HAZARDOUS AREA MOTOR/DRIVE PROTECTION PRINCIPLES AND OPTIMUM SELECTION CRITERIA
|
|
- Nora Charles
- 6 years ago
- Views:
Transcription
1 HAZARDOUS AREA MOTOR/DRIVE PROTECTION PRINCIPLES AND OPTIMUM SELECTION CRITERIA Copyright Material PCIC Europe Paper No. PCIC Middle East ME17-4 Dip.-Ing Hugo Stadler Siemens Germany Eur Ing Steve Jackson MA BSc CEng Siemens UK Abstract - This paper will provide an overview of hazardous area classifications including the implications of the latest IEC standards and the LV/HV motor & drive protection principles of nonsparking, increased safety, flame proof and pressurised. The relative advantages for each technique will then be discussed for different scenarios such as atmosphere, overload, starting, inverter operation, size, weight, flexibility and cost. Index Terms Hazardous Area, Protection, Motors, Increased Safety, Flame Proof, Non-Sparking, Purge. I. INTRODUCTION This paper will cover hazardous area basics, a description and comparison of motor Ex protection types followed by advice on matching drives to Ex motors and a cost evaluation. II. HAZARDOUS AREA MOTORS & DRIVES A. Ex-protection in Electrical Apparatus Ignition source EXPLOSION Three components are required to make a hazardous situation: - flammable material, oxygen and an ignition source. B. Definition of Zones Fig 2 Hazardous Area Zones Zones are defined on the probability of a hazard occurring in that area. Zone 0 which has a permanent threat of an occurrence is generally not suitable for any sort of electrical machine. C. Precautions Zone : Gas & Vapors Zone : Dust N America Div 1 Class I ~ Gas Zone 1 Div 2 Class I ~ Gas Zone 2 Risk minimization basic principles according to EN Protection measures have to be undertaken in the following sequence: Primary Ex-protection Prevent hazardous atmospheres - Limit concentration of flammable material - Inertization (add Nitrogen, Carbon Dioxide) Occurrence: rare, short time ( <10h/a) Occurrence: occasional (10h/a < 1000h/a) Occurrence: permanent, long term (>1000h/a) Secondary Ex-protection Avoid every potential ignition source Explosive atmosphere: gas, vapor, fog, dust and air in Correct dispersion and concentration Fig 1 Conditions for Explosion Tertiary Ex-protection Limit the consequences of an explosion to a harmless degree. Protection methods for electrical machines are part of the secondary precaution to avoid every potential ignition source. 1
2 D. Classification of Electrical Directive 94/9/EC EN I II category Types of protection Examples EPL Protection Level Fig 3 Electrical Classification In the Category designations M means Mines, G means Gases and D means Dust. This paper will only focus on the G Gases category. In approximate terms the Explosion Protection Levels (EPL) Ga, Gb, Gc correspond to the Categories 1G, 2G and 3G which align with the Zones 0, 1 and 2. The latest IEC standards mean that na (non sparking) will become ec (for EPL increased - zone 2); e (increased safety) will become eb (for EPL high - zone 1) and d (flameproof) will become db (for EPL high zone 1). This terminology is mandatory from E. Classification of Gases and Vapours Fig 4 Gases and Vapours Classification Level of protection M1 Ex ia Ma I M2 Ex d, Ex e Mb high Z0 ~ 1G Ex ia Z1 ~ 2G Ex d, Ex e, Ex px II Gb high Hydrogen is a very combustible gas but has a high ignition temp. The higher the gas combustibility the lower the Minimum Ignition Energy (MIE) and the lower the Minimum Ignition Current (MIC) for intrinsic safety circuits; and the smaller the Maximum Experimental Safe Gap (MESG) for Ex d machines. The higher the ignition temperature; the higher the allowable surface temperature; and the lower the permissible temperature class. Ga Z2 ~ 3G Ex na, Ex pz Gc increased Z20 ~ 1D Ex ia, Ex ta Z21 ~ 2D Ex tb, pd, md III Db high Da Z22 ~ 3D Ex tc, pd, md Dc increased Gas s: IIA - Methane, ammonia, ethyl alcohol, etc. IIB - Town gas, ethylene, hydrogen sulfide, etc. IIC - Hydrogen, acetylene, etc. Gas Groups IIA (US Group D) IIB (US Group C) IIC (US Group A) Ammonia, methane, ethane Ethyl alcohol, n-butane Benzene, n-hexane Town gas, acrylonitrile Ethylene, ethylene oxide Dust s:(ip55) IIIA - Combustible flyings IIIB - Non-conductivedust IIIC - Conductivedust(IP65) Ignition temperature Hydrogen > 450 C Ethyne (acetylene) > 300 C 450 C Hydrogen sulfide > 200 C 300 C Acetaldehyde Ethyl ether > 135 C 200 C Carbon disulfide Combustibilityincreases (maximumexperimental safe gap, minimum ignition energy becomes smaller) > 100 C 135 C > 85 C 100 C Permissible temperature class T1 Max. 450 C T2 Max. 300 C T3 Max. 200 C T4 Max. 135 C T5 Max. 100 C T6 Max. 85 C IIB gas and T3 (200 C) temperature class motors are by far the most common. Ingression protection to IP55 - dust protected and water jets is standard for all types of Ex motors which is equivalent to NEMA 3. IP56 - dust protected and heavy seas are also common. Dust tight IP65 is required for IIIC conductive dust and is possible for roller bearing HV motors. F. Protection Classes Flameproof enclosure (d) > (db) Pressurized apparatus (p) Fig 5 Classes of Protection Electrical machines use different protection methods than monitoring devices. However motors may have installed monitoring devices that require separate protection. Ex-protection Non Sparking na Electrical machines Increased safety (e) >(eb) Non sparking(na)>(ec) G. Non Sparking na in future ec Construction standards EN (EN EN 50021) Fig 6 Non Sparking Motor According to EN this is an explosion protection type in which the risk of ignition sources occurring during normal operation is minimised by utilising additional methods which can be: na non-sparking nc enclosed break nl limited energy nr restricted breathing Construction standards Regulation 94/9/EG ATEX, European Norms, IEC-Norms Basic principle Monitoring devices Intrinsic safety (ia, ib) Encapsulation (m) Oil immersion (o) Powder filling (q) Arcs and sparks are prevented during normal operation. Maximum surface temperature does not exceed the limits of temperature class. na will considered as ec in the future EN Zone 2 protection level Gc 2
3 na is the most appropriate method of protection for electrical machines. In future na (non sparking) will become ec for Protection Level (EPL) - increased - zone 2. That is Ex n motors can only be used in zone 2. A rotor design ignition risk assessment is required for Ex n motors >100kw and other than S1 or S2 operating modes. A stator winding ignition risk assessment is required for motors >1kV and other than S1 or S2 operating modes. (EN ) H. Increased Safety e in future eb Ex-protection Construction standards Increased safety e Fig 7 Increased Safety Motor Ex e motors are always de-rated to prevent hazardous temperatures, sparks and arcs during normal operation including start-up. This de-rating makes Ex e motors unpopular and not widely used. In addition Ex e motors typically can only handle a T3 temperature class. A stator winding ignition risk assessment is required for motors >1kV. (EN ) also anticondensation heaters must be fitted and additional protection during start-up maybe required (purging, measure gas concentration etc.) In future e (increased safety) will become eb for EPL high - zone 1. Ex-protection Flameproof d EN (EN EN 50019) is designed to prevent hazardous temperatures, sparks and arcs during normal operation. Ignition during breakdown is prevented by additional mechanical, electrical and thermic safety measures. I. Flameproof d in future db Construction standards EN (EN EN 50018) Basic principle Basic principle Fig 8 Flameproof Motor Zone 1 Zone 2 protection level Gb Gc All parts capable of igniting flammable gases are placed inside a flameproof enclosure. An explosion inside is not propagated outside the enclosure. The outer parts of the flameproof enclosure do not exceed permissible surface temperatures. Zone 1 Zone 2 protection level Gb Gc L w A flameproof motor must fulfil three prime requirements. Firstly the design must limit the outside surface temperature not to exceed the permitted temperature class. Secondly the explosion resistance must ensure that an explosion cannot spread to the external surroundings. Lastly the pressure resistance prevents any lasting damage or deformation to the protection of the motor following explosions within the enclosure. Ex d motors typically can handle up to a T4 temperature class and with special designs even T5 and T6 can be achieved. In future d (flameproof) will become db for EPL high zone 1. An Ex d motor may have withstood many internal explosions during its lifetime without affecting operation. Ex-protection Pressurised px py pz J. Pressurized Apparatus p EN (EN EN 50016) All parts capable of igniting flammable gases are placed inside an enclosure, pressurized by a protective gas (min. 0.5bar). The surrounding atmosphere cannot enter during operation. Fig 9 Pressurized Motor The px system where a pressurised enclosure which reduces the device protection level inside the pressurised enclosure housing from Gb (zone 1) to not at risk of explosions is the most common. The py system is not suitable for motors and the pz method can be used for zone 2 but is not popular. Leakage Loss Compensation is generally used for electrical machines rather than a continuous purge. K. Protection Comparison for Low Temps Construction standards Basic principle Zone 1 Zone 2 Fig 10 Low Temp Protection Comparison protection level Gb Gc + + o Low temperatures + + o o BVS 11 ATEX E 084 X The range of ambient temperatures is 40 C down to -20 C. This temperature range may be extended to 60 C down to -40 C with a special electrical or thermal design in which suitable terminal boxes, materials and components are used, or with the data for the electrical ratings. 3
4 Motors in all explosion protection types are available for low temperatures down to -40 C and below. However, often supplementary measures must be utilized for low temperature operation. It should also be noted that at low temperatures, the strength values of the motor materials decrease, especially plastics. L. Protection Comparison for Inverter Use o Inverter operation o Additional effort for testing and certification Fig 11 Inverter Use Protection Comparison Non-sparking machines must, as a minimum, first be type tested as a system with the actual inverter to be used or a comparable one. For Ex na it must be ensured that the permissible inner as well as outer temperature does not exceed the temperature class limit during operation, particularly at low speeds when the cooling fan may also be running slowly. Ex e motors must always be tested and certified as a complete system together with the actual inverter to be used (the only exception is PTB certification with significant power de-rating taking into account the thermal reserves and only for a square law load torque). Ex p motors can always be operated with an inverter. However if the purge system fails it must be ensured that the inner temperatures do not exceed the permissible temperature class limit. This also applies to mounted/installed components, for example heating systems. For all Ex e, Ex na and Ex p motors, the permissible inverter must be specified on the certificate, and the necessary tripping device on the manufacturer's declaration or on the Ex certificate. The inner components of Ex d motors e.g. heating system, do not generally require an Ex version. The installed temperature sensors are selected and located so that they trip earlier before the motor surface reaches the temperature limit. This is the reason that other inverters can be used with Ex d motors, assuming that the company operating the drive system complies with the regulations specified by the motor manufacturer. Thermal sole protection test means that the temperature sensor trip (PTC in winding) is tested because it is the sole (only) means of protection to x Thermalsole protection means that the PTC is the ONLY temperature protection device. * dependent on inverter type, counter torque characteristic and speed range prevent the outside surface exceeding the temperature class limit. Fig 12 Monitoring Investment Comparison M. Protection Comparison by Weight Fig 13 Weight Protection Comparison Ex na and Ex p motors have the lowest weight. Generally Ex e motors with the same power rating are at least one or two frame sizes larger (especially for 2 and 4-pole motors) and are therefore heavier. The higher the power rating, the more significant the differences in the corresponding shaft heights. Generally, an Ex d motor has the same active part as an Ex na or Ex p motor. However, the enclosure and the end shields are significantly bigger and therefore also heavier as they must withstand high explosion pressures. N. Protection Comparison for Large Power Fig 14 Large Power Protection Comparison o - + Monitoring investment o Ex na -Motor Ex e-motor Ex d-motor Ex p-motor DOL-operation: Motor protection switch and/or thermal monitoring DOL-operation: certified motor prot. Switch with Is/Ir-tE-timecurve and/or thermal monitoring DOL-operation: Motor protection switch and/or thermal monitoring DOL-operation: Motor protection switch and/or thermal monitoring plus Ex p -monitoring Inverter operation: thermal monitoring by LV-PTC s / HV PT100 thermal sole protection test required HV with anti-cond. heater KG/KW Inverter operation: thermal monitoring by LV-PTC s / HV PT100 certified thermal sole protection test required HV with anti-cond. heater Inverter operation: thermal monitoring by LV-PTC s / HV PT100 thermal sole protection test required L w Inverter operation: thermal monitoring by LV-PTC s / HV PT100 plus Ex p -monitoring thermal sole protection test required + + o - Weight Weight comparison for LV motors Ex na - 1PS1 Ex d - 1PS Shaft height KG Weight comparison for HV-motors Ex na - 1PS1 Ex d - 1PS5 Ex px - 1PS6 250kW 710kW 1250kW 4000kW o - o Large power rating o + + Output power limits 6kV/50Hz air cooled. kw pole 4-pole 6-pole 8-pole Ex na Ex e Ex d Ex px 4
5 HV Ex d motors, as a result of the necessary explosion protection, can only have higher power ratings in IC511/IC516 (tube cooling, tubes concentrically arranged around the stator core); a mounted cooler is not possible. 1000mm is the maximum shaft height that can still be tested in the worlds largest Ex d test laboratory. As a consequence, the maximum power for a 4-pole motor with 6kV is approx. 8 MW. 2 and 4 pole Ex e motors, with power ratings above approx. 2.5 MW are no longer practical because achieving a reasonable (long) safe locked rotor time (te) it is necessary to reduce the starting current, which leads to a low starting torque. When it comes to higher power ratings, there are no restrictions for Ex na and Ex p motors. O. Protection Comparison for Flexibility o Flexibilityforapplications o independent installation Process reliability DOL / Inverter operation Duty types Ambient temperatures Applications Fig 15 Flexibility Protection Comparison Ex d motors have the best flexibility, because in principle, they can be designed for normal line operation, intermittent duty, inverter operation as well as heavy-duty starting. For an Ex na motor, intermittent duty is no longer considered normal operation; as a consequence, starting must also be taken into account in the explosion protection assessment, which makes it similar to an Ex e motor. Intermittent duty is only possible for an Ex p motor if it is continually purged (also at standstill). An essential advantage of Ex d high-voltage motors, when compared to Ex p and Ex e motors (which must be purged before starting) is that following a power failure or after the motor has been switched off, it can be immediately restarted % 98.0% 96.0% 94.0% 92.0% 90.0% 88.0% 86.0% 84.0% 82.0% 80.0% 78.0% P. Protection Comparison by Ops Costs Fig 16 Ops Costs Protection Comparison As a result of the lower thermal utilization, an Ex e motor has lower copper losses, and therefore in comparison, a higher efficiency. For Ex p motors, the costs associated with the purging air supply (purchase, installation and operating costs) is an additional cost, which depending on the motor size and bearing design, can amount to several thousand Euros per year. Q. Protection Comparison Summary Table Fig 17 Comparison Summary Table Evaluation Key ++ Very well suited + Well suited 0 Suited - Less suited -- Not suited R. Cost Comparison Operational costs Comparison of efficiency for 3kW 55kW 250kW 710kW Ex na / Ex d / Ex p 97.5% 97.0% 96.5% 96.0% 95.5% 95.0% 94.5% 94.0% Comparison of efficiency for Ex na / Exd / Ex p 250kW 710kW 1250kW 4000kW Operation in Zone 1 Gas/Vapors Gas ((IIA, IIB, IIC) o Temperature class (T3-T6) o o o - + Dust ignition proof o - + o o o - Ability for corrosive cooling medium o o Low temperatures + + o o Overload operation o - + Heavy duty starting o o Inverter operation o o - + Monitoring investment o o - Weight o - o Large power rating o + + o Flexibility for applications o Operational costs o o o Maintenance costs o o o - 150% 140% 130% Comparison based on experience from Service and Engineering information 6kV / 50Hz 1500rpm -AT -20/+40 C, air cooled Ex na (1PS1) Ex e (1PS2)* Ex d (1PS4) Ex px (1PS6) 120% 110% 100% 90% 300kW 800kW 1600kW 2500kW 5000kW Fig 18 Cost Comparison 5
6 Ex na motors are always the most cost effective but are only suitable for zone 2 operation. Ex e motors are always expensive because they are de-rated. Ex p are the most expensive when small but become cheaper the bigger the motor size because the purge system becomes less as a proportion of the total motor cost. Ex d becomes the most expensive as the explosion proof enclosure becomes a larger proportion of the total motor cost. S. Info required for Ideal Motor Selection Certification Norm Country e.g.: Gost / Russia Fig 19 Motor Selection Info Required It is easier to optimise the proposed motor/drive solution when more information can be specified at the quotation stage. III. Driven e.g..: Pump Mg ~ n² Operation mode e.g. DOL or Inverter overload duty cycle CONCLUSION Zone, Gas Temperature -class e.g.: IIC T4 Cooling temperature altitude e.g. -45/+40 C 1000m Starting conditions e.g. 3/2 cold/hot 80% RV Required cooling type e.g. IC411, IC511, IC81W etc. Flameproof Ex d motors provide the best flexibility across LV and HV ranges; they can also be used with any manufacturer s inverter without special testing. However, Ex d motors become increasingly expensive & heavy with a maximum limit of circa 8MW, so Ex p is better for larger sizes. [3] EN :2011 Explosive atmospheres. Explosion prevention and protection. Basic concepts and methodology [4] Directive 2014/34/EU for potentially explosive atmospheres (ATEX) [5] EN :2014. Explosive atmospheres. protection by flameproof enclosures "d". [6] EN :2014. Explosive atmospheres. protection by pressurized enclosure "p". [7] EN :2015. Explosive atmospheres. protection by increased safety "e" [8] EN :2010. Explosive atmospheres. protection by type of protection "n". [9] EN :2014. Explosive atmospheres. Electrical installations design, selection and erection [10] Barata et al. Flameproof Motors operating in the Artic Circle without the need for preheating PCIC Europe Conference Record, BER [11] Munro et al. Are the IEC requirements for overpressure testing of Ex d equipment appropriate? PCIC Europe Conference Record, BER [12] Mistry et al. What is new in next edition of IEC standard of Ex e motors? PCIC Europe Conference Record, LO [13] Neleman et al. Motor Controls for Ex Motors in Hazardous Areas: An Application Guide PCIC Europe Conference Record, BA VI. VITA Dipl.-Ing Hugo Stadler Hugo Stadler graduated from the Fachhochschule Regensburg with an Electrical Engineer Dipl.-Ing. (FH). After six years in the development department for variable speed drives at SIEMENS (Loher) he moved into the sales department and served key customers in the Oil & Gas and Chemical industry. Hugo s competence is electrical motors, frequency inverters and ex-protection with over 40 years service and experience with the SIEMENS (Loher) company. Today Hugo Stadler is responsible for the SIEMENS sales of LV drive systems to the Oil & Gas industry. IV. ACKNOWLEDGEMENTS Eur Ing Steve Jackson MA BSc CEng The authors acknowledge the contributions made to this paper over the years by such hazardous area motor luminaries as Helmut Hasch, Karl Hofbauer, Klaus Neupert, Thomas Mutzl, Thomas Fuchs and Ulrich Schanzer. V. REFERENCES [1] Siemens Loher, Ruhstorf Explosion proof drives Planning and Engineering Course: DR-EX-PL [2] Siemens ABC of Motors Manual October 2009 Steve Jackson graduated from the University of Bath Chemical Engineering School with a BSc (Hons) in During 2016 he enhanced his academic qualifications with a Masters in Sales Management from the University of Portsmouth. In 1987 Steve became a Chartered Engineer and in 1994 a European Engineer. He has been a Member of the Institute of Measurement and Control for nearly 30 years. Over the course of his career Steve has worked for Fisher Controls, Elsag Bailey, ABB, Endress+Hauser and for the last 12 years SIEMENS in the fields of automation, instrumentation, process analytics and electrical engineering. Steve is also a committee member for the Energy Industries Council (EIC). 6
7 VII. APPENDIX Enlarged Figures Directive 94/9/EC EN category Types of protection Examples EPL Protection Level Level of protection I II M1 Ex ia Ma I M2 Ex d, Ex e Mb high Z0 ~ 1G Ex ia Ga Z1 ~ 2G Ex d, Ex e, Ex px II Gb high Z2 ~ 3G Ex na, Ex pz Gc increased Z20 ~ 1D Ex ia, Ex ta Da Z21 ~ 2D Ex tb, pd, md III Db high Z22 ~ 3D Ex tc, pd, md Dc increased Gas s: IIA - Methane, ammonia, ethylalcohol, etc. IIB - Town gas, ethylene, hydrogen sulfide, etc. IIC - Hydrogen, acetylene, etc. Dust s:(ip55) IIIA - Combustible flyings IIIB - Non-conductivedust IIIC - Conductivedust (IP65) Fig 3 Electrical Classification o Inverter operation o Additional effort for testing and certification Thermalsole protection means that the PTC is the ONLY temperature protection device. x * dependent on inverter type, counter torque characteristic and speed range Fig 11 Inverter Use Protection Comparison 7
8 + + o - Weight KG/KW Weight comparison for LV motors Shaft height Ex na - 1PS1 Ex d - 1PS5 KG Fig 13 Weight Protection Comparison Fig 17 Comparison Summary Table 0 Weight comparison for HV-motors Ex na - 1PS1 Ex d - 1PS5 Ex px - 1PS6 250kW 710kW 1250kW 4000kW Operation in Zone 1 Gas/Vapors Gas ((IIA, IIB, IIC) o Temperature class (T3-T6) o o o - + Dust ignition proof o - + o o o - Ability for corrosive cooling medium o o Low temperatures + + o o Overload operation o - + Heavy duty starting o o Inverter operation o o - + Monitoring investment o o - Weight o - o Large power rating o + + o Flexibility for applications o Operational costs o o o Maintenance costs o o o - Comparison based on experience from Service and Engineering information Fig 20 Gas Hazard Marking in future the EPL will be added to the end eg Ex d IIC T4 Gb 8
Intrinsic Safety & Hazardous Areas
Intrinsic Safety & Hazardous Areas by Steve Mackay 1 EIT Micro-Course Series Every two weeks we present a 35 to 45 minute interactive course Practical, useful with Q & A throughout PID loop Tuning / Arc
More informationATEX SOLUTONS FROM AERZEN
ATEX SOLUTONS FROM AERZEN Rotary Lobe Blowers, Rotary Lobe Compressors and Screw Compressors in accordance with Directive 94/9/EC AERZEN. YOUR PARTNER FOR EXPLOSION PROTECTION COMPLIANCE. Directive 94/9/EC
More informationHazardous-Area Classification Methods and Equipment
Hazardous-Area Classification Methods and Equipment The term hazardous location once meant a place within a petrochemical or some other equally volatile plant. Today, hazardous manufacturing processes
More informationMarine motors. 10/2 Orientation 10/2 Overview 10/3 Benefits 10/3 Application 10/3 Technical specifications 10/5 More information
/2 Orientation /2 Overview /3 Benefits /3 Application /3 Technical specifications /5 More information /6 Type approved standard motors up to frame size 315 L /6 Overview /7 Type approved explosion-proof
More informationTechnical News. Introductory guide to hazardous areas in Australia and New Zealand
Issue #69 - Autumn 2014 (updated May 2015) Technical News Industrial Electrical and Automation Products, Systems and Solutions Introductory guide to hazardous areas in Australia and New Zealand Written
More informationA Guide to Selecting Motors for Hazardous Locations
A Guide to Selecting Motors for Hazardous Locations Grain Handling and Processing Facilities Since 1980, more than 500 dust explosions have occurred in industrial facilities throughout the U.S., causing
More informationThe Responsible Person AKA Technical Person with Executive Functions
Peter Roberts Explosive Atmospheres Essential Guidance Series EGS 0035 Edition 1 Supplement for the CompEx Ex 14 training course. The Responsible Person AKA Technical Person with Executive Functions ExVeritas
More informationXMP i. Precision Pressure Transmitter for the Process Industry with HART -Communication. Stainless Steel Sensor
Precision Pressure Transmitter for the Process Industry with HART -Communication Stainless Steel Sensor accuracy according to IEC 0770: 0. % FSO Nominal pressure from 0... 00 mbar up to 0... 00 bar Output
More informationXMP i. Precision Pressure Transmitter for the Process Industry with HART -Communication. Stainless Steel Sensor
Precision Pressure Transmitter for the Process Industry with HART -Communication Stainless Steel Sensor accuracy according to IEC 0770: 0. % FSO Nominal pressure from 0... 400 mbar up to 0... 00 bar Output
More informationLoad cells Type: RTB Safety Instructions
Load cells Type: RTB Safety Instructions BVH2539 GB PASS - A service you can count on. Fast, comprehensive and anywhere in the world. Quality and reliability are the cornerstones of our company s philosophy.
More informationAIR TREATMENT IN EXPLOSIVE ENVIRONMENTS
AIR COMFORT AIR TREATMENT AIR TREATMENT IN EXPLOSIVE ENVIRONMENTS ATEX Save energy, economy and environment with Fläkt Woods. Energy optimization is an important aspect of ventilation solutions and an
More informationsira IECEx Certificate of Conformity
IECEx Certificate of Conformity INTERNATIONAL ELECTROTECHNICAL COMMISSION IEC Certification Scheme for Explosive Atmospheres for rules and details of the IECEx Scheme visit www.iecex.com Certificate No.:
More informationMagnetic float switch For vertical installation Model FLS for nuclear power plants
Level measurement Magnetic float switch For vertical installation Model FLS for nuclear power plants KSR data sheet FLS for NPP for further approvals see page 3 Applications Level measurement for almost
More informationLSA Rating Table Low Voltage Alternators - 4 pole
LSA Rating Table Low Voltage Alternators - 10 to 3300 kva - 50 Hz / 12.5 to 3900 kva - 60 Hz General features and ratings Summary 1 - RATING DEFINITION... 3 2 - INSULATION CLASS AND TEMPERATURE RISE...
More informationNEMA Enclosure Types
The purpose of this document is to provide general information on the definitions of NEMA Enclosure Types to architects, engineers, installers, inspectors and other interested parties. [For more detailed
More informationEx CLASSIFIED LUMINAIRES
Ex CLASSIFIED LUMINAIRES DECEMBER 2016 ZONE 1/ZONE 2 BEKA PROTECTALINE BEKA PROTECTALINE - Emergency ZONE 2 OMNIstar LEDbay-midi BEKA LEDnova BEKA LEDnova - Emergency BEKA SUPRANOVA/PC BEKA SUPRANOVA/AC
More informationFloor stand grinder. The inspection was carried out in accordance with the checklist for Tooling Machines, dated
CHECKLIST for Tooling Machines Floor stand grinder Issue Date: 2009-03-30, Rev. 1 I. Nature of the inspection First inspection Follow-up inspection Job No. II. Details of the machine: In-house system designation
More informationELECTRONIC EARTHING EQUIPMENT SERIES GRD 4200
ELECTRONIC EARTHING EQUIPMENT SERIES GRD 4200 The GRD 4200 is an electronic earthing equipment for tankers during loading and unloading operations of flammable liquids in places with danger of explosion.
More informationHAZARDOUS AREAS FOR WATER & WASTEWATER FACILITIES
HAZARDOUS AREAS FOR WATER & WASTEWATER FACILITIES Paper Presented by : Neil Dennis Author: Neil Dennis, Associate Director, Maunsell Australia 68 th Annual Water Industry Engineers and Operators Conference
More informationKDS. All Metal Variable Area Flowmeter. for liquids and gases. Measuring range: l/h l/h water 5-50 Nl/h...
All Metal Variable Area Flowmeter for liquids and gases measuring monitoring analysing : 0.1-1 l/h... 20-200 l/h water 5 - Nl/h... 600-6000 Nl/h Accuracy: ±3 % of full p max : 420 bar; t max : 130 C OConnection:
More informationSensor unit MC2 for toxic gases and oxygen with analog output
Page 1 July 2016-2 Exchangeable sensor unit including digital value processing, temperature compensation and self control for the continuous monitoring of the ambient air. The sensor unit MC2 houses a
More informationILMK 382. Stainless Steel Probe. Ceramic Sensor. accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % FSO.
ILMK 8 Stainless Steel Probe Ceramic Sensor accuracy according to IEC 60770: standard: 0.5 % FSO option: 0.5 % FSO Nominal pressure from 0... 40 cmh O up to 0... 00 mh O Output signals -wire: 4... 0 ma
More informationCOMTEC O 2. InSitu analyzer systems. / CO e DEVELOPED AND MANUFACTURED IN GERMANY
COMTEC InSitu analyzer systems DEVELOPED AND MANUFACTURED IN GERMANY SENSOR TECHNOLOGY COMTEC co e THE INDICATOR OF SAFE COMBUSTION The family of ENSitu sensors are engineered for maximum durability. ENOTEC
More informationEx Competent Person Training and Certification Program Hazardous Areas Classification
Ex Competent Person Training and Certification Program Hazardous Areas Classification - training & certification program to enhance and upgrade the competencies of Engineering Managers, Engineers & Technician
More informationFGA 300 Panametrics Flue Gas Oxygen Analyzer. GE Sensing. Features. Applications
Applications An ex situ zirconium oxide analyzer for excess oxygen measurement in dirty, rugged combustion applications such as: Boilers: all fuels and all types, including marine, recover, and utility
More informationExplosion Hazard Evaluation and Determination of the Explosion Parameters for Selected Hydrocarbons C6 C8
Explosion Hazard Evaluation and Determination of the Explosion Parameters... 399 Central European Journal of Energetic Materials, 2012, 9(4), 399-409 ISSN 1733-7178 Explosion Hazard Evaluation and Determination
More informationJournal of Research and Development Vol. 2, No.2, 2014 HAZARDOUS LOCATIONS
HAZARDOUS LOCATIONS Ghadir Hendu Kalaee 1, Nakisa Moghaddas 2 1-Bachelor in Electrical Engineering Major of Power, Hadaf University of Sari 2-Bachelor in Electrical Engineering Major of Power, Hadaf University
More informationLSA 42.3 Low Voltage Alternators - 4 pole
LSA 42.3 Low Voltage Alternators - 4 pole 2 to 60 kva - 0 Hz / 31. to 7 kva - 60 Hz Electrical and mechanical data Specially adapted to applications The LSA 42.3 alternator is designed to be suitable for
More informationBiogas analysers. Product overview. MRU over 30 years of innovative gas analysis! Biogas, landfill gas, biomethane, coal mine gas, CHP exhaust gas
MRU over 30 years of innovative gas analysis! Biogas analysers Biogas, landfill gas, biomethane, coal mine gas, CHP exhaust gas Product overview MRU Biogas analysers Whether biogas, landfill and coal mine
More informationATOMSCOPE HF200A. Operating Instruction Manual. Ver. 3.1
ATOMSCOPE HF00A Operating Instruction Manual Ver.. This special purpose portable equipment is for diagnostic radiography only. It is not designed, nor does it meet, the standards for any other use. CONTENTS
More informationHazardous area classifications and protection methods
White Paper Hazardous area classifications and protection methods Keith Riley Executive Summary A paper which describes what the hazardous area classifications are and what specific protection methods
More informationMiniWarn. Fits Your Application. Intelligent. Rugged. Flexible. Ergonomic. Easy to use. Multi-Gas Instrument
Fits Your Application Intelligent Rugged Flexible Ergonomic Easy to use Multi-Gas Instrument Draeger: First in detection Since 1937, when we introduced our first detector tube, Dräger has been the world
More informationN-pump, Standard Motor
N-pump, Standard Motor N-pump, Standard Motor Product description Usage Installation type P, S, T, Z Installation type L A submersible pump for efficient pumping of clean water, surface water, and wastewater
More informationCHOOSING THE RIGHT RFID TECH FOR MANUFACTURING
CHOOSING THE RIGHT RFID TECH FOR MANUFACTURING 1 Choosing the Right RFID Technology for Manufacturing and Harsh Environments Richard Aufreiter, HID Global raufreiter@hidglobal.com Visit us at Booth #722
More informationThe complete guide to transformers and packaged substations
LAND LOGICAL POWER The complete guide to transformers and packaged substations Contents Land Logical Power transformers An introduction to the complete range of Land Logical Power transformers and package
More informationCertificate of Compliance
Certificate of Compliance Certificate: 1602514 (LR 39156) Master Contract: 212516 Issued to: Rosemount Analytical Inc. Process Analytic Division Solon Research & Development Ctr 6565-P Davis Industrial
More informationGas-insulated medium-voltage switchgear. for wind parks. Answers for energy.
Gas-insulated medium-voltage switchgear for wind parks Answers for energy. Switchgear for wind turbines: 8DH10 up to 24 kv, up to 20 ka, up to 1,250 A up to 17.5 kv, up to 25 ka, up to 1,250 A Best performance
More informationPM Generators and the Magnet price development. Drivetrain concepts for wind turbines Bremen, 22.Oct Christian Contini, Dipl.-Ing.
PM Generators and the Magnet price development Drivetrain concepts for wind turbines Bremen, 22.Oct.2012 Christian Contini, Dipl.-Ing. (FH) PM Generator Overview Magnet Price Development Alternatives to
More information8.27/210 * 7.28/ / / /108. n x d. b f ML00343b. Dimensions are in inches/millimeters *8.86/225 for Pg 13.5 with adapter 2.
SITRANS P DSIII Pressure Transmitters All versions of the SITRANS P transmitter, DS III series, are smart two-wire transmitters The output signal is a load-independent direct current of 4 to 20 ma proportional
More informationOPW Fluid Transfer Group Europe BV Function Key Rack Monitor 8800E/8801E
Manual OPW Fluid Transfer Group Europe BV Function Key Rack Monitor 8800E/8801E Disclaimer With this document an user manual is presented of the OPW Function Key and is designed to use in conjunction with
More informationMagnetically Coupled Submerged Cryogenic Pumps and Expanders for Ammonia Applications
Paper 4d Magnetically Coupled Submerged Cryogenic Pumps and Expanders for Ammonia Applications Liquefied Ammonia, or Liquid NH3, is (like LNG or liquefied natural gas) a cryogenic fluid and production
More informationLinde Quality you can rely on. Linde fork lift trucks for explosion-hazardous areas
Linde Quality you can rely on Linde fork lift trucks for explosion-hazardous areas SAFETY For many years now, Linde has been one of the world s leading experts in the manufacture of vehicles for explosion-hazardous
More informationINNOVATIVE LIFE-CYCLE CONCEPTS FOR MEDIUM-VOLTAGE SWITCHGEAR ON BROWN COAL SURFACE MINING DEVICES
INNOVATIVE LIFE-CYCLE CONCEPTS FOR MEDIUM-VOLTAGE SWITCHGEAR ON BROWN COAL SURFACE MINING DEVICES Dr. S. Ruhland, Dr. U. Riedl ALSTOM Sachsenwerk GmbH, Germany The requirements for medium voltage switchgear
More informationCertificate of Compliance
Certificate of Compliance Certificate: 2531848 (030391_0_000) Issued to: EGS Electrical Group LLC 9377 W Higgins Rd Rosemont, Illinois 60018 USA Attention: Mickey Scherer The products listed below are
More informationTEST REPORT IEC Information technology equipment Safety Part 22: Equipment to be installed outdoors
Report Reference No.... : TEST REORT IEC 60 950-22 Information technology equipment Safety art 22: Equipment to be installed outdoors Date of issue... : 30 October 2014 Total number of pages... 19 S143891.01
More informationCLM-36 MISURATORI CAPACITIVI IN CONTINUO CONTROLLI DI LIVELLO. Capacitive level meters CLM 36. Features of variants. Accessories
CLM-36 MISURATORI CAPACITIVI IN CONTINUO CONTROLLI DI LIVELLO Capacitive level meters CLM 36 Capacitive level meters Riels CLM are designed for continuous level measurement of liquids, powders and bulk-solid
More informationAS950 ALL-WEATHER REFRIGERATED SAMPLER
AS950 ALL-WEATHER REFRIGERATED SAMPLER Applications Wastewater Collection systems Industrial pretreatment Environmental monitoring Stormwater Sampling has never been this easy. Hach's AS950 sampler controller
More informationFlygt 3057, 50Hz. Technical Specification
Flygt 3057, 50Hz Technical Specification Table of Contents Table of Contents C-pump...2 Product description...2 Motor rating and performance curves...4 D-pump...6 Product description...6 Motor rating and
More informationNEW MOBILITY IN MIG/MAG PULSED ARC TECHNOLOGY MEGAPULS 250
NEW MOBILITY IN MIG/MAG PULSED ARC TECHNOLOGY MEGAPULS 250 2 A powerful package portable and multi-functional Perfect for handcraft, medium sized companies and industrial use MEGAPULS 250 is a portable
More informationFunctional safety in the process industry
Functional safety in the process industry You want that feeling of security. You require uninterrupted production. We bring you safety and reliability. Our expertise Your advantage Page 3 SIL Safety Integrity
More informationHAZADOUS LOCATION LED FLOOD LIGHT
HAZADOUS LOCATION LED FLOOD LIGHT LED Explosion-Proof Floodlight FL- 80w, 100w, 150 w Class 1 Division 1 Groups C&D 130 Lumens Per Watt Harsh & Hazardous Duty L90 Value 100,000+ Hours Crisp White 5000K
More informationx act i Precision Pressure Transmitter for Food Industry, Pharmacy and Biotechnology Stainless Steel Sensor accuracy according to IEC 60770: 0.
Precision Pressure Transmitter for Food ndustry, Pharmacy and Biotechnology Stainless Steel Sensor accuracy according to EC 60770: 0. % FSO Nominal pressure from 0... 400 mbar up to 0... 40 bar Output
More informationP r o d u C T I N f o r m at I o n. The atmosphere must be just right
P r o d u C T I N f o r m at I o n INESIC700 TBS The atmosphere must be just right INESIC700 TBS The atmosphere must be just right onitoring gas levels in underground coal mines is a challenging task and
More informationEC medium pressure axial fans.
EC medium pressure axial fans. The efficient system solution. The engineer s choice GreenTech EC technology in a new dimension. Thanks to these new new axial axial fans, fans, our our highly highly efficient
More informationGlass Reinforced Polyester Enclosures BPG. Glass Reinforced Polyester Enclosures
BPG 42 The BPG range comprises 16 sizes of enclosure manufactured in glass reinforced polyester (GRP). This material is highly resistant to contamination from oils, fats, aliphatic and aromatic carbohydrates,
More information3SP_CO_1000 Package
15x15 CO Sensor 1000 ppm Package 110-102 BENEFITS Small Size with Low Profile (20x20x3.8 mm) Long Life (10 years expected life) Fast Response (< 15 seconds) Robust (passes 5000 ppm overload) Low Power
More informationALUBOX Series Junction boxes in IP66 aluminium alloy
UBOX Series Junction boxes in IP aluminium alloy > ENCLOSURES IP UBOX Series UBOX-EX Series Dimensions () Screw for attaching cover Earthing screws Weight (Kg) 00 x 00 x 59 n 2 M5x0 n M4x 0,290 /32 53.00
More informationCOMBIMASS Thermal Gas Flow
COMBIMASS Thermal Gas Flow The COMBIMASS series enables gas flow measurement for various applications in all industry sectors. COMBIMASS works according to the principle of thermal dispersion and determines
More informationB. Provide liquid-filled secondary substation transformers as indicated on drawings.
SECTION 26 12 13 PART 1 - GENERAL 1.01 WORK INCLUDED A. Comply with the provisions of Sections 26 05 00. B. Provide liquid-filled secondary substation transformers as indicated on drawings. 1.02 RELATED
More informationFlygt 3171, 50Hz. Technical Specification
Flygt 3171, 50Hz Technical Specification Table of Contents Table of Contents F-pump, Standard Motor...2 Product description...2 Motor rating and performance curves...5 F-pump, Premium Efficiency Motor
More informationSafety Test Report. Reliability Laboratory of Huawei Technologies Co., Ltd.
Safety Test Report roduct Name: roduct Model: roduct Type: Report Number: ower System T48200A T48200A-H15A3,T48200A-H15A5, T48200A-D15A1,T48200E-H09A1, T48200E-D09A1 SYBH (A)00679762-2 Reliability Laboratory
More informationCombined Cycle Power Plants. Combined Cycle Power Plant Overview (Single- and Multi-Shaft) Training Module. ALSTOM (Switzerland) Ltd )*+,
Power Plant Overview Training Module ALSTOM (Switzerland) Ltd )*+, We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without
More informationProtection classification IP 23
TIG 180 AC/DC puls 290-020200-00000 TEAMWELDER TIG 180 AC/DC the specialist for aluminium welding TIG and MMA welding Ideal for aluminium: Optimum ignition and stabilisation of the alternating current
More informationBig bag filling station
Company House., street City, State, ZIP code Country Point of contact Given name, family name Department Telephone Fax E-mail Request no/reference Ms. Mr. Title Product information Designation Granular
More informationPlastic tube flowmeters Series PT/PS Variable area flowmeter for liquids and gases
Plastic tube flowmeters Series PT/PS Variable area flowmeter for liquids and gases Low cost, excellent readability and light weight Simple installation (flanged, threaded or socket ends for solvent or
More informationTM Series Cooling Tower Specification
1.0 Cooling Tower TM Series Cooling Tower Specification 1.1 General: Furnish and install factory-assembled, induced draft, counterflow cooling tower(s) with vertical air discharge conforming in all aspects
More informationThermocouple for Flue Gas Temperature Measurements,
Electrical Temperature Measurement Thermocouples for Flue Gas Temperature Measurements Model TC81 with Thermowell Model TW81 WIKA Data Sheet TE 65.81 Applications Blast furnaces, air heaters Red-heat and
More informationFor informational use only -- no certified translation (1) EC design inspection certificate (2) Devices and protective systems for intended use within potentially explosive areas Directive 94/9/EC (3)
More informationFlygt 3057, 50Hz. Technical Specification
Flygt 3057, 50Hz Technical Specification Table of Contents Table of Contents C-pump...2 Product description...2 Motor rating and performance curves...4 D-pump...6 Product description...6 Motor rating
More informationARC WHITE PAPER DART Ushers in the Next Generation of Intrinsic Safety
ARC WHITE PAPER By ARC Advisory Group FEBRUARY 2011 DART Ushers in the Next Generation of Intrinsic Safety Executive Overview... 3 Business Goals Drive Improvements in Intrinsically Safe Fieldbus... 3
More informationMAX300-RTG PRODUCT NOTE. Real-Time Gas Analysis Process Automation and Control Product Quality Analysis. Industrial Process Mass Spectrometer
MAX300-RTG Industrial Process Mass Spectrometer PRODUCT NOTE Real-Time Gas Analysis Process Automation and Control Product Quality Analysis www.extrel.com Introducing the MAX300-RTG Optimize Your Manufacturing
More informationGuide book AS 300 G. Waste water filtration unit. Im Geer 20, D Isselburg. Description / Type-No.: AS 300 G Type 523
Waste water filtration unit Manufacturer: deconta GmbH Im Geer 20, D - 46419 Isselburg Description / Type-No.: Type 523 Table of contents on Page 1 Introduction 3 2 Basic safety advice 4 2.1 Intended use
More informationJet Tunnel Fans.
Jet Tunnel Fans www.systemair.de by Division AJ (T) Tunnel Jet Fans Standard features: Thrust efficiency in excess of 40 N/kW Adjustable aluminium impellers for maximum efficiency Terminal box on the casing
More informationGas Turbine Inlet Air Cooling System
Gas Turbine Inlet Air Cooling System Presented by Bob Omidvar Heavy Duty GT - Effects of Ambient Temp 110% 105% 100% 95% 90% 85% 80% 75% 0 5 10 15 20 25 30 35 40 45 GT Inlet Temp (deg C) Heat rate kj/kwh
More informationShur-Shot X-Proof Hydrogen Fluoride Alarm Operations Manual
Shur-Shot X-Proof Hydrogen Fluoride Alarm Operations Manual P/N 1000006053 Rev E $7%$QDO\WLFV// //& 733 Dairy Rd. Parkton, Md. 21120 www.atbanalytics.com (410) 733-6365 Table of Contents Chapter 1: Getting
More informationLSA 47.2 Low Voltage Alternators - 4 pole
LSA 47.2 36 to 6 kva - Hz / 46 to 7 kva - 6 Hz Electrical and mechanical data LSA 47.2-36 to 6 kva - Hz / 46 to 7 kva - 6 Hz Specially adapted to applications The LSA 47.2 alternator is designed to be
More information3820 en / c
38 en -.6 / c Alternators LSA 44.2-4 Pole Electrical and mechanical data SPECIALLY ADAPTED FOR APPLICATIONS The LSA 44.2 alternator is designed to be suitable for typical generator applications, such as:
More informationFlanged Water Meters (non-continuous flow)
Flanged Water Meters (non-continuous flow) Features MW-F Suitable for use with domestic water Pulsed output Low head loss Specification Product Codes Meter: Cold water: Fluid temp. range: Cold 0 to 30
More informationMINOR. Electrical submersible drainage pump. Tel Fax Hz. No: PD603-EN. Revision
o: PD63-E Revision 27.12 z MIOR 793 mm Ø 286 mm Ø1 mm Weight: 2 kg P (kw) 6 (m) 4 3 2 1 4 3 3 2 2 1 1 1 1 2 2 3 3 ISO 996/A : ormal pressure : igh pressure Insulation class (IEC 8) Rated output Max. power
More informationProduct Data Sheet RESOPAL EXCELLENT
Product Data Sheet RESOPAL EXCELLENT This information describes the composition of RESOPAL Excellent and gives advice for their handling, processing, use, and disposal. Such Elements are used as kitchen
More informationTechnical Note TN-114 rev 16 wy/wh.11-04
Sensor Specifications And Cross-Sensitivities Technical Note TN-114 Note: All performance specifications are subject to change without notice and are based upon conditions at 68 o F (20 o C), 50% relative
More informationSCOPE OF ACCREDITATION TO ISO/IEC 17025:2005
SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 QUALITECH 30 Hasivim Street Petah-Tikva 4959338, ISRAEL Teodor Weisz Phone: 972 3 926 6218 Email: Tedy.Weisz@ecitele.com Eli Avital Phone: 972 3 926 6170 MECHANICAL
More informationWELDING Topic and Contents Hours Marks
Topic and Contents Hours Marks 3.1 Introduction 04 Marks Classification and selection of welding process. Working principle of Gas welding and types of flames. 3.2 Arc welding process 08 Marks Metal arc,
More informationSilicone Dielectric Fluids Fredi Jakob, Karl Jakob, Nicholas Perjanik Analytical ChemTech International, Inc.
Silicone Dielectric Fluids Fredi Jakob, Karl Jakob, Nicholas Perjanik Analytical ChemTech International, Inc. I. Introduction Mineral oil based dielectric fluids have been used more extensively than other
More informationPioneering ALD experience since The ALD Powerhouse PRODUCT CATALOGUE FOR SUNALE P-SERIES ALD SYSTEMS
Pioneering ALD experience since 1974 The ALD Powerhouse PRODUCT CATALOGUE FOR SUNALE P-SERIES ALD SYSTEMS SUNALE P-SERIES ALD SYSTEMS PRODUCT CATALOGUE Description SUNALE P-series ALD system SUNALE P-series
More informationGantiel Vensott E.P.S. Pty. Ltd. Vendel N_B. [ White_Black Acetal ] Material Safety Data Sheet
Product Name: White_Black Acetal Company Name: antiel ensott E.P.S. Pty. Ltd. Address: 15, Bearing Road, Seven Hills, NSW 2047 Telephone No: +61 2 8678 9491 Fax No: +61 0 8678 9492 Email: sales@gantiel.com
More information// XPLORER-NS. Full range Total Nitrogen, Total Sulfur instrument for the modern Laboratory.
Configuration: XPLORER with ARCHIE and GLS* // XPLORER-NS Full range Total Nitrogen, Total Sulfur instrument for the modern Laboratory. TE Instruments has developed the XPLORER-NS, a Total Nitrogen and
More informationFire Risk Assessment for Ammonia Onshore Export Terminal
4B-2 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea Fire Risk Assessment for Ammonia Onshore Export Terminal Yu. N. Shebeko, I. A. Bolodian, V. P. Molchanov,
More informationMP-400. The most thermally efficient, robust and reliable medical incinerators on the market. Simply Built Better!
The most thermally efficient, robust and reliable medical incinerators on the market Simply Built Better! Specifically designed for medical waste. MP-400 The MP medical hot hearth Incinerators designed
More informationFLOWSERVE CORPORATION Guardian Pumps. Centrifugal ANSI Pumps Product Training Program
FLOWSERVE CORPORATION Guardian Pumps Centrifugal ANSI Pumps Product Training Program April 2017 Sealless Pumps Definition A pump that is designed with no externally actuated shaft penetrating the pump
More informationRESOPAL -Decorative High Pressure Laminates HPL according to EN 438
Product Data Sheet RESOPAL -Decorative High Pressure Laminates HPL according to EN 438 This information describes the composition of RESOPAL -HPL and gives advice for their handling, processing, use, and
More informationx act i Precision Pressure Transmitter for Food Industry, Pharmacy and Biotechnology Stainless Steel Sensor accuracy according to IEC 60770: 0.
Precision Pressure Transmitter for Food ndustry, Pharmacy and Biotechnology Stainless Steel Sensor accuracy according to EC 60770: 0. % FSO Nominal pressure from 0... 400 mbar up to 0... 40 bar Output
More informationCoal Mine Gas. Utilization Principles
Coal Mine Gas Utilization Principles ` Global Methane Emission Coal provides 25 percent of global primary energy needs and generates 40 percent of the world s electricity, according to the World Coal Institute.
More informationEnergy & Data Transmission Systems for Underground Applications
Energy & Data Transmission Systems for Underground Applications Systems for Underground Applications Conductix-Wampfler energy & data transmission systems keep tunnels moving forward. Whether it s for
More informationIt s All a Matter of TechNiQ. NiQ: Our latest generation of energy-saving motors.
It s All a Matter of TechNiQ. NiQ: Our latest generation of energy-saving motors. About ebm-papst. As a leader in technologies for ventilation and drive engineering, ebm-papst is in demand as an engineering
More informationTechnical Leaflet. Product Data Sheet for HPL Composite Panels
Technical Leaflet Product Data Sheet for HPL Composite Panels 2 Product Data Sheet for HPL Composite Panels Preface This information describes the composition of HPL Composite Panels and gives advice for
More informationDESIGN. DEVELOP. DELIVER. CAPABILITY STATEMENT
DESIGN. DEVELOP. DELIVER. CAPABILITY STATEMENT Mining & Industrial Switchgear Kiosk Substations Water Infrastructure Projects Project Management Slurry Management Systems Pumping Solutions Fire Protection
More informationSPRING LOADED THERMOCOUPLE CONFIGURATIONS
SPRING LOADED THERMOCOUPLE CONFIGURATIONS FOR USE WITH THERMOWELLS II 3G Ex na/nl TCRN/WN/TN S30 S31 S36-1 S36-2 1 FEATURES TECHNICAL SPECIFICATION ASSEMBLY The industrial spring loaded configuration guarantees
More informationSPRING LOADED THERMOCOUPLE CONFIGURATIONS THERMOWELL & REPLACEABLE INSERT II 2G/D Ex e TCRE/WE
SPRING LOADED THERMOCOUPLE CONFIGURATIONS THERMOWELL & REPLACEABLE INSERT II 2G/D Ex e TCRE/WE C20 C21 C26-2 C26-2 1 FEATURES TECHNICAL SPECIFICATION ASSEMBLY The industrial spring loaded configuration
More information