Implementing Demand Controlled Ventilation to Meet ASHRAE Standard By KlasC. Haglid, P.E., R.A., CEM
|
|
- Meryl Nelson
- 6 years ago
- Views:
Transcription
1 Implementing Demand Controlled Ventilation to Meet ASHRAE Standard By KlasC. Haglid, P.E., R.A., CEM 1
2 Klas C. Haglid, P.E., R.A., CEM - Bio ASHRAE Distinguished Service Award 2011 ASHRAE Handbook, HVAC Applications and Management, Chapter 37, Author, Klas C. Haglid P.E. R.A. ASHRAE Standard 189.1, Corresponding Member GPC 32P -Sustainable, High Performance Operations & Maintenance, Voting Member, Contributing, Co-Author Technical Committee 5.5 -Air-To-Air Energy Recovery, Handbook Subcommittee Chairman, Past Chairman Technical Committee System Energy Utilization, Voting Member Technical Committee 7.8 -Owning and Operating Costs of Commercial Buildings, Past Chairman ASHRAE Standard R, Voting Member Reviewed draft of ASHRAE Standard R and provided engineering details for efficiency calculations. 2
3 Objectives Complying with ASHRAE Std to improve IAQ while increasing energy efficiency ASHRAE Std can be accomplished with: Displacement Ventilation Demand Controlled Ventilation Energy Recovery Ventilators Variable Speed Drives 3
4 ASHRAE Std Ventilation for Acceptable Indoor Air Quality How to determine minimum prescriptive ventilation rates How to use Demand Side Ventilation to meet ASHRAE Standard
5 Definitions acceptable indoor air quality: air in which there are no known contaminants at harmful concentrations as determined by cognizant authorities and with which a substantial majority (80% or more) of the people exposed do not express dissatisfaction. ASHRAE Standard pg. 3 5
6 Definitions Demand Control Ventilation (DCV): any means by which the breathing zone (Vbz) can be varied to the occupied space or spaces based on the actual or estimated number of occupants and/or ventilation requirements of the occupied zone ASHRAE Standard pg. 4 6
7 6.1.1 Ventilation Rate Procedure The following procedure for determining the minimum prescriptive ventilation rates can be used on any zone type Takes into consideration: Space type Number of Occupants Floor Area Typical contaminant sources and source strength 7
8 Ventilation Rate Procedure Breathing Zone (bz) Outdoor Airflow (OA) V bz = R p P z + R a A z where: R p = outdoor airflow rate required per person as determined from Table 6-1*. P z = zone population R a = outdoor airflow rate required per unit area as determined from Table 6-1*. A z = zone floor area *Table 6-1 from ASHRAE Standard
9 Two Parts to the Formula Type and size of space? How many people? 9
10 First Part of the Equation Rate Per Person Rp Zone Pop Pz cfm for people ASHRAE Std
11 Second Part Rate Per Person Rp Zone Pop Pz cfm for People Rate Per Area Ra Zone Area Az cfm for Area 11
12 Combined cfm for People Vbz cfm for Area Breathing Zone Outdoor Airflow 12
13 Office Example What is the prescriptive design for outdoor air (cfm) of a 1500 square foot office with 12 occupants? Eq6-1 : V bz = R p P z + R a A z Design inputs for office space: Pz= 12 people Az= 1,500 square feet of floor area V bz = (5x12) + (.06 x 1500) = = 150 cfm 13
14 School Example What is the prescriptive design for outdoor air (cfm) of a 1100 square foot classroom with 30 students? Eq6-1 : V bz = R p P z + R a A z From Table 6-1: R p = 10 cfm/person R a = 0.12 cfm/ft 2 Design inputs from school classroom project for ventilation: P z = 30 people A z = 1100 square feet V bz = (10 x 30) + (.12 x 1100) = = 432 cfm 14
15 General Manufacturing Example (Excludes Heavy Industrial and processes using chemicals) What is the prescriptive design for outdoor air (cfm) of a 50,000 square foot coat hanger production facility with 20 machinists? Eq6-1 : V bz = R p P z + R a A z From Table 6-1: R p = 10 cfm/person R a = 0.18 cfm/ft 2 Increase Production facility input data: P z = 20 people A z = 50,000 square feet of floor area V bz = (10 x 20) + (.18 x 50000) = ,000= 9,200 cfm Notice the Area outdoor air rate (Ra) increased for a manufacturing facility. 15
16 Ventilation Rate Procedure Zone Outdoor Airflow V oz = V bz /E z (E z ) The zone air distribution effectiveness shall be determined using ASHRAE Std , Table 6-2. (Partial Table) 16
17 Methods of Providing Outdoor Air to Zone Dilution Ventilation Displacement Ventilation 17
18 Dilution Ventilation It s important to design ventilation system to have maximum air distribution. This will help eliminate dead space and short circuiting of air flow Poor distribution of air across classroom breathing zone 18
19 Dilution Ventilation Typical in U.S. construction Outdoor air is brought into space and dilutes contaminant concentrations in the space. Adequate air mixing 19
20 Air Mass Exchange Diagram shows good air circulation providing fresh air on one end of room and exhaust pulling air out on the other end to maximize removing contaminant concentrations by displacing room temperature air across a Breathing Zone 20
21 Displacement Ventilation (DV) Uses natural convection to provide Buoyancyassisted forced ventilation Effectively removes contaminants from people and objects locally ASHRAE Std Table 6-2 recognizes DV to be 1.2 times more effective than traditional dilution ventilation Some applications measured DV to be 2 to 2.5 more effective than traditional dilution ventilation 21
22 Displacement Ventilation Using displacement ventilation and then measuring air quality of the space is an effective way to improve IAQ Often times, balancing airflow according to how effective the displacement ventilation system is can reduce required airflow by 50% This saves energy and reduces latent loads Can be achieved with Variable Speed Drives (VSD) 22
23 Demand Controlled Ventilation (DCV) any means by which the breathing zone outdoor airflow (Vbz) can be varied to the occupied space or spaces based on the actual or estimated number of occupants and/or ventilation requirements of the occupied zone. ASHRAE Std pg. 4 23
24 Example of DCV Methods Fan Relays ERV EA SOA CO2 Sensor comes on over 700 ppm and turns off under 600 ppm People ERV- Energy Recovery Ventilator EA- Exhaust Air SOA- Supply Outside Air 24
25 DCV CO 2 concentrations in outdoor air generally range from 300 to 500 ppm ASHRAE std and 2010 recognize 700 ppm of CO 2 above outdoor ambient levels or 1000 to 1200 ppm to be acceptable air quality for an indoor space. Reference page 37 of Appendix C Displacement Ventilation with CO 2 Demand Controlled Ventilation properly engineered and installed will keep CO 2 levels well below 1000 ppm DCV can reduce runtime from 168 hours per week to 30 hours per week for a classroom. That is an 82% reduction in runtime. 25
26 Fan Affinity Laws Assuming fan diameter and air density are constant Eq(1) : Eq(2) : Eq(3) : 26
27 Fan Affinity Laws Eq(1) : rpm rpm 27
28 Fan Affinity Laws Eq (2) : rpm rpm Pressure is squared rpm rpm 28
29 Fan Affinity Laws Eq (3) : rpm rpm Energy Expended is Cubed BHP BHP 29
30 Example What is the percent difference in BHP required to run a ventilation system if alternative 2 has a 50% increase in static pressure from alternative 1? Alternative 1 Conditions: CFM = 8,000 SP = 1 in wg BHP = 5 RPM =
31 Example Continued Rearranging Eq(2): RPM 2 = SP 2 /SP 1 x RPM 1 RPM 2 = 1.5/1 x 1000 = 1225 Eq(3): BHP 2 = BHP 1 x ( RPM 2 /RPM 1 ) 3 BHP 2 = 5x ( 1225/1000) 3 = 9.2 BHP 9.2-5/5 = 84% Increase A 50% increase in static pressure results in an 84% increase in power consumption 31
32 Not All ERVs Are the Same ERV Features to Compare: Airflow Arrangement Thermal Effectiveness Pressure Drop Fan Efficiency Maintenance Sound Levels 32
33 Heat Exchanger Airflow Arrangement ASHRAE states: Counter-flow heat exchangers are theoretically capable of achieving 100% Sensible Effectiveness* Parallel Flow heat exchangers: 50% (Max) Cross-flow heat exchangers and Enthalpy Wheels: 50-75% (Max) *Note: Source: 2012 ASHRAE Handbook HVAC Systems and Equipment, Chapter 26: Air-to-Air Energy Recovery Equipment. 33
34 High Efficiency Fans Typical fan efficiency can range from 5 to 10 W/cfm A high efficiency fan can be expected to be approximately 0.2 W/cfm The EER of an ERV s performance is formulated by the BTUs recovered divided by the watts of power consumed from the fan energy. EER = BTUs Recovered Watts of Fan Power 34
35 Thermal Efficiency vs. Overall Efficiency Effectiveness (%) Fan Power (W) EER (BTU/W) High Eff. ERV Typical ERV Typical ERV has an EER of around 11. High efficiency ERV can be well above 120. Combining premium Efficiency fans with High efficiency ERVs and a low static pressure system can yield great energy savings 35
36 Efficiency = Payback A short term savings in build cost is outweighed by sustainable gains over present consumption. 36
37 Maintenance Costs are Essential There s more to a product than its initial costs and efficiency Maintenance and efficiency equal long term and continuous ROI Corrosion resistant equipment Minimal moving parts Low static pressure Appropriate filters and size Efficient fans Location/Operation 37
38 Tools to Meet ASHRAE Std and Improve IAQ While Increasing Energy Efficiency, ASHRAE Std Displacement Ventilation Demand Controlled Ventilation CO2 controls or other contaminant monitoring sensors ERV Counter flow heat exchanger Low Pressure Drops High efficiency fans Variable Speed Drives Air balancing Better control 38
39 39
DISPLACEMENT VENTILATION
DISPLACEMENT VENTILATION D3 OVERVIEW The fundamental approach to displacement ventilation utilizes the natural buoyancy forces created by the convective flows from heat sources in the space. As supply
More informationCompliance Evaluation: ASHRAE Standard Ventilation for Acceptable Indoor Air Quality
Compliance Evaluation: ASHRAE Standard 62.1-2001 Ventilation for Acceptable Indoor Air Quality Photo rendering courtesy of Hooper Shiles Architects Philadelphia School District Administration Headquarters
More informationVentilation. Demand-controlled ventilation (DCV) Demand-Controlled. With ASHRAE Standard Based
CO Demand-Controlled 2 -Based Ventilation With ASHRAE Standard 62.1 Though not as straightforward as it once was, remains a practical way to reduce costs Editor s note: Following is an update of the November
More informationTechnical Report #1 ASHRAE Standard 62: Ventilation Compliance Evaluation
Mechanical Option Technical Report #1 Technical Report #1 ASHRAE Standard 62: Ventilation Compliance Evaluation Instructor: Dr. Srebric 10.06.04 Building Sponsors: CCG Facilities Integration Table of Contents
More informationThe Palestra Building London, England
Architectural Renderings compliments of Alsop Architects Ventilation Report Becca Allen The Pennsylvania State University Architectural Engineering AE 481W, Fall 2005 Table of Contents I. Executive Summary
More informationMechanical Technical Assignment One ASHRAE Standard Compliance Evaluation
Mechanical Technical Assignment One ASHRAE Standard 62.1-2007 Compliance Evaluation The Prepared By: Maxwell S. Chien October 5 th, 2007 Prepared For: Dr. William P. Bahnfleth, Ph.D., P.E., Professor Department
More informationYORK UNITIZED ENERGY RECOVERY VENTILATOR (ERV) Superior air-flow 300 6,200 CFM
YORK UNITIZED ENERGY RECOVERY VENTILATOR (ERV) Superior air-flow 300 6,200 CFM YORK UNITIZED ENERGY RECOVERY VENTILATORS Regardless of building type or rating system, today s building must be as energy
More informationUnderf loor For Schools
The following article was published in ASHRAE Journal, May 2008. Copyright 2008 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
More informationIAQ & Energy Impact of Exhaust Air Transfer Ratio
This article was published in ASHRAE Journal, November 207. Copyright 207 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission
More informationChanges to the Minnesota Commercial Energy Code. Presented by: Andy Thielen, PE
Changes to the Minnesota Commercial Energy Code Presented by: Andy Thielen, PE Warning! The following is an outline of proposed code changes. There is no guarantee that the final code adopted by the State
More informationHow to Reduce Energy Use in Your Labs by Up to 50%
How to Reduce Energy Use in Your Labs by Up to 50% Illinois Chapter of ASHRAE April 11, 2017 Dan Doyle, Chairman Grumman/Butkus Associates 1 Course Description Labs have high exhaust requirements and large
More informationASHRAE Standard 62.1 Ventilation Report
Mechanical Technical Report 1 ASHRAE Standard 62.1 Ventilation Report The nue New York, NY 10022 Faculty Advisor: Dr. Jelena Srebric October 5, 2005-1 - Table of Contents 1.0 Executive Summary 2.0 Building
More informationEvaluation of Underfloor Air Distribution
McCarran International Airport Terminal 3 L as Vegas, NV Evaluation of Underfloor Air Distribution and Displacement Ventilation Systems The Pennsylvania State University AESenior ThesisPresentation, Spring
More informationCalculating the Efficiency of Energy Recovery Ventilation and its Effect on Efficiency and Sizing of Building HVAC Systems
AHRI Guideline V (I-P) 20 Guideline for Calculating the Efficiency of Energy Recovery Ventilation and its Effect on Efficiency and Sizing of Building HVAC Systems IMPORTANT SAFETY DISCLAIMER AHRI does
More informationVentilation standards EN15251 and ANSI/ASHRAE 62.1 Professor Bjarne W. Olesen, Ph.D.
Ventilation standards EN15251 and ANSI/ASHRAE 62.1 Professor Bjarne W. Olesen, Ph.D. Technical University of Denmark Energy consumption for ventilation Exhaust Ventilation air Up to 30% of the total energy
More informationDEMAND CONTROLLED VENTILATION (DCV) SYSTEMS
DEMAND CONTROLLED VENTILATION (DCV) SYSTEMS Mari-Liis Maripuu, PhD CIT Energy mari-liis.maripuu@cit.chalmers.se Swegon Air Academy, Portugal, 27 May 211 Outline Introduction Concept of a DCV system Adapting
More informationUpdate to ASHRAE Ventilation Standards. William P. Bahnfleth, PhD, PE, FASHRAE, FASME The Pennsylvania State University University Park, PA, USA
Update to ASHRAE Ventilation Standards William P. Bahnfleth, PhD, PE, FASHRAE, FASME The Pennsylvania State University University Park, PA, USA REHVA Annual Conference Riga, Latvia May 8 9, 2015 Acknowledgements
More information2019 Title 24 Codes & Standards Enhancement (CASE) Proposal Nonresidential Ventilation & Indoor Air Quality (IAQ)
2019 Title 24 Codes & Standards Enhancement (CASE) Proposal Nonresidential Ventilation & Indoor Air Quality (IAQ) September 27, 2016 Ryan Sit Integral Group rsit@integralgroup.com Anna Brannon Integral
More informationLEED And Your Indoor Environment
LEED And Your Indoor Environment An overview of LEED v3 and Indoor Air Quality David McCauley, CIE Council Certified Indoor Environmentalist ACAC CIE #1008005 USGBC's Mission To transform the way buildings
More informationEnergy Recovery Ventilation Equipment
ANSI/AHRI Standard 1060 (I-P) 2014 Standard for Performance Rating of Airto-Air Exchangers for Energy Recovery Ventilation Equipment Approved by ANSI on May 15, 2015 IMPORTANT SAFETY DISCLAIMER AHRI does
More informationASHRAE 62.2: What s New in 2016
ASHRAE 62.2: What s New in 2016 Rick Karg 2016 Residential Energy Dynamics, LLC What We Will Talk About Overview of mechanics of 62.2-2016. Logic behind the Standard. Sizing local ventilation (exhaust-only).
More informationWalter Reed National Military Medical Center Bethesda, MD
Walter Reed National Military Medical Center Bethesda, MD Technical Report Three: Mechanical Systems Existing Conditions Evaluation Prepared For: Dr. James D. Freihaut Prepared By: Justin Herzing Date:
More informationACTIVA Rooftop. YKN2open. ARC-ARG-ARH-ARD A complete range from 48 kw up to 84 kw. Nomenclature A R C 045 B B. Features
ACTIVA Rooftop ARC-ARG-ARH-ARD A complete range from 48 kw up to 84 kw YKN2open Features High efficiency EER and COP Low noise level All configurations: Cooling only, Cooling + gas, Heating, Heating +
More informationValent Packaged Rooftop Units A Fresh Choice for High-Percentage Outdoor Air Designs. Valent is a business of Unison Comfort Technologies.
Valent Packaged Rooftop Units A Fresh Choice for High-Percentage Outdoor Air Designs Valent is a business of Unison Comfort Technologies. When your HVAC system design calls for high-percentage or 100%
More informationA. The project is intended to achieve LEED Certification at the Silver Level per the U.S. Green Building Council LEED for Schools 2007 rating system.
SECTION 23 01 01 HVAC LEED REQUIREMENTS PART 1 -GENERAL 1.1 WORK INCLUDES A. Compliance with LEED project requirements. B. Coordination of LEED construction phase activities. C. Data gathering of construction
More informationApplication of Advanced Energy Technologies
GLOBALCON 2002 Philadelphia, Pennsylvania March 27, 2002 Application of Advanced Energy Technologies Michael K. West, Ph.D., P.E. Building Systems Scientist Advantek Consulting, Inc. www.advantekinc.com
More informationOptimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016
Optimizing Indoor Environments for Occupant Satisfaction Presented by: Kelli Goldstone April 2016 Outline Function of HVAC Thermal Comfort Air Distribution Radiant Heating / Cooling Case Study Function
More informationThe Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma
LEED Green Building Certification The purpose of the LEED Green Building Rating is to provide a national standard that aims to improve environmental, health and economic performance of buildings using
More informationCeiling Radiant Cooling Panels
2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc (wwwashraeorg) Published in ASHE Journal Vol 48, Oct 2006 For personal use only Additional reproduction, distribution,
More informationPRESENTATION BY: Sean P. Murray Energy/Facility Use Manager St. Lucie County Public Schools. Art Munns Senior Project Engineer OCI Associates, Inc.
PRESENTATION BY: Sean P. Murray Energy/Facility Use Manager St. Lucie County Public Schools Jason Smith, PE, LEED AP BD+C, CEM Principal / Dir. of Mech. Engineering OCI Associates, Inc. Art Munns Senior
More informationMEP's Letter of Assurance
MEP's Letter of Assurance Instructions Multifamily Residential WELL Certification is determined by onsite Performance Verification and documentation, including Letters of Assurance from the appropriate
More informationIMPACT OF THE SEMCO ANTI-STICK FACE COATING ON THE COLLECTION AND CLEANING OF ENVIRONMENTAL TOBACCO SMOKE FROM THE WHEEL SURFACE RESEARCH FINDINGS
AIR QUALITY ANTI-STICK EFFICIENT IMPACT OF THE SEMCO ANTI-STICK FACE COATING ON THE COLLECTION AND CLEANING OF ENVIRONMENTAL TOBACCO SMOKE FROM THE WHEEL SURFACE 2 ANTI-STICK WHEEL FACE COATING Impact
More informationMEP's Letter of Assurance
MEP's Letter of Assurance Instructions WELL Certification is determined by onsite Performance Verification and documentation, including Letters of Assurance from the appropriate professionals overseeing
More informationLEED v4 Building Design and Construction Quiz #8 EQ
LEED v4 Building Design and Construction Quiz #8 EQ 1. Which of these is considered an unoccupied space? [Choose three] A. School classroom B. Mechanical room C. Meeting room D. Locker room E. Restroom
More informationProgressive Design Concepts for the Evolving Learning Environment
Progressive Design Concepts for the Evolving Learning Environment Learning Objectives 1. Understand how air movement can maximize energy savings and comfort in a range of educational applications. 2. Demonstrate
More informationLEED. Leadership in Energy and Environmental Design
LEED Leadership in Energy and Environmental Design GREEN BUILDING In years past, the theory of high performance green buildings was hard to define and the practice even more obscure. All of that is rapidly
More informationNJ AIHA CIH Review Industrial Ventilation
NJ AIHA CIH Review Industrial Ventilation Thomas Block, CIH MPH tblock@aps.rutgers.edu 848-445-2550 2016 American Industrial Hygiene Association, New Jersey Section, Inc. Course Objectives At the end of
More informationProduct Data. 50TC Cooling Only/Electric Heat Packaged Rooftop 15 to 25 Nominal Tons. (Unit shown with optional economizer.
Cooling Only/Electric Heat Packaged Rooftop 15 to 25 Nominal Tons Product Data (Unit shown with optional economizer.) C09262 the environmentally sound refrigerant This product has been designed and manufactured
More informationIndoor Air Quality (IAQ) Tailoring Lease Specifications S-852
Indoor Air Quality (IAQ) Tailoring Lease Specifications S-852 June 2015 Table of Contents Printed with permission from authors...3 Introduction...4 Outside air distribution...4 Air contaminant source...6
More informationIndoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms
Indoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms Abstract Finland is a country without a debate on natural ventilation. In such a cold climate, it
More informationEnergy Recovery Application Manual
Energy Recovery Application Manual March 1997 Table of Contents Chapter 1: The Need for Mechanical Ventilation.................................. 3 Chapter 2: The Enthalpy Wheel...8 Chapter 3: Product Application
More informationIECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST
IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST ENVELOPE REQUIREMENTS Project: Date: Instructions RECOMMENDED: List performance values, note exceptions that were applied, or provide other
More informationASHRAE STANDARD Ventilation for Acceptable Indoor Air Quality
ANSI/ASHRAE Addenda g, r, and t to ANSI/ASHRAE Standard 62.1-2007 ASHRAE STANDARD Ventilation for Acceptable Indoor Air Quality Approved by the ASHRAE Standards Committee on January 23, 2010; by the ASHRAE
More informationNOTE: Some guidance on a performance approach to natural ventilation systems design is provided in the Supplement to this Standard.
19 SECTION 3 NATURAL VENTILATION 3.1 SCOPE OF SECTION This Section specifies the means of achieving the quantity of outdoor air required in a naturally ventilated enclosure. The provisions described include
More informationMilwaukee, WI. Darron Rempel
Application of Hydronic Radiant and Beam Systems ASHRAE Region IV Conference Milwaukee, WI May 14, 2010 Darron Rempel darronr@price hvac hvac.comcom Introduction Topics covered: o Theory of using water
More informationDo European standards for indoor air quality take into account outdoor air quality? Professor Bjarne W. Olesen, PhD, Department of Civil Engineering
Do European standards for indoor air quality take into account outdoor air quality? Professor Bjarne W. Olesen, PhD, Department of Civil Engineering Technical University of Denmark Global impact on people
More informationProduct Data. (Unit shown with optional economizer.)
COOLING ONLY/ELECTRIC HEAT PACKAGED ROOFTOP UNIT 15 TO 27.5 NOMINAL TONS Product Data (Unit shown with optional economizer.) C09316 Use of the AHRI Certified TM Mark indicates a manufacturer s participation
More informationMEP Engineer's Letter of Assurance
Instructions MEP Engineer's Letter of Assurance WELL Building Standard, Jan 2016 WELL Certification and WELL Core and Shell Compliance are determined by onsite Performance Verification and Documentation,
More informationTYP. SINGLE PLY ROOFING ROOF SHEETING BROAN VENT CAP #10 x 1" GASKETED SMS TYP. 4 SIDES 8" FRAMED CURB HVAC SYSTEMS "BASIS OF DESIGN" ROOF INSULATION R-19 WALL INSULATION R-13 LIGHTING EFFIECNCY PER STANDARDS
More informationWEST VIRGINIA UNIVERSITY ALUMNI CENTER Morgantown, West Virginia
TECHNICAL REPORT I ASHRAE STANDARDS 62.1 AND 90.1 COMPLIANCE EVALUATION 8/29/08 WEST VIRGINIA UNIVERSITY ALUMNI CENTER Morgantown, West Virginia GREGORY SMITHMYER PENN STATE UNIVERSITY ARCHITECTURAL ENGINEERING
More informationDo Risks Outweigh Potential Rewards?
The following article was published in ASHRAE Journal, October 2004. Copyright 2004 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
More informationDevelopment of Design Guidance for K-12 Schools: From 30% to 50% Energy Savings
Development of Design Guidance for K-12 Schools: From 30% to 50% Energy Savings Shanti Pless, Paul Torcellini, and Nicholas Long, National Renewable Energy Laboratory ABSTRACT This paper describes the
More informationLEED 2009 for New Construction and Major Renovations
LEED 2009 for New Construction and Major Renovations Bayshore District Operations Building Project Checklist 4.28.6 20 4 0 Sustainable Sites Possible Points: 26 Y? N d/c Notes: Y C Prereq Construction
More informationCARRIER PRODUCTS AND LEED CERTIFICATION
CARRIER PRODUCTS AND LEED CERTIFICATION Carrier Cpation Syracuse, New Yk August 2007 TABLE OF CONTENTS INTRODUCTION... 3 LEED RATING SYSTEM OVERVIEW... 4 LEED FOR NEW CONSTRUCTION... 4,5 ENERGY & ATMOSPHERE
More informationCERTIFICATE OF FIELD VERIFICATION & DIAGNOSTIC TESTING (Page 1 of 8)
CERTIFICATE OF FIELD VERIFICATION & DIAGNOSTIC TESTING (Page 1 of 8) Builder or Installer Name Builder or Installer Contact Telephone Plan/Permit (Additions or Alterations) Number Compliance Method (Prescriptive)
More informationExample LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal
Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal The following documentation provides an example submittal for the LEED-NC v2.1 Energy & Atmosphere Credit 1 (EAc1). This sample EAc1 submittal
More informationFresh Air Ideas SUPPORTING GREEN INITIATIVES WITH INNOVATION
Fresh Air Ideas SUPPORTING GREEN INITIATIVES WITH INNOVATION SUPPORTING GREEN INITIATIVES WITH INNOVATION As one of the first manufacturers of air movement and control equipment to join the U.S. Green
More informationDesigning Air-Distribution Systems To Maximize Comfort
Designing Air-Distribution Systems To Maximize Comfort By David A. John, P.E., Member ASHRAE An air-distribution system that provides occupant thermal comfort can be a complicated system to predict and
More informationSouth Carolina Society for Hospital Engineers
South Carolina Society for Hospital Engineers Selecting Energy Partners: Criteria & Pitfalls and the Top 10 Ways to Reduce Energy in a Hospital Presented by Jon Dierking, PE, CEM, LEED AP Director of Energy
More informationWalter Reed National Military Medical Center Bethesda, MD
Walter Reed National Military Medical Center Bethesda, MD Technical Report One: ASHRAE Standard 62.1 2007 and 90.1 2007 Analysis Prepared For: Dr. James D. Freihaut Prepared By: Justin Herzing Date: 10/05/2009
More informationArticles. Figure 2. Typical set-up of personalized ventilation system.
Revision of 15251: ndoor Environmental Criteria Abstract: 15251 specifies indoor environmental input parameters for design and assessment of energy performance of buildings addressing indoor air quality,
More informationChilled Beams. The new system of choice?
Chilled Beams The new system of choice? Presented By: Kevin M. Pope P.E. Jason Leffingwell Hammel Green And Abrahamson, Inc. and Ken Bauer, P.E., LEED AP Butters-Fetting Co., Inc. History of Chilled Beams
More informationIn the school year, U.S. K-12 public schools provided instruction to over 46 million
A Joint EPA Working Paper from ENERGY STAR and Indoor Air uality September 2003 Energy Efficiency and Indoor Air uality in Schools Overview In the 1998-99 school year, U.S. K-12 public schools provided
More informationEES Energy Efficient Systems Rotary Screw Air Compressors kw Horsepower
S-energy EES Energy Efficient Systems Rotary Screw Air Compressors 30-75 kw 40-100 Horsepower Superior energy savings Payback in less than 2 years 90% of wasted heat is recoverable Excellent source of
More informationAnalysis 2: Mechanical System
Background and problem Analysis 2: Mechanical System Outpatient Medical center is a medical center for children and adolescences with developmental disabilities. It therefore requires the building to have
More informationTHERMA-FUSER VARIABLE AIR VOLUME DIFFUSER SYSTEMS
SUSTAINABLE DESIGN FORM 010.901 REV 1211 THERMA-FUSER VARIABLE AIR VOLUME DIFFUSER SYSTEMS SUSTAINABLE DESIGN GUIDE StopWaste.Org LEED-NC Platinum Energy Foundation LEED-CI Platinum Adobe East Tower LEED-EB
More informationASHRAE 62.1 Outside Air Reduction
ASHRAE 62.1 Outside Air Reduction CosaTron has long been recognized for our ability to dramatically improve indoor air quality. The effectiveness of our system has been demonstrated through thousands of
More informationProduct Data. 48TC Gas Heat/Electric Cooling Packaged Rooftop 15 to 25 Nominal Tons. (Unit shown with optional economizer.) C09248
Gas Heat/Electric Cooling Packaged Rooftop 15 to 25 Nominal Tons Product Data (Unit shown with optional economizer.) C09248 the environmentally sound refrigerant This product has been designed and manufactured
More information2010 Standard for Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and Heat Pump Equipment
ANSI/AHRI Standard 1230 with Addendum 2 2010 Standard for Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and Heat Pump Equipment Approved by ANSI on 2 August 2010 ANSI/AHRI
More informationMcCarran International Airport Terminal 3
McCarran International Airport Terminal 3 The Pennsylvania State University Architectural Engineering Senior Thesis Final Report Evaluation of Underfloor Air Distribution and Displacement Ventilation Systems
More informationTAB (test-adjustbalance) in the Sustainable Environment & Lessons Learned. HVAC Excellence Conference & Training March 17-18, 2013 Tom Hanlon
TAB (test-adjustbalance) in the Sustainable Environment & Lessons Learned HVAC Excellence Conference & Training March 17-18, 2013 Tom Hanlon Outline: Sustainable Environment?? LEED V3 Green Globes ASHRAE
More informationDo-It-Yourself Energy Audit. Bob Furgeson, PE CEM CBCP GBE CEA Shive-Hattery Architects+Engineering
Do-It-Yourself Energy Audit Bob Furgeson, PE CEM CBCP GBE CEA Shive-Hattery Architects+Engineering Agenda» Basic Terminology» Background» Benchmarking» Audit Types/ASHRAE Standard» Building Audit Systems
More informationOEM WHEEL EQUIPMENT ENTHALPY RECOVERY WHEELS INDOOR AIR QUALITY VENTILATION ENERGY RECOVERY
INDOOR AIR QUALITY VENTILATION ENERGY RECOVERY OEM WHEEL EQUIPMENT ENTHALPY RECOVERY WHEELS AHRI certified & independently tested wheel performance Highest effectiveness and Recovery Efficiency Ratio (RER)
More informationOEM WHEEL EQUIPMENT ENTHALPY RECOVERY WHEELS INDOOR AIR QUALITY VENTILATION ENERGY RECOVERY
INDOOR AIR QUALITY VENTILATION ENERGY RECOVERY OEM WHEEL EQUIPMENT ENTHALPY RECOVERY WHEELS AHRI certified & independently tested wheel performance Highest effectiveness and Recovery Efficiency Ratio (RER)
More informationRebel commercial packaged rooftop systems
Rebel commercial packaged rooftop systems Advanced technologies propel performance and energy savings to uncommon levels 3-28 tons Rebel features and benefits 18 13 6 5 3 6 4 43% Energy Savings 5 11 12
More informationHELPING HVAC PROFESSIONALS TAKE THE LEED ACHIEVING LEED CERTIFICATION
HELPING HVAC PROFESSIONALS TAKE THE LEED ACHIEVING LEED CERTIFICATION Green proof of performance pays Sustainable design saves energy, opens doors and improves building status The rapidly growing segment
More informationAdvanced Variable Air Volume Control Sequences. Steven T. Taylor, PE Taylor Engineering Alameda, CA
Advanced Variable Air Volume Control Sequences Steven T. Taylor, PE Taylor Engineering Alameda, CA November 12, 2013 Agenda VAV Box Control Sequences AHU Control Sequences Zone Groups DP setpoint reset
More informationPaul W. Francisco University of Illinois at Urbana Champaign
Paul W. Francisco University of Illinois at Urbana Champaign 1 (it s not really that scary) 2 15 cfm/person originated from smell tests in the 1930s (Yaglou et al. 1936) and more or less again in 1983
More informationBuilding & Fire Appeals Board
Building & Fire Appeals Board Date: March 10, 2016 Time: 3:30 p.m. - 5:00 p.m. Location: St Etienne Room City of Des Moines Armory Building 602 Robert D. Ray Drive Des Moines, Iowa 50309-1881 Summersfield
More informationItalcementi Center for Research and Innovation
Italcementi Center for Research and Innovation Bergamo, Italy LEED-NC v2.1 EAc1 A. Project Narrative (Viridian) analyzed the energy use of the proposed Italcementi Center for Research and Innovation located
More informationIntegration of Mechanical System Redesign. Geothermal Heat Pumps with DOAS
Integration of Mechanical System Redesign Geothermal Heat Pumps with DOAS Lutheran Theological Seminary at Philadelphia The New Learning Center Prepared For: William P. Bahnfleth, Ph.D., P.E. Department
More informationModeling for LEED. Refer to Additional LEED credits on page 6 90 for a list of credits TRACE 700 may help to achieve.
Modeling for LEED USGBC s Leadership in Energy and Environmental Design (LEED) program updates its products to closely align with the latest industry standards. LEED version 3, the most recent version
More informationLab Ventilation Safety & Energy Efficiency. Agenda & Objectives
Lab Ventilation Safety & Energy Efficiency Methods to Achieve Safe and Energy Efficient Laboratory Ventilation Systems Thomas C. Smith tcsmith@labhoodpro.com Agenda & Objectives Introduction Laboratory
More informationAnalysis of the air conditioning systems in a blown films manufacturing plant in the southeastern United States
Analysis of the air conditioning systems in a blown films manufacturing plant in the southeastern United States Dr. George Ford 1, Dr. William McDaniel 2 and Mr. Paul Yanik 3 ABSTRACT This paper is a study
More informationLIFE CYCLE COST OF DISPLACEMENT VENTILATION IN AN OFFICE BUILDING WITH A HOT AND HUMID CLIMATE
LIFE CYCLE COST OF DISPLACEMENT VENTILATION IN AN OFFICE BUILDING WITH A HOT AND HUMID CLIMATE By LANE W. BURT A THESIS PRESENTED TO THE GRADUATE SCHOOL OF THE UNIVERSITY OF FLORIDA IN PARTIAL FULFILLMENT
More informationI S O. Eco-Smart Energy Recovery Ventilator
I S O I S O 9 0 0 1 1 4 0 0 1 Eco-Smart Energy Recovery Ventilator What s Eco-Smart? Holtop has manufactured heat and energy recovery ventilation products for over 12 years. We pay high attentions on the
More informationRhode Island Commercial Codes FAQs
Rhode Island Commercial Codes FAQs When does the new code go into effect? The new suite of building codes (including the new state energy conservation code, SBC-8) was adopted on July 1, 2013. A brief
More informationThe ASHRAE Energy Code: How it Will Affect Your Projects
The ASHRAE 90.1-2010 Energy Code: How it Will Affect Your Projects Presenter Jeff Boldt, PE, LEED AP, HBDP KJWW Engineering Principal Director of Engineering Voting Member ASHRAE SSPC-90.1 Member SSPC
More informationVENTILATION REQUIREMENTS TO PREVENT PIT AIR UP-DRAFTING IN
This is not a peer-reviewed article. Pp. 05-030 in Swine Housings II Proceedings of the -5 October 003 Conference (Research Triangle Park, North Carolina USA), Publication Date October 003. ASAE Publication
More informationUsing CFD to Wring Out Energy Efficiency in Laboratory Settings
Using CFD to Wring Out Energy Efficiency in Laboratory Settings Energy Conservation Strategies for Cornell University Laboratories Primary focus is on controls to reduce outside air use Occupancy sensors
More information780 CMR: 9 th Edition Massachusetts State Building Code. Presented to: BSA Codes Committee. DATE: January 20, 2016
780 CMR: 9 th Edition Massachusetts State Building Code Presented to: BSA Codes Committee DATE: January 20, 2016 This course is registered with AIA CES for continuing professional education. Credit(s)
More informationCASE STUDY. Two Dogs and Two Cats Insufficient Air Exchange with High CO2
FOR MORE INFORMATION, VISIT: HTTP://BUILDEQUINOX.COM/BLACKBOX/ CASE STUDY Two Dogs and Two Cats Insufficient Exchange with High CO2 A Black Box IAQ was placed in the main living area of a pre-1900 home.
More informationErrata Sheet. LEED for Schools Reference Guide First Edition for the document titled:
Errata Sheet for the document titled: LEED for Schools Reference Guide First Edition 2007 Notes: Updates to this document are posted on the LEED for Schools Rating System page and the Reference Guide electronic
More informationBaffled Openings at Chain Link Fencing: Design shall consist of two end-posts set 4 feet apart, and a 10 foot wide chain-link fence panel equal in height as the adjacent fence. Chain link fence panel shall
More informationConstruction Indoor Air Quality (IAQ) Management Plan
Denver School of Science & Technology Middle School 2000 Valentia Street Denver, CO 80238 Telephone: 303-643-5775 Main Fax: 303-673-5776 Construction Indoor Air Quality (IAQ) Management Plan Denver School
More informationChilled Water Plant Redesign
17 Chilled Water Plant Redesign OVERVIEW The chilled water plant redesign includes the addition of a thermal energy storage system. This allows for economic and operational benefits for the facility by
More informationCentral Chiller Plants
Central Chiller Plants Institute for Facilities Management New Orleans, LA January 18,2016 Course 319 Presenter: John Vucci Associate Director HVAC Systems University of Maryland College Park, Maryland
More informationCentre for Sustainability of the Built Environment
Case Study Report Indoor air quality of a demandcontrolled air-conditioning system Mayfield House Lecture Theatre, Falmer Campus, University of Brighton European Regional Development Fund Executive summary
More informationTHE REVISION OF STANDARD 62: WHAT A DIFFERENCE A DECADE MAKES
THE REVISION OF STANDARD 62: WHAT A DIFFERENCE A DECADE MAKES A Persily * National Institute of Standards and Technology, Gaithersburg, MD, USA ABSTRACT The American Society of Heating, Refrigerating and
More informationResearch Analysis: Building Envelope and LEED Credits Introduction
: Building Envelope and LEED Credits Introduction Green buildings are no longer a new idea and are quickly becoming the trend in the slowly changing industry of building construction. Even though the essence
More information