1 INDOOR AIR QUALITY CALUMET COUNTY HIGHWAY FACILITY -CARBON MONOXIDE- 206 COURT ST CHILTON, WI SAMPLING DATE: MARCH 14, 2011 REPORT DATE: APRIL 4, 2011 EMC PROJECT NUMBER: PREPARED FOR: MR. JAY SHAMBEAU CALUMET COUNTY HIGHWAY FACILITY 206 COURT ST CHILTON, WI Prepared by/or under the direct supervision of: PREPARED BY: ENVIRONMENTAL MANAGEMENT CONSULTING, INC. W7748 COUNTY HIGHWAY V LAKE MILLS, WI DAVID A. SHERRARD INDUSTRIAL HYGIENIST David A. Sherrard, CIH Certified Industrial Hygienist

2 TABLE OF CONTENTS SECTION I INTRODUCTION SECTION II WORK SITE EVALUATION SECTION III METHODS/SURVEY STRATEGY - MONITORED OPERATIONS SECTION IV CONTROL LEVELS & STANDARDS SECTION V RESULT- DATA SUMMARY SECTION VI CONCLUSIONS/RECOMMENDATIONS SECTION VII APPENDICES - Appendix A Sample Data - Graphs - Appendix B Worker Documentation of Monitoring Results - Appendix C Floor Plans

3 SECTION I INTRODUCTION

4 INTRODUCTION Environmental Management Consulting, Inc. (EMC) was contacted by Calumet County Administration to conduct air monitoring/investigation related to possible indoor air quality issues at the County Highway Facility 206 Court St, Chilton, WI. The 1936 building was renovated and altered several times (two additions) in order to accommodate additional equipment and services. Concerns had developed regarding worker exposure to Carbon Monoxide (CO) and overall indoor air quality. In order to measure possible worker exposure to Carbon Monoxide, representative employees and locations were monitored for a complete shift. Office and garage staff exposures were measured. Additionally, continuous area data logging meters were placed to measure Carbon Monoxide, Carbon Dioxide, temperature and relative humidity for three (3) full days. This data was used to measure air exchange within each space. Samples were gathered under typical, representative work conditions March 14-17, Results were compared to Occupation Safety and Health Administration (OSHA) permissible exposure limits (PEL), American Conference of Governmental Industrial Hygienists (ACGIH) Threshold Limit Value (TLV), as well as ASHRAE standards for acceptable indoor air quality, where appropriate. Historical data was also provided which reflected measured CO levels during a snow event. Indoor vehicle preparations and staging during the snow event create a situation which was evaluated as a peak CO exposure. David A. Sherrard, CIH Certified Industrial Hygienist - EMC

5 SECTION II WORK SITE EVALUATION

6 SECTION II WORK SITE EVALUATION Work Site The Calumet County Highway Department is responsible for snow removal and general maintenance of Calumet County roads. At the Chilton facility, on-site mechanics service in-house equipment as well as other county vehicles (Police, transport cars, vans). The structure is a three level building with three large service bays. The facility was built in The Chilton staff distribution is as follows: office personnel (2), shop supervisors (2), mechanics (2), field personnel (9)

7 SECTION III METHODS/SURVEY STRATEGY

8 SAMPLING METHODS/SURVEY STRATEGY Personal sample collection was observed using TOXI Pro and Quest SL100 data logging Carbon Monoxide monitoring meters. These instruments measure CO TWA as specified by the American Council of Government Industrial Hygienists and OSHA. Devices were calibrated as recommended by each manufacturer Continuous monitoring for CO, CO2, relative humidity, and temperature was performed using TSI s Q trak. Each meter was calibrated as recommended by the manufacturer. Carbon Monoxide (CO) Sampling Equipment - Quest SafeLog 100 Single Gas Data Log Monitor - Sperian Toxipro CO Data Log Monitor Range: 0-999ppm Resolution: 1ppm Accuracy: ±0.5% Drift: <2% High Alarm: 200ppm Alarm STEL: 100ppm Alarm TWA: 35ppm Carbon Monoxide (CO), Carbon Dioxide, Relative Humidity, Temperature Sampling Equipment - TSI s Qtrak. Indoor air quality meter Model 7565 Data logging Real time display: CO, CO2, RH, Temp. Monitoring March 14-17, 2011 Continuous monitoring for CO, CO2, relative humidity, and temperature was performed in the office and garage area. Data was gathered for three (3) full days.

9 Representative employees were monitored in order to measure an accurate staff cross section. The following describes specific conditions present at the time of monitoring: March 14, 2011 Michelle Maas Administrative, Office Assistant Ms. Maas was monitored for Carbon Monoxide (CO) for the complete shift. Work conducted on the day of monitoring entailed secretarial work within the office. No specific PPE was noted. The forced air HVAC was operating (Heat). No special ventilation was noted. Mike Ottery Supervisor, Office Mr. Ottery was monitored for Carbon Monoxide for the complete shift. Work conducted on the day of monitoring entailed administrative work within the office area. No specific PPE was noted. The forced air system was operating (heat). No special ventilation was noted. Andy Fuhrmann Shop Supervisor Shop Mr. Fuhrman was monitored for Carbon Monoxide (CO) for the complete shift. Work conducted on the day of monitoring entailed supervising activities within the shop floor and shop office. No specific PPE was noted. The shop HVAC was operating. As vehicles were serviced in the shop area exhaust was captured and vented out of the area. Mike Gaskell Mechanic Shop Mr. Gaskell was monitored for Carbon Monoxide (CO) for the complete shift. Work conducted on the day of monitoring entailed mechanical vehicle service. No specific PPE was noted. The shop HVAC was operating. As vehicles were serviced in the shop area exhaust was captured and vented out of the area. Area Samples Work Bays In addition to representative personal sampling, area samples were gathered in each bay (two in the shop area). Doors separated each bay. Forced air HVAC units supplied heat to each bay as needed. Exhaust fans, though present in bay 1 were not operational. Ceiling fans circulated air in each shop area. Repair work was performed in the shop and bay 2. Vehicle washing was performed in bay 1 on the day of monitoring.

10 SECTION IV CONTROL LEVELS & STANDARDS

11 CONTROL LEVELS & STANDARDS Carbon Monoxide (CO) Carbon Monoxide OSHA PEL-50ppm ACGIH TLV-25ppm Carbon monoxide (CO) can be present from a source of incomplete combustion. Though OSHA Time Weighted Average (TWA) exposures are the only strictly enforceable regulations, the American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), World Health Organization )WHO) and Canadian residential IAQ guidelines establish the following indoor air quality CO guidelines: Carbon Monoxide ASHRHE WHO Canadian IAQ Guidelines Below 9 ppm Below 11ppm Below 11ppm Carbon Dioxide (CO 2 ) Carbon Dioxide measures are used as a tracers gas to determine air exchange and ventilation effectiveness within a building/area. Carbon Dioxide is generated by occupants and accumulates in an occupied area throughout a given period unless the area is properly ventilated. The ANSI/ASHRAE IAQ standard generally calls for cubic feet per minute per person (CFM/p) fresh air exchange. This equates to a Carbon Dioxide build up of ppm above outdoor levels. Outdoor CO 2 levels in Wisconsin typically range from Therefore poor air exchange within a given space is generally indicated by CO 2 build up in excess of 1200 ppm.

12 SECTION V RESULTS DATA SUMMARY

13 TABLE A-1 CALUMET COUNTY CARBON MONOXIDE - MARCH 14, 2011 Unit Personnel Job Compound Sample 8 Hour OSHA ACGIH Number Name/Area Description Monitored Period (min) Peak TWA PEL-ppm TLV-ppm S1 Michelle Maas/ Office Carbon Monoxide (CO) Office S2 Mike Ottery/ Office/Supervisor Carbon Monoxide (CO) Office S3 Andy Fuhrmann/ Shop Office Carbon Monoxide (CO) Shop S4 Mike Gaskell/ Shop Carbon Monoxide (CO) Shop S5 Storage West Wall Carbon Monoxide (CO) S6 Bay 2 Bench-West Carbon Monoxide (CO) SL-1 Shop Work Bench Carbon Monoxide (CO) SL-2 Shop East Wall Carbon Monoxide (CO) Key: PEL - Permissible Exposure Limit TLV - Threshold Limit Value STEL - Short Term Exposure Limit C-Ceiling Concentration no to be exceeded pmm - Parts per Million

14 TABLE A-2 CARBON MONOXIDE Sampling Date: February 7, 2011 Personnel 8 Hour OSHA ACGIH Sample Name/Area Compound Period TWA TWA TLV-ppm 1 Andy Fuhrmann Carbon Monoxide ppm 50 ppm 8 hours 25 ppm 8 hours Shop Supervisor 2 Josh Torrison / Shop Carbon Monoxide ppm 50 ppm 8 hours 25 ppm 8 hours 3 Mike Gaskell / Shop Carbon Monoxide ppm 50 ppm 8 hours 25 ppm 8 hours 4 Todd Schneider / Shop Carbon Monoxide ppm 25 ppm 8 hours 25 ppm 8 hours 5 Michelle Maas / Office Carbon Monoxide ppm 50 ppm 8 hours 25 ppm 8 hours 6 Mike Ottery / Supervisor Carbon Monoxide ppm 50 ppm 8 hours 25 ppm 8 hours 5-2 Shop Workbench Area Southwest Corner Carbon Monoxide ppm 25 ppm 8 hours 25 ppm 8 hours 8 Bay 2 Vechicle Storage North Wall Carbon Monoxide ppm 50 ppm 8 hours 25 ppm 8 hours 7 Bay 2 Vechicle South Wall Carbon Monoxide ppm 50 ppm 8 hours 25 ppm 8 hours

15 TABLE A-2 CARBON MONOXIDE Sampling Date: February 7, 2011 Personnel 8 Hour OSHA ACGIH Sample Name/Area Compound Period TWA TWA TLV-ppm 6-2 Compressor Room North Wall Carbon Monoxide ppm 50 ppm 8 hours 25 ppm 8 hours 9 Basement Break Room Carbon Monoxide ppm 50 ppm 8 hours 25 ppm 8 hours 1-2 Break Area Bay 1 Vechicle Storage Carbon Monoxide ppm 50 ppm 8 hours 25 ppm 8 hours 3-2 Bay 1 Break Area Vechicle Storage Carbon Monoxide ppm 50 ppm 8 hours 25 ppm 8 hours South Wall 8 Bay 3 Vechicle Storage (Cold) Carbon Monoxide ppm 50 ppm 8 hours 25 ppm 8 hours East Wall 10 General Office Area by Stairs Carbon Monoxide ppm 50 ppm 8 hours 25 ppm 8 hours Leading to Shop Area 7-2 Superintendents Office Carbon Monoxide ppm 50 ppm 8 hours 25 ppm 8 hours 9-2 Shop Supervisors Office / Carbon Monoxide ppm 50 ppm 8 hours 25 ppm 8 hours Parts Area 8-2 North East Wall Shop Area Carbon Monoxide ppm 50 ppm 8 hours 25 ppm 8 hours

16 TABLE A-2 CARBON MONOXIDE Sampling Date: February 7, 2011 Personnel 8 Hour OSHA ACGIH Sample Name/Area Compound Period TWA TWA TLV-ppm 10-2 Center Post 1st Bay North Shop Carbon Monoxide ppm 50 ppm 8 hours 25 ppm 8 hours 4-2 Welding Area Shop Carbon Monoxide ppm 50 ppm 8 hours 25 ppm 8 hours ppm - parts per million REL - Recommended Exposure Limit STEL - Short Term Excursion ppb - parts per billion PEL - Permissable Exposure Limit Limit or 15 minute Time BDL - Below analytical detection limit C - Ceiling limit not to be exceeded Weighted Average Exposure Limit NO - Not Applicable f/cc - fibers per cubic centimeter OEL - Occupational Exposure Limi NE - Not Established µg/ft2 - micrograms per square foot TWA - Time Weighted Average

17 TSI-QTRAK Sample Meter Location Analyte Time Average Peak CO Office- CO 2 March 14-17, Maas Work Area Temp RH CO Shop- CO 2 March 14-17, Bench Temp RH Key: PEL - Permissible Exposure Limit TLV - Threshold Limit Value STEL - Short Term Exposure Limit C-Ceiling Concentration no to be exceeded pmm - Parts per Million

18 SECTION VI CONCLUSIONS/RECOMMENDATIONS

19 CONCLUSIONS & RECOMMENDATIONS CONCLUSIONS Air monitoring results for the representative typical work day indicated Carbon Monoxide worker exposures below OSHA and ACGIH regulatory limits. Personal and area time weighted average results showed no measured exposure over 25 ppm for this session. However, peak exposures were shown elevated. Historical date also indicated worker exposures above OSHA and ACGIH limits where an increased work load/snow event occurs. Exposure are likely to be exceeded each time these events occur, using the in place work practices and controls. Weighing all the available data, workers are statistically likely to often exceed regulatory levels of CO exposure within the Calumet County Chilton Highway facility. Additionally, OSHA and ACGIH standards are established for the working population. Exposure criteria are concentrations to which nearly all workers may be repeatedly exposed for a working lifetime without adverse effects. ASHRAE standard ventilation for acceptable indoor air quality are based on protection of the general population with consideration of morbidity and exacerbation of existing health conditions. EMC recommends that the ASHRAE standard be observed in the office space, at a minimum. Using this criteria, elevated worker carbon monoxide exposures are experienced at a frequency that demands immediate attention. Continuous data gathered also indicates an inefficient air exchange within the garage and office spaces. Carbon dioxide accumulates during occupied times, and is slow to dissipate. This indicates poor introduction of outside air, and inefficient exchange. RECOMMENDATIONS In order to ensure a safe work environment the following minimum recommendations are offered: HVAC systems should be evaluated and recommendations implemented in the office space to ensure Carbon Monoxide cannot migrate into the office space. A proper balance of outside air within the area would create a positive pressure space and insure no CO infiltration. The garage space/work floor HVAC and/or work practices should also be evaluated to minimize the generation of indoor Carbon Monoxide and promote ventilation, once the gas is produced. Carbon Monoxide generating vehicles and equipment should not be run indoors un-ventilated for any extended time. The HVAC should be evaluated and upgrade to bring in enough outside air to maintain Carbon Monoxide exposures below regulatory limits.

20 SECTION VII APPENDICES

21 APPENDIX A - SAMPLE DATA - GRAPHS

22

23

24

25

26

27

28

29

30

31

32

33

34

35 TrackPro Report about:blank Page 1 of 1 4/13/2011 Test 001 Office Instrument Model VelociCalc/Q-Trak 7565 Meter S/N 7565X Probe Model 982 Probe S/N P Meter Cal Date 07/19/2010 CO2 Cal 07/23/2010 Temperature Cal 07/23/2010 Humidity Cal 07/23/2010 CO Cal 07/23/2010 Data Properties Start Date 03/13/2011 Start Time 18:08:16 Stop Date 03/16/2011 Stop Time 18:08:16 Total Time 3:00:00:00 Logging Interval 300 seconds Statistics CO2 T H CO Avg 877 ppm 74.8 deg F 24.4 %rh 2.3 ppm Max 1344 ppm 77.7 deg F 41.8 %rh 4.5 ppm Max Date 03/14/ /13/ /13/ /16/2011 Max Time 03:33:15 20:23:16 18:08:16 04:18:07 Min 596 ppm 61.7 deg F 20.0 %rh 0.6 ppm Min Date 03/16/ /13/ /13/ /15/2011 Min Time 16:53:05 18:08:16 20:23:16 18:43:09 TWA (8 hr) TWA Start Date 03/13/ /13/2011 TWA Start Time 18:08:16 18:08:16 TWA End Time 18:08:16 18:08:16

36

37 TrackPro Report about:blank Page 1 of 1 4/13/2011 Test 001 Test 001 Instrument Model VelociCalc/Q-Trak 7565 Meter S/N 7565X Probe Model 982 Probe S/N P Meter Cal Date 07/22/2010 CO2 Cal 07/26/2010 Temperature Cal 07/26/2010 Humidity Cal 07/26/2010 CO Cal 07/26/2010 Data Properties Start Date 03/14/2011 Start Time 06:35:49 Stop Date 03/17/2011 Stop Time 06:05:49 Total Time 2:23:30:00 Logging Interval 300 seconds Statistics CO2 T H CO Avg 822 ppm 67.6 deg F 31.5 %rh 2.5 ppm Max 1257 ppm 71.7 deg F 46.9 %rh 11.9 ppm Max Date 03/14/ /14/ /16/ /16/2011 Max Time 08:45:49 08:05:49 14:05:38 14:00:38 Min 553 ppm 54.0 deg F 18.8 %rh 0.0 ppm Min Date 03/14/ /14/ /14/ /14/2011 Min Time 07:25:49 07:25:49 08:05:49 06:35:49 TWA (8 hr) TWA Start Date 03/14/ /14/2011 TWA Start Time 06:35:49 06:35:49 TWA End Time 06:05:49 06:05:49

38 CO High, CO TWA Calumet CO - Shop East Wall 06:21:31 07:50:48 09:20:05 10:49:22 12:18:38 13:47:55 CO H Logged between 3/14/2011 6:20:31 AM and 3/14/2011 3:16:12 PM at 1 min intervals

39 Calumet County Shop East Wall SafeLog 100 Datalogging Gas Monitor FW Version: Serial Number: TRC Name: Company: Work Area: Area Shop - East Calument County Highway Department Shop East Wall Test #1 Sensor Type: CO Serial Number: 4CF Alarm Settings High: ppm Pre-Alarm High: N/A STEL: ppm Pre-Alarm Low: N/A TWA: 50.0 ppm Calibration History 60.0 ppm 2/28/2011 3:38:31PM Summary Information High: High STEL: Average: TWA: 9.0 ppm 3/14/2011 8:45:41AM 7.0 ppm 3/14/2011 8:52:31AM 4.0 ppm 5.0 ppm Page -1 of 1

40 12.0 Calumet County - Shop Work Bench CO High, CO TWA :20:14 07:49:04 09:17:54 10:46:45 12:15:35 13:44:25 Logged between 3/14/2011 6:19:14 AM and 3/14/2011 3:12:15 PM at 1 min intervals 0 CO High (ppm) CO TWA (ppm)

41 Calumet County Shop Work Bench SafeLog 100 Datalogging Gas Monitor FW Version: Serial Number: TRC Name: Company: Work Area: Area - Shop Calumet County Highway Department Shop - Work Bench Test #1 Sensor Type: CO Serial Number: 4CF Alarm Settings High: ppm Pre-Alarm High: N/A STEL: ppm Pre-Alarm Low: N/A TWA: 50.0 ppm Calibration History 60.0 ppm 2/28/2011 3:33:56PM Summary Information High: High STEL: Average: TWA: 12.0 ppm3/14/2011 9:45:09AM 9.0 ppm 3/14/2011 9:56:14AM 5.0 ppm 5.0 ppm Page -1 of 1

42 APPENDIX B WORKER DOCUMENTATION OF MONITORING RESULTS

43 DOCUMENTATION OF EXPOSURE MONITORING RESULTS CONSULTATION Date Monitored: March 14, 2011 Employee Monitored: Operation Monitored: Building: Name of Contaminant: Michelle Maas Office Assistant Office Carbon Monoxide Result Compound Monitored TWA PEAK OSHA PEL ACGIH TLV Carbon Monoxide (CO) 4 ppm 13ppm 50 ppm 25 ppm Report Explained By: Signature: Safety Representative Employee Date Explained: TWA Time Weighted Average OSHA Occupational Safety & Health Administration

44 DOCUMENTATION OF EXPOSURE MONITORING RESULTS CONSULTATION Date Monitored: March 14, 2011 Employee Monitored: Operation Monitored: Building: Name of Contaminant: Mike Ottery Supervisor Office Carbon Monoxide Result Compound Monitored TWA PEAK OSHA PEL ACGIH TLV Carbon Monoxide (CO) 4ppm 15ppm 50 ppm 25 ppm Report Explained By: Signature: Safety Representative Employee Date Explained: TWA Time Weighted Average OSHA Occupational Safety & Health Administration

45 DOCUMENTATION OF EXPOSURE MONITORING RESULTS CONSULTATION Date Monitored: March 14, 2011 Employee Monitored: Operation Monitored: Building: Name of Contaminant: Andy Fuhrmann Shop Supervisor Shop Carbon Monoxide Result Compound Monitored TWA PEAK OSHA PEL ACGIH TLV Carbon Monoxide (CO) 7ppm 25ppm 50 ppm 25 ppm Report Explained By: Signature: Safety Representative Employee Date Explained: TWA Time Weighted Average OSHA Occupational Safety & Health Administration

46 DOCUMENTATION OF EXPOSURE MONITORING RESULTS CONSULTATION Date Monitored: March 14, 2011 Employee Monitored: Operation Monitored: Building: Name of Contaminant: Mike Gaskell Mechanic Shop Carbon Monoxide Result Compound Monitored TWA PEAK OSHA PEL ACGIH TLV Carbon Monoxide (CO) 5 ppm 19ppm 50 ppm 25 ppm Report Explained By: Signature: Safety Representative Employee Date Explained: TWA Time Weighted Average OSHA Occupational Safety & Health Administration

47 APPENDIX C - FLOOR PLAN

48

Indoor Air Quality Assessments during Renovations at Waverly Elementary School Project #J (January 4, 12, 15, 25 and 29, 2018)

Indoor Air Quality Assessments during Renovations at Waverly Elementary School Project #J (January 4, 12, 15, 25 and 29, 2018) March 29, 2018 Mr. Jeff Klenk Howard County Public School System (HCPSS) 10910 Route 108 Ellicott City, MD 21043 RE: Indoor Air Quality Assessments during Renovations at Waverly Elementary School Project

More information

Visible emissions were not observed in the school in the vicinity of the construction containment.

Visible emissions were not observed in the school in the vicinity of the construction containment. June 22, 2018 To: Waverly Elementary School From: Christopher Madden, CIH Indoor Environmental Quality Manager Re: Indoor Air Quality Testing During Renovations - May As Waverly Elementary School is currently

More information

Visible emissions were not observed in the school in the vicinity of the construction containment.

Visible emissions were not observed in the school in the vicinity of the construction containment. April 23, 2018 To: Waverly Elementary School From: Christopher Madden, CIH Indoor Environmental Quality Manager Re: Indoor Air Quality Testing During Renovations - March As Waverly Elementary School is

More information

BREATHE A LITTLE EASIER WITH TSI

BREATHE A LITTLE EASIER WITH TSI BREATHE A LITTLE EASIER WITH TSI PROFESSIONAL MEASUREMENT SOLUTIONS THAT HELP YOU SAVE ENERGY, INCREASE OCCUPANT COMFORT AND ASSURE A HEALTHY ENVIRONMENT Indoor air quality (IAQ) is a growing concern.

More information

Monitoring & Oversight Activities Conducted During Lead Remediation of Elevator Structure Located at Carlsbad Caverns National Park

Monitoring & Oversight Activities Conducted During Lead Remediation of Elevator Structure Located at Carlsbad Caverns National Park Monitoring & Oversight Activities Conducted During Lead Remediation of Elevator Structure Located at Carlsbad Caverns National Park James Lieberman, CIH Environmental Information Services jlieberman@eis1.us

More information

THE LEADER IN PERFORMANCE INDOOR AIR QUALITY MEASUREMENTS

THE LEADER IN PERFORMANCE INDOOR AIR QUALITY MEASUREMENTS THE LEADER IN PERFORMANCE INDOOR AIR QUALITY MEASUREMENTS INDOOR AIR QUALITY INSTRUMENTS UNDERSTANDING, ACCELERATED BREATHE A LITTLE EASIER WITH TSI Indoor air quality is a growing concern. With the increasing

More information

October 31, Colorado State Judicial Branch 101 West Colfax Avenue, Suite 500 Denver, Colorado 80202

October 31, Colorado State Judicial Branch 101 West Colfax Avenue, Suite 500 Denver, Colorado 80202 October 31, 2017 Colorado State Judicial Branch 101 West Colfax Avenue, Suite 500 Denver, Colorado 80202 Attention: Subject: John Gossett Air Quality Assessment Archuleta District Court Pagosa Springs,

More information

January 20, Mr. Marty Foutch Facilities Director Bixby Public Schools 109 N. Armstrong Bixby, OK 74008

January 20, Mr. Marty Foutch Facilities Director Bixby Public Schools 109 N. Armstrong Bixby, OK 74008 January 0, 0 Mr. Marty Foutch Facilities Director Bixby Public Schools 09 N. Armstrong Bixby, OK 0 RE: Bixby th, th, and 6 th Elementary Indoor Air Quality CO and % Liberty OHM File Number 0-09 Dear Mr.

More information

Temperature, Relative Humidity, and Carbon Dioxide Data Logging Report. Franklin High School Rooms 104, 109, 115, 120, East Fourth Street

Temperature, Relative Humidity, and Carbon Dioxide Data Logging Report. Franklin High School Rooms 104, 109, 115, 120, East Fourth Street Cincinnati 3959 Fulton Grove Rd Cincinnati, Ohio 45245 (513) 752-9111 (513) 752-7973 (Fax) Cleveland 1667 E. 40th Street Loftworks Building, Suite 1G2 Cleveland, Ohio 44103 (216) 916-7378 (513) 752-7973

More information

Re: Casey Middle School at 1301 High Street in Boulder, Colorado Follow-Up Indoor Air Quality Monitoring (Hydrogen Sulfide)

Re: Casey Middle School at 1301 High Street in Boulder, Colorado Follow-Up Indoor Air Quality Monitoring (Hydrogen Sulfide) April 16, 2014 Mike Cuskelly Boulder Valley School District 6500 Arapahoe, P.O. Box 9011 Boulder, CO 80301 Re: Casey Middle School at 1301 High Street in Boulder, Colorado 80304 Follow-Up Indoor Air Quality

More information

Introduction. IAQ - 5 School Building Summary 2009

Introduction. IAQ - 5 School Building Summary 2009 Introduction Vortex Inc. was contracted by Ed Collins, [Facilities Director with the Middletown School Dept.] to provide Indoor Air Quality (IAQ) testing within the five (5) school buildings while they

More information

The Leader in Performance Indoor Air Quality Measurements

The Leader in Performance Indoor Air Quality Measurements The Leader in Performance Indoor Air Quality Measurements ENERGY AND COMFORT TRUST. SCIENCE. INNOVATION. Breathe a Little Easier with TSI Indoor air quality is a growing concern. With the increasing amount

More information

The Leader in Performance Indoor Air Quality Measurements

The Leader in Performance Indoor Air Quality Measurements The Leader in Performance Indoor Air Quality Measurements ENERGY AND COMFORT TRUST. SCIENCE. INNOVATION. Breathe a Little Easier with TSI Indoor air quality is a growing concern. With the increasing amount

More information

Background Information

Background Information March 11, 2014 DRAFT Colin Morrison Boulder Valley School District 6500 Arapahoe, P.O. Box 9011 Boulder, CO 80301 Re: Casey Middle School at 1301 High Street in Boulder, Colorado 80304 Indoor Air Quality

More information

1204 North Road (Rt. 117) Groton, Connecticut 06340

1204 North Road (Rt. 117) Groton, Connecticut 06340 FTP Construction A nil 2014 Communications (24 hours): website: www.mysticair.com e-mail: maqc2 @ aol.com Office: (860) 449-8903 FAX: (860) 449-8860 Toll Free: 1 (800) 247-7746 monoxide, carbon dioxide,

More information

INDOOR AIR QUALITY PROGRAM

INDOOR AIR QUALITY PROGRAM INDOOR AIR QUALITY PROGRAM (Adopted from California State University Office of the Chancellor s Sample IAQ Program) 1 TABLE OF CONTENTS Page 1.0 REGULATORY AUTHORITY.........................................

More information

FINAL Occupational Hygiene Lead Monitoring Survey The Recreation Association 2451 Riverside Drive, Ottawa, Ontario

FINAL Occupational Hygiene Lead Monitoring Survey The Recreation Association 2451 Riverside Drive, Ottawa, Ontario Occupational Hygiene Lead Monitoring Survey 2451 Riverside Drive, Ottawa, Ontario Prepared for: 2451 Riverside Drive Ottawa, ON K1H 7X7 Attn: Ross Rankin Director, Facility and Property Services November

More information

Illinois Department of Public Health Guidelines for Indoor Air Quality

Illinois Department of Public Health Guidelines for Indoor Air Quality Page 1 of 8 Illinois Department of Public Health Guidelines for Indoor Air Quality Awareness of indoor air quality issues continues to increase throughout Illinois and the country. Studies conducted by

More information

TN Tatem Middle School Indoor Air Quality Assessment September 2016

TN Tatem Middle School Indoor Air Quality Assessment September 2016 TN Tatem Middle School Indoor Air Quality Assessment September 2016 Completed by Island Air Quality Services P.O. Box SN139 Southampton SNBX Bermuda Table of Contents 1 Report Summary... 1 2 Introduction

More information

AIR QUALITY ENGINEERING M66V HEXAVALENT CHROMIUM TESTING M66V: 2HP with B.I. Blower: with 95% DOP Installed with UPGRADED SEAL JUNE 25, 2011

AIR QUALITY ENGINEERING M66V HEXAVALENT CHROMIUM TESTING M66V: 2HP with B.I. Blower: with 95% DOP Installed with UPGRADED SEAL JUNE 25, 2011 AIR QUALITY ENGINEERING M66V HEXAVALENT CHROMIUM TESTING M66V: 2HP with B.I. Blower: with 95% DOP Installed with UPGRADED SEAL JUNE 25, 2011 INTRODUCTION Hamlin & Harris, Incorporated (H&H) conducted Industrial

More information

Measuring Indoor Air Quality presented to AAFAME Members Nov. 14, 2017

Measuring Indoor Air Quality presented to AAFAME Members Nov. 14, 2017 Measuring Indoor Air Quality presented to AAFAME Members Nov. 14, 2017 What is Indoor Air Quality? Appropriate IAQ can be defined as a function of three different components: 1) appropriate thermal comfort,

More information

TEXAS FACILITIES COMMISSION Edit Date: 4/13/2012 ARCHITECTURAL/ENGINEERING GUIDELINES

TEXAS FACILITIES COMMISSION Edit Date: 4/13/2012 ARCHITECTURAL/ENGINEERING GUIDELINES General The following guidelines must be met by both the Architect/Engineer (A/E) consultant and the contractor to assure indoor air quality of the building being provided. At the direction of the Project

More information

Chapter 14 Indoor Air Quality

Chapter 14 Indoor Air Quality Chapter 14 Indoor Air Quality 1 Indoor Environment and Built Environment Buildings Transportations vehicles 2 1 Indoor Air Quality (IAQ) Indoor air quality (IAQ) is the quality of air in an indoor environment.

More information

Indoor Air Quality Program

Indoor Air Quality Program Indoor Air Quality Program Table of Contents I. Program Goals and Objectives... 2 II. Scope and Application... 2 III. Definitions... 2 IV. Responsibilities... 2 V. Reporting Procedures... 3 VI. Investigation

More information

VENTILATION REQUIREMENTS IN A RETAIL STORE

VENTILATION REQUIREMENTS IN A RETAIL STORE - VENTILATION REQUIREMENTS IN A RETAIL STORE D.T. Grimsrud, B.B. Bridges, N.G. Carlson, D.E. Hadlich University of Minnesot~ USA ABSTRACT This field study was organized to determine the ventilation required

More information

Background Air Sampling Auburn Village School, New Modular Classrooms SLGL File Number

Background Air Sampling Auburn Village School, New Modular Classrooms SLGL File Number March 20, 2014 Mr. Peter Barbuto, Director of Maintenance School Administrative Unit No. 15 Hooksett School District 90 Farmer Road Hooksett, New Hampshire 03106 Re: Background Air Sampling Auburn Village

More information

Weekly Air Monitoring Report August 23, 2010 Hangar 1 Remedial Action, Moffett Field, California Contract N D

Weekly Air Monitoring Report August 23, 2010 Hangar 1 Remedial Action, Moffett Field, California Contract N D Weekly Air Monitoring Report August 23, 2010 Hangar 1 Remedial Action, Contract N62473-08-D-8816-0005 This report summarizes the air monitoring activities performed as part of the Non-Time Critical Removal

More information

Environment. Indoor Air Quality and Ventilation in Photographic Processing Facilities. Kodak s health, safety, and environmental

Environment. Indoor Air Quality and Ventilation in Photographic Processing Facilities. Kodak s health, safety, and environmental Environment I N F O R M A T I O N F R O M K O D A K Indoor Air Quality and Ventilation in Photographic Processing Facilities J-314(ENG) $10.00 Kodak s health, safety, INTRODUCTION The Occupational Safety

More information

DUQUESNE UNIVERSITY ASBESTOS MANAGEMENT PROGRAM

DUQUESNE UNIVERSITY ASBESTOS MANAGEMENT PROGRAM DUQUESNE UNIVERSITY ASBESTOS MANAGEMENT PROGRAM Revised January 2017 Prepared by: Environmental Health and Safety Department TABLE OF CONTENTS Page Purpose 1 Scope 2 Definitions 2 Responsibilities 3 Hazard

More information

INDOOR AIR QUALITY ASSESSMENT

INDOOR AIR QUALITY ASSESSMENT INDOOR AIR QUALITY ASSESSMENT Biddeford Intermediate School Biddeford Primary School JFK Memorial Kindergarten Center Biddeford High School Air Quality Management Services, Inc. PREPARED FOR Biddeford

More information

CASE STUDY. Improved Radon Needs More Air

CASE STUDY. Improved Radon Needs More Air FOR MORE INFORMATION, VISIT: HTTP://BUILDEQUINOX.COM/BLACKBOX/ CASE STUDY Improved Radon Needs More The subject of this test is a well maintained home occupied by a family of four (two adults and two children).

More information

IAQ Workshop. Assessing Common IAQ Contaminants and Ventilation Systems. Dru Sahai

IAQ Workshop. Assessing Common IAQ Contaminants and Ventilation Systems. Dru Sahai IAQ Workshop Assessing Common IAQ Contaminants and Ventilation Systems Dru Sahai Public Health Ontario Indoor air quality workshop CIPHI National Meeting Winnipeg, MB June 22, 2013 Outline Introduction

More information

Industrial Hygiene for the Telecommunications Professional. John Malone, CSP, CIH Senior Safety Manager

Industrial Hygiene for the Telecommunications Professional. John Malone, CSP, CIH Senior Safety Manager Industrial Hygiene for the Telecommunications Professional John Malone, CSP, CIH Senior Safety Manager Objective Provide information that will enable you to decide how to proceed with Industrial Hygiene

More information

OSHA Act of 1970 Section 5(a)(1) Duties, as may be amended.

OSHA Act of 1970 Section 5(a)(1) Duties, as may be amended. TO: FROM: PREPARED BY: SUBJECT: PPM #: ALL COUNTY PERSONNEL VERDENIA C. BAKER COUNTY ADMINISTRATOR RISK MANAGEMENT INDOOR AIR QUALITY (IAQ) PROGRAM CW-L-037 ====================================================================

More information

MATERIAL SAFETY DATA SHEET

MATERIAL SAFETY DATA SHEET MATERIAL SAFETY DATA SHEET SECTION 1 - CHEMICAL PRODUCT AND COMPANY IDENTIFICATION Product Name: Chemical Name: Product Use/Class: Company Information: M-Guard V-11 Adhesive Adhesive Premium Clear Thin

More information

Exposure Hazards in Oil and Gas Extraction Workers: Flowback and Production Testing (Completions Operations)

Exposure Hazards in Oil and Gas Extraction Workers: Flowback and Production Testing (Completions Operations) Exposure Hazards in Oil and Gas Extraction Workers: Flowback and Production Testing (Completions Operations) Bradley King, PhD, MPH, CIH NIOSH Western States Office WestON September 12, 2014 Golden, CO

More information

April 21, Dear Mike,

April 21, Dear Mike, AECOM 1555 North RiverCenter Drive Suite 214 Milwaukee, Wisconsin 53212 414.944.6080 tel 414.944.6081 fax April 21, 2015 Mr. Michael Lewis, P.E. City of West Allis Department of Public Works/City Engineer

More information

Case Study Leaky Single Story High Radon

Case Study Leaky Single Story High Radon Case Study Leaky Single Story High Radon How can a home be leaky with a lot of infiltrated air passing through have high radon? The answer lies in the nature of the building leakage. Infiltrated air, what

More information

Material Safety Data Sheet

Material Safety Data Sheet Material Safety Data Sheet Section 1 General Information Manufacturer: Zinsser Company, Inc. 173 Belmont Drive Somerset, NJ 08875 (732) 469-8100 Emergency Telephone: Chemtrec (800) 424-9300 Date: July

More information

ASHRAE Standard INTRODUCTION AND OVERVIEW Plus a few other issues: Outdoor Air Quality and the IAQ Procedure

ASHRAE Standard INTRODUCTION AND OVERVIEW Plus a few other issues: Outdoor Air Quality and the IAQ Procedure ASHRAE Standard 62.1-2004 INTRODUCTION AND OVERVIEW Plus a few other issues: Outdoor Air Quality and the IAQ Procedure Andy Persily ASHRAE Fellow National Institute of Standards and Technology ASHRAE Winter

More information

MANAGING RISK IN THE WORKPLACE WELDING FUME CONTROL AN INDUSTRIAL HYGIENE GUIDE

MANAGING RISK IN THE WORKPLACE WELDING FUME CONTROL AN INDUSTRIAL HYGIENE GUIDE MANAGING RISK IN THE WORKPLACE WELDING FUME CONTROL AN INDUSTRIAL HYGIENE GUIDE OCCUPATIONAL HEALTH & SAFETY ADMINISTRATION STANDARD The Occupational Safety and Health Administration (OSHA) promulgated

More information

Indoor Air Quality and Mechanical Ventilation (Page 1 of 5)

Indoor Air Quality and Mechanical Ventilation (Page 1 of 5) Indoor Air Quality and Mechanical Ventilation (Page 1 of 5) Title 24, Part 6, Section 150.0(o) Ventilation for Indoor Air Quality. All dwelling units shall meet the requirements of ANSI/ASHRAE Standard62.2.

More information

SAN BERNARDINO COMMUNITY COLLEGE DISTRICT FOR CRAFTON HILLS COLLEGE

SAN BERNARDINO COMMUNITY COLLEGE DISTRICT FOR CRAFTON HILLS COLLEGE October 4, 2016 Michael Strong Vice President of Administrative Services SAN BERNARDINO COMMUNITY COLLEGE DISTRICT FOR CRAFTON HILLS COLLEGE 114 South Del Rosa Drive San Bernardino, California 92408 Re:

More information

Indoor Air Quality (IAQ) Requirements

Indoor Air Quality (IAQ) Requirements University of New Hampshire University of New Hampshire Scholars' Repository Division 01 General Requirements Chapter 5 Technical Construction and Renovation Standards 1-25-2013 013560 - Indoor Air Quality

More information

CO2 transmitters. Introduction 44. CO 2 transmitters 45. CO 2 and temperature transmitters 46. CO 2 transmitters for special applications 47-48

CO2 transmitters. Introduction 44. CO 2 transmitters 45. CO 2 and temperature transmitters 46. CO 2 transmitters for special applications 47-48 Introduction 44 CO 2 transmitters 45 CO 2 and temperature transmitters 46 CO 2 transmitters for special applications 47-48 43 Fundamentals of CO2 Carbon dioxide (CO2) is a colorless and odorless gas that

More information

Energy Savings Audit

Energy Savings Audit Energy Savings Audit PREPARED FOR Steve Bennett Eileen Horn City of Lawrence ASSESSMENT SITE City of Lawrence Arts Center 940 new Hampshire St. Lawrence, KS 66044 ASSESSMENT PERFORMED BY P1 Group Inc 16210

More information

Glossary. CARCINOGEN - A substance or physical agent that may cause cancer in animals or humans.

Glossary. CARCINOGEN - A substance or physical agent that may cause cancer in animals or humans. Glossary ACGIH - The American Conference of Governmental Industrial Hygienists is a voluntary membership organization of professional industrial hygiene personnel in governmental or educational institutions.

More information

Material Safety Data Sheet

Material Safety Data Sheet Material Safety Data Sheet Section 1 General Information Manufacturer: HMIS Rating Zinsser Company, Inc. HEALTH: 1 173 Belmont Drive FLAMMABILITY: 0 Somerset, NJ 08875 REACTIVITY: 0 (732) 469-8100 Emergency

More information

INDOOR AIR QUALITY TESTING AT CARLISLE COUNTY ELEMENTARY SCHOOL

INDOOR AIR QUALITY TESTING AT CARLISLE COUNTY ELEMENTARY SCHOOL INDOOR AIR QUALITY TESTING AT CARLISLE COUNTY ELEMENTARY SCHOOL For: Keith Shoulders Carlisle County Schools 4557 State Route 1377 Bardwell, Kentucky 42023 Testing Performed By: Christopher K. Adkins Air

More information

SECTION 1 - CHEMICAL PRODUCT AND COMPANY IDENTIFICATION. Rubber Floor Tile / Stair Treads / Risers / Wall Base

SECTION 1 - CHEMICAL PRODUCT AND COMPANY IDENTIFICATION. Rubber Floor Tile / Stair Treads / Risers / Wall Base PRODUCT DATA SHEET SECTION 1 - CHEMICAL PRODUCT AND COMPANY IDENTIFICATION Product Name: Chemical Name: Product Use/Class: Company Information: Mannington Rubber Floor Tile / Stair Treads / Risers / Wall

More information

Industrial Hygiene. Introduction to Industrial Hygiene ENVIRONMENTAL SCIENCE

Industrial Hygiene. Introduction to Industrial Hygiene ENVIRONMENTAL SCIENCE Introduction to Industrial Hygiene Environmental Safety and Health ENVIRONMENTAL SCIENCE is the study of how the parts of nature and human societies operate and interact. is devoted to the control of biological,

More information

Material Safety Data Sheet

Material Safety Data Sheet Material Safety Data Sheet Section 1 General Information Manufacturer: HMIS Rating William Zinsser and Company, Inc. HEALTH: 1 173 Belmont Drive FLAMMABILITY: 0 Somerset, NJ 08875 REACTIVITY: 0 (732) 469-8100

More information

Material Safety Data Sheet

Material Safety Data Sheet Material Safety Data Sheet Section 1 General Information Manufacturer: Rust-Oleum Corporation 11 Hawthorn Parkway Vernon Hills, IL 60061 24 Hour Assistance: 1-847-367-7700 www.rustoleum.com DATE: June

More information

A. The project is intended to achieve LEED Certification at the Silver Level per the U.S. Green Building Council LEED for Schools 2007 rating system.

A. The project is intended to achieve LEED Certification at the Silver Level per the U.S. Green Building Council LEED for Schools 2007 rating system. SECTION 23 01 01 HVAC LEED REQUIREMENTS PART 1 -GENERAL 1.1 WORK INCLUDES A. Compliance with LEED project requirements. B. Coordination of LEED construction phase activities. C. Data gathering of construction

More information

MATERIAL SAFETY DATA SHEET

MATERIAL SAFETY DATA SHEET MATERIAL SAFETY DATA SHEET SECTION 1 - CHEMICAL PRODUCT AND COMPANY IDENTIFICATION Product Name: Mannington M-Guard Ultra Premium Commercial Carpet Adhesive Chemical Name: Synthetic Resin Emulsion Product

More information

Shannon Horn P.E., AHJ, LEED A.P. Timothy Lockhart CIH, CHMM

Shannon Horn P.E., AHJ, LEED A.P. Timothy Lockhart CIH, CHMM Shannon Horn P.E., AHJ, LEED A.P. Timothy Lockhart CIH, CHMM Participants will be able to: 1. Provide a convincing argument to Authorities Having Jurisdiction (AHJ) and Environmental Health and Safety

More information

MONITORING OF INDOOR AIR QUALITY FOR IMPROVEMENT OF SAFETY AND HEALTH FACTOR TOWARDS SUSTAINABLE WORK ENVIRONMENT IN INDUSTRY

MONITORING OF INDOOR AIR QUALITY FOR IMPROVEMENT OF SAFETY AND HEALTH FACTOR TOWARDS SUSTAINABLE WORK ENVIRONMENT IN INDUSTRY MONITORING OF INDOOR AIR QUALITY FOR IMPROVEMENT OF SAFETY AND HEALTH FACTOR TOWARDS SUSTAINABLE WORK ENVIRONMENT IN INDUSTRY A. M. Leman 1, A. R. Omar 2,A. Husain 1, M.A. Halmi 1, N.M. Adam 3, and M.Z.M.

More information

Material Safety Data Sheet

Material Safety Data Sheet Material Safety Data Sheet Section 1 General Information Manufacturer: Rust-Oleum Corporation 11 Hawthorn Parkway Vernon Hills, IL 60061 24 Hour Assistance: 1-847-367-7700 www.rustoleum.com Date: May 5,

More information

NORTH DAKOTA DEPARTMENT OF TRANSPORTATION REQUEST FOR PROPOSAL ASBESTOS AIR MONITORING SERVICES

NORTH DAKOTA DEPARTMENT OF TRANSPORTATION REQUEST FOR PROPOSAL ASBESTOS AIR MONITORING SERVICES NORTH DAKOTA DEPARTMENT OF TRANSPORTATION REQUEST FOR PROPOSAL ASBESTOS AIR MONITORING SERVICES September 12, 2008 INTRODUCTION North Dakota Department of Transportation (NDDOT) is seeking an asbestos

More information

How We Obtained LEED Certification pertaining to the Indoor Environmental Quality Category. Ron Fields, CAFS, NCT General Dynamics C4 Systems

How We Obtained LEED Certification pertaining to the Indoor Environmental Quality Category. Ron Fields, CAFS, NCT General Dynamics C4 Systems How We Obtained LEED Certification pertaining to the Indoor Environmental Quality Category Ron Fields, CAFS, NCT General Dynamics C4 Systems Outline What is LEED EB? GD LEED Costs and savings IEQ Prerequisites

More information

360-INDOOR AIR QUALITY PROGRAM

360-INDOOR AIR QUALITY PROGRAM 360.1 PURPOSE A. To help ensure employees and students at Central New Mexico Community College (CNM) are provided a workplace free of recognized indoor air quality hazards. 360.2 SCOPE A. CNM recognizes

More information

Material Safety Data Sheet

Material Safety Data Sheet Material Safety Data Sheet Section 1 General Information Manufacturer: HMIS Rating William Zinsser and Company, Inc. HEALTH: 1 173 Belmont Drive FLAMMABILITY: 0 Somerset, NJ 08875 REACTIVITY: 0 (732) 469-8100

More information

Mechanical vs. Natural Ventilation in Schools: Less Can Be More

Mechanical vs. Natural Ventilation in Schools: Less Can Be More Mechanical vs. Natural Ventilation in Schools: Less Can Be More Brad Stanley Purafil, Inc. Seminar 5 -Natural Ventilation in Schools: Boon or Bust? ASHRAE Annual Meeting Long Beach, California June 24-27,

More information

Indoor Air Quality Solutions

Indoor Air Quality Solutions Indoor Air Quality Solutions Ultimate Solutions for Indoor Air Quality Investigation Demand for quality indoor air continues to increase as we are spending more time indoors than ever before. Indoor air

More information

6.1 INTRODUCTION 6.2 REGULATORY FRAMEWORK NATIONAL AMBIENT AIR QUALITY STANDARDS COMPLIANCE STATUS TRANSPORTATION CONFORMITY

6.1 INTRODUCTION 6.2 REGULATORY FRAMEWORK NATIONAL AMBIENT AIR QUALITY STANDARDS COMPLIANCE STATUS TRANSPORTATION CONFORMITY Chapter 6 Air Quality 6.1 INTRODUCTION This chapter presents a project-level analysis of the potential for air quality impacts that could result from mobile and stationary sources of air emissions generated

More information

Washington State Department of Health Division of Environmental Health

Washington State Department of Health Division of Environmental Health Washington State Department of Health Division of Environmental Health School Indoor Air Quality Monitoring Project Washington Resource Conservation Manager (RCM) Meeting July 19, 2007 Washington Middle

More information

Demand Controlled Ventilation. A Detailed Study of Energy Usage by Simulation

Demand Controlled Ventilation. A Detailed Study of Energy Usage by Simulation Demand Controlled Ventilation. A Detailed Study of Energy Usage by Simulation B.R. Sørensen Narvik University College, Building Science, NO-8514 Narvik, Norway, e-mail: brs@hin.no ABSTRACT Detailed mathematical

More information

Good indoor air quality (IAQ) management has become paramount in the construction industry as study

Good indoor air quality (IAQ) management has become paramount in the construction industry as study Creating and Maintaining Good Indoor Air Quality Good indoor air quality (IAQ) management has become paramount in the construction industry as study after study shows that employee productivity and health

More information

FANROOMLESS VENTILATION SYSTEM FOR AN UNDERGROUND PARKING LOT

FANROOMLESS VENTILATION SYSTEM FOR AN UNDERGROUND PARKING LOT FANROOMLESS VENTILATION SYSTEM FOR AN UNDERGROUND PARKING LOT Eon Ku Rhee 1, Seong Hwan Yi 2,* 1Ph.D. Professor of Architecture, Chung-Ang University, Seoul, Korea 2 Ph.D. Candidate of Architecture, Chung-Ang

More information

MATERIAL SAFETY DATA SHEET

MATERIAL SAFETY DATA SHEET SECTION 1 GENERAL INFORMATION Manufacturer: HMIS Rating Modern Masters Inc. HEALTH 1 9380 San Fernando Road FLAMMABILITY 0 Sun Valley, California 91352 REACTIVITY 0 818-683-0201 Emergency Telephone: 800-942-3166

More information

Material Safety Data Sheet

Material Safety Data Sheet Material Safety Data Sheet Section 1 General Information Manufacturer: Rust-Oleum Corporation 11 Hawthorn Parkway Vernon Hills, IL 60061 24 Hour Assistance: 1-847-367-7700 www.rustoleum.com Date: April

More information

Meet today s webinar team

Meet today s webinar team Meet today s webinar team Presenter: Al Capps Al is a professional engineer with over 5 years experience in workplace safety. He holds a bachelor s in chemical engineering from The University of Texas.

More information

MATERIAL SAFETY DATA SHEET

MATERIAL SAFETY DATA SHEET SECTION 1 GENERAL INFORMATION Manufacturer: HMIS Rating Modern Masters, Inc. HEALTH 1 9380 San Fernando Road, FLAMMABILITY 0 Sun Valley, California 91352 REACTIVITY 0 818-683-0201 Emergency Telephone:

More information

On April 23, 2012, KCI industrial hygienist Josh Julius met with Mr. Ben Locke to discuss these and other potential exposures.

On April 23, 2012, KCI industrial hygienist Josh Julius met with Mr. Ben Locke to discuss these and other potential exposures. E NGINEERS P LANNERS S CIENTISTS C ONSTRUCTION M ANAGERS 936 RIDGEBROOK ROAD SPARKS, MD 21152 410-316-7800 (FAX) 410-316-7935 May 10, 2012 Ms. Denelle Bowser Environmental Health and Safety Manager Maryland

More information

MATERIAL SAFETY DATA SHEET

MATERIAL SAFETY DATA SHEET SECTION 1 GENERAL INFORMATION Manufacturer: HMIS Rating Modern Masters, Inc. HEALTH 1 13201 Saticoy Street, FLAMMABILITY 0 North Hollywood, California 91605 REACTIVITY 0 818-765-2915 Emergency Telephone:

More information

Indoor Air Quality Tools for Schools

Indoor Air Quality Tools for Schools CT School Indoor Environment Resource Team 2nd Training Session: Walkthrough Investigations Indoor Air Quality Tools for Schools Agenda: Welcome, Introductions Show and Tell: Presentation of Blueprints,

More information

Civil Engineering Research Exchange Symposium Session I STRUCTURES AND MATERIALS

Civil Engineering Research Exchange Symposium Session I STRUCTURES AND MATERIALS Session I STRUCTURES AND MATERIALS 1 Indoor Air quality and human activities in buildings Perera T.M. 1,*, Jayasinghe C. 2, Perera S.A.S 3, Rajapaksa S.W. 4 Abstract People spend most of their time indoors

More information

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma LEED Green Building Certification The purpose of the LEED Green Building Rating is to provide a national standard that aims to improve environmental, health and economic performance of buildings using

More information

Material Safety Data Sheet

Material Safety Data Sheet Material Safety Data Sheet Section 1 General Information Manufacturer: Zinsser Company, Inc. 173 Belmont Drive Somerset, NJ 08875 (732) 469-8100 Emergency Telephone: Chemtrec (800) 424-9300 Date: February

More information

Indoor Air Quality Report

Indoor Air Quality Report Indoor Air Quality Report Test Number: Normal Occupancy Name: Equinox Email address: test@buildequinox.com Test Location: Urbana, IL Report Date: 12/20/2012 Overview: This Black Box IAQ report provides

More information

Machine Dishwasher Detergent Powder with Rinse Aid Regular Strength

Machine Dishwasher Detergent Powder with Rinse Aid Regular Strength Page 1 of 5 Phoenix Brands Consumer Service Telephone Number: 1-866-794-0800 1437 West Morris Street Emergency Contact: PROSAR IPC Indianapolis, Indiana 46221 USA Emergency Phone Number: 1-866-794-0800

More information

CLASS I AND II ABATEMENT PROJECT SUBMITTALS

CLASS I AND II ABATEMENT PROJECT SUBMITTALS 5.1 Pre-Work Submittals CLASS I AND II ABATEMENT PROJECT SUBMITTALS Abatement contractors shall submit the following in a bound notebook to AU or our designated representative at the mandatory pre-construction

More information

Project Monitoring & Air Sampling

Project Monitoring & Air Sampling Project Monitoring & Air Sampling 1. Qualifications of Air Sampling Personnel. The project air sampling shall be conducted by an asbestos project air sampling technician who has been trained in the selected

More information

A Comparison of the Approaches in the Implementation of Good Indoor Air Quality Practices in Malaysia

A Comparison of the Approaches in the Implementation of Good Indoor Air Quality Practices in Malaysia A Comparison of the Approaches in the Implementation of Good Indoor Air Quality Practices in Malaysia Anuar Mohd. Mokhtar* Department of Occupational Safety & Health, Malaysia *Corresponding email: anumokh@hotmail.com

More information

PRODUCT SAFETY DATA SHEET

PRODUCT SAFETY DATA SHEET PRODUCT SAFETY DATA SHEET SECTION 1 - CHEMICAL PRODUCT AND COMPANY IDENTIFICATION Product Name: Chemical Name: Product Use/Class: Company Information: Luxury Vinyl Tile Heterogeneous Floor Tile LVT Heterogeneous

More information

UNITED NATIONS PROACTIVE INDOOR AIR QUALITY REINSPECTION REPORT

UNITED NATIONS PROACTIVE INDOOR AIR QUALITY REINSPECTION REPORT UNITED NATIONS PROACTIVE INDOOR AIR QUALITY REINSPECTION REPORT 405 East 42nd Street Headquarters Service Drive New York, NY Site Visit: January 19, 2017 Northeast Region 75 South Orange Ave, Suite 206

More information

MATERIAL SAFETY DATA SHEET

MATERIAL SAFETY DATA SHEET MATERIAL SAFETY DATA SHEET SECTION 1 - CHEMICAL PRODUCT AND COMPANY IDENTIFICATION Product Name: Mannington INFINIITY Chemical Name: Aqueous acrylic copolymer emulsion Product Use/Class: Company Information:

More information

University of Rochester Environmental Health & Safety Indoor Air Quality Program March 23, 2005

University of Rochester Environmental Health & Safety Indoor Air Quality Program March 23, 2005 University of Rochester Environmental Health & Safety Indoor Air Quality Program March 23, 2005 1. Purpose: The purpose of this program is to inform the University community about indoor air quality (IAQ).

More information

Indoor Air Quality Assessment Report

Indoor Air Quality Assessment Report Indoor Air Quality Assessment Report For M&W Business Centre At Unit B, 19/F, Kyoto Plaza, 491-499 Lockhart Road, Causeway Bay, Hong Kong Tel: 3896 0399 Attn: Melody Ko Tested and prepared by: Carman Lam

More information

INDOOR AIR QUALITY ASSESSMENT. Department of Developmental Services & Department of Mental Health Service Center 35 Nagog Park Acton, Massachusetts

INDOOR AIR QUALITY ASSESSMENT. Department of Developmental Services & Department of Mental Health Service Center 35 Nagog Park Acton, Massachusetts INDOOR AIR QUALITY ASSESSMENT Department of Developmental Services & Department of Mental Health Service Center 35 Nagog Park Acton, Massachusetts Prepared by: Massachusetts Department of Public Health

More information

Thermal Environment evaluation in Commercial kitchens: Procedure of data collection

Thermal Environment evaluation in Commercial kitchens: Procedure of data collection Thermal Environment evaluation in Commercial kitchens: Procedure of data collection Angela Simone *, Bjarne W. Olesen ICIEE-BYG, Technical University of Denmark, Kgs. Lyngby, Denmark * email: asi@byg.dtu.dk

More information

SECTION 1 - CHEMICAL PRODUCT AND COMPANY IDENTIFICATION. P.O. Box 30 - Route Mannington Mills Road Salem, New Jersey U.S.A.

SECTION 1 - CHEMICAL PRODUCT AND COMPANY IDENTIFICATION. P.O. Box 30 - Route Mannington Mills Road Salem, New Jersey U.S.A. PRODUCT DATA SHEET SECTION 1 - CHEMICAL PRODUCT AND COMPANY IDENTIFICATION Product Name: Chemical Name: Product Use/Class: Company Information: Infinity Broadloom & Modular Carpet, 6 Foot Vinyl-Backed

More information

PERCENT OUTDOOR AIR CALCULATION AND ITS USE

PERCENT OUTDOOR AIR CALCULATION AND ITS USE PERENT OUTDOOR AIR ALULATION AND ITS USE APPLIATION NOTE TSI-138 TSI s IAQ instruments calculate Percent Outdoor Air (%OA). In order to take advantage of this feature, it is important to first understand

More information

MATERIAL SAFETY DATA SHEET

MATERIAL SAFETY DATA SHEET MATERIAL SAFETY DATA SHEET SECTION 1 CHEMICAL PRODUCT AND COMPANY IDENTIFICATION PRODUCT NAME: BUEHLER EDGEMET SOLUTION B IDENTIFICATION NUMBER: 20-8192b (SOLUTION B) PRODUCT USE/CLASS: Prep solution SUPPLIER:

More information

Stack Air Emission Test Report

Stack Air Emission Test Report Stack Air Emission Test Report Client Name : GMS COMPOSITE KNITTING IND. LTD. Client Address : Shardagonj, Kashimpur, Gazipur Sampling Date : 09 June 2016 Reporting Date : 11 June 2016 Description of Sampling:

More information

Corridor Pressurization System Performance in Multi-Unit Residential Buildings

Corridor Pressurization System Performance in Multi-Unit Residential Buildings Corridor Pressurization System Performance in Multi-Unit Residential Buildings Lorne Ricketts Student Member ASHRAE John Straube, PhD, P.Eng. Associate Member ASHRAE ABSTRACT Corridor pressurization based

More information

Indoor Air Quality Assessments

Indoor Air Quality Assessments HS13_IAQ_SOP 1. Purpose and Requirements Symptoms arising from poor indoor air quality often mimic those symptoms commonly associated with a cold, flu or allergies. These symptoms may include upper respiratory

More information

Basic Characterization and Information Gathering

Basic Characterization and Information Gathering Basic Characterization and Information Gathering Walkthrough Survey The basic characterization builds on the walkthrough survey which industrial hygienists have practiced for many years. To assess exposures

More information