paper, residence and office prototypes are considered. Other programs including retails and manufacturing spaces will be studied in future work. Vancouver SanFrancisco Salem Alburquerque Boise LosAngeles Minot Duluth Burlington Boston Lisbon ElPaso Chicago TelAviv Phoenix Houston Miami Mumbai Riyadh Kuwait CLIMA+ discomfort hours for residence High Humidity High Temperature Figure 36 A comparison of number of discomfort hours due to high temperature and high humidity. 52

53 Limitation of natural ventilation cooling in different climates can be because of high humidity or high temperature. About 100% of discomfort in the climates of Kuwait, Riyadh and Phoenix is due to high temperature, which is above the adaptive comfort maximum threshold while in Miami, Mumbai and Houston discomfort is due to a combination of high humidity and temperature (See Figure 36). The distinction between high temperature and high humidity is important in selecting natural ventilation strategies and other complementary active systems when necessary. If the main cause of discomfort is high outdoor temperature the goal of design will be to lower operative temperatures. On the other hand, if the main cause of discomfort is high air humidity the strategy will be to increase physiological cooling by enhancing air movement. CLIMA+ on thermal mass effectiveness Vancouver SanFrancisco Salem Alburquerque Boise LosAngeles Minot Duluth Burlington Boston Lisbon ElPaso Chicago TelAviv Phoenix Houston Miami Mumbai Riyadh Kuwait Low Thermal Mass High Thermal Mass Figure 37 Effect of thermal mass Hours of discomfort due to overheating calculated for residence for all hours to study the effect of thermal mass 53

54 Designing naturally ventilated buildings with thermal mass reduces overheated hours significantly. A comparison of residence prototypes with high and low thermal mass for the selected 20 cities is shown in Figure 37. This allows for daytime ventilation when outdoor temperature is below adaptive comfort s upper threshold. Moreover, when the condition for daytime ventilation is not met, night ventilation will be used to cool thermal mass to a lower temperature during the previous night. With this mode of ventilation, daytime ventilation will not be allowed and the space will be kept in comfort temperature during the day by radiation and convection from the cooled thermal mass. When acceptable comfort cannot be met with only natural ventilation and thermal mass, a hybrid system shall be considered by integrating mechanical cooling and ventilation. The proposed method gives annual building performance analysis for a given climate by indicating times in the year where conditions are above acceptable maximum thresholds (Figure 38). Two separate bars report overheated hours and high humidity hours. This in turn can be used to predict the need for active cooling and ventilation to provide comfortable environment. The first two charts at the top of Figure 38 illustrates analysis with the proposed method for high thermal mass residence prototypes for Kuwait and Miami. Discomfort hours in naturally ventilated space in Kuwait are due to overheating in May through August. In comparison, number of discomfort hours in Miami is a fifth of that of Kuwait and is due to both overheating and high humidity. 54

55 Kuwait (left) and Miami (right) prototypes with high thermal mass Phoenix, residence (left) and office (right) with low thermal mass Albuquerque, with high thermal mass (left) and with low thermal mass (right) San Francisco, with high thermal mass (left) and with low thermal mass (right) Figure 38 The comparisons of temporal graphs for the climates of Kuwait, Phoenix, Albuquerque, and San Francisco 55

56 4 Mapping Natural Ventilation Potential Globally By 2030, 1.1 billion more people will live on Earth bringing the total to about 8.5 billion (Forman et Wu 2016). Such an increase in population will result in urban expansion and more pollution, and it will alter the built environment as well as the natural environment. The mapping of natural ventilation potential globally shows the potential of ventilation in cities worldwide ranging from cold to hot and from humid to dry. Different sources of climatic data that have outdoor temperature and humidity are explored. The environmental data presented by ASHRAE 169: Climate Data for Building Design Standards and CIBSI Guide A: Environmental Design have been compared. However, digitally available weather data in EPW format is chosen for this study because of its convenience for a python script based calculation method. Typical Meteorological Year (TMY) weather files are available for 1,600 locations (Source: Dru Crawly et Linda Lawrie, Big Ladder Software). However, these weather files do not have sufficient coverage in the Sub-Saharan Africa and the Latin America where cities with large number of population are located. Additional EPW format weather files are accessed using Meteonorm ( A total of 2,450 weather files are compiled into a library to create the global map. The mapping is done using Data-Driven Documents (D3.js) by Mike Bostock which is a JavaScript library for visualizing data using web standards. It includes special libraries for data mapping on available geographical, topographical and choropleth maps. D3 creates interactive data visualizations for the web (Murray 2013). ArcGis platforms enabled by ESRI is used to preanalyze some of the data on maps. The resulting interactive global map is hosted on the web for public access. Please visit 56

57 Figure 39 Global maps showing natural ventilation predictions Each of these maps show the natural ventilation prediction parameters discussed in the second section CLIMA+ Phase I. The dots on the maps represent the locations of the 2,450 cities that have accessible weather data from EnergyPlus weather database and Meteonorm. The size of each dot represent the number of predicted natural ventilation hours. The distribution of the variation in the size of the dotes gives insights about the dominant predicted natural ventilation method for different regions of the globe. 57

58 5 Concluding Remarks The different natural ventilation cooling potential prediction methods currently used during the different phases of a design process of buildings can lead to inconsistent results, especially in cooling and heating dominated climates. This may lead to confusion among design team members and uncertainties whether natural ventilation is actually an option for a particular project. Going forward, the method promoted in this manuscript is important for steadfast design concept development by giving feedback on the best strategies where natural ventilation will be most effective. Temporal visualizations of comfort indicators inform when in the year selected strategies have achieved thermal comfort. Finally, the capability to analyze only for occupied hours of the building or for all hours of the year helps to customize design strategies based on intended programs of the project. CLIMA+ has the benefit of comparing strategies by enhancing indoor air movement, improving envelope properties and adding thermal mass. Furthermore, it shows the number of comfort hours added by the selected strategies. In the case of climate-file based analysis using building bioclimatic charts the application of all strategies is considered to increase comfort hours in all climates. Nevertheless, simulation based analysis clearly shows that strategies such as improving envelope performance and adding thermal mass do not necessarily contribute to comfort hours in some climates. Hence, the proposed method with CLIMA+ for an early design aims to guide designers towards reliable decisions by resolving inconsistencies during a design process. Comparing the building templates created for residence and office programs shows that the effectiveness of strategies differs among different climates. The templates are combinations of high and low thermal mass for envelope performances of the 9 climate zones as defined by ASHRAE 90.1 Energy Standard for Buildings. Designing high performance envelopes with lower U-values in hot climates such as Kuwait, Riyadh, Mumbai, Houston and Phoenix will increase hours of discomfort. However, adding thermal mass in these warm to hot climates will significantly increase comfort hours. As discussed in the third section of this manuscript, using a single zone model for evaluating potential of natural ventilation for cooling by lowering operative temperature as well as providing physiological cooling effect is made possible. This approach allows to account for building envelope properties and internal loads from occupancy, equipment and lighting in contrast to other climate-file based early design tools. The single zone model used for the proposed method is compared with the energy model of DOE s middle-sized commercial prototype building in Phoenix. The simulations are done using EnergyPlus engine and Archsim, which is a Grasshopper plugin in the 3D CAD working environment called Rhinoceros (Rhino3D, Grasshopper3D). The validation analysis has shown that the whole building simulation result is consistent with the proposed method. 58

59 5.1 Further Work C L I M A + Additional Capabilities Radiation analysis on vertical surfaces will be added to further enhance calculations of overheated hours. In addition to the annual temporal chart used to show simulated results in the tool s user interface, a psychrometric chart will be added in the options tab to display comfort predictions. The psychrometric chart will show comfort evaluations based on the PMV method as well as the adaptive comfort model for the predicted indoor conditions. Weather file morphing method for changed climate based on IPCC database will be integrated into CLIMA+. This feature will morph existing weather data for any location to enable building performance study under future climates (Jentsch et al). Climate data generations and morphing for natural ventilation and building performance study purposes require availability of building design related weather parameters. The study requires a coupling of climatic parameters such as temperature and humidity, and building design parameters including envelope performance, thermal mass and ventilation openings by comparing climate-file and thermodynamics based methods. Nine climate parameters have been looked at by M.F.Jentsch et al. These parameters are available readily in the HadCM3 s A2 model of Third Assessment Report (TAR). Generating Non-Geometric Building Template The climate file study proposed in CLIMA+ Phase I can be further expanded to auto-generate building template that is customized for the selected climate. The new building template can have heating, cooling and natural ventilation schedules optimized based on preferred strategies. Effect of Climate Change on Natural Ventilation Potential In higher greenhouse-gas emission scenarios, a global average 2 C warming threshold is likely to be crossed by 2060, whereas in a lower emissions scenario, the crossing of this threshold is delayed by up to several decades. On regional scales, however, the 2 C threshold will probably be exceeded over large parts of Eurasia, North Africa and Canada by 2040 if emissions continue to increase well within the lifetime of many people living now (Joshi et al 2011). A much bigger challenge of accommodating the projected 10.9 billion people in 2100 (Gerland et al 2014) follows the current challenge of accommodating the next billion people by The study of natural ventilation in buildings requires considering a longer period. Such a study has to deal with possible challenges of a changed climate in addition to population growth. Climate research can answer questions such as how does the climate influence weather and how does the climate affect the habitability of regions and, design research can respond to questions such as where to build (Marotzke et al 2017). The lifespan of a building can be different among different stakeholders involved in the construction and operation. Roof, mechanical systems, windows, wall, claddings, structure, floor 59

60 and foundation have different lifetime for refurbishment. A factsheet by University College London Faculty of Engineering sciences time generalizes life expectancy of a building to be 80 years while the other time horizon seen by energy policy is 5 to 50 years (UCL Engineering). This calls for a careful study of building performance in relation to external environmental conditions in current time as well as in projected period. The global-scale land planning proposed by Forman et Wu in their publication Where to put the next billion people has marked locations which are Suitable and Somewhat suitable for the next billion people. Working towards accommodating projected global population in the 21st century requires addressing climate change impact. Heating dominated regions will get warmer, hence higher chance for natural ventilation. On the other hand, temperate and cooling dominated regions could experience temperatures higher than acceptable comfort ranges reducing natural ventilation potential. Future study will answer a much broader question: What will be the effect of climate change on natural ventilation? Can natural ventilation enhance accommodation of the next billion people? 60

61 Appendix A. Thermal Climate Zone Definition 61

62 B. Temporal Charts of the Selected 20 Climates 62

63 63

A Comparison of Methods for Evaluating Ventilation Cooling Potential Building Program Based Climate Analysis for Early Design Decisions

A Comparison of Methods for Evaluating Ventilation Cooling Potential Building Program Based Climate Analysis for Early Design Decisions A Comparison of Methods for Evaluating Ventilation Cooling Potential Building Program Based Climate Analysis for Early Design Decisions Alpha Yacob Arsano and Christoph Reinhart Massachusetts Institute

More information

A Process to Assist Architects Utilize Wind Information for Passive Cooling

A Process to Assist Architects Utilize Wind Information for Passive Cooling PLEA2013-29th Conference, Sustainable Architecture for a Renewable Future, Munich, Germany 10-12 September 2013 A Process to Assist Architects Utilize Wind Information for Passive Cooling RASHED KHALIFA

More information

Thermal Comfort in Architecture

Thermal Comfort in Architecture Thermal Comfort in Architecture Ommid Saberi [1], Parisa Saneei [2] Amir Javanbakht [3] 1. Ph.D. Student (Architecture & Energy) in Shahid Beheshti Uni. Tehran Iran e: omid_saberi@yahoo.com 2. Architect

More information

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE S447 THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE by Bojan V. ANDJELKOVIĆ *,a, Branislav V. STOJANOVIĆ b, Mladen M. STOJILJKOVIĆ b, Jelena N. JANEVSKI

More information

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France Sylvain Boulet 1, Stéphanie Armand-Decker 2, FCBA Technological Institute I2M-TREFLE laboratory -

More information

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE Andjelković, V., B.et. al.: Thermal Mass Impact on Energy Performance of A Low, Medium and Heavy S507 THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE by Bojan

More information

SOLAR PASSIVE DESIGN: PRINCIPLES AND PRACTICE

SOLAR PASSIVE DESIGN: PRINCIPLES AND PRACTICE SOLAR PASSIVE DESIGN: PRINCIPLES AND PRACTICE Understanding Climate and Atmosphere Human impact on global weather Energy outlook in India Energy needs in buildings Comfort zone Solar passive design- Case

More information

Bio Climatic Analysis of Bhubaneswar-An Investigation to Arrive Human Comfort through Natural Ventilation

Bio Climatic Analysis of Bhubaneswar-An Investigation to Arrive Human Comfort through Natural Ventilation International Journal of Scientific and Research Publications, Volume 6, Issue 5, May 2016 557 Bio Climatic Analysis of Bhubaneswar-An Investigation to Arrive Human Comfort through Natural Ventilation

More information

Thermal Delight in Architecture

Thermal Delight in Architecture THERMAL COMFORT OPR Ball State Architecture ENVIRONMENTAL SYSTEMS 1 Grondzik 1 Thermal Delight in Architecture This work began with the hypothesis that the thermal function of a building could be used

More information

Potential for Improved Outdoor Comfort by Design in U.S. Climates

Potential for Improved Outdoor Comfort by Design in U.S. Climates Nathaniel Johnson, Adrian Turcato, Erik Olsen Transsolar New York Summary This white paper presents the potential for passive design strategies to improve comfort in outdoor environments in different regions

More information

IESVE Compliance for ASHRAE IES Virtual Environment

IESVE Compliance for ASHRAE IES Virtual Environment IESVE Compliance for ASHRAE 90.1 - IES Virtual Environment July 2018 IES Virtual Environment and Compliance with ASHRAE 90.1-2004, 2007, 2010 & 2013; Appendix G, Performance Rating Method and Chapter 11,

More information

POST OCCUPANCY DESIGN INERVENTION TO IMPROVE COMFORT AND ENERGY PERFORMANCE IN A DESERT HOUSE

POST OCCUPANCY DESIGN INERVENTION TO IMPROVE COMFORT AND ENERGY PERFORMANCE IN A DESERT HOUSE POST OCCUPANCY DESIGN INERVENTION TO IMPROVE COMFORT AND ENERGY PERFORMANCE IN A DESERT HOUSE Vidar Lerum Arizona State University P O Box 871605, Tempe, AZ, 85287-1605, USA vidar.lerum@asu.edu Venkata

More information

A Comparative Study of the Thermal Comfort of Different Building Materials in Sana a

A Comparative Study of the Thermal Comfort of Different Building Materials in Sana a American Journal of Engineering and Applied Sciences, 6 (1): 20-24, 2013 ISSN: 1941-7020 2014 Alhaddad and Jun, This open access article is distributed under a Creative Commons Attribution (CC-BY) 3.0

More information

681: Environmentally Responsive Architecture; Passive Design for School in Southern India

681: Environmentally Responsive Architecture; Passive Design for School in Southern India 681: Environmentally Responsive Architecture; Passive Design for School in Southern India Varun Kohli* Architectural Association School of Architecture, London, UK * varun.kohli@som.com Abstract This paper

More information

Simulation Before Design? A New Software Program for Introductory Design Studios

Simulation Before Design? A New Software Program for Introductory Design Studios SIMULATION BEFORE DESIGN? 1 Simulation Before Design? A New Software Program for Introductory Design Studios TROY NOLAN PETERS California Polytechnic State University INTRODUCTION The 2010 Imperative states:

More information

Thermal comfort evaluation of natural ventilation mode: case study of a high-rise residential building

Thermal comfort evaluation of natural ventilation mode: case study of a high-rise residential building J. Zuo, L. Daniel, V. Soebarto (eds.), Fifty years later: Revisiting the role of architectural science in design and practice: 50 th International Conference of the Architectural Science Association 2016,

More information

Design Strategies and Guide lines for Tropical Coast of Pakistan, Using Climate Consultant

Design Strategies and Guide lines for Tropical Coast of Pakistan, Using Climate Consultant European Journal of Sustainable Development (2016), 5, 3, 505-512 ISSN: 2239-5938 Doi: 10.14207/ejsd.2016.v5n3p505 Design Strategies and Guide lines for Tropical Coast of Pakistan, Using Climate Consultant

More information

Thermal Delight in Architecture

Thermal Delight in Architecture THERMAL COMFORT DESIGN CRITERIA Ball State Architecture ENVIRONMENTAL SYSTEMS 1 Grondzik 1 Thermal Delight in Architecture This work began with the hypothesis that the thermal function of a building could

More information

FULL YEAR PERFORMANCE SIMULATION OF A DIRECT-COOLED THERMAL STORAGE ROOF (DCTSR) IN THE MIDWEST

FULL YEAR PERFORMANCE SIMULATION OF A DIRECT-COOLED THERMAL STORAGE ROOF (DCTSR) IN THE MIDWEST FULL YEAR PERFORMANCE SIMULATION OF A DIRECT-COOLED THERMAL STORAGE ROOF (DCTSR) IN THE MIDWEST Richard C. Bourne Davis Energy Group, Inc. 123 C Street Davis, CA 95616 and Dr. Bing Chen Passive Solar Research

More information

HUMAN-BEHAVIOR ORIENTED CONTROL STRATEGIES FOR NATURAL VENTILATION IN OFFICE BUILDINGS

HUMAN-BEHAVIOR ORIENTED CONTROL STRATEGIES FOR NATURAL VENTILATION IN OFFICE BUILDINGS HUMAN-BEHAVIOR ORIENTED CONTROL STRATEGIES FOR NATURAL VENTILATION IN OFFICE BUILDINGS Haojie Wang 1, Qingyan Chen 1,2* 1 School of Mechanical Engineering, Purdue University, West Lafayette, IN 47907 2

More information

Bioclimatic Design Approach Integration into Architectural Design: a Library Case Study

Bioclimatic Design Approach Integration into Architectural Design: a Library Case Study PLEA 2016 Los Angeles - 36 th International Conference on Passive and Low Energy Architecture. Cities, Buildings, People: Towards Regenerative Environments Bioclimatic Design Approach Integration into

More information

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates Kittitach Pichatwatana, and Fan Wang Abstract This paper examines the TAS computer

More information

Design and retrofitting of a hybrid building in Athens

Design and retrofitting of a hybrid building in Athens International Conference Passive and Low Energy Cooling 597 Design and retrofitting of a hybrid building in Athens A. Gavalas Gavalas Architects, Athens ABSTRACT This paper s aim is to present a building

More information

ScienceDirect. Simulation based mixed mode building design

ScienceDirect. Simulation based mixed mode building design Available online at www.sciencedirect.com ScienceDirect Energy Procedia 00 (2016) 000 000 www.elsevier.com/locate/procedia 5th International Conference on Advances in Energy Research, ICAER 2015, 15-17

More information

Energy and indoor temperature consequences of adaptive thermal comfort standards

Energy and indoor temperature consequences of adaptive thermal comfort standards Energy and indoor temperature consequences of adaptive thermal comfort standards L. Centnerova and J.L.M. Hensen Czech Technical University in Prague, Czech Republic (lada@tzb.fsv.cvut.cz) Technische Universiteit

More information

Optimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016

Optimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016 Optimizing Indoor Environments for Occupant Satisfaction Presented by: Kelli Goldstone April 2016 Outline Function of HVAC Thermal Comfort Air Distribution Radiant Heating / Cooling Case Study Function

More information

4.432/4.433 Modeling Urban Energy Flows: Towards Sustainable Cities and Neighborhoods

4.432/4.433 Modeling Urban Energy Flows: Towards Sustainable Cities and Neighborhoods 4.432/4.433 Modeling Urban Energy Flows: Towards Sustainable Cities and Neighborhoods Department School of Architecture and Planning (Course 4) Time / Location Instructor Teaching Assistant Prerequisites

More information

Thermal and Energy Performance of Double Skin Facades in Different Climate Types

Thermal and Energy Performance of Double Skin Facades in Different Climate Types University of Massachusetts Amherst From the SelectedWorks of Ajla Aksamija 2017 Thermal and Energy Performance of Double Skin Facades in Different Climate Types Dr. Ajla Aksamija, University of Mass Available

More information

Evaluating the Building Performance of the Center for Promotion of Science in Block 39 in Belgrade, Serbia

Evaluating the Building Performance of the Center for Promotion of Science in Block 39 in Belgrade, Serbia Evaluating the Building Performance of the Center for Promotion of Science in Block 39 in Belgrade, Serbia Berrak Balci Abstract This paper presents the evaluation of the building performance of the previously

More information

CLIMATE ENERGY INDEX AND BUILDING ENERGY INDEX: NEW INDICES TO ASSESS AND BENCHMARK BUILDING ENERGY PERFORMANCE

CLIMATE ENERGY INDEX AND BUILDING ENERGY INDEX: NEW INDICES TO ASSESS AND BENCHMARK BUILDING ENERGY PERFORMANCE CLIMATE ENERGY INDEX AND BUILDING ENERGY INDEX: NEW INDICES TO ASSESS AND BENCHMARK BUILDING ENERGY PERFORMANCE Don McLean, Ya Roderick, Richard Quincey, David McEwan, Integrated Environmental Solutions

More information

Therma-Fuser Energy Analysis Report 2016

Therma-Fuser Energy Analysis Report 2016 Therma-Fuser Energy Analysis Report 2016 Executive Summary This study compares the annual HVAC energy use of a Therma-Fuser VAV system to that of a conventional VAV box system. A typical 68,800 square

More information

carbon-neutral architectural design Pablo La Roche CRC Press Taylor & Francis Croup Boca Raton London NewYork CRC Press is an imprint of the

carbon-neutral architectural design Pablo La Roche CRC Press Taylor & Francis Croup Boca Raton London NewYork CRC Press is an imprint of the carbon-neutral architectural design Pablo La Roche CRC Press Taylor & Francis Croup Boca Raton London NewYork CRC Press is an imprint of the Taylor fit Francis Group, an informs business Contents Preface

More information

Information paper 17. Prepared by: David Clark. book:

Information paper 17. Prepared by: David Clark. book: Information paper 17 Thermal comfort standards Prepared by: David Clark A paper referenced in the book: Cundall Johnston & Partners LLP. 2013 Issue 1.0: 29 July 2013 This information paper is one of a

More information

Perception of Thermal Comfort for Naturally Ventilated High School Classrooms in San Rafael, CA

Perception of Thermal Comfort for Naturally Ventilated High School Classrooms in San Rafael, CA Perception of Thermal Comfort for Naturally Ventilated High School Classrooms in San Rafael, CA GWENEDD MURRAY 1 1 Architectural Association, Inc., London, United Kingdom ABSTRACT: The primary intention

More information

Energy consumption and thermal comfort in a passive house built in Romania

Energy consumption and thermal comfort in a passive house built in Romania Chapter 3 - High Performance Sustainable Building Solutions Energy consumption and thermal comfort in a passive house built in Romania Cristina Tanasa, Cristian Sabau, Daniel Dan & Valeriu Stoian Polytechnic

More information

Influence of Building Orientation on the Indoor Climate of Buildings

Influence of Building Orientation on the Indoor Climate of Buildings 78 Influence of Building Orientation on the Indoor Climate of Buildings Marcelino Januário Rodrigues 1, Anne Landin 2. 1 PhD Student, Faculty of Engineering, Eduardo Mondlane University, P. O. Box 257,

More information

SUSTAINABLE BY PASSIVE ARCHITECTURE, USING COURTYARDS IN NON-DOMESTIC BUILDINGS IN SOUTHEAST QUEENSLAND

SUSTAINABLE BY PASSIVE ARCHITECTURE, USING COURTYARDS IN NON-DOMESTIC BUILDINGS IN SOUTHEAST QUEENSLAND 01-140 The 2005 World Sustainable Building Conference, SUSTAINABLE BY PASSIVE ARCHITECTURE, USING COURTYARDS IN NON-DOMESTIC BUILDINGS IN SOUTHEAST QUEENSLAND Upendra RAJAPAKSHA 1 PhD (Arch) Qld Richard

More information

CLIMATE CONTROL: OPR

CLIMATE CONTROL: OPR CLIMATE CONTROL: OPR A review/restatement of information from ARCH 273. Thermal comfort and indoor air quality (coming up) are critical foundations for active climate control (HVAC system) design. OPR

More information

4.432/4.433 Modeling Urban Energy Flows: Towards Resilient Cities and Neighborhoods

4.432/4.433 Modeling Urban Energy Flows: Towards Resilient Cities and Neighborhoods 4.432/4.433 Modeling Urban Energy Flows: Towards Resilient Cities and Neighborhoods Department School of Architecture and Planning (Course 4) Time / Location Instructor Teaching Assistant Prerequisites

More information

Available online at ScienceDirect. Procedia Engineering 169 (2016 )

Available online at   ScienceDirect. Procedia Engineering 169 (2016 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 169 (2016 ) 158 165 4th International Conference on Countermeasures to Urban Heat Island (UHI) 2016 Indoor Thermal Comfort Assessment

More information

Assessing thermal comfort of dwellings in summer using EnergyPlus

Assessing thermal comfort of dwellings in summer using EnergyPlus Assessing thermal comfort of dwellings in summer using EnergyPlus Irina Bliuc, Rodica Rotberg and Laura Dumitrescu Gh. Asachi Technical University of Iasi, Romania Corresponding email: irina_bliuc@yahoo.com

More information

Leluo Zhang 1, Murali Annavaram 1, Kyle Konis 1. Abstract. Introduction

Leluo Zhang 1, Murali Annavaram 1, Kyle Konis 1. Abstract. Introduction Occupant-Aware Energy Management: Simulated Energy Savings Achievable Using Learned Cooling Temperature Set-points Over a Range of Climates and Cooling System Designs Leluo Zhang 1, Murali Annavaram 1,

More information

A SENSITIVITY STUDY OF BUILDING PERFORMANCE USING 30-YEAR ACTUAL WEATHER DATA

A SENSITIVITY STUDY OF BUILDING PERFORMANCE USING 30-YEAR ACTUAL WEATHER DATA A SENSITIVITY STUDY OF BUILDING PERFORMANCE USING 30-YEAR ACTUAL WEATHER DATA Tianzhen Hong 1, *, Wen-Kuei Chang 2, Hung-Wen Lin 2 1 Lawrence Berkeley National Laboratory, 1 Cyclotron Road, Berkeley, CA

More information

Cost-Benefit Analysis of Dwelling Retrofit Options

Cost-Benefit Analysis of Dwelling Retrofit Options Cost-Benefit Analysis of Dwelling Retrofit Options The objective was to study the thermal behaviour of the existing house and suggest cost effective improvements. Over recent years the energy efficiency

More information

UC Berkeley Indoor Environmental Quality (IEQ)

UC Berkeley Indoor Environmental Quality (IEQ) UC Berkeley Indoor Environmental Quality (IEQ) Title Energy savings from extended air temperature setpoints and reductions in room air mixing Permalink https://escholarship.org/uc/item/28x9d7xj Authors

More information

171: An urban office designed for the southern Brazilian climate

171: An urban office designed for the southern Brazilian climate 171: An urban office designed for the southern Brazilian climate Marianne Costella Elemento 5 Bioclimatic Architecture, Brazil marianne@elemento5.com Abstract The climate in southern Brazil is characterised

More information

COMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES

COMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES COMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES Lusi Susanti 1, Hiroshi Matsumoto 2, and Hiroshi Homma 2 1 Department of

More information

COMMERCIAL LOAD ESTIMATING. Load Estimating Level 3: Block and Zone Loads. Technical Development Program

COMMERCIAL LOAD ESTIMATING. Load Estimating Level 3: Block and Zone Loads. Technical Development Program COMMERCIAL LOAD ESTIMATING Load Estimating Level 3: Block and Zone Loads Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design,

More information

Assessing external double skin envelopes coupled with night ventilation and thermal mass for passive cooling in the tropics

Assessing external double skin envelopes coupled with night ventilation and thermal mass for passive cooling in the tropics J. Zuo, L. Daniel, V. Soebarto (eds.), Fifty years later: Revisiting the role of architectural science in design and practice: 50 th International Conference of the Architectural Science Association 2016,

More information

Potential of passive design strategies using the free-running temperature

Potential of passive design strategies using the free-running temperature 850 2nd PALENC Conference and 28th AIVC Conference on Building Low Energy Cooling and Potential of passive design strategies using the free-running temperature L. Rosales, M. E. Hobaica Universidad Central

More information

Field investigation on indoor thermal environment of a high-rise condominium in hot-humid climate of Bangkok, Thailand

Field investigation on indoor thermal environment of a high-rise condominium in hot-humid climate of Bangkok, Thailand Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 00 (2017) 000 000 www.elsevier.com/locate/procedia International High- Performance Built Environment Conference A Sustainable

More information

Pinoleville Pomo Nation Sustainable Home: A case study of energy modeling on sustainable design

Pinoleville Pomo Nation Sustainable Home: A case study of energy modeling on sustainable design Pinoleville Pomo Nation Sustainable Home: A case study of energy modeling on sustainable design By Jeffrey Lee BS (Georgia Institute of Technology) 2013 A report submitted in partial satisfaction of the

More information

Passive Houses in South West Europe

Passive Houses in South West Europe Dr. Wolfgang Feist Passivhaus Institut Rheinstraße 44/46 D-64283 Darmstadt www.passiv.de Passive Houses in South West Europe A quantitative investigation of some passive and active space conditioning techniques

More information

URBAN HEAT ISLAND MITIGATION: LOOKING BEYOND POLICIES TO LOWER AIR TEMPERATURE

URBAN HEAT ISLAND MITIGATION: LOOKING BEYOND POLICIES TO LOWER AIR TEMPERATURE Cities and Climate Change Conference March 5 7, 2018 Edmonton, Alberta, Canada URBAN HEAT ISLAND MITIGATION: LOOKING BEYOND POLICIES TO LOWER AIR TEMPERATURE Evyatar Erell Ben Gurion University of the

More information

Thermal Comfort Measurements in a Hybrid Ventilated Office Room

Thermal Comfort Measurements in a Hybrid Ventilated Office Room Eawag 5237 Thermal Comfort Measurements in a Hybrid Ventilated Office Room Thomas Frank 1), Herbert Güttinger 2) and Stefan van Velsen 3) 1 Swiss Federal Laboratories for Materials Testing and Research

More information

Assessing the energy performance of modern glass facade systems

Assessing the energy performance of modern glass facade systems Assessing the energy performance of modern glass facade systems Abdelsalam Aldawoud * Architectural Engineering Department, University of Sharjah Sharjah, United Arab Emirates Abstract. The design and

More information

Bio-climatic Chart for Different Climatic Zones of Northeast India

Bio-climatic Chart for Different Climatic Zones of Northeast India Proceedings of 3 rd International Conference on Solar Radiation and Day Lighting (SOLARIS 27) February 7-9, 27, New Delhi, India Copyright 27, Anamaya Publishers, New Delhi, India Bio-climatic Chart for

More information

Simplified climate information for building designers

Simplified climate information for building designers J. Zuo, L. Daniel, V. Soebarto (eds.), Fifty years later: Revisiting the role of architectural science in design and practice: 50 th International Conference of the Architectural Science Association 2016,

More information

CLIMATE CONTROL: INTENT/CRITERIA

CLIMATE CONTROL: INTENT/CRITERIA CLIMATE CONTROL: INTENT/CRITERIA This lecture is a review/restatement of information from ARCH 273. Thermal comfort and indoor air quality (coming up) are critical foundations for HVAC system design. Ball

More information

COMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING

COMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING COMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING ABSTRACT F. Bagheri 1, M. Fakoor 1, B. Young 1, C. Cranswick 1 1 BC Building Science Ltd. 611 Bent

More information

Thermal comfort conditions in outdoor spaces

Thermal comfort conditions in outdoor spaces International Conference Passive and Low Energy Cooling 761 Thermal comfort conditions in outdoor spaces N. Gaitani and M. Santamouris University of Athens, Department of Physics, Division of Applied Physics,

More information

3C.1 Passive Solar Design National Sustainable Building Advisor Program

3C.1 Passive Solar Design National Sustainable Building Advisor Program 3C.1 Passive Solar Design National Sustainable Building Advisor Program Pablo La Roche PhD Passive Cooling But first. Strategies to Reduce Overheating Minimize Conductive Heat Flow Strategies to minimize

More information

Climatic Adaptation: Impacts On The Thermal Comfort Of Offices Buildings At Curitiba - Brazil.

Climatic Adaptation: Impacts On The Thermal Comfort Of Offices Buildings At Curitiba - Brazil. Climatic Adaptation: Impacts On The Thermal Comfort Of Offices Buildings At Curitiba - Brazil. Antonio Augusto P. Xavier and Ivan Azevedo Cardoso Technological Federal University of Parana UTFPR Curitiba

More information

PRINCIPLES AND POTENTIALS OF VENTILATIVE COOLING

PRINCIPLES AND POTENTIALS OF VENTILATIVE COOLING PRINCIPLES AND POTENTIALS OF VENTILATIVE COOLING PER HEISELBERG OPERATING AGENT IEA EBC ANNEX 62 BACKGROUND THE CURRENT DEVELOPMENT TOWARDS NEARLY- ZERO ENERGY BUILDINGS HAVE LEAD TO AN INCREASED NEED

More information

10 tips from your Architect

10 tips from your Architect 10 tips from your Architect Within the context of the national week of Energy Efficiency, in collaboration with the Energy Efficiency Management Office, the Mauritius Association of Architects offers you

More information

IMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS

IMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS IMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS Daeho Kang 1, Richard K. Strand 2 1 Department of Environmental Control Technology, New York

More information

THE USE OF THE CORRECTED EFFECTIVE TEMPERATURE INDEX

THE USE OF THE CORRECTED EFFECTIVE TEMPERATURE INDEX AN ASSIGNMENT ON THE USE OF THE CORRECTED EFFECTIVE TEMPERATURE INDEX BY OMOBUDE IGHODALO FELIX. ARC/05/5640. COURSE CODE: ARC. 810. COURSE TITLE: BUILDING CLIMATOLOGY. COURSE LECTURER: PROF. O. OGUNSOTE.

More information

Allowing for Thermal Comfort in Free-running Buildings in the New European Standard EN15251

Allowing for Thermal Comfort in Free-running Buildings in the New European Standard EN15251 Allowing for Thermal Comfort in Free-running Buildings in the New European Standard EN15251 Fergus Nicol, Low Energy Architecture Research Unit (LEARN), School of Architecture, London Metropolitan University,

More information

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS Bjarne W. Olesen Ph. D, International Centre for Indoor Environment and Energy, Department of Mechanical Engineering, Technical

More information

Part 1 Review Questions on material covered in Midterms I & II

Part 1 Review Questions on material covered in Midterms I & II 1 Arch 463 ECS Fall 2001 Name FINAL 40 Multiple Choice Questions Part 1 Review Questions on material covered in Midterms I & II 1. Passive systems for environmental control A. can enhance human comfort

More information

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Available online at  ScienceDirect. Procedia Engineering 121 (2015 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 121 (2015 ) 2044 2051 9th International Symposium on Heating, Ventilation and Air Conditioning (ISHVAC) and the 3rd International

More information

CAE 331/513 Building Science Fall 2017

CAE 331/513 Building Science Fall 2017 CAE 331/513 Building Science Fall 2017 November 14, 2017 Heating load calculations Advancing energy, environmental, and sustainability research within the built environment www.built-envi.com Twitter:

More information

Workshop: Architecture-Tradition and Modernization. Climate Responsive Urban Design

Workshop: Architecture-Tradition and Modernization. Climate Responsive Urban Design Workshop: Architecture-Tradition and Modernization Climate Responsive Urban Design Trends of none sustainable planning Planners of the twentieth Century seem to have assumed that urban settlements were

More information

PASSIVE COOLING STRATEGIES. Passive Cooling

PASSIVE COOLING STRATEGIES. Passive Cooling PASSIVE COOLING STRATEGIES www.ecohomes.gr/ fact or fiction: does saying it s so with arrows make it so? Ball State Architecture ENVIRONMENTAL SYSTEMS 1 Grondzik 1 Passive Cooling Before refrigeration

More information

CHAPTER 6 CONCLUSION

CHAPTER 6 CONCLUSION 255 CHAPTER 6 CONCLUSION This study thoroughly assessed the design principles employed in simple, durable and eco-friendly vernacular dwellings in the coastal regions of Tamil Nadu and their effectiveness

More information

Improving Thermal Comfort & Reducing Energy Consumption in Naturally Ventilated University Buildings

Improving Thermal Comfort & Reducing Energy Consumption in Naturally Ventilated University Buildings Australasian Campuses Towards Sustainability 26 th -28 th September 2012: Brisbane, Australia Improving Thermal Comfort & Reducing Energy Consumption in Naturally Ventilated University Buildings Laia Ledo,

More information

Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building

Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building Shafqat Hussain and Patrick H. Oosthuizen Department of Mechanical and Materials Engineering, Queen s

More information

A first look at the affect of outdoor planting on the indoor environment of St. Loyes Residence. David Coley. March 2011 Internal Document 776

A first look at the affect of outdoor planting on the indoor environment of St. Loyes Residence. David Coley. March 2011 Internal Document 776 Centre for Energy and the Environment Tel. (01392) 264144 Fax. (01392) 264143 Website http://www.ex.ac.uk/cee/ E-mail d.a.coley@ex.ac.uk A first look at the affect of outdoor planting on the indoor environment

More information

PASSIVE SOLAR BUILDING DESIGN STRATEGIES IN LALITPUR, POKHARA AND DHARAN CITIES OF NEPAL

PASSIVE SOLAR BUILDING DESIGN STRATEGIES IN LALITPUR, POKHARA AND DHARAN CITIES OF NEPAL PASSIVE SOLAR BUILDING DESIGN STRATEGIES IN LALITPUR, POKHARA AND DHARAN CITIES OF NEPAL Prativa Lamsal 1, Sushil B. Bajracharya 2 1 Department of Mechanical Engineering, 2 Department of Architecture,

More information

What is Sustainable Design?

What is Sustainable Design? What is Sustainable Design? Part Three: The Basic Principles of Passive Design Terri Meyer Boake BES, BArch, MArch, LEED AP Associate Director School of Architecture University of Waterloo Past President

More information

A SIMPLE USER INTERFACE FOR ENERGY RATING OF BUILDINGS

A SIMPLE USER INTERFACE FOR ENERGY RATING OF BUILDINGS Proceedings of Building Simulation 2011: 1 2 3 4 5 6 7 8 9 10 A SIMPLE USER INTERFACE FOR ENERGY RATING OF BUILDINGS Abraham Yezioro 1, Oren Shapir 1, and Guedi Capeluto 1 1 Faculty of Architecture and

More information

Findings of Field Survey for Thermal Comfort and Ventilation in US Office Buildings

Findings of Field Survey for Thermal Comfort and Ventilation in US Office Buildings Findings of Field Survey for Thermal Comfort and Ventilation in US Office Buildings Liangcai Tan 1, Samir Moujaes, HDR Inc. University of Nevada Las Vegas SUMMARY This paper presents the measured data

More information

ENERGY-EFFICIENCY IN AIR-CONDITIONED BUILDINGS: AN OVERVIEW

ENERGY-EFFICIENCY IN AIR-CONDITIONED BUILDINGS: AN OVERVIEW ENERGY-EFFICIENCY IN AIR-CONDITIONED BUILDINGS: AN OVERVIEW ABSTRACT Essam E. Khalil Professor of Mechanical Engineering, Cairo University, Egypt Convenor ISO TC205_WG2 The Egyptian community in its path

More information

Introduction to basics of energy efficient building design

Introduction to basics of energy efficient building design Introduction to basics of energy efficient building design Pierre Jaboyedoff Seminar on Energy Efficient & Thermally Comfortable Buildings in Amravati For CRDA, Andhra Pradesh May 2 nd 2017 Indo-Swiss

More information

ARPAN JOHARI. Architect. 13/08/10 AW Design. Ahmedabad

ARPAN JOHARI. Architect. 13/08/10 AW Design. Ahmedabad ARPAN JOHARI. Architect THERMAL MASS Thermal mass (or thermal capacitance) is defined as the ability of a body to store heat THERMAL MASS Thermal mass is also known as Fabric Energy Storage, FES (The Concrete

More information

Energy simulation of traditional vs. adaptive thermal comfort for two

Energy simulation of traditional vs. adaptive thermal comfort for two Hensen, J.L.M. & Centnerova, L. (2001). Energy simulation of traditional vs. adaptive thermal comfort for two moderate climate regions. Proceedings of the International conference "Moving Thermal Comfort

More information

COPYRIGHTED MATERIAL. Contents Overview WHAT'S IN THE SWL PRINTED WHAT'S IN THE SWL ELECTRONIC I NAVIGATION 20 VIII DETAILED DESIGN STRATEGIES E.

COPYRIGHTED MATERIAL. Contents Overview WHAT'S IN THE SWL PRINTED WHAT'S IN THE SWL ELECTRONIC I NAVIGATION 20 VIII DETAILED DESIGN STRATEGIES E. WHAT'S IN THE SWL PRINTED I NAVIGATION 20 SWL Printed Contents SWL Electronic Contents Additional Navigation Methods II USING SUN, WIND & LIGHT 50 Buildings and Energy Use Design Decision Chart for Net-Zero

More information

Thermal environment and thermal comfort in a passive residential building in the severe cold area of China

Thermal environment and thermal comfort in a passive residential building in the severe cold area of China Thermal environment and thermal comfort in a passive residential Yuchen Ji Ph D. Candidate Harbin Institute of Technology China 15B927029@hit.edu.cn Professor, Zhaojun Wang, Harbin Institute of Technology,

More information

Responsive Building Elements Actual Development and Trends Within IEA

Responsive Building Elements Actual Development and Trends Within IEA Responsive Building Elements Actual Development and Trends Within IEA Dipartimento di Energetica, Politecnico di Torino Torino (Italy( Italy) e_mail: marco.perino@polito.it Research and technological innovation,

More information

OPEN COMPETITION Energy Design of High Performance Buildings Organised by EC-JRC and ESRU

OPEN COMPETITION Energy Design of High Performance Buildings Organised by EC-JRC and ESRU OPEN COMPETITION Energy Design of High Performance Buildings Organised by EC-JRC and ESRU Target group: under-graduate, postdoc, PhD students and researchers level SUMMARY The objective is to assess for

More information

Module 3: Simulation and Data Analysis

Module 3: Simulation and Data Analysis INSTRUCTIONAL MODULES DEMONSTRATING BUILDING ENERGY ANALYSIS USING A BUILDING INFORMATION MODEL Christian Daniel Douglass Industrial and Enterprise Systems Engineering December 1, 2010 Module Summary In

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Research on indoor thermal environment of stilted buildings in Chongqing, China

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Research on indoor thermal environment of stilted buildings in Chongqing, China Healthy uildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0270 ISN: 978-83-7947-232-1 Research on indoor thermal environment of stilted buildings in Chongqing, China Ya nan Xu 1, Zhenjing Yang

More information

Summer thermal comfort in traditional buildings of the 19th century in Florina, north-western Greece

Summer thermal comfort in traditional buildings of the 19th century in Florina, north-western Greece International Conference Passive and Low Energy Cooling 239 Summer thermal comfort in traditional buildings of the 19th century in Florina, north-western Greece A. Oikonomou Department of Architectural

More information

UNDERSTANDING CLIMATE FOR ENERGY EFFICIENT OR SUSTAINABLE DESIGN

UNDERSTANDING CLIMATE FOR ENERGY EFFICIENT OR SUSTAINABLE DESIGN UNDERSTANDING CLIMATE FOR ENERGY EFFICIENT OR SUSTAINABLE DESIGN Anir Kumar Upadhyay Freelance Architect/ Urban Planner, Australia E-mail: anirupadhyay@yahoo.com ABSTRACT Understanding climate is a pre-requisite

More information

Impact of Cooling Strategies on Energy Reduction

Impact of Cooling Strategies on Energy Reduction Proceedings of the 2 nd World Congress on Civil, Structural, and Environmental Engineering (CSEE 17) Barcelona, Spain April 2 4, 2017 Paper No. AWSPT 151 ISSN: 2371-5294 DOI: 10.11159/awspt17.151 Impact

More information

SRM UNIVERSITY FACULTY OF ENGINEERING AND TECHNOLOGY SCHOOL OF ARCHITECTURE AND INTERIOR DESIGN

SRM UNIVERSITY FACULTY OF ENGINEERING AND TECHNOLOGY SCHOOL OF ARCHITECTURE AND INTERIOR DESIGN SRM UNIVERSITY FACULTY OF ENGINEERING AND TECHNOLOGY SCHOOL OF ARCHITECTURE AND INTERIOR DESIGN DEPARTMENT OF ARCHITECTURE & INTERIOR DESIGN: Course Code : ARE0201 Course Title : CLIMATOLOGY Branch : B.Tech

More information

Simulating a Passive Downdraft Evaporative Cool Tower

Simulating a Passive Downdraft Evaporative Cool Tower Simulating a Passive Downdraft Evaporative Cool Tower Liam Buckley 1 1 IES Ltd, Boston, MA, USA Abstract This paper is focussed on the concept, design and simulation methodology for a passive downdraft

More information

Bioclimatic approaches of modern residential architecture in Cyprus,

Bioclimatic approaches of modern residential architecture in Cyprus, European Association for the Development of Renewable Energies, Environment and Power Quality (EA4EPQ) International Conference on Renewable Energies and Power Quality (ICREPQ 10) Granada (Spain), 23th

More information

PCM s in application for acclimatization of buildings. Nick Barnard, Faber Maunsell VSK2008, Workshop on heat storage

PCM s in application for acclimatization of buildings. Nick Barnard, Faber Maunsell VSK2008, Workshop on heat storage PCM s in application for acclimatization of buildings Nick Barnard, Faber Maunsell VSK2008, Workshop on heat storage Overview Case study building Cooling solution 1: Night cooling + thermal mass Cooling

More information

546: High Altitude Design, Optimising Residential Architecture in the Alborz Mountains, Iran

546: High Altitude Design, Optimising Residential Architecture in the Alborz Mountains, Iran 546: High Altitude Design, Optimising Residential Architecture in the Alborz Mountains, Iran Yasamin Arbabi Architectural Association, Graduate School Abstract Darbandsar is a village located in the Alborz

More information