TOGA PRESENTATION REVIEW OF CASE STUDIES. Paul Boman,
|
|
- Piers Cannon
- 6 years ago
- Views:
Transcription
1 TOGA PRESENTATION REVIEW OF CASE STUDIES Paul Boman, October 8, 2014
2 HSB s TOGA History TOGA Transformer Oil Gas Analyst Registered trademark of Hartford Steam Boiler Inspection and Insurance Formed mid-1980 s Insulating fluid Expanded to include other fluids like; Lube oil Hydraulic fluid Heat transfer fluid for Pulp and Paper Gas like Landfill or Methane Produced from Digesters Internet based The Hartford Steam Boiler Inspection and Insurance Company. All rights reserved. 10/3/2014 2
3 Transformer Failure Rates Translates into Equipment Numbers 5 to 30 of 1,000 power transformers fail IEEE Gold Book Survey Varies greatly by region and company 5.8 of 1,000 (.58%) HSB Insured transformers fail Based on claims data Estimated 100,000 population pp 2014 The Hartford Steam Boiler Inspection and Insurance Company. All rights reserved. 10/3/2014 3
4 TOGA Failure Rates Failure rate over a 4-year period 1.5 of 1,000 (.15%)TOGA Transformers Fail All causes 8 of 100,000 (.008%)TOGA Transformers Fail TOGA effective causes like Overheating Thermal Arcing 2014 The Hartford Steam Boiler Inspection and Insurance Company. All rights reserved. 10/3/2014 4
5 Catastrophic Failure Rates CIGRÉ Brochure 537 from A2.33 Study Based on Canadian Population of Transformers Insulating Fluid typically mineral oil 70% to 80% of catastrophic failures due to bushings Serious Failures at ½% to 1.4% Fire estimated at 5% to 15% of all Serious Failures 2014 The Hartford Steam Boiler Inspection and Insurance Company. All rights reserved. 10/3/2014 5
6 Successful Analytic Programs Have Consistent sample extraction Repeatable laboratory analysis Accurate result evaluation Follow-up of results 2014 The Hartford Steam Boiler Inspection and Insurance Company. All rights reserved. 10/3/2014 6
7 Consistent Sample Method Sample Procedures Check for tank vacuum DGA & moisture from syringe Condition of Equipment Flush bottle & syringe Screen tests from bottle Equipment On-line Cleanliness Cleanliness Timely processing Atmospheric contamination 2014 The Hartford Steam Boiler Inspection and Insurance Company. All rights reserved. 10/3/2014 7
8 Quality Control Programs 2014 The Hartford Steam Boiler Inspection and Insurance Company. All rights reserved. 10/3/2014 8
9 Dissolved Gas Analysis Models Symbol Fault Duval Examples PD D1 D2 T1 T2 Partial discharges Discharges of low energy Discharges of the cold plasma ( corona ) type in gas bubbles or voids, with the possible formation of X-wax in paper. Partial discharges of the sparking type, inducing pinholes, carbonized punctures in paper. Low energy arcing inducing carbonized perforation or surface tracking of paper, or the formation of carbon particles in oil. Discharges of Discharges in paper or oil, with power followthrough, g, resulting in extensive damage to paper pp high energy or large formation of carbon particles in oil, metal fusion, tripping of the equipment and gas alarms. Thermal fault, Evidenced by paper turning brownish ( >200 C T <300 C ) or carbonized ( >300 C) ). Thermal fault, 300 <T<700 C Carbonization of paper, formation of carbon particles in oil. T3 Thermal fault, Extensive formation of carbon particles in oil, >700 C metal coloration ( 800 C ) or metal fusion ( >1000 C ) PD T T2 23 % CH 4 % C 2 H D1 D2 DT T % C 2 H The Hartford Steam Boiler Inspection and Insurance Company. All rights reserved. 10/3/2014 9
10 Dissolved Gas Analysis Models IEC Ratio Diagnostics Case Term 1 Term 2 Term 3 Partial discharge (PD) =C 2 H 2 / C 2 H 4 = CH 4 / H 2 = C 2 H 4 / C 2 H 6 Nonsignificant <0.1 < 0.2 (NS) Discharges of low energy (D1) > > 1 Discharges of high energy (D2) 0.6 to > 2 Thermal fault, t <300 C (T1) NS >1 but NS < 1 Thermal fault, 300 C < t < 700 C (T2) < 0.1 >1 1 4 Thermal fault, t > 700 C (T3) < 0.2 >1 > The Hartford Steam Boiler Inspection and Insurance Company. All rights reserved. 10/3/
11 Case Study: LIGHTNING STRIKE De-energized Tap Changer (DETC) Lead DGA (PPM) 11-Jan-01 1-Feb Feb Mar Jul Distribution Transformer base rating of 12 MVA, 69 kv to 13.8 kv Days between The transformer tripped off-line from Samples protective relays during a lightning storm. Electrical testing did not Hydrogen indicated a problem. Oxygen 2, ,290 1, ,553 5,276 Nitrogen 76,042 82,848 73,290 64,447 90,279 Methane Carbon Monoxide Carbon Dioxide Ethylene Ethane Acetylene The Hartford Steam Boiler Inspection and Insurance Company. All rights reserved. 10/3/
12 . PA Core Problem on a New Transformer Dissolved Gas Analysis Hydrogen 6,277 Oxygen 1,822 Nitrogen 6,711 02/11/2012 Roger's Ratios Method 02/11/2012 R1 (CH 4 /H 2 ) R2 (C 2 H 6 /CH 4 ) 0.83 R3 (C 2 H 4 /C 2 H 6 ) 5.36 R4 (C 2 H 2 /C 2 H 4 ) 0.01 Methane 111,021 Carbon Monoxide Carbon Dioxide Diagnostic Other Important t Ratios Closest Fit; core ground O 2 / ( O 2 + N 2 ) 0.21 CO 2 /CO - Duval Triangle Method 02/11/2012 Ethylene 492,176 Ethane 91,767 % CH4 18.3% %C2H4 81.2% %C2H2 0.5% Acetylene 2,993 Diagnostic Code T2 Region, 2014 The Hartford Steam Boiler Inspection and Insurance Company. All rights reserved. 10/3/
13 Times to Sample New Fluid (Baseline Sample) Full Sample Prior to Energized Establish Trend Initial Sample Sequence Monitors Equipment when Energized 24-hour, 48-hour and 72-hour DGA only Samples 1 week DGA, 1 month DGA, 3 month DGA, 6 month DGA Routine Sample Schedule Unit Transformer - 6 month DGA, annual physical and dissolved moisture Other Transformers - annual ldga, physical and ddissolved dmoisture testst 2014 The Hartford Steam Boiler Inspection and Insurance Company. All rights reserved. 10/3/
14 Case Study: High Resistance Connection Low Voltage Compression Connection DGA (PPM) Sample Date 20-May Jun-08 2-Jul-08 7-Jul Jul Aug-08 Days between Samples 21 OEM Insp Hydrogen Oxygen 2,414 2, , ,004 Nitrogen 101,590 58, ,954 51,468 86,139 Methane CO CO Ethylene 473 1, Ethane Acetylene The Hartford Steam Boiler Inspection and Insurance Company. All rights reserved. 10/3/
15 Case Study: High Resistance Connection Low Voltage Compression Connection DGA Rate of change (PPM / Day) Sample Date 17-Jul Aug Sep Oct Oct-12 Hydrogen Oxygen Nitrogen Methane Carbon Monoxide Carbon Dioxide Ethylene Ethane Acetylene The Hartford Steam Boiler Inspection and Insurance Company. All rights reserved. 10/3/
16 Natural Ester Case Study High Resistance Shield Connection Sample Data (PPM) Sample Date 18 JAN AUG JUL AUG 2007 Days between Sample Hydrogen (H2) Oxygen (O2) 1, ,539 Nitrogen (N2) 62,708 60,086 42,571 50,300 Methane (CH4) CO CO Ethylene (C2H4) Ethane (C2H6) Acetylene (C2H2) The Hartford Steam Boiler Inspection and Insurance Company. All rights reserved. 10/3/
17 Natural Ester Case Study High Resistance Shield Connection Duval Triangle Ratios Ratios 31-Jul Aug-07 % CH 4 0.6% 16.8% %C 2 H % 15.0% %C 2 H % 66.6% Diagnostic Code Discharges of Low Discharges of Energy Low Energy D1 D The Hartford Steam Boiler Inspection and Insurance Company. All rights reserved. 10/3/
18 Natural Ester Case Study Transformer Winding Shield Shield Ground Conductor 2014 The Hartford Steam Boiler Inspection and Insurance Company. All rights reserved. 10/3/
19 Natural Ester Case Study DGA Results for Bank of Single Phase 238 kv Transformers (PPM ) Unit Sample Date T1 pre- repair 18-Jan- 06 T2 31-Jul- 07 T3 31-Julspare 07 T4 24-Oct- 07 T1 post 14-Seprepair 10 Hydrogen Oxygen Nitrogen Methane CO Carbon Dioxide Ethylene Ethane Acetylene , , ,901 47, ,353 55, , The Hartford Steam Boiler Inspection and Insurance Company. All rights reserved. 10/3/
20 . High Voltage Loose Connection Dissolved Gas Analysis Hydrogen 10,097 Oxygen 6,695 Nitrogen 62,130 Methane 1,083 03/08/2012 Roger's Ratios Method 03/08/2012 R1 (CH 4 /H 2 ) 0.11 R2 (C 2 H 6 /CH 4 ) 0.32 R3 (C 2 H 4 /C 2 H 6 ) 1.56 R4 (C 2 H 2 /C 2 H 4 ) 0.02 Diagnostic Closest Fit; Conductor Overheating Carbon Monoxide 541 Carbon Dioxide 4,656 Ethylene 533 Ethane 342 Acetylene 11 Other Important t Ratios O 2 / ( O 2 + N 2 ) 0.10 CO 2 /CO 8.61 Duval Triangle Method 03/08/2012 % CH % %C 2 H % %C 2 H 2 0.7% Diagnostic Code T2 Region, 2014 The Hartford Steam Boiler Inspection and Insurance Company. All rights reserved. 10/3/
21 High Resistance Connection De-energized Tap Changer (DETC) Contact DGA Rates of Change (PPM/Day) Sample Date 11/22/02 07/31/02 01/14/02 11/21/01 Hydrogen Methane (2.55) 4.09 Carbon Monoxide Carbon Dioxide Ethylene Ethane Acetylene The Hartford Steam Boiler Inspection and Insurance Company. All rights reserved. 10/3/
22 THANK YOU VERY MUCH FOR YOUR ATTENTION Paul Boman, October 8, 2014
TOGA Electrical Insulating Fluid Analysis. Improving performance and protecting assets.
TOGA Electrical Insulating Fluid Analysis Improving performance and protecting assets. It happens all the time - transformers fail unexpectedly, and there are often no external visual clues on what caused
More informationPower Transformers. Dissolved Gas Analysis Siemens Energy, Inc. All Rights Reserved
Power Transformers Dissolved Gas Analysis 2008 Siemens Energy, Inc. All Rights Reserved Application ü DGA allows to detect the presence and severity of faults: Air leaks Hot metal faults Arcing and partial
More informationICM Project Station Infrastructure and Equipment
EB 0 00 ( pages) ICM Project Station Infrastructure and Equipment Stations Power Transformers Segment (THESL) EB 0 00 I EXECUTIVE SUMMARY. Project Description This segment consists of replacing power transformers
More informationPractical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter. Ian.A.R. Gray
Practical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter Ian.A.R. Gray Largest aluminium smelter in the Southern hemisphere South Africa's major producer of primary aluminium It
More informationCondition Assessment of High Voltage Power Transformer Using Dissolved Gas Analysis
ISSN 348-7X September 5 Condition Assessment of High Voltage Power Transformer Using Dissolved Gas Analysis Jugasri Joy Sarma M.E. Scholar, EE Department, Assam Engineering College, Guwahati, India Dr.
More informationINTELLIGENT DIAGNOSTIC METHOD FOR PREDICTION OF INTERNAL CONDITION OF TRANSFORMER USING FUZZY LOGIC
INTELLIGENT DIAGNOSTIC METHOD FOR PREDICTION OF INTERNAL CONDITION OF TRANSFORMER USING FUZZY LOGIC by LAXMANRAO ALUR KARNATAKA POWER CORPORATION LTD.,INDIA alur.laxman@gmail.com 1 INDEX INTRODUCTION DISSOLVED
More informationDGA - Method in the Past and for the Future
DGA - Method in the Past and for the Future IVANKA ATANASOVA-HÖHLEIN Höhlein, Folie 1 Höhlein, Folie 2 -1970 Doerenburg introduced the differentiation between electrical and thermal failure mode and introduced
More informationIEEE Transformer Committee Atlanta Arturo Núñez MISTRAS Group, Inc. (dba Physical Acoustics Corporation)
IEEE Transformer Committee Atlanta 2016 Arturo Núñez MISTRAS Group, Inc. (dba Physical Acoustics Corporation) A A A A A A A A A AE Sensor ACOUSTIC EMISSIONS INSTALLATION AE SENSORS HFCT Other info: DGA
More informationTECHNICAL PAPER PRESENTATION
1 W E L C O M E T O A C O M E T 2 1 7 TECHNICAL PAPER PRESENTATION 2 Analytics for Dissolved Gas Analysis BY RANDY COX A B O U T T H E A U T H O R Randy Cox is the Domain Expertise Manager for GE Grid
More informationDissolved Gas Analysis of Transformer Oils: Effects of electric arc
Proceedings of the 6th WSEAS International Conference on Power Systems, Lisbon, Portugal, September 22-24, 26 376 Dissolved Gas Analysis of Transformer Oils: Effects of electric arc SUWARNO School of Electrical
More informationDissolved Gas Analysis for transformer. health. management. Precise DGA measurements are required to look for transformer condition changes COLUMN
COLUMN Precise DGA measurements are required to look for transformer condition changes ABSTRACT Complex studies have led to the development of powerful methods to assess the health of the insulation system,
More informationThe effectiveness of oil analysis for failure prediction of power transformers
The effectiveness of oil analysis for failure prediction of power transformers by Krige Visser and Yashin Brihmohan, University of Pretoria The availability of an electricity network is of utmost importance
More informationSilicone Dielectric Fluids Fredi Jakob, Karl Jakob, Nicholas Perjanik Analytical ChemTech International, Inc.
Silicone Dielectric Fluids Fredi Jakob, Karl Jakob, Nicholas Perjanik Analytical ChemTech International, Inc. I. Introduction Mineral oil based dielectric fluids have been used more extensively than other
More informationSoftware Implementation of Duval Triangle Technique for DGA in Power Transformers
International Journal of Electrical Engineering. ISSN 0974-2158 Volume 4, Number 5 (2011), pp. 529-540 International Research Publication House http://www.irphouse.com Software Implementation of Duval
More informationOnline dissolved gas analysis sensor
GAS Guard 8 Online dissolved gas analysis sensor Answers for energy. Dissolved Gas Analysis (DGA) Dissolved gas analysis is the single-most comprehensive tool for transformer condition assessment. The
More informationSmart Grid Monitoring of Transformers by DGA. Michel Duval. CIGRE Thailand, Bangkok 2013
Smart Grid Monitoring of Transformers by DGA Michel Duval CIGRE Thailand, Bangkok 2013 1 Electric Power 2 Power Transformers 3 Catastrophic Failures 4 Failures in Service - The failure rate of power transformers
More informationSuperior client serv ice. Electrical confidence. CARGILL LIMITED Transformer Oil Sampling and Analysis. June 7, 2016 File: C
Superior client serv ice. Electrical confidence. CARGILL LIMITED 6 Transformer Oil Sampling and Analysis June 7, 6 File: C- Project Manager: George Shehata, P.Eng. info@magnaiv.com www.magnaiv.com Engineering
More informationOil Diagnostics - Test Information
Oil Diagnostics - Test Information For both financial and operational reasons it is very important that transformers are managed efficiently. Optimising the future management of large transformers on networks
More informationFORECASTING THE NATURE OF POWER TRANSFORMER INSULATION OIL USING CHEMICAL PROPERTIES OF DISSOLVED GASES
Int. J. Chem. Sci.: 13(4), 2015, 1777-1786 ISSN 0972-768X www.sadgurupublications.com FORECASTING THE NATURE OF POWER TRANSFORMER INSULATION OIL USING CHEMICAL PROPERTIES OF DISSOLVED GASES K. IYSWARYA
More informationCondition Assessment of Power Transformer Using Dissolved Gas Analysis
Condition Assessment of Power Transformer Using Dissolved Gas Analysis Jagdeep Singh, Kulraj Kaur, Priyam Kumari, Ankit Kumar Swami School of Electrical and Electronics Engineering, Lovely Professional
More informationPractical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter. Ian Gray Transformer Chemistry Services
Practical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter By Ian Gray Transformer Chemistry Services 1 Practical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter
More informationVisit our website:
Lab Services ISO/IEC 17025:2005 Lab Services Lab Services MORGAN SCHAFFER, located in Montreal, Canada pioneered Dissolved Gas Analysis (DGA) in America. Almost 50 years of experience in transformer oil
More informationEnhance Power Equipment Reliability with Predictive Maintenance Technologies
Enhance Power Equipment Reliability with Predictive Maintenance Technologies November 2012/1910DB1208 by S. Frank Waterer, Electrical Engineerinig, Fellow Schneider Electric USA, Inc. Make the most of
More informationDGA Method-Based ANFIS Expert System for Diagnosing Faults and Assessing Quality of Power Transformer Insulation Oil
Modern Applied Science; Vol. 10, No. 1; 2016 ISSN 1913-1844 E-ISSN 1913-1852 Published by Canadian Center of Science and Education DGA Method-Based ANFIS Expert System for Diagnosing Faults and Assessing
More informationPrediction of the Characteristics of Transformer Oil under Different Operation Conditions
Prediction of the Characteristics of Transformer Oil under Different Operation Conditions EL-Sayed M. M. EL-Refaie, Mohamed R. Salem, and Wael A. Ahmed Digital Open Science Index, Electrical and Computer
More informationFeatured Product. Transformer Monitoring and Diagnostic Systems
Featured Product Transformer Monitoring and Diagnostic Systems Transformer Predictive Analysis Owners of critical transformer equipment can realize the benefits of predictive analysis on transformer health
More informationTransformer Program. Trevor Foster Electrical Engineering, Manager Calpine Corporation April 16 17, 2013
Transformer Program Trevor Foster Electrical Engineering, Manager Calpine Corporation April 16 17, 2013 Overview of Calpine Established in 1984 One of the largest Independent power producers in the U.S.,
More informationComponents, Systems and Service for Transformers.
Components, Systems and Service for Transformers. HYDAC Headquarters in Germany HYDAC China Your Professional Partner for the Optimization of Transformers. With over 5,500 employees worldwide HYDAC is
More informationoil standards TRUE NORTH AND ATLANTIS
oil standards TRUE NORTH AND ATLANTIS Accuracy Matters Accurate lab data is critical to sound decision making. Running certified oil standards is the ideal way to ensure the accuracy of your DGA results.
More informationTHE APPLICATION OF NEWFOUNDLAND AND LABRADOR HYDRO (Hydro) STATES. 1. Hydro is a corporation continued and existing under the Hydro Corporation Act,
IN THE MATTER OF the Electrical Power Control Act, RSNL 1994, Chapter E-5.1 (the EPCA) and the Public Utilities Act, RSNL 1990, Chapter P-47 (the Act), and regulations thereunder; AND IN THE MATTER OF
More informationOil Regeneration in 132kV and 33kV Transformers 6 December 2017
1 Oil Regeneration in 132kV and 33kV Transformers 6 December 2017 Paul Marshall Innovation Project Manager Agenda Introduction Research IFI oil regeneration project Oil regeneration results Oil regeneration
More informationIEC Publication [1] provides a coded list of faults
F E A T U R E A R T I C L E A Review of Faults Detectable by Gas-in-Oil Analysis in Transformers Key Words: Transformer, fault, dissolved gas analysis IEC Publication 60599 [1] provides a coded list of
More informationOn Site Dissolved Gas Analysis for Transformer Condition Assessment. Robin Watson - Kelman UK Karl Smith - Kelman Africa Henk Fourie - Kelman Africa
On Site Dissolved Gas Analysis for Transformer Condition Assessment Robin Watson - Kelman UK Karl Smith - Kelman Africa Henk Fourie - Kelman Africa Catastrophic Failure of Transformers The state of the
More informationFAILURE ANALYSIS OF POWER TRANSFORMERS BY DGA, OIL TESTS AND MARKOV APPROACH
FAILURE ALYSIS OF POWER TRANSFORMERS BY DGA, OIL TESTS AND MARKOV APPROACH Mohammed Abdul Rahman Uzair Research Scholar, Department of EEE, GITAM University, Hyderabad, Telangana, INDIA Dr. Basavaraja
More informationTransformer Monitoring
100x 100x Offshore 100x-3/-2/-1 Load Voltage kv ma Load Current Ambient Oil Position Top Oil Bottom Oil MS-7 X1 X2 X3 H3 H1 Bushing Monitor ZVCM-1001 Transformer Monitoring Overview of modular system components
More informationPROGRESS IN PAPER DEGRADATION ASSESSMENT IN SERVICE-AGED TRANSFORMERS
PROGRESS IN PAPER DEGRADATION ASSESSMENT IN SERVICE-AGED TRANSFORMERS H. Ding, R. Heywood, J. Lapworth, S. Ryder and A. Wilson Presenter: Dr Hongzhi Ding Doble PowerTest Ltd UK INSUCON - 17 th May 2017
More informationCIGRE 16 BRUGGE Partial Discharge and Dissolved Gas Analysis In bio-degradable transformer oil. The University of New South Wales Australia
CIGRE 16 BRUGGE 2007 Partial Discharge and Dissolved Gas Analysis In bio-degradable transformer oil D. IMAMOVIC *, K.X. LAI, N.A. MUHAMAD, B.T. PHUNG and T.R. BLACKBURN # The University of New South Wales
More informationData Mining Approach With IEC Based Dissolved Gas Analysis For Fault Diagnosis Of Power Transformer
Data Mining Approach With IEC Based Dissolved Gas Analysis For Fault Diagnosis Of Power Transformer Ms Kanika Shrivastava M.E. in H.V.P.S. Electrical Engineering, JEC, Jabalpur, (M.P) Mr. Ashish Choubey
More informationResidual Life assessment with DGA, Furan content in transformer oil and Degree of polymerization of solid insulation
International Journal of Scientific and Research Publications, Volume 6, Issue 7, July 2016 230 Residual Life assessment with DGA, Furan content in transformer oil and Degree of polymerization of solid
More informationTransformer Life Extension. CJC V30 Transformer Oil Vacuum Filtration Unit and Ion Exchange Filtration Units
Transformer Life Extension CJC V30 Transformer Oil Vacuum Filtration Unit and Ion Exchange Filtration Units Agenda Examples of V30 installations Background info Theory Field results Added safety Conclusion
More informationExpertise method to diagnose transformer conditions
Expertise method to diagnose transformer conditions J. BILBAO, C. M. REBOLLO, and P. GONZÁLEZ Applied Mathematics Department. University of the Basque Country Engineering School, Alda. de Urquijo s/n,
More informationTransformer is gassing-what to do
Transformer is gassing-what to do V.V. Sokolov Scientific and Engineering Center ZTZ-Service Company, Dnepropetrovskoye shosse, 99 Zaporozhye, Ukraine Phone: (38)-()-595-87; Fax: (38)-()-5-498 Z. Berler,
More informationMOISTURE IN PAPER ASSESSMENT FROM CONTINUOUS MONITORING OF MOISTURE IN OIL. GE Energy
MOISTURE IN PAPER ASSESSMENT FROM CONTINUOUS MONITORING OF MOISTURE IN OIL Jacques Aubin GE Energy Brian D Sparling Abstract Moisture content of solid insulation is a persistent concern for power transformer
More informationAvailable online at ScienceDirect. Study on Dissolved Gas Due Tue Thermally Degraded Insulating Paper in Transformer Oil
Available online at www.sciencedirect.com ScienceDirect Procedia Technology 11 ( 2013 ) 257 262 The 4th International Conference on Electrical Engineering and Informatics (ICEEI 2013) Study on Dissolved
More informationUniversity of Cape Town
The copyright of this thesis vests in the author. No quotation from it or information derived from it is to be published without full acknowledgement of the source. The thesis is to be used for private
More informationUnderstanding the Breakdown Mechanism of Bushings and Implementing Appropriate Life-Cycle Oriented Maintenance Strategies
Understanding the Breakdown Mechanism of Bushings and Implementing Appropriate Life-Cycle Oriented Maintenance Strategies By Thomas Schuette, Emmanuel Santos Understanding the Breakdown Mechanism of Bushings
More informationCONDITION-BASED ASSESSMENT OF ON-LOAD TAP CHANGERS
ISSUE 66 CONDITION-BASED ASSESSMENT OF ON-LOAD TAP CHANGERS By I.A.R. Gray transformer division manager, WearCheck Condition Monitoring Specialists I.A.R. Gray transformer division manager, WearCheck INTRODUCTION
More informationAnil Kumar*, Ajay Rathore** Ashish Patra ***
Analysis of Power Transformer using fuzzy expert and neural network system Anil Kumar*, Ajay Rathore** Ashish Patra *** Electrical Department MITS Gwalior (MP)INDIA474002 Abstract- Power transformers being
More informationTurning data from monitoring and condition assessment into transformer reliability information
1 Turning data from monitoring and condition assessment into transformer reliability information or dealing with the Big Data tsunami! Craig L Stiegemeier Director of Technology and Business Development
More informationOnline Condition Monitoring of Transformer
Online Condition Monitoring of Transformer ---------------------------------------------------- Heart of any power system An essential Part of a Cost efficient maintenance Program. It is well known that
More informationExample of Information for EOL Projects. American Municipal Power October 19, 2017
Example of Information for EOL Projects American Municipal Power October 19, 2017 Baseline Project: Description of Project Add detailed map for all facilities mentioned for Problem Statement: PJM/NERC/TO
More informationGas-in-oil and moisture-in-oil Standards
Gas-in-oil and moisture-in-oil Standards Accuracy Matters Accurate lab data is critical to sound decision making. Running certified oil standards is the ideal way to ensure the accuracy of your DGA results.
More informationQuality assessment of 11 KV transformer by internal dissolved gas analysis using CFD
INTERNATIONAL JOURNAL OF INNOVATIVE RESEARCH IN ELECTRICAL, ELECTRONICS, INSTRUENTATION AND CONTROL ENGINEERING Quality assessment of 11 KV transformer by internal dissolved gas analysis using CFD ithu
More informationPower Transformer Fault Detection and Isolation based on Intuitionistic Fuzzy System
Power Transformer Fault Detection and Isolation based on Intuitionistic Fuzzy System 1 Manikandan Pandiyan, 2 Geetha Mani, Department of Instrumentation and Control Systems Engineering PSG College of Technology,
More informationRemnant Life Estimation of Power Transformers Based on Chemical Diagnostic Parameters Using Adaptive Neuro- Fuzzy Inference System
Faculty of Science and Engineering Department of Electrical and Computer Engineering Remnant Life Estimation of Power Transformers Based on Chemical Diagnostic Parameters Using Adaptive Neuro- Fuzzy Inference
More informationQ & A on Moisture in Transformer Oil
Q & A on Moisture in Transformer Oil A unique opportunity to answer your specific questions about Moisture in Transformer Oil Behavior Steven Jiroutek Business Development Manager - Industrial Measurements
More informationTRANSFORMER OIL ANALYSIS
A member of the Set Point group I S S U E 3 6 TRANSFORMER OIL ANALYSIS By Neil Robinson, B.Sc. Hons. A basic introduction to an essential part of a cost-efficient maintenance programme It is well known
More informationThe analysis of electrical and mechanical faults in power transformers by Fuzzy expert system
Scientific Research and Essays Vol. 5 (24), pp. 4018-4027, 18 December, 2010 Available online at http://www.academicjournals.org/sre ISSN 1992-2248 2010 Academic Journals Full Length Research Paper The
More informationTransformers are the heart of an
98 Technical Article Reliability of Electrical Systems: From Testing to Monitoring Specific data from a fault gas monitor study will be presented, as well as a test case that focuses on the relationship
More informationBachelor of Electrical Engineering (Industrial Power)
TRANSFORMER DISSOLVED GAS ANALYSIS USING DUVAL TRIANGLE METHOD VIA ANDROID Mohamad Hafiz Bin Abdul Wahid Bachelor of Electrical Engineering (Industrial Power) June 2014 " I hereby declare that I have read
More informationInternational Trends in Asset and Maintenance Management through Enhanced Monitoring and Diagnostics of Electrical Facilities
International Trends in Asset and Maintenance Management through Enhanced Monitoring and Diagnostics of Electrical Facilities Presented by Tony McGrail, Kenneth Elkinson Doble Engineering Company Agenda
More informationStudy on Thermal Ageing Characteristics of Silicone Rubber and Pressboard in Mineral Oil
Study on Thermal Ageing Characteristics of Silicone Rubber and Pressboard in Mineral Oil M.Sc. Smitha Karambar, Prof. Dr.-Ing. Stefan Tenbohlen University of Stuttgart, Institute of Power Transmission
More informationAn Overview of Online Oil Monitoring Technologies
An Overview of Online Oil Monitoring Technologies Tim Cargol Weidmann-ACTI, Inc. 71 Bishop St., Framingham, MA 01702, USA tcargol@weidmann-acti.com Abstract Several new and exciting oil monitoring technologies
More informationPomona, CA May 24 25, 2016
Pomona, CA May 24 25, 2016 Transformer Technology Seminar Modular approach on economic condition assessment for power transformer; data management, Fleet screening and risk ranking Siemens AG 2014 All
More informationAsset Health Appraisal of Transformers in Eskom's Distribution Network
Asset Health Appraisal of Transformers in Eskom's Distribution Network Adesh Singh 09/02/2017 In fulfilment of the Masters of Science, College of Agriculture, Engineering and Science, University of KwaZulu-Natal
More informationNAVSEA STANDARD ITEM. 1.1 Title: Piping System Cleanliness (Non-Nuclear); accomplish
NAVSEA STANDARD ITEM ITEM NO: 009-107 DATE: 18 JUL 2014 CATEGORY: II 1. SCOPE: 1.1 Title: Piping System Cleanliness (Non-Nuclear); accomplish 2. REFERENCES: 2.1 Standard Items 2.2 S9AAO-AB-GOS-010, General
More informationPerformance Data on Jet Compressors
Bulletin F Supp. Performance Data on Jet Compressors Description Performance Table 1 - Thermal Data for Gases Symbols Used In Thermodynamic Formulas Page Chart A - Sizing Chart for Thermocompressors (Types,,,,
More informationFailure Investigations on Electrical Motors and Transformers Dr Morris Lockwood Technical Manager, Power systems, ERA Technology Ltd
Failure Investigations on Electrical Motors and Transformers Dr Morris Lockwood Technical Manager, Power systems, ERA Technology Ltd 1 Summary Intended audience What is a failure and the consequences of
More informationPresentation to: Western Mining Electric Association
Presentation to: Western Mining Electric Association World s Largest Database of Test Records 4,000,000 Customer Transformer Test Records. World s Leading Reclaimer of Transformer Oil Over 1 Billion Gallons
More informationNAVSEA STANDARD ITEM. 1.1 Title: Piping System Cleanliness Restoration (Non-Nuclear); accomplish
NAVSEA STANDARD ITEM ITEM NO: 009-107 DATE: 18 NOV 2016 CATEGORY: II 1. SCOPE: 1.1 Title: Piping System Cleanliness Restoration (Non-Nuclear); accomplish 2. REFERENCES: 2.1 Standard Items 2.2 S9AAO-AB-GOS-010,
More informationMoisture Phenomena in Insulating Systems of Dry, Gas Insulated and Liquid Immersed Transformers & Reactors
Presenting Proposed New Reference Document Moisture Phenomena in Insulating Systems of Dry, Gas Insulated and Liquid Immersed Transformers & Reactors Prof. Valery G. Davydov, Consultant Melbourne, Australia
More informationINTEGRATED SUBSTATION CONTROL SYSTEM WITH EQUIPMENT MONITORING AND DIAGNOSTICS
INTEGRATED SUBSTATION CONTROL SYSTEM WITH EQUIPMENT MONITORING AND DIAGNOSTICS K. Caird W.J. Ros GE Harris Energy Control Systems GE Power Systems Energy Consulting Calgary, CANADA Schenectady, NY 12345
More informationELECTRICITY SUPPLY - POWER SYSTEM MAINTENANCE Carry out routine inspection and service on oil filled distribution power transformers 11kV to 400V
1 of 8 level: 4 credit: 8 planned review date: December 2006 sub-field: purpose: entry information: Electricity Supply People credited with this unit standard are able to: prepare for routine service transformers
More informationAn Approach to Power Transformer Asset Management Using Health Index
F E A T U R E A R T I C L E An Approach to Power Transformer Asset Management Using Health Index Key Words: Power transformer, health index, failure, life, age, capital plan Introduction Power transformers
More informationApplying Grey Theory Prediction Model on the DGA Data of the Transformer Oil and Using It for Fault Diagnosis
Applying Grey Theory Prediction Model on the DGA Data of the Transformer Oil and Using It for Fault Diagnosis ANJALI CHATTERJEE Electronics & Instrumentation. Central Mechanical Engineering Research Institute.
More informationADDITIONAL CONTACT INFORMATION:
RENEWABLE ENERGY Experience in the industry Bringing renewable power economically to the end customer requires today s most efficient technologies. As a leader in reliable transformer design and manufacturing,
More informationMAINTENANCE &' ASSET MANAGEMENT. 1mointwor ~
MAINTENANCE &' ASSET MANAGEMENT 1mointwor ~ Special Theme: Power Transmission The Transformer Cannot Possibly Be Down! Evaluating New Monitoring Solutions with a Business Case The cannot possibly be down!
More informationSouthside Wastewater Treatment Plant Renewable Energy Leasing Project
City of Dallas Water Utilities Department Southside Wastewater Treatment Plant Renewable Energy Leasing Project Presented to the TEC September 8, 2008 Southside Wastewater Treatment Plant Renewable Energy
More informationCASE STUDIES INVOLVING INSULATING LIQUIDS AND MATERIALS FROM THE DOBLE MATERIALS LABORATORIES
CASE STUDIES INVOLVING INSULATING LIQUIDS AND MATERIALS FROM THE DOBLE MATERIALS LABORATORIES Lance R. Lewand and Paul J. Griffin Doble Engineering Company, USA ABSTRACT This paper discusses cases that
More informationLA Engineering Academy
Laxmi Associates Consultancy Third party Inspection RLA Testing& Commissioning AMC Project Management Training 323-324, Sunplaza1, GIDC Road, Makarpura, Vadodara-390010. lxassociates@gmail.com, www.laxmiassociates.in,
More informationInside View Features and Specifications Software Version 3.0
Inside View Features and Specifications Software Version 3.0 page 1 / 15 Introduction Inside View is a software system that was conceived and designed to identify warning events rapidly from large amounts
More informationSonia Samir, PhD Civil Engineer III Parkhill, Smith & Cooper, Inc.
Sonia Samir, PhD Civil Engineer III Parkhill, Smith & Cooper, Inc. April 11, 2017 Introduction & Background 2015 Waste Greenhouse Gas sources (U.S. EPA Inventory of U.S. Greenhouse Gas Emissions and Sinks:
More informationAsset Management of Power Transformers
Asset Management of Power Transformers Prof. Dr.-Ing. C. Neumann TRANSFORM Partner Claus Neumann Study of electrical engineering at Technical University of Aachen, Germany Dr.-thesis at Technical University
More informationTrials and Tribulations of Transformers and Turbines at a Pesky Peaking Power Plant
Eugene Water & Electric Board Trials and Tribulations of Transformers and Turbines at a Pesky Peaking Power Plant NWHA Technical Seminar May 7 th, 2015 Carmen- Smith Diversion Smith Dam Storage Trail Bridge
More informationA Novel Approach for Diagnosis of Power Transformers Internal Faults Using an Electronic Nose
808 J. Basic. Appl. Sci. Res., 1(7)808-815, 2011 2011, TextRoad Publication ISSN 2090-4304 Journal of Basic and Applied Scientific Research www.textroad.com A Novel Approach for Diagnosis of Power Transformers
More informationExperience With Use of C LTC DGA Guide IEEE TRANSFORMER COMMITTEE MEETINGS
Experience With Use of C57.139 LTC DGA Guide IEEE TRANSFORMER COMMITTEE MEETINGS OCTOBER 23, 2011 JOHN PRUENTE DIR. ENG. TECHNICAL SUPPORT SPX Transformer Solutions, Inc. 2012 Outline of Presentation Background
More informationA Comparative Study of DGA and PD Test on Mineral and Biodegradable Based Transformer Insulation Oil
A Comparative Study of DGA and PD Test on Mineral and Biodegradable Based Transformer Insulation Oil Mohd Fikri Hilmi Mohd Taib, Yanuar Z. Arief, Nor Asiah Muhamad, Zuraimy Adzis Institute of Voltage &
More informationGround Fault Protection. Medium Voltage Artificial Neutrals
Ground Fault Protection Medium Voltage Artificial Neutrals Installation and Maintenance Instruction Manual 7615 Kimbel Street, Mississauga, Ontario Canada L5S 1A8 Tel: (905)673-1553 Fax: (905)673-8472
More informationHealth Index: the TERNA s Practical Approach for Transformers Fleet Management
213 Electrical Insulation Conference, Ottowa, Onterio, Canada, 2 to 5 June 213 Health Index: the TERNA s Practical Approach for Transformers Fleet Management Fabio Scatiggio TERNA RETE ITALIA SpA Via delle
More informationTransport, installation and commissioning of power transformers
EVENTS DISPATCH Transport, installation and commissioning of power transformers ABSTRACT Whilst much attention is quite rightly given to power transformer design, manufacturing and factory acceptance testing,
More informationLifetime Decisions. Investments can be planned, lifetime costs of equipment made transparent and decisions based on informed fact.
Lifetime Decisions Ageing assets, rising energy demand, and the need to deliver without outage are issues facing utilities and industries around the world. At the same time, financial constraints demand
More informationBOOSTING ENERGY PRODUCTION THROUGH CO-DIGESTION
BOOSTING ENERGY PRODUCTION THROUGH CO-DIGESTION Jennifer Dreyfus, Allwater, Adelaide, South Australia Pablo Kroff, Suez, Paris, France Ben van den Akker, SA Water, Adelaide, South Australia ABSTRACT Many
More informationWaterside Cleaning of Recovery Boilers.. Pay Now or Pay Later
Waterside Cleaning of Recovery Boilers.. Pay Now or Pay Later Norris N. Johnston Application Team Manager Water Management Technology Lacey s Spring, Alabama USA Quebec City_06202006-1 Waterside Cleaning
More informationPRODUCT SPECIFICATION
Sep., 2005 PAGE / 8 Jan. 20, 2007 PRODUCT NAME : STW-F RATING : 55 C, 000V rms No. Revised Date Revised Details Page Report Jan. 20, 2007 Emendation of Specification All - REPORTED BY: APPROVED BY: Q.M.
More informationReal World Experiences with a Plant- Based Alternative to Chemical Treatment in Cooling Water Systems
Real World Experiences with a Plant- Based Alternative to Chemical Treatment in Cooling Water Systems Steve Chewning, CWT, Southeastern Laboratories, Inc. September 2018 Companies adopting sustainable
More informationLarge Valve Oven Analyzers for Refinery Gas Analysis. ASTS 2015 Houston Shannon Coleman Application Specialist Agilent Technologies
Large Valve Oven Analyzers for Refinery Gas Analysis ASTS 2015 Houston Shannon Coleman Application Specialist Agilent Technologies 1 7890B Large Valve Oven (LVO) Isothermal Zone for Valves and Columns
More informationSolar Photovoltaic (PV) GreenSmart Energy Performance Report
Solar Photovoltaic (PV) GreenSmart Energy Performance Report 2014-2016 A GreenSmart Energy Initiative TABLE OF CONTENTS INTRODUCTION... 1 TOTAL ELECTRICAL Production... 2 MONTHLY ELECTRICAL PRODUCTION...
More informationBEYOND O&M. Shawn Maurer SEDAC Building Energy Specialist. Smart Energy Design Assistance Center (SEDAC), University of Illinois at Urbana Champaign
BEYOND O&M Shawn Maurer SEDAC Building Specialist Smart Design Assistance Center (SEDAC), University of Illinois at Urbana Champaign PRESENTATION OVERVIEW and Take away: Regular costs less over the long
More informationTransmission Owner Asset Management
Transmission Owner Asset Management Pieces of Asset Management New customers, load growth, repairs, maintenance, operational issues, etc. All the pieces make up the asset management plan for repair or
More informationTransformer Risk Assessment Considerations. Victor Sokolov José Mak Armando Bassetto Dave Hanson
Transformer Risk Assessment Considerations by Victor Sokolov José Mak Armando Bassetto Dave Hanson TRANSFORMER RISK ASSESSMENT CONSIDERATIONS Victor Sokolov ZTZ Service Armando Bassetto Jose Mak Bassetto
More information