TECHNICAL PAPER PRESENTATION

Size: px
Start display at page:

Download "TECHNICAL PAPER PRESENTATION"

Transcription

1 1 W E L C O M E T O A C O M E T TECHNICAL PAPER PRESENTATION

2 2 Analytics for Dissolved Gas Analysis BY RANDY COX

3 A B O U T T H E A U T H O R Randy Cox is the Domain Expertise Manager for GE Grid Solutions, M&D. His current duties include interfacing with the industry, committee work and education of customers on the technical advantages of GE Randy Cox DOMAIN EXPERTISE MANAGER GE GRID SOLUTIONS M&D technology, products, software and solutions. Randy is also a current member of IEEE.

4 4 O V E R V I E W & ABSTRACT SUMMARY Dissolved Gas Analysis has proven to be one of the most useful tools in analyzing the condition of oil filled power transformers. By observing the discreet values of the various combustible gases, developing faults can often be detected in their early stages. In recent years it has been discovered that trending the CO2/CO ratio, over time, can also be very useful in predicting a transformer s end of life. By trending this ratio, it may also be determined whether the severity of an incident is life ending, or simply an isolated event.

5 5 THE RELEVANT GASES It is important to distinguish and categorize the gases. This is vital in our efforts to diagnose issues within a power transformer. Hot metal gases are well known and understood by the industry. However, the carbon oxide gases (carbon dioxide and carbon monoxide) have continued to be problematic for the average technician.

6 U S E F U L I N D U S T R Y T O O L S C O M E T TRADITIONAL RATIOS FOR KEY GASES UTILIZING INDUSTRY TOOLS Industry tools can be very useful for determining the temperature of a given fault, or post-trip fault. While determining the temperature of the fault is important, another important piece to this puzzle is determining the location of the fault. Faults which occur in the winding insulation are not conducive to onsite repairs, while overheated connections (such as a de-energized tap changer) may make an on-site repair possible.

7 7 T H E T R A D I T I O N N A L V I E W TRADITIONAL DATA EVALUATION DISCREET VALUES As gases begin to generate, we determine what the temperature of the fault is based on individual levels and rate of change HOT METAL GAS RATIOS Early pioneers of DGA created charts with HMG ratios for us to calculate so that we could distinguish partial discharge from overheating SNAPSHOT CO2/CO RATIO Industry standards, such as IEEE and CIGRE provide guidance with a specific range where the ratio is considered to be normal

8 8 CO2/CO RATIO EXPERIMENT SETTING UP THE TEST 9 The testing was performed utilizing a YOUR TITLE HERE D877 oil tester, which holds a very small amount of oil, about the size of a coffee cup. New oil was used for each test. First, oil was flashed, a DGA collected with CO2 and CO measured and the CO2/CO RATIO oil flash oil w/paper appropriate ratio reflected. YOUR TITLE Next, the HERE oil 3 test cup was flushed with new oil, then 2 another sample of new oil added, but 1 this time with a single piece of transformer Kraft paper added between the electrodes with the test repeated. The test was repeated a total of 1 test1 test2 test3 test4 test5 test6 tes 7 test8 test9 test1

9 9 CATEGORIZING FAULTS Nitrogen Sealed #1 36 MVA Nitrogen Sealed #2 3 MVA 4% 35% YOUR 3% TITLE HERE 25% 2% 15% 1% 5% 4% 35% 3% 25% 2% 15% 1% 5% % H2 CH4 C2H6 C2H4 C2H2 % H2 CH4 C2H6 C2H4 C2H2 12 CO2/CO 7 CO2/CO 1 YOUR TITLE HERE Pre Event Post Event 4 3 Pre Event Post Event

10 1 CATEGORIZING FAULTS CONTINUED Winding Failure #1 Primary Lead Repairable #2 Transformer Replaced Transformer Repaired

11 11 CATEGORIZING EVENTS 2136 ppm 21 ppm CO Failed the following year, CO CO CO C2H C2H6 185 ppm 2 ppm 12 CO2/CO Ratio 2136 ppm 21 ppm ppm 2 ppm Failed the following year,

12 , 15 MVA, 1 kv TRANSFORMER M Date H2 O2 CO2 CO CH4 C2H6 C2H4 C2H2 CO2/CO 211 < < < < < <1 <1 < < <1 <1 < < <1 < CO2/CO 8 CO2/CO 83% Drop

13 , 15 MVA, 1 kv, Complete Picture Date H2 O2 CO2 CO CH4 C2H6 C2H4 C2H2 CO2/CO 211 < < < < < <1 <1 < < <1 <1 < < <1 < post fault CO2/CO 96% Drop CO2/CO CO2/CO Linear (CO2/CO)

14 14 SUMMARY Trending the CO2/CO ratio is a useful tool for detecting breakdown of the solid insulation. The CO2/CO ratio appears to provide insight into deteriorating insulation in the absence of hot metal gases. The CO2/CO ratio is also useful in determining if an incipient fault is occurring in the winding insulation, or perhaps a more repairable location, such as a DETC, bushing connection, etc. This method is also useful in determining the need for offline testing, as well as the effect loading may have on the solid insulation. Trending of the carbon oxide ratios is most reliable when performed over time, using multiple samples. Special attention should always be given to all gases measured, including oxygen and nitrogen.

15 15 PAPER Q&A C O M E T C O L L A B O R A T E S H A R E K N O W L E D G E P R O G R E S S

16 16 GET IN TOUCH RANDY COX. GE Grid Solutions Monitoring & Diagnostics LINKEDIN

TOGA PRESENTATION REVIEW OF CASE STUDIES. Paul Boman,

TOGA PRESENTATION REVIEW OF CASE STUDIES. Paul Boman, TOGA PRESENTATION REVIEW OF CASE STUDIES Paul Boman, paul_boman@hsb.com October 8, 2014 HSB s TOGA History TOGA Transformer Oil Gas Analyst Registered trademark of Hartford Steam Boiler Inspection and

More information

INTELLIGENT DIAGNOSTIC METHOD FOR PREDICTION OF INTERNAL CONDITION OF TRANSFORMER USING FUZZY LOGIC

INTELLIGENT DIAGNOSTIC METHOD FOR PREDICTION OF INTERNAL CONDITION OF TRANSFORMER USING FUZZY LOGIC INTELLIGENT DIAGNOSTIC METHOD FOR PREDICTION OF INTERNAL CONDITION OF TRANSFORMER USING FUZZY LOGIC by LAXMANRAO ALUR KARNATAKA POWER CORPORATION LTD.,INDIA alur.laxman@gmail.com 1 INDEX INTRODUCTION DISSOLVED

More information

TOGA Electrical Insulating Fluid Analysis. Improving performance and protecting assets.

TOGA Electrical Insulating Fluid Analysis. Improving performance and protecting assets. TOGA Electrical Insulating Fluid Analysis Improving performance and protecting assets. It happens all the time - transformers fail unexpectedly, and there are often no external visual clues on what caused

More information

The effectiveness of oil analysis for failure prediction of power transformers

The effectiveness of oil analysis for failure prediction of power transformers The effectiveness of oil analysis for failure prediction of power transformers by Krige Visser and Yashin Brihmohan, University of Pretoria The availability of an electricity network is of utmost importance

More information

Practical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter. Ian.A.R. Gray

Practical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter. Ian.A.R. Gray Practical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter Ian.A.R. Gray Largest aluminium smelter in the Southern hemisphere South Africa's major producer of primary aluminium It

More information

Dissolved Gas Analysis for transformer. health. management. Precise DGA measurements are required to look for transformer condition changes COLUMN

Dissolved Gas Analysis for transformer. health. management. Precise DGA measurements are required to look for transformer condition changes COLUMN COLUMN Precise DGA measurements are required to look for transformer condition changes ABSTRACT Complex studies have led to the development of powerful methods to assess the health of the insulation system,

More information

Power Transformers. Dissolved Gas Analysis Siemens Energy, Inc. All Rights Reserved

Power Transformers. Dissolved Gas Analysis Siemens Energy, Inc. All Rights Reserved Power Transformers Dissolved Gas Analysis 2008 Siemens Energy, Inc. All Rights Reserved Application ü DGA allows to detect the presence and severity of faults: Air leaks Hot metal faults Arcing and partial

More information

FORECASTING THE NATURE OF POWER TRANSFORMER INSULATION OIL USING CHEMICAL PROPERTIES OF DISSOLVED GASES

FORECASTING THE NATURE OF POWER TRANSFORMER INSULATION OIL USING CHEMICAL PROPERTIES OF DISSOLVED GASES Int. J. Chem. Sci.: 13(4), 2015, 1777-1786 ISSN 0972-768X www.sadgurupublications.com FORECASTING THE NATURE OF POWER TRANSFORMER INSULATION OIL USING CHEMICAL PROPERTIES OF DISSOLVED GASES K. IYSWARYA

More information

DGA - Method in the Past and for the Future

DGA - Method in the Past and for the Future DGA - Method in the Past and for the Future IVANKA ATANASOVA-HÖHLEIN Höhlein, Folie 1 Höhlein, Folie 2 -1970 Doerenburg introduced the differentiation between electrical and thermal failure mode and introduced

More information

PROGRESS IN PAPER DEGRADATION ASSESSMENT IN SERVICE-AGED TRANSFORMERS

PROGRESS IN PAPER DEGRADATION ASSESSMENT IN SERVICE-AGED TRANSFORMERS PROGRESS IN PAPER DEGRADATION ASSESSMENT IN SERVICE-AGED TRANSFORMERS H. Ding, R. Heywood, J. Lapworth, S. Ryder and A. Wilson Presenter: Dr Hongzhi Ding Doble PowerTest Ltd UK INSUCON - 17 th May 2017

More information

ICM Project Station Infrastructure and Equipment

ICM Project Station Infrastructure and Equipment EB 0 00 ( pages) ICM Project Station Infrastructure and Equipment Stations Power Transformers Segment (THESL) EB 0 00 I EXECUTIVE SUMMARY. Project Description This segment consists of replacing power transformers

More information

Silicone Dielectric Fluids Fredi Jakob, Karl Jakob, Nicholas Perjanik Analytical ChemTech International, Inc.

Silicone Dielectric Fluids Fredi Jakob, Karl Jakob, Nicholas Perjanik Analytical ChemTech International, Inc. Silicone Dielectric Fluids Fredi Jakob, Karl Jakob, Nicholas Perjanik Analytical ChemTech International, Inc. I. Introduction Mineral oil based dielectric fluids have been used more extensively than other

More information

Enhance Power Equipment Reliability with Predictive Maintenance Technologies

Enhance Power Equipment Reliability with Predictive Maintenance Technologies Enhance Power Equipment Reliability with Predictive Maintenance Technologies November 2012/1910DB1208 by S. Frank Waterer, Electrical Engineerinig, Fellow Schneider Electric USA, Inc. Make the most of

More information

Featured Product. Transformer Monitoring and Diagnostic Systems

Featured Product. Transformer Monitoring and Diagnostic Systems Featured Product Transformer Monitoring and Diagnostic Systems Transformer Predictive Analysis Owners of critical transformer equipment can realize the benefits of predictive analysis on transformer health

More information

Condition Assessment of High Voltage Power Transformer Using Dissolved Gas Analysis

Condition Assessment of High Voltage Power Transformer Using Dissolved Gas Analysis ISSN 348-7X September 5 Condition Assessment of High Voltage Power Transformer Using Dissolved Gas Analysis Jugasri Joy Sarma M.E. Scholar, EE Department, Assam Engineering College, Guwahati, India Dr.

More information

Oil Diagnostics - Test Information

Oil Diagnostics - Test Information Oil Diagnostics - Test Information For both financial and operational reasons it is very important that transformers are managed efficiently. Optimising the future management of large transformers on networks

More information

Residual Life assessment with DGA, Furan content in transformer oil and Degree of polymerization of solid insulation

Residual Life assessment with DGA, Furan content in transformer oil and Degree of polymerization of solid insulation International Journal of Scientific and Research Publications, Volume 6, Issue 7, July 2016 230 Residual Life assessment with DGA, Furan content in transformer oil and Degree of polymerization of solid

More information

Dissolved Gas Analysis of Transformer Oils: Effects of electric arc

Dissolved Gas Analysis of Transformer Oils: Effects of electric arc Proceedings of the 6th WSEAS International Conference on Power Systems, Lisbon, Portugal, September 22-24, 26 376 Dissolved Gas Analysis of Transformer Oils: Effects of electric arc SUWARNO School of Electrical

More information

Available online at ScienceDirect. Study on Dissolved Gas Due Tue Thermally Degraded Insulating Paper in Transformer Oil

Available online at   ScienceDirect. Study on Dissolved Gas Due Tue Thermally Degraded Insulating Paper in Transformer Oil Available online at www.sciencedirect.com ScienceDirect Procedia Technology 11 ( 2013 ) 257 262 The 4th International Conference on Electrical Engineering and Informatics (ICEEI 2013) Study on Dissolved

More information

Superior client serv ice. Electrical confidence. CARGILL LIMITED Transformer Oil Sampling and Analysis. June 7, 2016 File: C

Superior client serv ice. Electrical confidence. CARGILL LIMITED Transformer Oil Sampling and Analysis. June 7, 2016 File: C Superior client serv ice. Electrical confidence. CARGILL LIMITED 6 Transformer Oil Sampling and Analysis June 7, 6 File: C- Project Manager: George Shehata, P.Eng. info@magnaiv.com www.magnaiv.com Engineering

More information

Prediction of the Characteristics of Transformer Oil under Different Operation Conditions

Prediction of the Characteristics of Transformer Oil under Different Operation Conditions Prediction of the Characteristics of Transformer Oil under Different Operation Conditions EL-Sayed M. M. EL-Refaie, Mohamed R. Salem, and Wael A. Ahmed Digital Open Science Index, Electrical and Computer

More information

IEEE Transformer Committee Atlanta Arturo Núñez MISTRAS Group, Inc. (dba Physical Acoustics Corporation)

IEEE Transformer Committee Atlanta Arturo Núñez MISTRAS Group, Inc. (dba Physical Acoustics Corporation) IEEE Transformer Committee Atlanta 2016 Arturo Núñez MISTRAS Group, Inc. (dba Physical Acoustics Corporation) A A A A A A A A A AE Sensor ACOUSTIC EMISSIONS INSTALLATION AE SENSORS HFCT Other info: DGA

More information

Visit our website:

Visit our website: Lab Services ISO/IEC 17025:2005 Lab Services Lab Services MORGAN SCHAFFER, located in Montreal, Canada pioneered Dissolved Gas Analysis (DGA) in America. Almost 50 years of experience in transformer oil

More information

Practical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter. Ian Gray Transformer Chemistry Services

Practical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter. Ian Gray Transformer Chemistry Services Practical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter By Ian Gray Transformer Chemistry Services 1 Practical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter

More information

DGA Method-Based ANFIS Expert System for Diagnosing Faults and Assessing Quality of Power Transformer Insulation Oil

DGA Method-Based ANFIS Expert System for Diagnosing Faults and Assessing Quality of Power Transformer Insulation Oil Modern Applied Science; Vol. 10, No. 1; 2016 ISSN 1913-1844 E-ISSN 1913-1852 Published by Canadian Center of Science and Education DGA Method-Based ANFIS Expert System for Diagnosing Faults and Assessing

More information

CIGRE 16 BRUGGE Partial Discharge and Dissolved Gas Analysis In bio-degradable transformer oil. The University of New South Wales Australia

CIGRE 16 BRUGGE Partial Discharge and Dissolved Gas Analysis In bio-degradable transformer oil. The University of New South Wales Australia CIGRE 16 BRUGGE 2007 Partial Discharge and Dissolved Gas Analysis In bio-degradable transformer oil D. IMAMOVIC *, K.X. LAI, N.A. MUHAMAD, B.T. PHUNG and T.R. BLACKBURN # The University of New South Wales

More information

THE APPLICATION OF NEWFOUNDLAND AND LABRADOR HYDRO (Hydro) STATES. 1. Hydro is a corporation continued and existing under the Hydro Corporation Act,

THE APPLICATION OF NEWFOUNDLAND AND LABRADOR HYDRO (Hydro) STATES. 1. Hydro is a corporation continued and existing under the Hydro Corporation Act, IN THE MATTER OF the Electrical Power Control Act, RSNL 1994, Chapter E-5.1 (the EPCA) and the Public Utilities Act, RSNL 1990, Chapter P-47 (the Act), and regulations thereunder; AND IN THE MATTER OF

More information

TECHNICAL PAPER PRESENTATION

TECHNICAL PAPER PRESENTATION 1 W E L C O M E T O A C O M E T 2 0 1 7 TECHNICAL PAPER PRESENTATION 2 POWER TRANSFORMERS - Online detection of markers for cellulose aging. BY KAI HAEMEL 3 A B O U T T H E A U T H O R BRIEF BIO Kai Haemel

More information

IEEE Aging Study. 14 March 2012 ILSC

IEEE Aging Study. 14 March 2012 ILSC IEEE Aging Study 14 March 2012 ILSC IEEE Aging Study Purpose of the Study Aging Criteria from IEEE Distribution Transformer Sealed Tube Test Power Transformer Sealed Tube Test Dual Temperature Sealed Tube

More information

Smart Grid Monitoring of Transformers by DGA. Michel Duval. CIGRE Thailand, Bangkok 2013

Smart Grid Monitoring of Transformers by DGA. Michel Duval. CIGRE Thailand, Bangkok 2013 Smart Grid Monitoring of Transformers by DGA Michel Duval CIGRE Thailand, Bangkok 2013 1 Electric Power 2 Power Transformers 3 Catastrophic Failures 4 Failures in Service - The failure rate of power transformers

More information

Expertise method to diagnose transformer conditions

Expertise method to diagnose transformer conditions Expertise method to diagnose transformer conditions J. BILBAO, C. M. REBOLLO, and P. GONZÁLEZ Applied Mathematics Department. University of the Basque Country Engineering School, Alda. de Urquijo s/n,

More information

International Trends in Asset and Maintenance Management through Enhanced Monitoring and Diagnostics of Electrical Facilities

International Trends in Asset and Maintenance Management through Enhanced Monitoring and Diagnostics of Electrical Facilities International Trends in Asset and Maintenance Management through Enhanced Monitoring and Diagnostics of Electrical Facilities Presented by Tony McGrail, Kenneth Elkinson Doble Engineering Company Agenda

More information

On Site Dissolved Gas Analysis for Transformer Condition Assessment. Robin Watson - Kelman UK Karl Smith - Kelman Africa Henk Fourie - Kelman Africa

On Site Dissolved Gas Analysis for Transformer Condition Assessment. Robin Watson - Kelman UK Karl Smith - Kelman Africa Henk Fourie - Kelman Africa On Site Dissolved Gas Analysis for Transformer Condition Assessment Robin Watson - Kelman UK Karl Smith - Kelman Africa Henk Fourie - Kelman Africa Catastrophic Failure of Transformers The state of the

More information

Online Condition Monitoring of Transformer

Online Condition Monitoring of Transformer Online Condition Monitoring of Transformer ---------------------------------------------------- Heart of any power system An essential Part of a Cost efficient maintenance Program. It is well known that

More information

Transformer Monitoring

Transformer Monitoring 100x 100x Offshore 100x-3/-2/-1 Load Voltage kv ma Load Current Ambient Oil Position Top Oil Bottom Oil MS-7 X1 X2 X3 H3 H1 Bushing Monitor ZVCM-1001 Transformer Monitoring Overview of modular system components

More information

Understanding the Breakdown Mechanism of Bushings and Implementing Appropriate Life-Cycle Oriented Maintenance Strategies

Understanding the Breakdown Mechanism of Bushings and Implementing Appropriate Life-Cycle Oriented Maintenance Strategies Understanding the Breakdown Mechanism of Bushings and Implementing Appropriate Life-Cycle Oriented Maintenance Strategies By Thomas Schuette, Emmanuel Santos Understanding the Breakdown Mechanism of Bushings

More information

Condition Assessment of Power Transformer Using Dissolved Gas Analysis

Condition Assessment of Power Transformer Using Dissolved Gas Analysis Condition Assessment of Power Transformer Using Dissolved Gas Analysis Jagdeep Singh, Kulraj Kaur, Priyam Kumari, Ankit Kumar Swami School of Electrical and Electronics Engineering, Lovely Professional

More information

INTEGRATED SUBSTATION CONTROL SYSTEM WITH EQUIPMENT MONITORING AND DIAGNOSTICS

INTEGRATED SUBSTATION CONTROL SYSTEM WITH EQUIPMENT MONITORING AND DIAGNOSTICS INTEGRATED SUBSTATION CONTROL SYSTEM WITH EQUIPMENT MONITORING AND DIAGNOSTICS K. Caird W.J. Ros GE Harris Energy Control Systems GE Power Systems Energy Consulting Calgary, CANADA Schenectady, NY 12345

More information

Online dissolved gas analysis sensor

Online dissolved gas analysis sensor GAS Guard 8 Online dissolved gas analysis sensor Answers for energy. Dissolved Gas Analysis (DGA) Dissolved gas analysis is the single-most comprehensive tool for transformer condition assessment. The

More information

Components, Systems and Service for Transformers.

Components, Systems and Service for Transformers. Components, Systems and Service for Transformers. HYDAC Headquarters in Germany HYDAC China Your Professional Partner for the Optimization of Transformers. With over 5,500 employees worldwide HYDAC is

More information

Anil Kumar*, Ajay Rathore** Ashish Patra ***

Anil Kumar*, Ajay Rathore** Ashish Patra *** Analysis of Power Transformer using fuzzy expert and neural network system Anil Kumar*, Ajay Rathore** Ashish Patra *** Electrical Department MITS Gwalior (MP)INDIA474002 Abstract- Power transformers being

More information

Presentation to: Western Mining Electric Association

Presentation to: Western Mining Electric Association Presentation to: Western Mining Electric Association World s Largest Database of Test Records 4,000,000 Customer Transformer Test Records. World s Leading Reclaimer of Transformer Oil Over 1 Billion Gallons

More information

Grid Solutions. ASSET PERFORMANCE MANAGEMENT for Electrical Substations

Grid Solutions. ASSET PERFORMANCE MANAGEMENT for Electrical Substations Grid Solutions ASSET PERFORMANCE MANAGEMENT for Electrical Substations Electrical equipment is a critical component of an asset portfolio. Beyond its financial value, it plays an even greater role in overall

More information

Oil Regeneration in 132kV and 33kV Transformers 6 December 2017

Oil Regeneration in 132kV and 33kV Transformers 6 December 2017 1 Oil Regeneration in 132kV and 33kV Transformers 6 December 2017 Paul Marshall Innovation Project Manager Agenda Introduction Research IFI oil regeneration project Oil regeneration results Oil regeneration

More information

Data Mining Approach With IEC Based Dissolved Gas Analysis For Fault Diagnosis Of Power Transformer

Data Mining Approach With IEC Based Dissolved Gas Analysis For Fault Diagnosis Of Power Transformer Data Mining Approach With IEC Based Dissolved Gas Analysis For Fault Diagnosis Of Power Transformer Ms Kanika Shrivastava M.E. in H.V.P.S. Electrical Engineering, JEC, Jabalpur, (M.P) Mr. Ashish Choubey

More information

FAILURE ANALYSIS OF POWER TRANSFORMERS BY DGA, OIL TESTS AND MARKOV APPROACH

FAILURE ANALYSIS OF POWER TRANSFORMERS BY DGA, OIL TESTS AND MARKOV APPROACH FAILURE ALYSIS OF POWER TRANSFORMERS BY DGA, OIL TESTS AND MARKOV APPROACH Mohammed Abdul Rahman Uzair Research Scholar, Department of EEE, GITAM University, Hyderabad, Telangana, INDIA Dr. Basavaraja

More information

The analysis of electrical and mechanical faults in power transformers by Fuzzy expert system

The analysis of electrical and mechanical faults in power transformers by Fuzzy expert system Scientific Research and Essays Vol. 5 (24), pp. 4018-4027, 18 December, 2010 Available online at http://www.academicjournals.org/sre ISSN 1992-2248 2010 Academic Journals Full Length Research Paper The

More information

MOISTURE IN PAPER ASSESSMENT FROM CONTINUOUS MONITORING OF MOISTURE IN OIL. GE Energy

MOISTURE IN PAPER ASSESSMENT FROM CONTINUOUS MONITORING OF MOISTURE IN OIL. GE Energy MOISTURE IN PAPER ASSESSMENT FROM CONTINUOUS MONITORING OF MOISTURE IN OIL Jacques Aubin GE Energy Brian D Sparling Abstract Moisture content of solid insulation is a persistent concern for power transformer

More information

CONDITION-BASED ASSESSMENT OF ON-LOAD TAP CHANGERS

CONDITION-BASED ASSESSMENT OF ON-LOAD TAP CHANGERS ISSUE 66 CONDITION-BASED ASSESSMENT OF ON-LOAD TAP CHANGERS By I.A.R. Gray transformer division manager, WearCheck Condition Monitoring Specialists I.A.R. Gray transformer division manager, WearCheck INTRODUCTION

More information

University of Cape Town

University of Cape Town The copyright of this thesis vests in the author. No quotation from it or information derived from it is to be published without full acknowledgement of the source. The thesis is to be used for private

More information

TRANSFORMER OIL ANALYSIS

TRANSFORMER OIL ANALYSIS A member of the Set Point group I S S U E 3 6 TRANSFORMER OIL ANALYSIS By Neil Robinson, B.Sc. Hons. A basic introduction to an essential part of a cost-efficient maintenance programme It is well known

More information

Asset Health Appraisal of Transformers in Eskom's Distribution Network

Asset Health Appraisal of Transformers in Eskom's Distribution Network Asset Health Appraisal of Transformers in Eskom's Distribution Network Adesh Singh 09/02/2017 In fulfilment of the Masters of Science, College of Agriculture, Engineering and Science, University of KwaZulu-Natal

More information

Transformer Program. Trevor Foster Electrical Engineering, Manager Calpine Corporation April 16 17, 2013

Transformer Program. Trevor Foster Electrical Engineering, Manager Calpine Corporation April 16 17, 2013 Transformer Program Trevor Foster Electrical Engineering, Manager Calpine Corporation April 16 17, 2013 Overview of Calpine Established in 1984 One of the largest Independent power producers in the U.S.,

More information

Imran Zulquifal Mamade

Imran Zulquifal Mamade A METHODOLOGY TOWARDS CONDITION-BASED ASSET MANAGEMENT Imran Zulquifal Mamade Instituto Superior Técnico, Lisboa, Portugal, 2016 imran.mamade@tecnico.ulisboa.pt Abstract: Back on the 1970s, electric utilities

More information

Lifetime Decisions. Investments can be planned, lifetime costs of equipment made transparent and decisions based on informed fact.

Lifetime Decisions. Investments can be planned, lifetime costs of equipment made transparent and decisions based on informed fact. Lifetime Decisions Ageing assets, rising energy demand, and the need to deliver without outage are issues facing utilities and industries around the world. At the same time, financial constraints demand

More information

CHAPTER 4 INVESTIGATIONS OF FURANIC DERIVATIVES AND PERFORMANCE EVALUATION OF TRANSFORMER OIL USING UV-VISIBLE SPECTROPHOTOMETER

CHAPTER 4 INVESTIGATIONS OF FURANIC DERIVATIVES AND PERFORMANCE EVALUATION OF TRANSFORMER OIL USING UV-VISIBLE SPECTROPHOTOMETER 7 CHAPTER 4 INVESTIGATIONS OF FURANIC DERIVATIVES AND PERFORMANCE EVALUATION OF TRANSFORMER OIL USING UV-VISIBLE SPECTROPHOTOMETER 4. INTRODUCTION Life of a Power transformer is mainly determined by its

More information

Transformers are the heart of an

Transformers are the heart of an 98 Technical Article Reliability of Electrical Systems: From Testing to Monitoring Specific data from a fault gas monitor study will be presented, as well as a test case that focuses on the relationship

More information

Stack Gas Analyzer ENDA-7000 ULTIMATE. Ultimate Reliability. Ultimate. Ultimate. Dependability. Accessibility

Stack Gas Analyzer ENDA-7000 ULTIMATE. Ultimate Reliability. Ultimate. Ultimate. Dependability. Accessibility Stack Gas Analyzer ENDA-7000 ULTIMATE Ultimate Reliability Ultimate Dependability Ultimate Accessibility ENDA-7000 ULTIMATE Experience HORIBA, the global Single Source Solutions Provider with over 50 years

More information

Transmission Owner Asset Management

Transmission Owner Asset Management Transmission Owner Asset Management Pieces of Asset Management New customers, load growth, repairs, maintenance, operational issues, etc. All the pieces make up the asset management plan for repair or

More information

Health Index: the TERNA s Practical Approach for Transformers Fleet Management

Health Index: the TERNA s Practical Approach for Transformers Fleet Management 213 Electrical Insulation Conference, Ottowa, Onterio, Canada, 2 to 5 June 213 Health Index: the TERNA s Practical Approach for Transformers Fleet Management Fabio Scatiggio TERNA RETE ITALIA SpA Via delle

More information

Transformer is gassing-what to do

Transformer is gassing-what to do Transformer is gassing-what to do V.V. Sokolov Scientific and Engineering Center ZTZ-Service Company, Dnepropetrovskoye shosse, 99 Zaporozhye, Ukraine Phone: (38)-()-595-87; Fax: (38)-()-5-498 Z. Berler,

More information

TRANSFORMER CONDITION ASSESSMENT USING ARTIFICIAL INTELLIGENCE. A THESIS IN ELECTRICAL ENGINEERING Master of Science in Electrical Engineering

TRANSFORMER CONDITION ASSESSMENT USING ARTIFICIAL INTELLIGENCE. A THESIS IN ELECTRICAL ENGINEERING Master of Science in Electrical Engineering TRANSFORMER CONDITION ASSESSMENT USING ARTIFICIAL INTELLIGENCE A THESIS IN ELECTRICAL ENGINEERING Master of Science in Electrical Engineering Presented to the faculty of the American University of Sharjah

More information

Remnant Life Estimation of Power Transformers Based on Chemical Diagnostic Parameters Using Adaptive Neuro- Fuzzy Inference System

Remnant Life Estimation of Power Transformers Based on Chemical Diagnostic Parameters Using Adaptive Neuro- Fuzzy Inference System Faculty of Science and Engineering Department of Electrical and Computer Engineering Remnant Life Estimation of Power Transformers Based on Chemical Diagnostic Parameters Using Adaptive Neuro- Fuzzy Inference

More information

Study on Thermal Ageing Characteristics of Silicone Rubber and Pressboard in Mineral Oil

Study on Thermal Ageing Characteristics of Silicone Rubber and Pressboard in Mineral Oil Study on Thermal Ageing Characteristics of Silicone Rubber and Pressboard in Mineral Oil M.Sc. Smitha Karambar, Prof. Dr.-Ing. Stefan Tenbohlen University of Stuttgart, Institute of Power Transmission

More information

Make Use of DGA to Carry Out the Transformer Oil-Immersed Paper Deterioration Condition Estimation with Fuzzy-Logic

Make Use of DGA to Carry Out the Transformer Oil-Immersed Paper Deterioration Condition Estimation with Fuzzy-Logic Available online at www.sciencedirect.com Procedia Engineering 30 (2012) 569 576 International Conference on Communication Technology and System Design 2011 Make Use of DGA to Carry Out the Transformer

More information

Smarter Choices, Better Air.

Smarter Choices, Better Air. Smarter Choices, Better Air. Intelligent protection against air pollution The three steps to better air Air pollution is the fourth greatest cause of death worldwide, with 92% of the world s population

More information

Asset Management of Power Transformers

Asset Management of Power Transformers Asset Management of Power Transformers Prof. Dr.-Ing. C. Neumann TRANSFORM Partner Claus Neumann Study of electrical engineering at Technical University of Aachen, Germany Dr.-thesis at Technical University

More information

A REVIEW ON FAULT ANALYSIS IN UNDERGROUND CABLES

A REVIEW ON FAULT ANALYSIS IN UNDERGROUND CABLES A REVIEW ON FAULT ANALYSIS IN UNDERGROUND CABLES Siddharth Lohia 1, Usman Khan 2, Swati Dixit 3 1, 2 Students, Electrical Engineering Department Greater Noida Institutes of Technology, Gr.Noida, (India)

More information

ADVANCED ASSET HEALTH MANAGEMENT FOR EFFECTIVE MAINTENANCE AND ASSET REPLACEMENT PLANNING

ADVANCED ASSET HEALTH MANAGEMENT FOR EFFECTIVE MAINTENANCE AND ASSET REPLACEMENT PLANNING ADVANCED ASSET HEALTH MANAGEMENT FOR EFFECTIVE MAINTENANCE AND ASSET REPLACEMENT PLANNING Jean-Louis COULLON First Name FAMILY NAME First Name FAMILY NAME ALSTOM Grid France Affiliation Country Affiliation

More information

Maintenance & Reliability Week South Africa. 24th of November 2010, Johan Grövik

Maintenance & Reliability Week South Africa. 24th of November 2010, Johan Grövik Maintenance & Reliability Week South Africa 24th of November 2010, Johan Grövik Development from a different perspective Source: NASA picture Satellite photo of earth at night 2 Outline Trends and directions

More information

Flexible Analytics for Management of Grid Assets

Flexible Analytics for Management of Grid Assets Journal of Energy and Power Engineering 9 (2015) 411-416 doi: 10.17265/1934-8975/2015.04.012 D DAVID PUBLISHING Jean-Louis Coullon 1 and Navin Rego 2 1. Alstom Grid, Immeuble Galilee, Paris La Defense

More information

Pomona, CA May 24 25, 2016

Pomona, CA May 24 25, 2016 Pomona, CA May 24 25, 2016 Transformer Technology Seminar Modular approach on economic condition assessment for power transformer; data management, Fleet screening and risk ranking Siemens AG 2014 All

More information

Quality assessment of 11 KV transformer by internal dissolved gas analysis using CFD

Quality assessment of 11 KV transformer by internal dissolved gas analysis using CFD INTERNATIONAL JOURNAL OF INNOVATIVE RESEARCH IN ELECTRICAL, ELECTRONICS, INSTRUENTATION AND CONTROL ENGINEERING Quality assessment of 11 KV transformer by internal dissolved gas analysis using CFD ithu

More information

Sustainable and available. Enhancing performance and reducing environmental impact of existing transformer fleets

Sustainable and available. Enhancing performance and reducing environmental impact of existing transformer fleets Sustainable and available Enhancing performance and reducing environmental impact of existing transformer fleets Pierre Lorin, Pravin Khanna, Roberto Asano, Anders Grano Aging assets, rising energy demand,

More information

Powering reliable solutions. for the commercial and industrial market

Powering reliable solutions. for the commercial and industrial market Powering reliable solutions for the commercial and industrial market We understand your challenges To maintain an uninterrupted operation, commercial and industrial users require the highest compliance

More information

Flexible Analytics for Management of Grid Assets. J.-L. COULLON Alstom Grid France

Flexible Analytics for Management of Grid Assets. J.-L. COULLON Alstom Grid France 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2014 Grid of the Future Symposium Flexible Analytics for Management of Grid Assets J.-L. COULLON Alstom Grid France SUMMARY

More information

MAINTENANCE &' ASSET MANAGEMENT. 1mointwor ~

MAINTENANCE &' ASSET MANAGEMENT. 1mointwor ~ MAINTENANCE &' ASSET MANAGEMENT 1mointwor ~ Special Theme: Power Transmission The Transformer Cannot Possibly Be Down! Evaluating New Monitoring Solutions with a Business Case The cannot possibly be down!

More information

ESI are Transformer Oil Regeneration and Filtration Specialists with over 25 years Field Experience in the Design and Operation of HighVoltage

ESI are Transformer Oil Regeneration and Filtration Specialists with over 25 years Field Experience in the Design and Operation of HighVoltage ESI are Transformer Oil Regeneration and Filtration Specialists with over 25 years Field Experience in the Design and Operation of HighVoltage Transformer Oil Reclamation Equipment. ESI SERVICES TO THE

More information

Substation Transformer Condition-Based Maintenance (CBM)

Substation Transformer Condition-Based Maintenance (CBM) Substation Transformer Condition-Based Maintenance (CBM) October 2017 Table of Contents Executive Summary... 3 Introduction... 3 High-Level Solution... 4 Transformer Operations... 4 Oil Temperatures...

More information

GE Grid Solutions ASSET LIFECYCLE FLEXIBLE SERVICES OPTIMIZING GRID ASSET MANAGEMENT MANAGEMENT STRATEGIES

GE Grid Solutions ASSET LIFECYCLE FLEXIBLE SERVICES OPTIMIZING GRID ASSET MANAGEMENT MANAGEMENT STRATEGIES GE Grid Solutions ASSET LIFECYCLE MANAGEMENT FLEXIBLE SERVICES OPTIMIZING GRID ASSET MANAGEMENT STRATEGIES TODAY S ENVIRONMENT Electrical grids are more and more exposed to complex and challenging environments

More information

CASE STUDIES INVOLVING INSULATING LIQUIDS AND MATERIALS FROM THE DOBLE MATERIALS LABORATORIES

CASE STUDIES INVOLVING INSULATING LIQUIDS AND MATERIALS FROM THE DOBLE MATERIALS LABORATORIES CASE STUDIES INVOLVING INSULATING LIQUIDS AND MATERIALS FROM THE DOBLE MATERIALS LABORATORIES Lance R. Lewand and Paul J. Griffin Doble Engineering Company, USA ABSTRACT This paper discusses cases that

More information

Powertech Transformers Services

Powertech Transformers Services Powertech Transformers Services Offering our Customers Peace of Mind Powertech Transformers has over 60 years of experience in the transformer industry. Buying a transformer from Powertech Transformers

More information

Performance of Oil and Paper in Transformers Based on IEC and Dielectric Response Techniques*

Performance of Oil and Paper in Transformers Based on IEC and Dielectric Response Techniques* F E A T U R E A R T I C L E Performance of Oil and Paper in Transformers Based on IEC 61620 and Dielectric Response Techniques* Key words: oil paper insulation, transformer, polarization, conduction, aging

More information

Asset Optimization and Condition-Based Maintenance (CBM) Improving Reliability and Quality

Asset Optimization and Condition-Based Maintenance (CBM) Improving Reliability and Quality Asset Optimization and Condition-Based Maintenance (CBM) Improving Reliability and Quality Ann Moore Business Development Executive Agenda Asset Management Issues and Trends Utility Use Cases PSE&G CMMS

More information

SESB TECHNICAL CONFERENCE 2009 BRIDGING TOWARDS COMPETENCY EXCELLENCE 2012

SESB TECHNICAL CONFERENCE 2009 BRIDGING TOWARDS COMPETENCY EXCELLENCE 2012 CONDITION MONITORING USING INFRARED THERMOGRAPHY Presented by: Racheal Lim Electrical Engineer Certified Thermographer level 1 Technical Support(Condition Monitoring Unit) Jabatan Senggaraan Penghantaran

More information

Flexible integrated transformer SOLUTION

Flexible integrated transformer SOLUTION Flexible integrated transformer SOLUTION At Prolec GE we are committed to building optimized and reliable solutions for your specific needs, along with comprehensive services that fits your project s budget.

More information

Bachelor of Electrical Engineering (Industrial Power)

Bachelor of Electrical Engineering (Industrial Power) TRANSFORMER DISSOLVED GAS ANALYSIS USING DUVAL TRIANGLE METHOD VIA ANDROID Mohamad Hafiz Bin Abdul Wahid Bachelor of Electrical Engineering (Industrial Power) June 2014 " I hereby declare that I have read

More information

An Overview of Online Oil Monitoring Technologies

An Overview of Online Oil Monitoring Technologies An Overview of Online Oil Monitoring Technologies Tim Cargol Weidmann-ACTI, Inc. 71 Bishop St., Framingham, MA 01702, USA tcargol@weidmann-acti.com Abstract Several new and exciting oil monitoring technologies

More information

Inside View Features and Specifications Software Version 3.0

Inside View Features and Specifications Software Version 3.0 Inside View Features and Specifications Software Version 3.0 page 1 / 15 Introduction Inside View is a software system that was conceived and designed to identify warning events rapidly from large amounts

More information

Analytically driven resilient electric grid

Analytically driven resilient electric grid Analytically driven resilient electric grid 12th SYMPOSIUM ON POWER SYSTEM MANAGEMENT Damir Zec Country Leader, IBM Hrvatska Michal Osladil Managing Consultant, Energy & Utilities, IBM Watson IoT CEE IBM

More information

LA Engineering Academy

LA Engineering Academy Laxmi Associates Consultancy Third party Inspection RLA Testing& Commissioning AMC Project Management Training 323-324, Sunplaza1, GIDC Road, Makarpura, Vadodara-390010. lxassociates@gmail.com, www.laxmiassociates.in,

More information

Experienced-based Evaluation of Economic Benefits of On-line Monitoring Systems for Power Transformers

Experienced-based Evaluation of Economic Benefits of On-line Monitoring Systems for Power Transformers 21, rue d'artois, F-75008 Paris http://www.cigre.org 12-110 Session 2002 CIGRÉ Experienced-based Evaluation of Economic Benefits of On-line Monitoring Systems for Power Transformers by S. Tenbohlen *,

More information

CIGRÈ 23 BRUGGE Onsite, Online and Post Mortem Insulation Diagnostics at Power Transformers. Germany

CIGRÈ 23 BRUGGE Onsite, Online and Post Mortem Insulation Diagnostics at Power Transformers. Germany CIGRÈ BRUGGE 7 Onsite, Online and Post Mortem Insulation Diagnostics at Power Transformers M. KOCH, S. TENBOHLEN, D. GISELBRECHT, C. HOMAGK, T. LEIBFRIED University of Stuttgart, University of Karlsruhe

More information

IEC Publication [1] provides a coded list of faults

IEC Publication [1] provides a coded list of faults F E A T U R E A R T I C L E A Review of Faults Detectable by Gas-in-Oil Analysis in Transformers Key Words: Transformer, fault, dissolved gas analysis IEC Publication 60599 [1] provides a coded list of

More information

Power Transformer Fault Detection and Isolation based on Intuitionistic Fuzzy System

Power Transformer Fault Detection and Isolation based on Intuitionistic Fuzzy System Power Transformer Fault Detection and Isolation based on Intuitionistic Fuzzy System 1 Manikandan Pandiyan, 2 Geetha Mani, Department of Instrumentation and Control Systems Engineering PSG College of Technology,

More information

Software Implementation of Duval Triangle Technique for DGA in Power Transformers

Software Implementation of Duval Triangle Technique for DGA in Power Transformers International Journal of Electrical Engineering. ISSN 0974-2158 Volume 4, Number 5 (2011), pp. 529-540 International Research Publication House http://www.irphouse.com Software Implementation of Duval

More information

An Approach to Power Transformer Asset Management Using Health Index

An Approach to Power Transformer Asset Management Using Health Index F E A T U R E A R T I C L E An Approach to Power Transformer Asset Management Using Health Index Key Words: Power transformer, health index, failure, life, age, capital plan Introduction Power transformers

More information

Electricity Supply to Africa and Developing Economies Challenges and Opportunities. Technology solutions and innovations for developing economies

Electricity Supply to Africa and Developing Economies Challenges and Opportunities. Technology solutions and innovations for developing economies Electricity Supply to Africa and Developing Economies Challenges and Opportunities Technology solutions and innovations for developing economies Employment of various strategies in Eskom to optimize the

More information

Weidmann Electrical Technology. Presenter Thomas A. Prevost, Weidmann-ACTI

Weidmann Electrical Technology. Presenter Thomas A. Prevost, Weidmann-ACTI Estimation of Insulation Life Based on a Dual Temperature Aging Model Weidmann-ACTI Inc. Fifth Annual Technical Conference Albuquerque, NM Nov. 13-15, 2006 Thomas A. Prevost, Hans Peter Gasser Weidmann

More information

Draw a ring around the correct answer to complete each sentence.

Draw a ring around the correct answer to complete each sentence. 1 Fossil fuels contain carbon. The figure below represents a carbon atom. Draw a ring around the correct answer to complete each sentence. (i) The name of the particle with a positive charge is an electron.

More information