BUILDING PERFORMANCE IMPROVEMENTS FROM NCC2019
|
|
- Lee King
- 5 years ago
- Views:
Transcription
1 BUILDING PERFORMANCE IMPROVEMENTS FROM NCC2019 DR PAUL BANNISTER, F.AIRAH FIEAUST Director, Innovation and Sustainability Energy Action (Australia) Pty Ltd PO Box 546 Belconnen ACT 2617 HONGSEN ZHANG, M.AIRAH Senior Consultant Energy Action (Australia) Pty Ltd PO Box 546 Belconnen ACT 2617 Hongsen ABOUT THE AUTHOR Dr Paul Bannister is an international authority on energy efficiency in the built environment and is a Board Member of AIRAH, IBPSA and EMANZ. Over a 25-year career in the sector he has undertaken hundreds of energy audits, been involved in scores of upgrade projects many of which have achieved energy savings in excess of 50%. Paul is also well known for his role as the primary technical author of the NABERS Energy and Water ratings for offices, hotels, shopping centres and data centres. Most recently he has led a major project to upgrade the National Construction Code, reported in this and other papers at this conference. Paul is currently working on projects in Australia, New Zealand and the UK. He has over 100 publications in the field of energy use and the built environment. ABSTRACT The National Construction Code of Australia Section J (Energy Efficiency) provisions for commercial buildings are being updated to include new stringency levels. This paper provides an overview of proposed new stringencies and uses simulation to predict the overall performance improvement in buildings based on the new provisions. The first step of the work was to establish a set of NCC 2016 compliant models across a range of building archetypes and use classes. These were then used in stringency analyses covering glazing, insulation, fans, pumps, chillers and boilers. Each of these measures was subjected to benefit cost analysis on an individual basis. Using the recommended updated stringencies, the base models were revised to a new set of models compliant with the proposed new levels of stringency. The performance of these models was then compared to the original models in order to determine the impact on total building performance and integrated benefit cost ratio. The revised models show a significant reduction in greenhouse emissions across all climate zones and building types, validating the savings potential from the proposed measures. Furthermore, most of the scenarios are predicted to be lower cost to build than the equivalent NCC2016 compliant scenarios; and where costs have increased the benefit cost ratio is acceptable in almost all cases. 1
2 INTRODUCTION Energy Action were contracted to review the current NCC Section J stringency provisions by the Australian Building Codes Board (ABCB). As a result of the review, numerous recommendations to the stringency of the future code have been proposed covering glazing, insulation, HVAC, lighting, and lifts. This paper presents an overview of major measures proposed for the NCC2019 revision of Section J, and reports on studies undertaken to ensure the sum of the individual recommendations provides a stringency that can deliver lower annual energy outcomes. IES <VE> dynamic thermal simulations are used to provide the means to qualitatively assess the energy performance for buildings compliant to NCC2016 and NCC2019 (proposed) stringencies. PROPOSED DTS MEASURES FOR NCC2019 The proposed Deemed to Satisfy measures for NCC 2019 cover all aspects of building energy consumption. The derivation of measures is described elsewhere, but in general was based on a benefit cost analysis with a target BCR of It is noted that this paper documents an intermediate stage of a 2-year code development process, and the final code requirements may differ from those presented. A number of areas where changes are already known to have occurred are identified in the footnotes. Readers are referred to the Australian Building Codes Board for the official version of any proposed code measures, which will be put through a full consultation process through The proposed measures are identified in the following sections. GLAZING NCC2016 specifies façade construction provisions on a separate wall construction and window construction basis. The wall construction must satisfy a minimum total R-Value, and the window construction must separately be assessed using the NCC glazing calculator. For NCC 2019, it is proposed to drop the glazing calculator approach in favour of an approach that specifies a maximum figure for the total solar admittance (which is the product of solar heat gain coefficient and window wall ratio, i,e., SHGC*WWR) and a maximum figure for the total U-value of the wall and window combination [Johnston et al 2017a]. This is closer to general international practice and enables the required performance to be summarised in a simple table, as shown in Table 1. 2
3 East North South West U total SHGC*WWR U total SHGC*WWR U total SHGC*WWR U total SHGC*WWR CZ CZ CZ CZ CZ CZ CZ CZ Table 1. Proposed stringency for NCC2019 showing maximum U-Value and SHGC*WWR 1 for daytime operating buildings. OPAQUE STRUCTURES No changes in stringency have been proposed for roof, wall or floor insulation, although it is noted that the wall R-values are affected significantly by the Utotal approach for the glazing in a manner that is still being resolved at the time of writing [Johnston et al 2017b]. However, it is proposed to remove many of the provisions for minor alterations to required R-values based on shading, solar absorptance, etc in order to simplify the code. It is also proposed to require that roof structures in Climate Zones 1-7 have a solar absorptance of 0.4 or less. No solar absorptance requirement is proposed for Climate Zone 8. CHILLERS, BOILERS AND PAC UNITS The NCC only makes requirements for chillers below 350kW and PAC units above 65kW because outside these side ranges the minimum efficiency of chillers is covered under MEPS. In the proposed revisions, incremental improvements have been made to the stated minimum efficiencies as shown in Table 2. Equipment Item Minimum COP 2019 (2016) Minimum IPLV 2019 (2016) Air-cooled Chillers <350kW 3.0 (2.5) 4.1 (3.4) Water cooled chillers <350kW (4.2) 6.7 (5.2) Air-cooled PAC Units >65kW 2.9 ( ) n/a Water-cooled PAC units >65kW 4.0 ( ) n/a Table 2. Proposed changes in equipment stringency for NCC2019. For boilers, the proposed NCC2019 stringency is a minimum gross thermal efficiency of 90%, which necessitates the use of a condensing boiler. Not that this only applies to space heating applications. 1 Since this paper was prepared, the U total requirements have been relaxed to 2.5W/m 2 K. 2 Since this paper was prepared, the requirements for water cooled chillers have been modified to a COP/IPLV of 4.5/6 for chillers below 200kW and 5/7.9 for chillers kW. 3
4 FAN AND PUMP SYSTEMS Under NCC2019, it is proposed to replace the current W/m 2 requirements with specific requirements as below. Minimum fan efficiencies based on ISO12759:2013 and set based on EU 2015 standards as listed in Table 3 and Table 4 [Department of Environment and Energy 2017] 3. Fan size Axial Centrifugal forward Centrifugal backward no housing Centrifugal backward with housing >125W and <0.75kW 31.4% 35.4% 47.7% 46.7% 0.75kW and <4kW 34.8% 38.8% 53.3% 52.3% 4kW and <10kW 38.5% 42.3% 59.3% 58.3% 10kW and <30kW 40.2% 44.2% 62.4% 61.4% 30kW and <185kW 41.2% 45.2% 63.7% 62.7% 185kW and <500kW 42.3% 46.3% 65.3% 64.3% Table 3. Recommended minimum wire-to-air efficiencies (%) for fans on static pressure basis. Fan size Axial Centrifugal forward Centrifugal backward no housing Centrifugal backward with housing >125W and <0.75kW 49.4% 40.4% n/a 49.7% 0.75kW and <4kW 52.8% 43.8% n/a 55.3% 4kW and <10kW 56.3% 47.3% n/a 61.3% 10kW and <30kW 58.2% 49.2% n/a 64.4% 30kW and <185kW 59.2% 50.2% n/a 65.7% 185kW and <500kW 60.3% 51.3% n/a 67.3% Table 4. Recommended minimum wire-to-air efficiencies (%) for fans on a total pressure basis. Use of turning vanes in bends. Maximum straight duct pressure drop as shown in Table 5 Maximum AHU coil and filter velocities shown in Table 6 and Table 7. Maximum Straight Duct Pressure Drop (Pa/m) Constant Speed System Maximum Straight Duct Pressure Drop (Pa/m) Variable Speed System <2000 hours hours >5000 hours <2000 hours hours >5000 hours Table 5. Proposed maximum pressure drop per metre length of straight duct. 3 Since this paper was prepared, it has been proposed to increase fan efficiency requirements to match the high efficiency requirements of the Emissions Reduction Fund. 4
5 Maximum average face velocity (m/s) 1-2 Constant Speed System Variable Speed System Coil only Coil + 1 filter ( MERV 11) Coil + 1 filter ( MERV 12) Coil + 2 filters Table 6. Proposed maximum velocities for filters and coils in a fan system 4. Constant Speed System Variable Speed System Filter Class Maximum allowable velocity (m/s) <125Pa@2.5m/s 125Pa@2.5m/s <125Pa@2.5m/s 125Pa@2.5m/s ( MERV 13) ( MERV 14) ( MERV 13) ( MERV 14) 2.5m/s 2.0m/s 2.5m/s 2.5m/s For pumps: Table 7. Proposed maximum velocities for filters in a fan system without a coil 4. A minimum pump energy efficiency standard (still being defined at the time of writing) A maximum straight pipe pressure drop as shown in Table 8. Nominal Pipe Diameter Maximum Pressure Drop (Pa/m) Constant Speed System Maximum Pressure Drop (Pa/m) Variable Speed System <2000 hours hours >5000 hours <2000 hours hours >5000 hours 20mm >20mm, <65mm mm Table 8. Proposed maximum pressure drops for pipes. 4 Since this paper was prepared, updated recommendations have simplified this table somewhat. 5
6 COOLING TOWERS The proposed stringencies for cooling towers are shown in Table 9. The major changes are an increase in stringency and a move to a uniform W fan power per kw heat rejection metric. Tower Type Induced draft 2019 (2016) Forced draft 2019 (2016) Open circuit cooling tower 10.4 W/kW (12.4) 19.5 W/kW (23.5) Closed circuit cooling tower 16.9 W/kW (19.9) n/a 5 (26.7) Evaporative Condenser 11 W/kW (18) 11 W/kW (22) Table 9. Proposed stringencies for cooling towers and evaporative condensers ECONOMY CYCLE The proposed stringency for the requirement to provide an economy cycle is somewhat relaxed from NCC2016 as shown in Table 10. Climate Zone Economy cycle required above cooling capacity (kw) NCC2019 NCC n/a n/a 2 n/a 50 3 n/a Table 10. Proposed economy cycle requirements for NCC2019. OUTSIDE AIR MANAGEMENT The provisions relating to the management of outside air have been increased in stringency as shown in Table 11 below. 5 Forced draft closed circuit cooling towers are proposed to not be available under NCC2019 due to poor efficiency. Note that we were unable to find any such towers that actually comply with the associated NCC2016 requirements. 6
7 Region HX/CO 2 OA Flow CZ1 CO 2 >500 l/s CZ2 Not required n/a CZ3 CO 2 >1000 l/s CZ4 HX or CO 2 >500 l/s CZ5 HX or CO 2 >1000 l/s CZ6 HX or CO 2 >500 l/s CZ7 HX or CO 2 >250 l/s CZ8 HX or CO 2 >250 l/s Table 11. Proposed outside air management requirements for NCC2019. LIGHTING The proposed NCC2019 lighting measures are significantly more stringent that the NCC2016, reflecting the change from fluorescent technologies to LED. The full range of proposed changes is reported elsewhere [Jolley-Rogers et al. 2017], but for the purposes of this study the major changes are as reported in Table 12. NCC2016 NCC2019 Building Class/Form IPD (W/m 2 ) IPD (W/m 2 ) 3A A B aC Table 12. Sample lighting power density revisions for NCC2019 TESTING THE MEASURES: NCC2016 VS NCC2019 The methodology used to obtain comparative energy consumption between NCC2016 and the proposed NCC2019 is as follows: 1. NCC2016 baseline models were defined and dynamic thermal simulations were ran. 2. NCC2019 test models were created making sure the proposed stringencies were met. Further to this, a benefit-cost analysis was undertaken of the NCC2019 versus NCC2016 models to understand the holistic impacts of the proposed measures. TEST BUILDINGS The four-building class/form combinations used in for the analysis are given in Table 5 below. They include models 3A, 5A, 6B and 9aC which represent hotel, office, retail and health care (clinic) occupancies respectively. These models are selected to be representative rather than comprehensive; result for other building types may vary. 7
8 Building NLA (m 2 ) Storeys Occupancy Type Floor Length (m) Floor Depth (m) Floor to Floor Height (m) Ceiling Height (m) Model 3A Hotel Model 5A Office Model 6B Retail Model 9aC Health Care Table 13. Building geometry details Screenshots of the models used are given in Figure 1, Figure 2 and Figure 3. Note that model 3A and 5A share the same building geometry but differ in the external constructions and internal loads such as equipment, people and lighting densities. Operating schedules were identical between NCC2016 and NCC2019 models. Figure 1. Model 3A and 5A, NCC2019 compliant format. Figure 2. Model 6B, NCC2019 compliant format. Figure 3. Model 9aC, NCC2019 compliant format. 8
9 For the NCC2016 models, the glazing was selected based on the largest windows that could be accommodated while just meeting compliance using common glazing types. As a result of how the glazing calculator works, this led to divergent glazing types and WWRs on different facades. For the NCC2019 models a fixed WWR of 30% 6 was used and the nature of the proposed measures meant that the glazing selection could be kept consistent between facades in almost all cases. SHGC and U value were selected to just meet compliance. A minimum 5% daylight factor was required for all NCC2019 scenarios to ensure that a minimum level of functionality was guaranteed. HVAC EQUIPMENT AND CONTROL Water cooled, hermetic centrifugal chillers with variable speed drive controlled compressors were used in the IES <VE> modelling for each climate zone. The in-built water-cooled chiller curves in IES were adjusted to match the COP requirements of NCC 2016 and NCC Non-condensing boilers were modelled for the NCC2016 scenarios. Heating hot water supply/return temperature was modelled at 80/60 C (fixed) with a rated boiler efficiency of 80%. Condensing boilers were modelled for NCC2019 DTS simulations, with a heating hot water temperature reset was modelled to be 80 C when the outside dry bulb is 4 C above design heating temperature, 60 C when the outside dry bulb is 14 C above design heating temperature and linear in between, reflecting a new control requirement proposed for NCC2019. The rated gross boiler efficiency was modelled to be 90% 7. Open circuit, induced draft cooling towers were used in both NCC2016 and NCC2019 simulations. The capacity of the cooling towers changed between NCC2016 and NCC2019 as a result of different building loads, and fan power requirements were set to comply with the measures in the respective codes. AHUs were used in model 5A and 9aC buildings with 3A and 6B models using FCUs. The AHU and FCU fan power were set up as per the NCC standards. The 2019 fan power density (W/m²) was calculated by applying all proposed limiting pressure drops and face velocities through each system component (straight duct, filters, coils etc) to the 2016 base case system. After applying these limiting factors, a revised pressure drop for the system was calculated and the resultant W/m² determined. This asserted a 40% to 50% reduction fan power between NCC2016 and NCC2019 scenarios [Balme et al 2017]. Control parameters were identical for NCC2016 and NCC2019 models. The zone set point was modelled to be 22.5 C with 1 C dead band and 1 C proportional band either side. The cooling supply air temperature was reset from 12 C to 22.5 C when the average zone temperature changes from 24 C to 23 C. The heating supply air temperature was reset from 30 C to 22.5 C when the average zone temperature changes from 21 C to 22 C. An economy cycle was incorporated into the HVAC models where required by NCC2016 and the NCC2019 proposed stringency. A dry bulb economy cycle was modelled which mixes the return air and outside air to achieve the desired supply air set point. A dry bulb lockout of 24 C and dew point lockout of 14 C was used. AHU supply air was delivered to the zones via VAV boxes. The VAV turndown was modelled at 50% for centre zones and 30% for perimeter zones. The FCU was modelled as a constant volume system. 6 As 25% of the wall faces the plenum, a 30% WWR is equivalent to a 40% WWR to the occupied space. 7 The efficiency of condensing boilers ranges from about 90% up to 98% or greater. 9
10 Electricity cost (Real 2016 $/kwh) CO2 control was used in the building simulations where instructed by NCC2016 and NCC2019 proposed stringencies. The CO2 control proportionally varies the outside air supply based on CO2 readings for each floor of the building. CO2 levels are controlled between 700 and 900 ppm using 50% outside air as supply at the lower value and 100% outside air used as supply for the higher level. No differences in pump system efficiency were modelled as the measures in this area had not yet been finalised. COST BENEFIT MODELLING Incremental capital costs were modelled using the cost models used in the benefit-cost analyses for each individual measure 8. Energy costs were modelled using forward estimate gas and electricity prices derived from AEMO forward estimates [AEMO 2016a, AEMO 2016b]. The forward price curves are shown in Figure 4 and Figure 5. It is noted that there is considerable uncertainty in the forward projection of energy costs; the AEMO data was selected as being a most probable scenario. The benefit cost analyses did not formally include sensitivity analysis, but informal assessment showed that the fundamental results determined using the stated cost assumptions were robust. Similarly, a potential carbon price was considered but omitted from the analysis on the grounds that the impact on results was not significant. $0.25 $0.20 $0.15 $0.10 $0.05 $ Year Figure 4. Forward price for electricity used in the analyses 8 Requests for more complete reportage on these analyses should be directed to the Australian Building Codes Board. 10
11 Gas Cost (2016 Real $/GJ) $30.00 $25.00 $20.00 $15.00 $10.00 $5.00 $ Figure 5. Forward price for gas used in the analyses For benefit cost analyses, component lives of 15 years were assumed for lighting and air-cooled equipment; 25 years for HVAC generally and 40 years for façade elements. A 7% discount rate was used in line with Federal Government guidelines. For each individual measure, a target of achieving an outcome of a benefit cost ratio of was set by the ABCB. This was assessed individually for each measure in order to set stringency. RESULTS The results show a significant reduction in energy use across almost all scenarios as shown in Table 14. Change in Annual Energy Use (%) Location 3A 5A 6B 9aC Climate Zone 1-10% -32% -37% -41% Climate Zone 2-37% -45% -39% -45% Climate Zone 3-31% -38% -39% -49% Climate Zone 4-32% -37% -37% -37% Climate Zone 5-36% -43% -43% -43% Climate Zone 6-33% -40% -39% -37% Climate Zone 7-35% -44% -38% -18% Climate Zone 8 4% -13% -28% 4% Table 14. Change in annual energy use as a result of NCC2019 stringency. Expressing the annual energy use in terms of greenhouse gas emissions (kg CO2 equivalent), the reduction from implementing the proposed NCC2019 stringency is significant, as shown in Table
12 Change in GHG Emissions (%) Location 3A 5A 6B 9aC Climate Zone 1-10% -32% -37% -41% Climate Zone 2-37% -45% -40% -46% Climate Zone 3-33% -36% -41% -52% Climate Zone 4-39% -39% -41% -44% Climate Zone 5-38% -43% -46% -46% Climate Zone 6-43% -46% -46% -48% Climate Zone 7-44% -49% -38% -38% Climate Zone 8-34% -38% -31% -31% Table 15. Change in annual greenhouse gas emissions as a result of NCC2019 stringency The change in capital costs between NCC2016 and the proposed NCC2019 was evaluated separately for an NCC2019 compliant case with a 30% WWR case and an equivalent performance NCC2019 compliant 45% WWR case. Results are shown in Table 16. Note that the percentage change refers only to the capital costs of the elements affected by the measures, rather than the cost of the whole building. In terms of a benefit cost ratio, the NCC2019 stringency compares to the NCC2016 provisions as found in Table 17. Location Modelled WWR 3A 5A 6B 9aC Climate Zone 1 30% -41% -52% -27% -23% 45% -5% -20% 13% 25% Climate Zone 2 30% -35% -33% -28% -30% 45% 5% 10% 9% 14% Climate Zone 3 30% -43% -22% -33% -36% 45% -9% 26% 2% 2% Climate Zone 4 30% -48% -38% -25% -26% 45% -18% 2% 12% 18% Climate Zone 5 30% -49% -24% -32% -35% 45% -19% 25% 4% 4% Climate Zone 6 30% -43% -29% -17% -19% 45% -9% 18% 25% 28% Climate Zone 7 30% -46% -49% -32% -34% 45% -13% -19% 2% 2% Climate Zone 8 30% -49% -43% -34% -27% 45% -10% -1% 10% 22% Table 16. Change in capital costs for building elements affect by code compliance between NCC2016 and NCC
13 Model Information Benefit Cost Ratios Location Modelled WWR 3A 5A 6B 9aC Climate Zone 1 30% negative cost negative cost negative cost negative cost 45% negative cost negative cost Climate Zone 2 30% negative cost negative cost Negative cost negative cost 45% Climate Zone 3 30% negative cost negative cost negative cost negative cost 45% negative cost Climate Zone 4 30% negative cost negative cost negative cost negative cost 45% negative cost Climate Zone 5 30% negative cost negative cost negative cost negative cost 45% negative cost Climate Zone 6 30% negative cost negative cost negative cost negative cost 45% negative cost Climate Zone 7 30% negative cost negative cost negative cost negative cost 45% negative cost negative cost Climate Zone 8 30% negative cost negative cost negative cost negative cost 45% negative cost negative cost Table 17. Benefit cost ratio summary for models with WWRs of 30% and 45%. DISCUSSION ENERGY AND EMISSIONS IMPACTS The results in Table 14 show that the proposed measures have a significant impact on energy use across all models and most climate zones. The exception is climate zone 8, where energy use rises as a result of increased heating loads; this is caused partly by the generally higher façade stringency of NCC2016 in this climate zone, and partly by the reduction in internal gains arising from the reduction in lighting power. Underlying the NCC2016/NCC2019 façade stringency difference is the fact that the analysis for NCC2019 uses a greenhouse gas basis rather than an unweighted energy total as used for NCC2016 and earlier; this change reduces the prioritisation of heating in NCC2019 relative to NCC2016. The results for achieved greenhouse gas savings are consistently beneficial, as can be seen in Table 15. CAPITAL COSTS AND BENEFIT COST RATIOS The incremental capital costs associated with the proposed changes under NCC2019 are dominated the reduced capital costs associated with the use of smaller windows 9. The high cost of façade means that even a moderate reduction in glazed area dominates the cost increases associated with other measures. As a result, the majority of scenarios for NCC2019 are actually cheaper than those 9 Opaque insulated wall costs were estimated at $198-$239/m 2, compared to glazing system costs used in this study of $225-$1245/m 2 plus $625/kW for increases in plant capacity. In later work, the glazing costs were revised based on industry feedback to a range of $302-$597/m 2, reducing this difference but still maintaining a significant additional cost for glazing relative to opaque wall. 13
14 for NCC2016. Where costs are larger, the benefit cost ratio is typically larger than 1, indicating an acceptable outcome under the economic framework set for the code upgrade. CONCLUSIONS The proposed DTS measures for NCC2019 represent a significant upgrade relative to the current code. Measures include more stringent requirements for glazing, lighting, and most HVAC components, mostly unchanged requirements for insulation and some relaxation of requirements for economy cycle installation. Modelling of four case study buildings under NCC2016 and proposed NCC2019 compliance scenarios shows greenhouse gas emission reductions mainly in the region of 31-49%. Assessment of capital costs shows that incremental costs are dominated by decisions on window wall ratio, as windows are significantly more expensive than opaque wall to build. The generally smaller WWR proposed under NCC2019 therefore results in lower capital costs in most scenarios. Where costs are higher than NCC2016, the benefit cost ratio is generally above 1, indicating that the overall suite of measures is viable on a whole building basis. REFERENCES 1. AEMO 2016a National Electricity Forecasting Report, Australian Energy Market Operator AEMO 2016b. National Gas Forecasting Report for Eastern and South Eastern Australia, Australian Energy Market Operator, December Balme et al Proposed Fan Measures for NCC2019 T. Balme, P. Bannister, H. Zhang, J. Spears, D. Johnston, AIRAH Future of HVAC Conference, Sydney, August Department of Energy and Environment E3 Consultation RIS for Fans, March Johnston et al 2017a Glazing studies for NCC2019 D. Johnston, H. Zhang, G. Wang, P. Bannister. AIRAH and IBPSA s Australasian Building Simulation 2017 Conference, Melbourne, November Johnston et al 2017b Roof, Walls and Floor insulation Study for NCC2019 D. Johnston, G. Wang, H. Zhang, P. Bannister AIRAH and IBPSA s Australasian Building Simulation 2017 Conference, Melbourne, November Jolley-Rogers et al Modelling for Potential Increases in Lighting Power Density Stringency in Section J6 of the NCC C. Jolley-Rogers, L. Boland, P. Bannister. AIRAH and IBPSA s Australasian Building Simulation 2017 Conference, Melbourne, November
GLAZING STUDIES FOR THE NATIONAL CONSTRUCTION CODE 2019
GLAZING STUDIES FOR THE NATIONAL CONSTRUCTION CODE 2019 DANIEL JOHNSTON Graduate Consultant, Projects & Advisory Services Division Energy Action Unit H, 58-69 Lathlain St Belconnen ACT 2617 daniel.johnston@energyaction.com.au
More informationProceedings of BS2013: 13th Conference of International Building Performance Simulation Association, Chambéry, France, August 26-28
HVAC CONTROL SIMULATION STUDY FOR AUSTRALIAN OFFICE BUILDINGS Hongsen Zhang and Paul Bannister Exergy Australia Pty Ltd, Canberra, Australia hongsen@xgl.com.au; paul@xgl.com.au ABSTRACT This paper presents
More informationProceedings of BS2015: 14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.
OPTIMISATION OF SUPPLY AIR TEMPERATURE CONTROLS FOR VAV SYSTEMS IN TEMPERATE AUSTRALIA Paul Bannister, Hongsen Zhang Energy Action (Australia) Pty Ltd, Canberra, Australia Paul.Bannister@energyaction.com.au;
More informationWhat simulation can tell us about building tuning
What simulation can tell us about building tuning Dr Paul Bannister, M.AIRAH, Hongsen Zhang Projects and Advisory Services Division Energy Action Pty Ltd (incorporating Exergy Australia Pty Ltd) ABSTRACT
More informationProposed Fan System Measures for NCC Section J, 2019
Proposed Fan System Measures for NCC Section J, 2019 Existing NCC 2016 DTS fan measures why change? Proposed NCC 2019 fan measures component based approach 2019 compliance methodology Comparison between
More informationTHE IMPACT OF GLAZING SELECTION ON DAYLIGHTING AND ENERGY PERFORMANCE FOR AN OFFICE BUILDING IN CANBERRA
THE IMPACT OF GLAZING SELECTION ON DAYLIGHTING AND ENERGY PERFORMANCE FOR AN OFFICE BUILDING IN CANBERRA Peter Taylor, Hélène Duponchel, and Paul Bannister Exergy Australia Pty Ltd PO Box 546 Belconnen
More informationGreat Ocean Rd Ice Creamery
Great Ocean Rd Ice Creamery BCA Section J - JV3 Compliance Report Revision: 01 Job No: 2171 Date: 7 July 2015 ADP Consulting Pty Ltd Level 10, 10 Queens Rd, Melbourne Vic 3004 www.adpconsulting.com.au
More informationEvaluation of Energy Savings of the New Chinese Commercial Building Energy Standard
Evaluation of Energy Savings of the New Chinese Commercial Building Energy Standard Wei Feng, Ke Huang, Mark Levine and Nan Zhou, Lawrence Berkeley National Laboratory Shicong Zhang, Lawrence Berkeley
More informationEnergy Efficiency in Building Active Design Part II
Energy Efficiency in Building Active Design Part II Presented by: CK Tang BSEEP Component 4 Manager Veritas Enviornment Sdn Bhd ck.tang@veritas.com.my Air Conditioning System System Sizing 1 Current Industry
More information275 GEORGE STREET, BRISBANE CASE STUDY. Andrew Gentner Norman Disney & Young, Spring Hill QLD, Australia
275 GEORGE STREET, BRISBANE CASE STUDY Andrew Gentner Norman Disney & Young, Spring Hill QLD, Australia ABSTRACT 275 George Street, Brisbane provides approximately 40,000m² of A Grade commercial office
More informationGreen Star Shopping Centre Design PILOT Energy Calculator Guide
Green Star Shopping Centre Design PILOT Energy Calculator Guide Prepared by: Advanced Environmental Green Building Council of Australia Page 1 of 29 EXECUTIVE SUMMARY The Green Star Shopping Centre Design
More informationChapter 4. Analysis of Building Energy Performance
Chapter 4 Analysis of Building Energy Performance 128 4.1 Introduction This chapter deals with energy modeling and simulation of the baseline models for the buildings to assess energy performance of the
More informationGreen Star Design & As Built Submission Template
Green Star Design & As Built Submission Template Ensure all prompts shown in Blue text have been responded to. Design Review / As Built Submission [Delete as appropriate] Credit: ENE Greenhouse Gas Emissions
More informationThe Impact of VISIONWALL High Performance Windows on the Northern Telecom Building in Ottawa, Ontario
The Impact of VISIONWALL High Performance Windows on the Northern Telecom Building in Ottawa, Ontario Visionwall Technologies Inc. 14904-123 Avenue Edmonton, Alberta, Canada T5V 1B4 Tel: 403 451 4000 Fax:
More informationSURNA Grow Facility: Systems Comparison - IEA
SURNA Grow Facility: Systems Comparison - IEA May 2016 SURNA Grow Facility This analysis provides the projected energy and associated cost comparison between the Surna proposed facility in comparison to
More informationModular Active Chilled Beams
Modular Active Chilled Beams Presented by: Darren Alexander, P.Eng. Modular Active Chilled Beams Current System Solutions Fan Coil Units - Medium/High energy, medium noise solution. Output = 100-200 w/m
More informationENERGY CALCULATOR & MODELLING PROTOCOL
Green Star SA Retail Centre v1 ENERGY CALCULATOR & MODELLING PROTOCOL GUIDE VERSION 1.1 Last Update: 17 June 2010 1 Executive Summary The Green Star SA Retail Centre v1 rating tool has been developed to
More informationPARK PLACE CASE STUDY VANCOUVER. Heat reclaim system expected to reduce steam consumption 80%, GHG emissions 68%
Heat reclaim system expected to reduce steam consumption 80%, GHG emissions 68% Address 666 Burrard St, Vancouver Management QuadReal Property Group Type of Building Office Year of Construction 1984 Number
More informationGreen Star Multi Unit Residential Calculator Guide
Green Star Multi Unit Residential Energy Calculator Guide 1 EXECUTIVE SUMMARY The Green Star Multi Unit Residential Energy Calculator has been developed to predict the performance of multi-unit residential
More informationMarket size and energy consumption of Korean building sector
Market size and energy consumption of Korean building sector Weather Condition of South Korea (Seoul) Target year for Net-ZERO BUILDING by countries - HDD : 2800-2950 Seoul - CDD : 750-908 Source : Towards
More informationEnergy simulation of existing buildings and refurbishments
Energy simulation of existing buildings and refurbishments Ania Hampton, B.Eng, M.AIRAH Hampton Sustainability 1. ABSTRACT Energy and thermal simulation is a valuable tool in the refurbishment of buildings.
More informationIECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST
IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST ENVELOPE REQUIREMENTS Project: Date: Instructions RECOMMENDED: List performance values, note exceptions that were applied, or provide other
More informationEnergy Efficiency Potential in Existing Building
Energy Efficiency Potential in Existing Building JKR HQ, Block F, Jalan Sultan Salahuddin Presented by: CK Tang CK@GBEET.COM BSEEP Consultant Building Energy Index (with Solar PV) Measured LEO (2004) 100
More informationNCC 2019 Proposed Provisions Insights from Case Study
NCC 2019 Proposed Provisions Insights from Case Study PC Thomas Director pcthomas@teamcatalyst.com.au +61 417 405 478 Aysh Venkatesan Associate aysh@teamcatalyst.com.au Dr Peter Lyons Fenestralia peter.lyons@fenestralia.com
More informationINCENTIVE ESTIMATOR HVAC USER GUIDE CONTENTS FLORIDA CUSTOM INCENTIVE PROGRAM
INCENTIVE ESTIMATOR HVAC USER GUIDE FLORIDA CUSTOM INCENTIVE PROGRAM CONTENTS 1. Getting Started... 2 2. Measure Tool Description... 3 2.1. Appropriate Use of the Tool... 3 2.2. Applicable Types of Air
More informationERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD (I-P edition) Energy Standard for Buildings Except Low-Rise Residential Buildings.
ERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD 90.1-2010 (I-P edition) Energy Standard for Buildings Except Low-Rise Residential Buildings March 8, 2018 The corrections listed in this errata sheet apply to
More informationEnergy Recovery Process Cooling Example. Presentation - Overview. Air Change Australia Pty Ltd. Air Change Energy Recovery Range
2 Presentation - Overview Energy Recovery Range + Designing Plant Rooms for Energy Efficiency The Company and the Technology Energy Recovery Product Range Product Range Pre-conditioners vs ERV-AHU s Energy
More informationItalcementi Center for Research and Innovation
Italcementi Center for Research and Innovation Bergamo, Italy LEED-NC v2.1 EAc1 A. Project Narrative (Viridian) analyzed the energy use of the proposed Italcementi Center for Research and Innovation located
More informationSECTION H ENERGY EFFICIENCY TABLE OF CONTENTS UNSW DESIGN & CONSTRUCTION REQUIREMENTS WEB ENTRY PAGE
SECTION H ENERGY EFFICIENCY TABLE OF CONTENTS UNSW DESIGN & CONSTRUCTION REQUIREMENTS WEB ENTRY PAGE SECTION A INTRODUCTION SECTION B DEVELOPMENT & PLANNING SECTION C ARCHITECTURAL REQUIREMENTS SECTION
More informationHVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya
HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya (vahid.vakiloroaya@engineer.com) ABSTRACT: The overall attainable reduction in energy consumption and enhancement of
More informationAssessment of Building Energy Performance for EEMs A Case Study in Mumbai
Assessment of Building Energy Performance for EEMs A Case Study in Mumbai Mr. Tej Singh Chouhan #1, Dr. (Prof.) Ashish Dutt Sharma *2 # Research Scholar in Mechanical Engineering JJT University, Vidyanagari,
More information201 Charlotte Street, Brisbane, Queensland
201 Charlotte Street, Brisbane, Queensland Building Profile Building Construction date 1983 Refurbishment date 2001 Owner Building Size Refurbishment Team Building Management Awards Ratings Overview 201
More informationCost Benefits of SunGuard SN 54
Cost Benefits of SunGuard SN 54 Guardian Industries recently introduced SunGuard SN 54 low-e glass. This new low-e glass is clear in appearance and has optimal energy performance for commercial building
More informationCase study of an ECBC Compliant, Energy Efficient Building: Aranya Bhawan, Jaipur
Case study of an ECBC Compliant, Energy Efficient Building: Aranya Bhawan, Jaipur Prashant Bhanware (BEEP) 2 nd REGIONAL WORKSHOP ON ECBC IMPLEMENTATION IN STATES March 15 & 16, 2017 Hyatt, Ahmedabad Outline
More informationContact Details: Phone Fax . Work Description: New Building Extensions Refurbishment Change of Use. Yes No Method:
BCA Section J- Energy Efficiency Deemed- to- Satisfy Provisions Assessment Sheet 1. Project Overview Client Name: Address: Contact Person: Contact Details: Phone Fax Email Project: Work Description: New
More informationERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD (I-P edition) Energy Standard for Buildings Except Low-Rise Residential Buildings.
ERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD 90.1-2010 (I-P edition) Energy Standard for Buildings Except Low-Rise Residential Buildings April 17, 2013 The corrections listed in this errata sheet apply to
More informationDEVELOPMENT OF A HIGH-PERFORMANCE OFFICE BUILDING SIMULATION MODEL FOR A HOT AND HUMID CLIMATE
Eleventh International IBPSA Conference Glasgow, Scotland July 27-3, 29 DEVELOPMENT OF A HIGH-PERFORMANCE OFFICE BUILDING SIMULATION MODEL FOR A AND HUMID CLIMATE Soolyeon Cho 1 and Jeff S. Haberl 2 1
More informationOptimized System for Your Bottom Line. Trane Training Class 1 Dec, 2017
Optimized System for Your Bottom Line Trane Training Class 1 Dec, 2017 Total Cost of Ownership Setting your system for great payback Where is money spent over a 30 year lifetime? First Cost 4.9% Service
More informationBCA Section J Compliance Report. Alterations & Additions to Cottage at St Johns College 10 Missenden Road Camperdown
BCA Section J Compliance Report Alterations & Additions to Cottage at St Johns College 10 Missenden Road Camperdown Prepared by: Gradwell Consulting ABN 68 872 791 784 Sustainability Consultants PO Box
More informationRetail Centre. Green Star - Calculator Guide. Date Issued: April 2009
Green Star - Retail v1 Energy Calculator Guide April 2009 1 EXECUTIVE SUMMARY The Green Star Retail v1 rating tool has been developed to assess the environmental attributes of new and refurbished retail
More informationThe commercial units were modelled as 2 separate units, please refer figure 1.1 and 1.2 for model details.
1.0 Introduction As part of the design for Plot G, a model was created of the commercial units which are located on the ground floor of the development, to calculate the carbon emissions. This model has
More informationAppendix E-1f: Small Building Methodology for Pre-SB2030 Projects
Appendix E-1f: Small Building Methodology for Pre-SB2030 Projects Prescriptive Bundle Option Method for Office Buildings less than 30,000 GSF This section describes energy strategy requirements for three
More informationGreen Star - Education v1
Green Star - Education v1 Energy Calculator Guide January 2009 EXECUTIVE SUMMARY The Green Star Education v1 rating tool has been developed to assess environmental attributes of new and refurbished education
More informationOptimise the Specification of a Building Envelope
Optimise the Specification of a Building Envelope Introduction The building under analysis is to be used as a relaxation and study place for the doctors of a major clinic in Santiago, Chile. The first
More informationEffective Energy Modeling WGBA Leadership Conference October 19, 2005
Effective Energy Modeling WGBA Leadership Conference October 19, 2005 Steven Carlson, P.E. CDH Energy Corp. Evansville, WI www.cdhenergy.com Presentation Overview What Why How Illustrated by experiences
More informationAustralian Solar Cooling Interest Group (ausscig) Conference Financial analysis of solar cooling systems in Australia
Financial analysis of solar cooling systems in Australia Dan Wu, Lu Aye, Priyan Mendis & Tuan Ngo Presenter: Dan Wu Renewable Energy and Energy Efficiency Group Melbourne School of Engineering, The University
More informationGreen Building Parameters & Case Studies
Green Building Parameters & Case Studies 14 th March, 2015 Mumbai Abdullah Nisar Siddiqui abdullah.nisar.siddiqui@undp.org Presentation Coverage 1. Energy Scenario in the Country 2. Green / Energy Efiicient
More informationGreen Star Education v1
Green Star Education v1 Energy Calculator Guide December 2009 Revision b EXECUTIVE SUMMARY The Green Star Education v1 rating tool has been developed to assess environmental attributes of new and refurbished
More informationAvailable online at ScienceDirect. The latest demonstrated technical innovations in Sydney CBD tall building.
Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 00 (2017) 000 000 www.elsevier.com/locate/procedia International High- Performance Built Environment Conference A Sustainable
More informationMGA Campus Building Greenhouse Gas Emissions Summary
MGA Campus Building Greenhouse Gas Emissions Summary Prepared for MGA Entertainment Date 4/16/214 Prepared by CONTENTS 1. Executive Summary... 3 2. Greenhouse Gas Emissions Assumptions... 4 3. Summary
More informationatspaceltd.co.uk SBEM Checklist Version 1.0 January 2017 Call us today on to speak with an adviser or visit atspaceltd.co.
Version 1.0 January 2017 SBEM Checklist Call us today on 0800 917 8922 to speak with an adviser or visit SBEM Checklist This checklist is split into four sections. Section 1 Project/Client details. Section
More informationEnergy modeling in IDA ICE according to ASHRAE , app. G
Energy modeling in IDA ICE according to ASHRAE 90.1-2007, app. G About this document This document is a user s guide for a relatively experienced IDA ICE operator for using the 90.1 add-in and for performing
More informationBack to basics: Green HVAC design. Green Star Design and As-built What you need to know. Karen Hovenga Sustainability Consulting
Back to basics: Green HVAC design Green Star Design and As-built What you need to know M.AIRAH karen@khovenga.com.au 24 June 2015 Green Star Design & As Built assesses the design and construction of any
More informationEcolibrium. Living landmark Barangaroo International Towers Sydney scores world-first WELL rating. MAY 2018 VOLUME 17.4 RRP $14.95
Ecolibrium MAY 2018 VOLUME 17.4 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001 Living landmark Barangaroo International Towers Sydney scores world-first WELL rating. PEER-REVIEWED TECHNICAL PAPERS
More informationSection 2: Estimating Energy Savings and Incentives
Section 2: Estimating Energy and Incentives 2.1 Estimating Energy and Incentives... 2 2.2 Customized Measures - Estimation Software... 2 2.2.1 AC&R I - High Efficiency Chiller... 4 2.2.2 AC&R I - Split/Packaged
More informationThe next step in energy rating: the international ETTV method vs. BCA Section-J Glazing Calculator
R.H. Crawford and A. Stephan (eds.), Living and Learning: Research for a Better Built Environment: 49 th International Conference of the Architectural Science Association 2015, pp.423 433. 2015, The Architectural
More informationExample LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal
Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal The following documentation provides an example submittal for the LEED-NC v2.1 Energy & Atmosphere Credit 1 (EAc1). This sample EAc1 submittal
More informationCooling coil optimisation in hot and humid climates for IAQ and energy considerations
Cooling coil optimisation in hot and humid climates for IAQ and energy considerations Chandra Sekhar 1, Uma Maheswaran 2 1 Department of Building, National University of Singapore 2 Jurong Consultants
More informationEducation and Industrial Energy Calculation Guide July 2009
Education and Industrial Energy Calculation Guide July 2009 This document was prepared on behalf of the NZGBC by Beca with funding from the Energy Efficiency Conservation Authority (EECA). The New Zealand
More informationhow to read an energy model
how to read an energy model Kohler Ronan, LLC is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported
More informationEcolibrium. Living landmark Barangaroo International Towers Sydney scores world-first WELL rating. MAY 2018 VOLUME 17.4 RRP $14.95
Ecolibrium MAY 2018 VOLUME 17.4 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001 Living landmark Barangaroo International Towers Sydney scores world-first WELL rating. London calling One of Canberra
More informationCOMPARISON OF ASHRAE STANDARD-90.1, AND IECC CODES FOR LARGE OFFICE BUILDINGS IN TEXAS
COMPARISON OF STANDARD-, AND IECC CODES FOR LARGE OFFICE BUILDINGS IN TEXAS Jaya Mukhopadhyay Juan-Carlos Baltazar, Ph.D. Hyojin Kim, Jeff S. Haberl, Ph.D., P.E., Cyndi Lewis, Bahman Yazdani, P.E. Energy
More informationHVAC Integration. Erin McConahey
HVAC Integration Erin McConahey Façade decisions are key to HVAC loads 3 Effect of façade on interior 20 deep perimeter zone is affected by external environment Stable interior zone Always requires cooling
More informationAir Cooled Packaged Air Conditioning
Cooling Capacity 11.6kW - 193.0kW Heating Capacity 10.8kW - 213.0kW eco series Packaged Air Conditioning Giving you complete control More than just another air conditioning company. temperzone is dedicated
More informationGerald R. Ford Museum
Gerald R. Ford Museum Grand Rapids, Michigan Executive Summary Building and Plant Energy Analysis Report: Part I Brendan J. Cullen The Pennsylvania State University AE Senior Thesis Mechanical Option September
More informationWhat s My Baseline? ASHRAE
2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, vol 116,part 2). For personal use only. Additional reproduction,
More informationDTS & ENERGY MODELLING PROTOCOL GUIDE Version 1.0
DTS & ENERGY MODELLING PROTOCOL GUIDE Version 1.0 Green Star SA Multi Unit Residential v1 DTS & Energy Modelling Protocol Guide First Released: 27 th October 2011 Last Update: 27 th October 2011 Change
More informationThe optimization of the mechanical night cooling system in the office building
The optimization of the mechanical night cooling system in the office building Milos Lain 1, Jan Hensen 2 1 Department of Environmental Engineering, Faculty of Mechanical Engineering, Czech Technical University
More informationDATABASE AND SIMULATION MODEL DEVELOPMENT FOR MODELLING THE ENERGY USE OF NON-RESIDENTIAL BUILDINGS. Yohei Yamaguchi and Yoshiyuki Shimoda
Eleventh International IBPSA Conference Glasgow, Scotland July 27-3, 29 DATABASE AND SIMULATION MODEL DEVELOPMENT FOR MODELLING THE ENERGY USE OF NON-RESIDENTIAL BUILDINGS Yohei Yamaguchi and Yoshiyuki
More informationGreen Building Guideline of Jordan
Green Building Guideline of Jordan T. Awadallah 1*, S. Habet 1, A. Mahasneh 1, H. Adas 2 1 Royal Scientific Society, Amman, Jordan 2 National Energy Research Center, Amman, Jordan * Corresponding author.
More informationResearch paper titled. Analysis and Evaluation of Energy Conservation Potential in an Indian Commercial Building A Case Study in Jaipur
Annexure: D Research paper titled Analysis and Evaluation of Energy Conservation Potential in an Indian Commercial Building A Case Study in Jaipur Published in Referred International Journal International
More informationDemonstration of modeling of radiant cooling system in design builder. Prashant Bhanware & Bharath Reddy
Demonstration of modeling of radiant cooling system in design builder Prashant Bhanware & Bharath Reddy CONTENTS Introduction to Design Builder Building Energy Simulation Modeling procedure Making a model
More informationUniversity of Minnesota Duluth Civil Engineering Building
Energy Data Attachment University of Minnesota Duluth Civil Engineering Building LEED Energy Modeling The energy modeling for LEED NC 2.2 was performed against ASHRAE 9.1-24 Appendix using equest version
More informationEnergyPro Building Energy Analysis. Nine-story Office Building
EnergyPro Building Energy Analysis Nine-story Office Building EnergyPro Building Energy Analysis for an office building Project Scope The purpose of the EnergyPro energy model was to evaluate the energy
More informationAnalysis and System Design of a Large Chiller Plant for Korea, with or without Thermal Storage
Analysis and System Design of a Large Chiller Plant for Korea, with or without Thermal Storage Christine Levin HVAC Designer Flack + Kurtz Consulting Engineers, LLP New York, New York Peter Simmonds Director
More informationEnergy Assessment Report Clayville Elementary School DRAFT October George Washington Highway, Clayville, RI DRAFT
Report Clayville Elementary School October 2016 3 George Washington Highway, Clayville, RI 02815 Clayville Elementary School Summary of Findings On behalf of the School Building Authority at Rhode Island
More informationBuilding regulations now in force
BCA Section J: Guide to compliance Publication date July 2008 Building regulations now in force BCA SECTION J: Mandatory energy efficiency measures for non-residential construction The new BCA Section
More informationBuilding Energy Efficiency Analysis for a High School
Building Energy Efficiency Analysis for a High School (LG Multi V III VRF System) School Building Air-Conditioning Engineering Study VRF-ES-BH-002-US 013A30 Executive Summary Contents Executive Summary...2
More informationEnman Pty Ltd Energy Management Consultants
Enman Pty Ltd Energy Management Consultants Feasibility Study of Hotel Energy Management System for Mercure Hotel Sydney April 2013 V-2.0 Experienced, Professional People at Your Service Table of Contents
More informationThe baseline building system for compliance with Senate Bill 668 is defined by Appendix G,
Project: North Carolina A&T State University New Student Health Center SCO #: 08-08109-01A 1.0 Heating, Ventilating and Air Conditioning (HVAC) Baseline Building Systems Senate Bill 668 Compliance The
More informationLarge University Central Chiller Plant Design Considerations
Carrier Engineering Newsletter Volume 5, Issue 3 Large University Central Chiller Plant Design Considerations Large campus chilled water plants have unique constraints and need careful evaluation for successful
More informationSIMULATION VERSUS REALITY 4 CASE STUDIES. Anthony Calderone Aurecon, Melbourne, Australia
SIMULATION VERSUS REALITY 4 CASE STUDIES Anthony Calderone Aurecon, Melbourne, Australia calderonea@ap.aurecongroup.com ABSTRACT This paper will focus on four completed projects that have gone through
More informationAsset Energy Calculator Guidance
Asset Energy Calculator Guidance Introduction This section has been produced to give BREEAM In-Use assessors further guidance on the workings of the asset energy calculator so it is clear how any improvements
More informationAnalysis of the Energy Savings Potential in K-5 Schools in Hot and Humid Climates. Jeff S. Haberl, Ph.D., P.E.
Analysis of the Energy Savings Potential in K-5 Schools in Hot and Humid Climates Piljae Im Graduate Student Jeff S. Haberl, Ph.D., P.E. Professor Energy Systems Laboratory Texas Engineering Experiment
More informationPART 2 ENERGY SAVINGS AND COST BENEFIT ANALYSIS
ENERGY SAVINGS AND COST BENEFIT ANALYSIS Table Of Contents 2.1 OVERVIEW... 2-1 2.2 WHOLE BUILDING ENERGY USE... 2-1 2.2.1 Assessing Whole Building Energy Use... 2-1 2.2.2 Building Archetypes and Modeling
More informationGreen Building Guideline of Jordan
Green Building Guideline of Jordan T. Awadallah 1*, S. Habet 1, A. Mahasneh 1, H. Adas 2 1 Royal Scintific Society, Amman, Jordan 2 National Energy Research Center, Amman, Jordan * Corresponding author.
More informationEcolibrium. Hive of activity When fitout matches culture. THE OFFICIAL JOURNAL OF AIRAH OCTOBER 2015 VOLUME 14.9
THE OFFICIAL JOURNAL OF AIRAH OCTOBER 2015 VOLUME 14.9 Ecolibrium Hive of activity When fitout matches culture. PRINT POST APPROVAL NUMBER PP352532/00001 AWARD FINALIST Special delivery Reflecting Australia
More informationCarbon-Smart Buildings. Tackling Energy Efficiency in Hong Kong s Commercial Buildings
Carbon-Smart Buildings Tackling Energy Efficiency in Hong Kong s Commercial Buildings Introduction Hong Kong buildings consume a massive 89% of the SAR s electricity and make a sizeable contribution to
More informationRetrocommissioning Investigation Report
Continuous Optimization for Commercial Buildings Program Retrocommissioning Investigation Report March 22, 2013 Prepared for: Thompson Rivers University International Building BC Hydro #:COP10-353 Prism
More informationTHERMAL BRIDGING CALCULATIONS AND IMPACTS
THERMAL BRIDGING CALCULATIONS AND IMPACTS ERICA KENNA Senior Program Officer Department of the Environment and Energy PO Box 787 Canberra ACT 2601 Erica.Kenna@environment.gov.au LYNLEY BOLAND Consultant
More informationATS Le Grandiose, Sector 150 Noida. Energy Conservation Building Code (ECBC) Compliance Report
Energy Conservation Building Code (ECBC) Compliance Report ATS Le Grandiose, Sector 150 Noida Energy Conservation Building Code (ECBC) Compliance Report For M/s. Nobility Estates Pvt. Ltd. ECBC CONTENTS
More informationEcolibrium. One with the lot. Quarantine facilities use serious kit... just like this. AIRAH AWARDS ANNUAL THE OFFICIAL JOURNAL OF AIRAH
THE OFFICIAL JOURNAL OF AIRAH Ecolibrium DECEMBER 217 VOLUME 16.11 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/1 THE ECOLIBRIUM ANNUAL AIRAH AWARDS SPECIAL One with the lot Quarantine facilities use
More informationEnergyPro Building Energy Analysis. Single-story School Building
EnergyPro Building Energy Analysis Single-story School Building EnergyPro Building Energy Analysis for a single-story school bulding Project Scope The purpose of the EnergyPro energy model was to evaluate
More informationBUILDING ENERGY EFFICIENCY CERTIFICATE
BUILDING ENERGY EFFICIENCY CERTIFICATE BUILDING DETAILS Building name 390 St Kilda Road Certificate no. Owner's name Building address The Trust Company (Australia) Limited 390 St Kilda Road, Melbourne,
More informationRevision 6c Copyright Executive Summary. Airius (Oceania) Pty Ltd P.O Box 6282 Alexandria 2015 w airius.com.au
Cooling Energy Savings Using Airius Air Pear Destratification and Air Circulation Fans in an HVAC Environment in Temperate and Sub Tropical zones. HAP Software Analysis. Engineered by Vahid Vakiloroaya.
More informationComputational and the real energy performance of a single-family residential building in Poland an attempt to compare: a case study
Computational and the real energy performance of a single-family residential building in Poland an attempt to compare: a case study Piotr Kowalski 1,*, and Paweł Szałański 1 1 Department of Air Conditioning,
More informationSlab cooling system design using computer simulation
Slab cooling system design using computer simulation Lain, M.; Zmrhal, V.; Drkal, F.; Hensen, J.L.M. Published in: Proceedings of the International CESB Conference 07, 24-26 September, Czech Technical
More informationTHE NEW WAY TO PROVIDE COMFORT IN 4 PIPES SYSTEMS APPLICATIONS
THE NEW WAY TO PROVIDE COMFORT IN 4 PIPES SYSTEMS APPLICATIONS COMFORT SOLUTIONS The use of the Aermec VCF_X4 valve allows to carry out 4-pipe systems with traditional fan coil units, fitted with a single
More informationEnergy Strategies That Work Case Studies
Energy Strategies That Work Case Studies Jean Ascoli, Architect, CEM, Program Director for New Construction Smart Energy Design Assistance Center University of Illinois, Urbana Champaign of Homeland Security
More informationHow to maximise energy efficiency and cost effectiveness of different type heat pump projects three case studies
How to maximise energy efficiency and cost effectiveness of different type heat pump projects three case studies Presenter: Alex Koncar GreenKon Pty Ltd, Sydney, Australia E-mail: alexkoncar@greenkon.com.au
More information