2. Facility/flowgate limitations and flows at the time the TLR was initiated.

Size: px
Start display at page:

Download "2. Facility/flowgate limitations and flows at the time the TLR was initiated."

Transcription

1 Entergy TLR 5 Investigation Report Flowgate 1327 (Scott-Bonin 138kV for the loss of Cocodrie-Ville Platte 230kV) TLR Level 5A: May 23, 2005 Report Issued: 1. Description of purpose/cause of hold/curtailment. This report is submitted in accordance with the NERC Transmission Loading Relief Investigation Procedure for the TLR 5 event that occurred on Flowgate 1327 on May 23, Flowgate 1327 is an Entergy flowgate. The TLR 5 was in effect from 10:28 on May 23, 2005 until 19:31 on May 23, Projected post-contingent flows on the Scott-Bonin 138kV line for the loss of the Cocodrie-Ville Platte 230kV line exceeded the OSL with all non-firm transactions on the flowgate curtailed. Heavy post contingent loading on the Scott-Bonin 138kV line was partly caused by the planned outage of the Scott-Semere 138kV line. 2. Facility/flowgate limitations and flows at the time the TLR was initiated. At the time the TLR 5A was first issued, the Limiting Element was rated at 247 MVA. Flow on the Limiting Element was 173 MVA. Flow on the Contingent Element was 217 MVA. The LODF was approximately 37.8%. Post-contingent flow on the Limiting Element was approximately 255 MVA. 3. TLR levels, timing, and relief requested amounts. TLRs levels, timing and relief requested amounts are shown in the table below: Date Time Level Relief Requested Firm PTP Transactions Curtailed 5/23/05 08: N/A 5/23/05 09: N/A 5/23/05 10:28 5a 0 0 5/23/05 10:37 5a 6 2 5/23/05 11:33 5a /23/05 12:29 5a /23/05 13:27 5a /23/05 14:29 5a /23/05 15:31 5a /23/05 16:28 5a /23/05 17:31 5a /23/05 18:29 5a /23/05 19: N/A 5/23/05 20: N/A 5/23/05 21: N/A 5/23/05 22:30 3a 0 N/A 5/23/05 23: N/A 1

2 4. Transmission and generation outages or changes from prediction that may have contributed. The planned outage of the Scott-Semere 138kV line significantly contributed to the constraint. It was a necessary outage related to the Wells substation tie-in. 5. Procedures implemented prior to hold/curtailment. TLR Level 4 was issued prior to issuance of TLR Level 5A. 6. The initial investigation shall compare all transaction curtailment lists as generated by the IDC with the list of transactions flowing as determined by the IDC (Whole Transaction Lists) both before and after curtailment. The reasons for any transactions that were excluded from curtailment shall be provided. For those transactions not curtailed, the Reliability Authority will identify those entities and any affiliation with said entities. There were no known transactions excluded from curtailment for this TLR. 7. List of known transactions not in the IDC with Transaction Contribution Factors greater than the curtailment threshold and actions taken to curtail such transactions. There were no known transactions not in the IDC. 8. Excerpts from the RA Operations Log containing information relevant to the TLR event. The Reliability Coordinators log is shown on pages 4 and Flowgate limitations as identified by security analysis processes conducted by the Reliability Authority for the day prior to the TLR event. See pages 6 through 8 for TOPs studies. 10. State Estimator snapshots and security analysis, including any contingency analysis or stability analysis, along with any other recorded data indicating need for TLR. See pages 9 through 21 for the State Estimator snapshots. 11. ATC limitations before, during, and after the TLR event. Entergy grants transmission service using an AFC process. This process evaluates each transmission request on a case by case basis. There are no ATC values for individual corridors to or from the Entergy system. Entergy was not granting any transmission requests that impacted the congested flowgate by 3 % or greater at the time of the TLR 5. 2

3 12. Description of actions taken to avoid future hold/curtailments. This TLR is the result of congestion caused by a dearth of online generation in the Lafayette area in combination with the Scott-Semere 138kV line outage. The resulting North-to-South transfers cause overloads on the 138 kv transmission system in this area. The addition of the Wells 500/230kV substation (expected completion May/June 2005) should help to alleviate the overloading issues that have been historically seen with the Lafayette area. The Scott-Semere outage is related to the Wells substation tie-in. 13. Provide IDC generated Congestion Management Reports showing transaction curtailment list and Control Area NNL (network and native load) curtailment responsibility. Congestion Management Reports for each issuance of the TLR are shown on pages 22 through Re-dispatch actions taken. During the TLR 5a event, CLECO raised the Teche 3 unit by approximately 200MW. The GSF for the Teche 3 unit was 22.6%. Because the LAFA unit was derated, it was only able to increase generation by approximately 75MW. It s GSF was 56.6%. 3

4 4

5 5

6 *** Contingency Results Summary. *** Total No. tested = 2398 Total LF iterations 5419 Converged = 2383 Voltage Collapse = 11 Not Converged = 4 ****** No violations encountered among selected monitored elements ****** *** MUST 5.0 *** TUE, MAY :39 *** BASED ON SEAMS BASE CASE DEVELOPED IN APRIL 2005 MAY23 Subsys.File d:\psse28\example\entergy.sub Monit.File d:\psse28\example\maac1.mon Contin.File d:\psse28\example\maac.con Exclud.File none *********************************************************************** *********************************************************************** ** Detailed Report On Non-Converged Contingencies ** *********************************************************************** *********************************************************************** ******* Contingency JACINTO CHJC_SER Branches to be opened ** From bus ** ** To bus ** CKT OutageFl JACINTO CHJC_SER ******* Contingency GRIMES GRMXF Branches to be opened ** From bus ** ** To bus ** CKT OutageFl GRIMES GRMXF ******* Contingency CHINA CHJC_SER Branches to be opened ** From bus ** ** To bus ** CKT OutageFl CHINA CHJC_SER ******* Contingency VLNTIN CLOVEL Branches to be opened ** From bus ** ** To bus ** CKT OutageFl VLNTIN CLOVEL ******* Contingency CLOVEL GMEADW Branches to be opened ** From bus ** ** To bus ** CKT OutageFl CLOVEL GMEADW

7 ******* Contingency GR-TC* HOLNDL Branches to be opened ** From bus ** ** To bus ** CKT OutageFl GR-TC* HOLNDL ******* Contingency B.WLSN VKSB-S Branches to be opened ** From bus ** ** To bus ** CKT OutageFl B.WLSN VKSB-S ******* Contingency VKSB-S PT GIB Branches to be opened ** From bus ** ** To bus ** CKT OutageFl VKSB-S PT GIB ******* Contingency BASTRP BASTAP Branches to be opened ** From bus ** ** To bus ** CKT OutageFl BASTRP BASTAP ******* Contingency ELD-NW ELD-UP* Branches to be opened ** From bus ** ** To bus ** CKT OutageFl ELD-NW ELD-UP* ******* Contingency ELD-UP* JUNCITY Branches to be opened ** From bus ** ** To bus ** CKT OutageFl ELD-UP* JUNCITY ******* Contingency AMITY * ALPINE# Branches to be opened ** From bus ** ** To bus ** CKT OutageFl AMITY * ALPINE# ******* Contingency ALPINE# BISMRK Branches to be opened ** From bus ** ** To bus ** CKT OutageFl ALPINE# BISMRK ******* Contingency BISMRK HSEHVW Branches to be opened ** From bus ** ** To bus ** CKT OutageFl BISMRK HSEHVW ******* Contingency 1539 Unit:97451 G1LEWIS 22.0 Id:1 Report on bus events 7

8 Remove unit 1 from bus G1LEWIS MW *********************************************************************** *********************************************************************** ** Detailed Report On Converged Contingencies ** *********************************************************************** *********************************************************************** ******* Contingency COCODR VILPLT Branches to be opened ** From bus ** ** To bus ** CKT OutageFl COCODR VILPLT Branches with MVA flow more than 99.9 % of nominal rating ** From bus ** ** To bus ** CKT Tp ContFlow BaseFlow Rating IntLd% SCOTT BONIN LN ******* Contingency BONIN PMOUTON Branches to be opened ** From bus ** ** To bus ** CKT OutageFl BONIN PMOUTON Branches with MVA flow more than 99.9 % of nominal rating ** From bus ** ** To bus ** CKT Tp ContFlow BaseFlow Rating IntLd% SCOTT BONIN LN

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35

36 36

37 37

38 38

39 39

2. Facility/flowgate limitations and flows at the time the TLR was initiated.

2. Facility/flowgate limitations and flows at the time the TLR was initiated. Entergy TLR 5 Investigation Report Flowgate 1349 (Richard-Colonial Academy 138 kv for the loss of Richard-Scott 138 kv) TLR Level 5B: December 23-25, 2004 Report Issued: January 21, 2005 1. Description

More information

2. Facility/flowgate limitations and flows at the time the TLR was initiated.

2. Facility/flowgate limitations and flows at the time the TLR was initiated. Entergy TLR 5 Investigation Report Flowgate 12607 (Richard-Colonial Academy 138kV for the loss of North Crowley-Scott Bulk 138kV) TLR Level 5B: January 25, 2005 Report Issued: February 25, 2005 1. Description

More information

Flowgate 3707, an OTDF Flowgate, consists of the following elements.

Flowgate 3707, an OTDF Flowgate, consists of the following elements. MISO Investigation Report on the Level 5 TLR Event Lore-Turkey River 161kV for the outage of Wempletown-Paddock 345kV Flowgate 3707 February 8, 2002 Report issued: February 25, 2002 This report is submitted

More information

MISO Investigation Report on the NERC TLR Level 5 Event Alliant Energy Flowgate 14266: Wisdom-Triboji 161kV flo Sherco #3 June 12, 2007

MISO Investigation Report on the NERC TLR Level 5 Event Alliant Energy Flowgate 14266: Wisdom-Triboji 161kV flo Sherco #3 June 12, 2007 MISO Investigation Report on the NERC TLR Level 5 Event Alliant Energy Flowgate 14266: Wisdom-Triboji 161kV flo Sherco #3 June 12, 2007 Report submitted to NERC on: July 26, 2007. This report is submitted

More information

MISO Initial Investigation Report on TLR Level 5 Event. For. FG 3706 Arnold-Hazleton 345 kv. July 02, 2003

MISO Initial Investigation Report on TLR Level 5 Event. For. FG 3706 Arnold-Hazleton 345 kv. July 02, 2003 MISO Initial Investigation Report on TLR Level 5 Event For FG 76 Arnold-Hazleton 5 kv July 2, 2 Page of 2 Contents of the Initial Investigation Report Description of purpose/cause of hold/curtailment...

More information

SPP REPORT ON MAY 26, 2000 TLR EVENT

SPP REPORT ON MAY 26, 2000 TLR EVENT SPP REPORT ON MAY 26, 2000 TLR EVENT On May 26, 2000, SPP initiated a TLR on the CraAshValLyd flow gate, #5008, that proceeded to the point of firm curtailments. NERC asked SPP to prepare a report on this

More information

SPP REPORT ON SEPTEMBER 7, 2000 TLR EVENT

SPP REPORT ON SEPTEMBER 7, 2000 TLR EVENT SPP REPORT ON SEPTEMBER 7, 2000 TLR EVENT On September 7, 2000, SPP initiated a TLR on the FtsXfrFtsXfr flow gate, #5017, that proceeded to the point of firm curtailments. In response to the reporting

More information

SPP REPORT ON MAY 16, 2000 TLR EVENT

SPP REPORT ON MAY 16, 2000 TLR EVENT SPP REPORT ON MAY 16, 2000 TLR EVENT On May 16, 2000, SPP initiated TLR on the MuskogPittsb flow gate #5036 that proceeded to the point of firm curtailments. On May 22, NERC asked for SPP to prepare a

More information

PJM Report on TLR Level 5A Activity For April 1 7, 2003

PJM Report on TLR Level 5A Activity For April 1 7, 2003 April 23, 2003 Mr. Dave Hilt Director Compliance NERC 116-390 Village Blvd. Princeton Forrestal Village Princeton, NJ PJM Report on TLR Level 5A Activity For April 1 7, 2003 Dear Mr. Hilt: PJM has been

More information

Transmission Loading Relief Eastern Interconnection

Transmission Loading Relief Eastern Interconnection Transmission Loading Relief Eastern Interconnection Purpose: This standard defines procedures for curtailment and reloading of Interchange Transactions to relieve overloads on transmission facilities modeled

More information

Standard IRO Reliability Coordination Transmission Loading Relief

Standard IRO Reliability Coordination Transmission Loading Relief Standard Development Roadmap This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed:

More information

Appendix 9C1 Transmission Loading Relief Procedure Eastern Interconnection Version 2b

Appendix 9C1 Transmission Loading Relief Procedure Eastern Interconnection Version 2b Appendix 9C1 Transmission Loading Relief Procedure Eastern Interconnection Version 2b [Appendix 9C1B, Interchange Transaction Reallocation During TLR Levels 3a and 5a ] [Appendix 9C1C, Interchange Transaction

More information

Reliability Coordinator Area System Operating Limit Methodology

Reliability Coordinator Area System Operating Limit Methodology Reliability Coordinator Area System Operating Limit Methodology Revision 1.0 MAINTAINED BY SPP Operations Staff PUBLISHED: 10/19/2018 LATEST REVISION: Effective 10/19/2018 Copyright 2018 by Southwest Power

More information

Glossary of Terms Used in Reliability Standards. Preliminary Draft Version 0 Reliability Standards September 1, 2004

Glossary of Terms Used in Reliability Standards. Preliminary Draft Version 0 Reliability Standards September 1, 2004 Glossary of Terms Used in Standards Preliminary Draft Version 0 Standards September 1, 2004 Source References (Noted in draft only will not be part of final glossary) Functional Model () Glossary (GL)

More information

Hourly values for at least the next 48 hours. Daily values for at least the next 31 calendar days.

Hourly values for at least the next 48 hours. Daily values for at least the next 31 calendar days. A. Introduction 1. Title: Available Transmission System Capability 2. Number: MOD-001-1a 3. Purpose: To ensure that calculations are performed by Transmission Service Providers to maintain awareness of

More information

Attachment 1-IRO Transmission Loading Relief Procedure Eastern Interconnection

Attachment 1-IRO Transmission Loading Relief Procedure Eastern Interconnection Standard IRO-006-0 Reliability Coordination Transmission Loading Relief Attachment 1-IRO-006-0 Transmission Loading Relief Procedure Eastern Interconnection Purpose This standard defines procedures for

More information

Exhibit A. Reliability Standards Proposed for Approval

Exhibit A. Reliability Standards Proposed for Approval Exhibit A Reliability Standards Proposed for Approval Proposed New Standard IRO-006-5 Standard IRO-006-5 Reliability Coordination Transmission Loading Relief A. Introduction 1. Title: Reliability Coordination

More information

5.4 Post Contingency Local Load Relief Warning

5.4 Post Contingency Local Load Relief Warning 5.4 Post Contingency Local Load Relief Warning Post Contingency Local Load Relief Warning Non-Market Post Contingency Local Load Relief Warning The purpose of the Post Contingency Local Load Relief Warning

More information

System Impact Study E001 Moon Lake 230 kv 200 MW Plant

System Impact Study E001 Moon Lake 230 kv 200 MW Plant System Impact Study E001 Moon Lake 230 kv 200 MW Plant Prepared by: Midcontinent Independent System Operator Independent Coordinator of Transmission 720 City Center Drive Carmel, IN 46032 Rev Issue Date

More information

Standard IRO-006-EAST-1 TLR Procedure for the Eastern Interconnection

Standard IRO-006-EAST-1 TLR Procedure for the Eastern Interconnection A. Introduction 1. Title: Transmission Loading Relief Procedure for the Eastern Interconnection 2. Number: IRO-006-EAST-1 3. Purpose: To provide an Interconnection-wide transmission loading relief procedure

More information

Glossary of Terms Used in Reliability Standards

Glossary of Terms Used in Reliability Standards Version 0 Draft 3 November 1, 2004 Adequacy Adjacent Balancing Authority Agreement The ability of the electric system to supply the aggregate electrical demand and energy requirements of the end-use customers

More information

Glossary of Terms Used in Reliability Standards

Glossary of Terms Used in Reliability Standards Version 0 Draft 4 January 7, 2005 Adequacy Adjacent Balancing Authority Agreement The ability of the electric system to supply the aggregate electrical demand and energy requirements of the end-use customers

More information

FRCC 2007 SYSTEM OPERATOR TRAINING SEMINARS. Reliability Coordinator Processes and Tools

FRCC 2007 SYSTEM OPERATOR TRAINING SEMINARS. Reliability Coordinator Processes and Tools FRCC 2007 SYSTEM OPERATOR TRAINING SEMINARS Reliability Coordinator Processes and Tools Objectives Describe how the FRCC Security Process addresses planning/coordination of the Bulk Electric System Describe

More information

Proposed Action Plan and Description of Current Draft:

Proposed Action Plan and Description of Current Draft: Standard Development Roadmap This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed:

More information

PJM Manual 37: Reliability Coordination Revision: 14 Effective Date: April 1, Prepared by Systems Operation Division

PJM Manual 37: Reliability Coordination Revision: 14 Effective Date: April 1, Prepared by Systems Operation Division PJM Manual 37: Reliability Coordination Revision: 14 Effective Date: April 1, 2017 Prepared by Systems Operation Division PJM 2017 Table of Contents Table of Contents Approval...4 Current Revision...5

More information

Minutes Conference Call Interchange Distribution Calculator Working Group

Minutes Conference Call Interchange Distribution Calculator Working Group Minutes Conference Call Interchange Distribution Calculator Working Group 2 4 p.m. (EDT) The Interchange Distribution Calculator Working Group (IDCWG) met by conference call on at 2:00 p.m. EDT. Chair

More information

RTO Overview and Day 2 Markets. EAI Technical Conference May 26, 2011

RTO Overview and Day 2 Markets. EAI Technical Conference May 26, 2011 RTO Overview and Day 2 Markets EAI Technical Conference May 26, 2011 1 Agenda RTO Day 2 markets and Locational Marginal Pricing (LMP) Why RTO Day 2 markets may benefit Entergy s customers Quantifiable

More information

Freeze Date Straw Proposal Draft 5/18/2017

Freeze Date Straw Proposal Draft 5/18/2017 Freeze Date Straw Proposal Draft 5/18/2017 0 Table of Contents 1.0 Introduction... 2 2.0 Executive Summary... 2 3.0 Existing Process Background... 2 4.0 Design Components... 5 4.1.0 4.2.0 4.3.0 4.4.0 4.5.0

More information

5. Effective Date: See the Implementation Plan for IRO-006-EAST-2.

5. Effective Date: See the Implementation Plan for IRO-006-EAST-2. A. Introduction 1. Title: Transmission Loading Relief Procedure for the Eastern Interconnection 2. Number: IRO-006-EAST-2 3. Purpose: To coordinate action between Reliability Coordinators within the Eastern

More information

MOD-001-1a Available Transfer Capability Implementation Document

MOD-001-1a Available Transfer Capability Implementation Document Available Transfer Capability Implementation Document For NERC MOD-001-2a Page 1 of 18 1.0 Purpose The California Independent System Operator Corporation (ISO), as a Transmission Service Provider 1 and

More information

LEER/TLR 5 Drill Procedure General Coordination Procedures and Drill Scenario

LEER/TLR 5 Drill Procedure General Coordination Procedures and Drill Scenario LEER/TLR 5 Drill Procedure General Coordination Procedures and Drill Scenario General The participants of the Lake Erie Emergency Redispatch (LEER) procedure will perform drills of various scenarios of

More information

SSR STUDY REPORT FINAL

SSR STUDY REPORT FINAL System Support Resource Study Escanaba 1 & 2: 25 MW Coal 36 Month Suspension 6/15/2012 6/15/2015 SSR STUDY REPORT FINAL June 21, 2012 Redacted version for January 3, 2013 filing EXECUTIVE SUMMARY An Attachment

More information

Power Flow Control Through Topology Optimization Software: Applications and Case Studies

Power Flow Control Through Topology Optimization Software: Applications and Case Studies 1 Power Flow Control Through Topology Optimization Software: Applications and Case Studies Pablo A. Ruiz IEEE PES Transmission & Distribution Conference and Expo Denver, CO, April 17, 2018 2 Current Congestion

More information

Generator Interconnection Affected System Impact Study. Plains & Eastern Clean Line Final Report

Generator Interconnection Affected System Impact Study. Plains & Eastern Clean Line Final Report Generator Interconnection Affected System Impact Study Plains & Eastern Clean Line Final Report May 19, 2015 MISO 2985 Ames Crossing Eagan Minnesota - 55121 http://www.misoenergy.org Midcontinent Independent

More information

IDC Regional Congestion Management Training Plan. Revision 0.9. March 22, 2004

IDC Regional Congestion Management Training Plan. Revision 0.9. March 22, 2004 IDC Regional Congestion Management Training Plan Revision 0.9 March 22, 2004 Change Record Version Person Date Change Record 0.0 0.9 IDCWG IDCWG February 12, 2004 March 22, 2004 IDCWG Created Document

More information

System Impact Study and Facilities Study Process Manual For Cleco Power LLC

System Impact Study and Facilities Study Process Manual For Cleco Power LLC System Impact Study and Facilities Study Process Manual For Cleco Power LLC Version 3 March 2010 System Impact Study and Facilities Study Manual for Cleco Power LLC 1.0 Introduction.3 1.1 Purpose.3 1.2

More information

Examples of Current Paradigm vs. Future Proposed Paradigm

Examples of Current Paradigm vs. Future Proposed Paradigm Examples of Current Paradigm vs. Future Proposed Paradigm 10/30/2013 POTF Meeting Webinar Created by Dede Subakti (CAISO), Bert Peters (APS), Vic Howell & Brett Wangen (WECC RC) Presented by Dede Subakti

More information

Southwest Power Pool, Inc. Entergy ENTERGY SPP RTO REGIONAL PLANNING PROCESS MEETING June 16, 2011 NET CONFERENCE AGENDA 1:30 3:00 PM

Southwest Power Pool, Inc. Entergy ENTERGY SPP RTO REGIONAL PLANNING PROCESS MEETING June 16, 2011 NET CONFERENCE AGENDA 1:30 3:00 PM Southwest Power Pool, Inc. Entergy ENTERGY SPP RTO REGIONAL PLANNING PROCESS MEETING June 16, 2011 NET CONFERENCE AGENDA 1:30 3:00 PM 1. Administrative A. Introductions... All B. SPP Antitrust Guidelines...

More information

FERC Directives in Order 693 Addressed in IROL Implementation Plan

FERC Directives in Order 693 Addressed in IROL Implementation Plan The following Interconnection Reliability Operating Limit (IROL) standards were under development when the Version 0 project was initiated: IRO-008 Reliability Coordinator Operational Analyses and Real-time

More information

Securing 100+kV Transmission Facilities in the Market Model Market Design Complete Presentation

Securing 100+kV Transmission Facilities in the Market Model Market Design Complete Presentation Securing 100+kV Transmission Facilities in the Market Model Market Design Complete Presentation Shaun Johnson DIRECTOR MARKET MITIGATION & ANALYSIS, NYISO Business Issues Committee September 12, 2018 Rensselear,

More information

Methodology for Calculating Operating Limits for Generators

Methodology for Calculating Operating Limits for Generators Page 1 of 6 Methodology for Calculating Operating Limits for Generators I. Generator Operating Limit Definition The Generator Operating Limit (GOL) for a generator establishes a pathspecific, directional,

More information

California Independent System Operator Corporation Fifth Replacement Tariff

California Independent System Operator Corporation Fifth Replacement Tariff Table of Contents Method to Assess Available Transfer Capability... 2 L.1 Description of Terms... 2 L.1.1 Available Transfer Capability (ATC)... 2 L.1.2 Total Transfer Capability (TTC)... 2 L.1.3 Existing

More information

California Independent System Operator Corporation Fifth Replacement Tariff

California Independent System Operator Corporation Fifth Replacement Tariff Table of Contents Method to Assess Available Transfer Capability... 2 L.1 Description of Terms... 2 L.1.1 Available Transfer Capability (ATC)... 2 L.1.2 Total Transfer Capability (TTC)... 2 L.1.3 Existing

More information

PJM M2M Market Flow Proposal. October 2014

PJM M2M Market Flow Proposal. October 2014 PJM M2M Market Flow Proposal October 2014 Table of Contents 1. Introduction... 1 2. M2M Market Flow... 1 3. Real-Time Balancing Congestion and M2M payments... 3 4. Firm Flow Entitlement Impact of Market

More information

Minutes Conference Call Interchange Distribution Calculator Working Group

Minutes Conference Call Interchange Distribution Calculator Working Group Minutes Conference Call Interchange Distribution Calculator Working Group 2 p.m. 3 p.m. (EDT) The Interchange Distribution Calculator Working Group (IDCWG) met by conference call on at 2:00 p.m. EDT. Chair

More information

I n t e g r a t e d T r a n s m i s s i o n P l a n n i n g N e a r - T e r m S c o p e. June 15, 2016 Engineering

I n t e g r a t e d T r a n s m i s s i o n P l a n n i n g N e a r - T e r m S c o p e. June 15, 2016 Engineering 2017 ITPNT 2 0 1 7 I n t e g r a t e d T r a n s m i s s i o n P l a n n i n g N e a r - T e r m S c o p e June 15, 2016 Engineering Revision History Date or Version Number Author Change Description Comments

More information

Standard MOD Flowgate Methodology

Standard MOD Flowgate Methodology Standard Development Roadmap This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed:

More information

Standard TOP Operations Planning

Standard TOP Operations Planning A. Introduction 1. Title: 2. Number: TOP-002-4 3. Purpose: To ensure that Transmission Operators and Balancing Authorities have plans for operating within specified limits. 4. Applicability: 4.1. Transmission

More information

Minutes Conference Call Interchange Distribution Calculator Working Group

Minutes Conference Call Interchange Distribution Calculator Working Group Minutes Conference Call Interchange Distribution Calculator Working Group 2:00 p.m. 3:00 p.m. (EDT) The Interchange Distribution Calculator Working Group (IDCWG) met by conference call on at 2:00 p.m.

More information

RCR-35 Reliability Coordinator Reliability Plan for the SaskPower Subregion of the Midwest Reliability Organization

RCR-35 Reliability Coordinator Reliability Plan for the SaskPower Subregion of the Midwest Reliability Organization RCR-35 Reliability Coordinator Reliability Plan for the SaskPower Subregion of the Midwest Reliability Organization - 1 - Introduction The North American Electric Reliability Council (NERC) requires every

More information

Methodology for Determining and Communicating System Operating Limits for the Planning Horizon (FAC-010 & -014) Revision Log

Methodology for Determining and Communicating System Operating Limits for the Planning Horizon (FAC-010 & -014) Revision Log Revision Log Page 2 of 13 Revision or Change Number Effective Date Affected Page Numbers Description of Revision/Change 0000 03-26-2011 All Converted TPD document to SPP format 0001 03-26-2012 All Annual

More information

2011 Probabilistic Assessment. 11JAN12 Interregional Coordination

2011 Probabilistic Assessment. 11JAN12 Interregional Coordination The 2011 Probabilistic Assessment was a pilot study performed by SPP at NERC s request to voluntarily conduct an assessment to determine reliability indices using probabilistic methods. The majority of

More information

Available Transfer Capability Implementation Document (ATCID)

Available Transfer Capability Implementation Document (ATCID) Available Transfer Capability Implementation Document (ATCID) Revision History Revision Date Revised By Comments 0 03/31/2011 Scott Parker Original document Wade Richards James Sharpe 1 07/8/2011 Scott

More information

ASSOCIATED NERC STANDARD(S): TPL (referred to as TPL-001 in this document) IMPLEMENTATION: In effect when approved.

ASSOCIATED NERC STANDARD(S): TPL (referred to as TPL-001 in this document) IMPLEMENTATION: In effect when approved. ASSOCIATED NERC STANDARD(S): TPL-001-4 (referred to as TPL-001 in this document) IMPLEMENTATION: In effect when approved. Phase in of individual TPL-001 requirements will be based on the effective dates

More information

PJM Overview: PJM Structure and Cross-Border Examples PJM 2010

PJM Overview: PJM Structure and Cross-Border Examples PJM 2010 PJM Overview: PJM Structure and Cross-Border Examples 1 PJM as Part of the Eastern Interconnection 6,038 substations KEY STATISTICS PJM member companies 614 millions of people served 51 peak load in megawatts

More information

Glossary of Terms Used in Reliability Standards

Glossary of Terms Used in Reliability Standards Glossary of Terms Used in Reliability Standards February 8, 2005 The NERC Board of Trustees approved 16 new standards with future and phased-in Effective Dates. The newly approved terms are included in

More information

Approved RMWG Discussion was held. ??? John Simpson need to assign SMART rating

Approved RMWG Discussion was held. ??? John Simpson need to assign SMART rating ALR1-1 Generator Reactive Limit Metric:Voltage schedules How many times did generators encounter var limits associated with holding voltage schedule. 10 3 2 1 1 3 1 Initial pilot effort completed, reaching

More information

Available Flowgate Capability and the AFC Methodology

Available Flowgate Capability and the AFC Methodology Available Flowgate Capability and the AFC Methodology Presented By Nate Schweighart h Reliability Engineering TVA E.ON Stakeholder Meeting 2009 What is a flowgate? Flowgate A single transmission element

More information

Summary details for SPC TSR # and MH TSR # are shown in Tables ES.1 and ES.2: Service Requested

Summary details for SPC TSR # and MH TSR # are shown in Tables ES.1 and ES.2: Service Requested Executive Summary Firm point to point transmission service has been requested by Transmission Service Request (TSR) #80439788, under the SaskPower Open Access Transmission Tariff (OATT). The purpose of

More information

Summary details for SPC TSR # and MH TSR # are shown in Tables ES.1 and ES.2: IFHS MH MW, firm :00:00 CS

Summary details for SPC TSR # and MH TSR # are shown in Tables ES.1 and ES.2: IFHS MH MW, firm :00:00 CS Executive Summary Firm point to point transmission service has been requested by Transmission Service Request (TSR) #80487374, under the SaskPower Open Access Transmission Tariff (OATT). The purpose of

More information

Order 1000 Lessons Learned Analysis: Proposed Voltage Threshold Proposal Window Process

Order 1000 Lessons Learned Analysis: Proposed Voltage Threshold Proposal Window Process Order 1000 Lessons Learned Analysis: Proposed Voltage Threshold Proposal Window Process Planning Committee Suzanne Glatz December 3, 2015 Challenge Under PJM Model: Order 1000 Implementation Model For

More information

Dispatch Signal & Locational Marginal Pricing (LMP)

Dispatch Signal & Locational Marginal Pricing (LMP) Dispatch Signal & Locational Marginal Pricing (LMP) PJM State & Member Training Dept. Objectives Students will be able to: Identify how PJM dispatches & utilizes LMP Dispatch Rate Economic control signal

More information

Manual 01 Revision 36

Manual 01 Revision 36 Manual 01 Revision 36 Bilge Derin Engineer, Real-Time Data Mgmt Markets & Reliability Committee December 21, 2017 M01 R36 Changes Summary Section Change to/updated Impact 2.3.1 NERC references updated

More information

PID 276 Feasibility Study Report 4.4MW Distribution Inter-Connection Mermentau Substation

PID 276 Feasibility Study Report 4.4MW Distribution Inter-Connection Mermentau Substation PID 276 Feasibility Study Report 4.4MW Distribution Inter-Connection Mermentau Substation Prepared by: Entergy Services, Inc. T & D Planning 639 Loyola Avenue New Orleans, LA 70113 Rev Issue Date Description

More information

TRANSMISSION PLANNING ASSESSMENT METHODOLOGY AND CRITERIA

TRANSMISSION PLANNING ASSESSMENT METHODOLOGY AND CRITERIA TRANSMISSION PLANNING ASSESSMENT METHODOLOGY AND CRITERIA For Compliance with NERC Reliability Standard: TPL-001-4 1/10/2017 Version: 4.2 Table of Contents 1 Revision and Approval History... 2 1.1 Revision

More information

Available Transfer Capability Implementation Document TP-OP-005-r15 Effective Date: AUG Purpose. 2 Scope. 3 Definitions

Available Transfer Capability Implementation Document TP-OP-005-r15 Effective Date: AUG Purpose. 2 Scope. 3 Definitions 001-1 R3.1 001-1 R1 R1.1 R1.2 001-1 R3.5 1 Purpose MISO has elected to utilize a flow-based approach for the evaluation of transmission service requests ( TSRs ). The Available Flowgate Capacity Methodology

More information

Rochelle Municipal Utilities TRANSMISSION PLANNING CRITERIA. March 21, 2017

Rochelle Municipal Utilities TRANSMISSION PLANNING CRITERIA. March 21, 2017 Rochelle Municipal Utilities TRANSMISSION PLANNING CRITERIA March 21, 2017 Contents 1 Background...3 2 National and Regional Criteria and Guides...4 2.1 2.1 NERC Transmission Planning Standards...4 2.2

More information

Implementation Plan for IRO Reliability Coordination Facilities Prerequisite Approvals Adoption of IRO-001-2, IRO-010-0, COM-001-2

Implementation Plan for IRO Reliability Coordination Facilities Prerequisite Approvals Adoption of IRO-001-2, IRO-010-0, COM-001-2 Prerequisite Approvals Adoption of IRO-001-2, IRO-010-0, COM-001-2 Conforming Changes to Requirements in s None Coordination with revisions proposed in other standards projects The IROL SDT proposes retiring

More information

October 18, Southwest Power Pool, Inc., Docket No. ER Submission of Tariff Revisions

October 18, Southwest Power Pool, Inc., Docket No. ER Submission of Tariff Revisions October 18, 2013 VIA ELECTRONIC FILING The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, N.E. Washington, D.C. 20426 Re: Southwest Power Pool, Inc., Docket

More information

Transmission and Voltage Emergencies RE Module. Interconnection Training Program PJM State & Member Training Dept.

Transmission and Voltage Emergencies RE Module. Interconnection Training Program PJM State & Member Training Dept. Disclaimer This training presentation is provided as a reference for preparing for the PJM Certification Exam. Note that the following information may not reflect current PJM rules and operating procedures.

More information

Independent Transmission Organization. Stakeholder s Meeting December 2006

Independent Transmission Organization. Stakeholder s Meeting December 2006 SPP Presentation Independent Transmission Organization Stakeholder s Meeting December 2006 2 Introduction Participants Agenda Facilities 3 ITO Overview EON US (LG&E/KU) Overview EON US Tariff vs MISO Tariff

More information

1.3 Planning Assumptions and Model Development

1.3 Planning Assumptions and Model Development Section 1: Process Overview In addition, projects that originate through local Transmission Owner planning will be posted on the PJM web site. This site will include all currently planned transmission

More information

Special NERC Operating Committee Meeting

Special NERC Operating Committee Meeting 5/21/2013 Special NERC Operating Committee Meeting Chairman s Opening Remarks May 15, 2013 Purpose of Meeting and Success Definition WORKING MEETING NO VOTING A Successful Meeting = Identify concerns with

More information

Feasibility Study for the Q MW Solar Project

Feasibility Study for the Q MW Solar Project Feasibility Study for the Q195 74.9 MW Solar Project August 2018 Bulk Transmission Planning, Florida i This document and any attachments hereto ( document ) is made available by Duke Energy Florida, LLC

More information

45-day Formal Comment Period with Parallel Initial Ballot December January 2014September - October 2013

45-day Formal Comment Period with Parallel Initial Ballot December January 2014September - October 2013 Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed

More information

Appendix 5B. Statement of Compliance Registry Criteria

Appendix 5B. Statement of Compliance Registry Criteria Appendix 5B Statement of Compliance Registry Criteria Revision 5.1 Effective: July 1, 2014 (as noted below) The highlighted terms Bulk Electric System and Load in this document will become effective as

More information

SYSTEM OPERATING LIMITS IN THE PLANNING HORIZON FAC-010 COMPLIANCE

SYSTEM OPERATING LIMITS IN THE PLANNING HORIZON FAC-010 COMPLIANCE SYSTEM OPERATING LIMITS IN THE PLANNING HORIZON FAC-010 COMPLIANCE System Operating Limits (SOLs) in the planning horizon are required to be identified by FAC-010. This guideline describes how Duke Energy

More information

SPP RTO Compliance Forum TPL Jason Terhune

SPP RTO Compliance Forum TPL Jason Terhune SPP RTO Compliance Forum TPL-001-4 Jason Terhune 501-688-8261 jterhune@spp.org 1 TPL Standards have been Consolidated TPL-001-0.1 TPL-002-0b TPL-003-0b TPL-004-0a TPL-001-4 R1 R2 R3 R4 R5 R6 R7 R8 2 Overview

More information

Transmission Reliability Margins. Table of Contents. Purpose. Operating Procedure

Transmission Reliability Margins. Table of Contents. Purpose. Operating Procedure Table of Contents Purpose... 1 1. Responsibilities... 2 2. Scope/Applicability... 2 2.1 Background... 2 2.2 Scope / Applicability... 3 3. Detail... 3 3.1 TRM Value Determination... 3 3.2 TRM Instructions...

More information

Description of Current Draft: This is the first draft of the proposed standard posted for stakeholders comment.

Description of Current Draft: This is the first draft of the proposed standard posted for stakeholders comment. Standard Development Roadmap This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed:

More information

Southwest Power Pool CRITERIA

Southwest Power Pool CRITERIA Southwest Power Pool CRITERIA LATEST REVISION: April 28, 2015 FOREWORD... i INTRODUCTION... ii 1.0 LOAD AND ENERGY FORECASTS...1-1 2.0 CAPACITY MARGIN...2-1 2.1 Definitions...2-1 2.1.1 Load Serving Member...2-1

More information

ECC Task Force Meeting August 30, 2016

ECC Task Force Meeting August 30, 2016 ECC Task Force Meeting August 30, 2016 Anti-Trust Statement I would like to remind ECC Task Force members and observers that this meeting is being conducted subject to the condition and requirements of

More information

NERC Reliability Functional Model

NERC Reliability Functional Model NERC Reliability Functional Model Function Definitions and Responsible Entities Version 3 Approved by Standing Committees: Operating Committee: December 6, 2006 Planning Committee: December 6, 2006 Standards

More information

PJM White Paper. Transource Independence Energy Connection Market Efficiency Project

PJM White Paper. Transource Independence Energy Connection Market Efficiency Project PJM White Paper PJM Interconnection November 15, 2018 This page is intentionally left blank. PJM 2018 www.pjm.com i P a g e Contents Highlights... 1 Executive Summary... 1 I. Introduction... 2 Reliability

More information

Standard INT Implementation of Interchange

Standard INT Implementation of Interchange A. Introduction 1. Title: Implementation of Interchange 2. Number: INT-009-2 3. Purpose: To ensure that Balancing Authorities implement the Interchange as agreed upon in the Interchange confirmation process.

More information

Available Transfer Capability Implementation Document TP-OP-005-r18 Effective Date: DEC Purpose. 2 Scope. 3 Definitions

Available Transfer Capability Implementation Document TP-OP-005-r18 Effective Date: DEC Purpose. 2 Scope. 3 Definitions 001-1a R3.1 001-1a R1 1 Purpose MISO has elected to utilize a flow-based approach for the evaluation of transmission service requests ( TSRs ). The Available Flowgate Capacity Methodology used requires

More information

Educating System Operators in the New Millennium! Background. Course Level. Target Audience. NERC Continuing Education Hours

Educating System Operators in the New Millennium! Background. Course Level. Target Audience. NERC Continuing Education Hours Background The class will be delivered over a 3-day period. The class is comprised of three training modules covering the areas of: Communications, Critical Thinking, and Restoration. The course consists

More information

ITP Year 20 Assessment Scope

ITP Year 20 Assessment Scope ITP 20 Year Scope 1 ITP Year 20 Assessment Scope January 6, 2010 Approved by TWG January 5, 2010 Endsored by ESWG January 5, 2010 Table of Contents Overview... 4 Objective... 4 Modeling... 5 1. Economic...

More information

APPENDIX G DISPATCH RELATED DATA

APPENDIX G DISPATCH RELATED DATA APPENDIX G DISPATCH RELATED DATA G.1 INTRODUCTION G.1.1 The information listed in sections G.2 to G.7 of this Appendix describes the dispatch related data referred to in sections 6.1 and 8.1 of this Chapter

More information

Functional Entity Roles and Responsibilities

Functional Entity Roles and Responsibilities Functional Entity Roles and Responsibilities NWPP MC Phase 3 Operations Integration Work Group 9/28/2014 Page 1 of 13 Table of Contents 1. Purpose... 3 2. Roles and Responsibilities of Functional Entities...

More information

Transmission Topology Optimization

Transmission Topology Optimization Transmission Topology Optimization P R E S E N T E D B Y Pablo A. Ruiz F e b r ua r y 1 9, 2 0 1 8 Copyright 2018 The Brattle Group, Inc. Agenda Objectives and Motivation Illustrative Example Current Practice

More information

2013 Economic Study Report

2013 Economic Study Report 2013 Economic Study Report PPL EnergyPlus, LLC December 19, 2013 Electric Transmission Planning Table of Contents Executive Summary... 3 Study Constraints and Conditions... 4 Study Parameters... 5 Steady-State

More information

NERC PLANNING STANDARDS

NERC PLANNING STANDARDS NERC PLANNING STANDARDS North American Electric Reliability Council April 2004 Version of All Planning Standards Terms and Their Definitions As Used in the Analysis (Study) an examination or simulation

More information

Increasing Efficiency On The Transmission Grid With Real Time Monitoring

Increasing Efficiency On The Transmission Grid With Real Time Monitoring Increasing Efficiency On The Transmission Grid With Real Time Monitoring Joint CEA Transmission Council & Corporate Partners Committee Strategic Workshop February 25, 2009 Presented by: Ron Stelmak The

More information

Project Coordinate Interchange Standards Mapping Document

Project Coordinate Interchange Standards Mapping Document Mapping Document Project Purpose The purpose of Project 2008 12 is to revise the set of Coordinate Interchange standards to ensure that each requirement is assigned to an owner, operator or user of the

More information

Generation Contingency Analysis

Generation Contingency Analysis Generation Contingency Analysis PJM 2016 Objectives Identify the procedure for redispatching generation to alleviate an overloaded monitored transmission line caused by a contingency PJM 2016 2 Agenda

More information

A. Introduction Balancing Authority Reliability Coordinator Transmission Operator. 5. Effective Date:

A. Introduction Balancing Authority Reliability Coordinator Transmission Operator. 5. Effective Date: A. Introduction 1. Title: Emergency Operations 2. Number: EOP-011-1 3. Purpose: To address the effects of operating Emergencies by ensuring each Transmission Operator and Balancing Authority has developed

More information

Impacts in PJM Day-Ahead Markets

Impacts in PJM Day-Ahead Markets Impacts in PJM Day-Ahead Markets Pablo A. Ruiz, Michael Caramanis, Evgeniy Goldis, Xiaoguang Li, Keyurbhai Patel, Russ Philbrick, Alex Rudkevich, Richard Tabors, Bruce Tsuchida Technical Conference On

More information

MISO-PJM JOA Biennial Review

MISO-PJM JOA Biennial Review MISO-PJM JOA Biennial Review Midcontinent ISO PJM Interconnection 1/20/2016 1. Background On January 4, 2011, Midwest 1 Independent Transmission System Operator, Inc. (MISO) and PJM Interconnection, LLC

More information