Visible emissions were not observed in the school in the vicinity of the construction containment.

Similar documents
Visible emissions were not observed in the school in the vicinity of the construction containment.

Indoor Air Quality Assessments during Renovations at Waverly Elementary School Project #J (January 4, 12, 15, 25 and 29, 2018)

Measuring Indoor Air Quality presented to AAFAME Members Nov. 14, 2017

Indoor Air Quality Assessment Report

Indoor Air Quality (IAQ) Requirements

OSHA Act of 1970 Section 5(a)(1) Duties, as may be amended.

Indoor Environmental Quality Policy

INDOOR AIR QUALITY ASSESSMENT

January 20, Mr. Marty Foutch Facilities Director Bixby Public Schools 109 N. Armstrong Bixby, OK 74008

INDOOR AIR QUALITY CALUMET COUNTY HIGHWAY FACILITY -CARBON MONOXIDE- 206 COURT ST CHILTON, WI

1204 North Road (Rt. 117) Groton, Connecticut 06340

A. The project is intended to achieve LEED Certification at the Silver Level per the U.S. Green Building Council LEED for Schools 2007 rating system.

BREATHE A LITTLE EASIER WITH TSI

THE REVISION OF STANDARD 62: WHAT A DIFFERENCE A DECADE MAKES

THE LEADER IN PERFORMANCE INDOOR AIR QUALITY MEASUREMENTS

CASE STUDY. Improved Radon Needs More Air

Introduction. IAQ - 5 School Building Summary 2009

Indoor Air Quality. Basic Management for Healthy Office Environments. Peter A Shelling CSP CIEC

Indoor Air Quality Tools for Schools

Component Goal Performance Measurement Unit. meet the sustainability criteria. described below. described below. from landfills.

New Montgomery County Elementary School. Construction Indoor Air Quality Management Plan IEQc3.1 IAQ Plan During Construction

INDOOR AIR QUALITY ASSESSMENT. Department of Developmental Services & Department of Mental Health Service Center 35 Nagog Park Acton, Massachusetts

According to our research and study most occupant complaints relating to IAQ are attributable to the following factors:

Construction Indoor Air Quality (IAQ) Management Plan

IAQ Walkthrough. Jordan Elementary. J o r d a n P u b l i c S c h o o l s IEA, INC. Contact Us: Inspection Date:

What s in the Air - Truths, Myths & Simple Strategies

TEXAS FACILITIES COMMISSION Edit Date: 4/13/2012 ARCHITECTURAL/ENGINEERING GUIDELINES

Illinois Department of Public Health Guidelines for Indoor Air Quality

AirRenew Gypsum Board Products - Frequently Asked Questions

Indoor Air Quality Management Plan

Indoor Air Quality Solutions

Chapter 14 Indoor Air Quality

e. Potential sources of air contaminants do not exist near the building. (e.g. chimneys, stacks, industrial plants, exhaust from nearby buildings)

Table of Contents. C. Recommended Remediation Firms: upon request

Francis (Bud) Offermann Indoor Environmental Engineering. Cheri Marcham Embry-Riddle Aeronautical University,

Indoor Air Quality Report

ASSESSMENT, CLEANING & RESTORATION OF HVAC SYSTEMS (ACR-2002)

Monitoring & Oversight Activities Conducted During Lead Remediation of Elevator Structure Located at Carlsbad Caverns National Park

The Leader in Performance Indoor Air Quality Measurements

The Leader in Performance Indoor Air Quality Measurements

CASE STUDY. Two Dogs and Two Cats Insufficient Air Exchange with High CO2

Temperature, Relative Humidity, and Carbon Dioxide Data Logging Report. Franklin High School Rooms 104, 109, 115, 120, East Fourth Street

MEP's Letter of Assurance

Sugen Building 3 LEED-CI Pilot Project

Washington State Department of Health Division of Environmental Health

SECTION INDOOR AIR QUALITY MANAGEMENT PLAN. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

LEED Best Practices Save $$$

Indoor Air Quality Program

Case Study Leaky Single Story High Radon

"INDOOR AIR QUALITY"

Contractor's Letter of Assurance

South Brunswick School District Indoor Air Quality (IAQ) Written Plan

MEP's Letter of Assurance

Indoor Air Quality Program

360-INDOOR AIR QUALITY PROGRAM

Read Health Canada s Tools for schools Action Kit s Introduction, Backgrounder and pages 14-3 to

University of Rochester Environmental Health & Safety Indoor Air Quality Program March 23, 2005

Notes on Indoor Air Quality

Indoor Air Quality Management Plan for LEED

User Guide v 1.0. Air Quality Monitor. by Air Ae Steward

CHAPTER 30 INDOOR AIR QUALITY MANAGEMENT

Comparison of indoor air quality on a passenger ship and a chemical ship

INDOOR AIR QUALITY AND ENERGY EFFICIENCY IN THE DESIGN OF BUILDING SERVICES SYSTEMS FOR SCHOOL CLASSROOMS

The 411 on emitting materials Designing Healthy Interiors A. Costello, P.E., LEED-AP

Mechanical vs. Natural Ventilation in Schools: Less Can Be More

RIVER VALE BOARD OF EDUCATION PROPERTY Page 1 of Indoor Air Quality Standards 7421 INDOOR AIR QUALITY STANDARDS

When Building a New Home

Good (4 points each) > mg/m Bq m Bq m Bq m -3 < ,000 1,000-10,000 10, ,000

October 31, Colorado State Judicial Branch 101 West Colfax Avenue, Suite 500 Denver, Colorado 80202

April 21, Dear Mike,

IAQ - BEYOND MATERIAL SELECTION

A Comparison of the Approaches in the Implementation of Good Indoor Air Quality Practices in Malaysia

INDOOR AIR QUALITY TESTING AT CARLISLE COUNTY ELEMENTARY SCHOOL

About Active Energy Engineering

TN Tatem Middle School Indoor Air Quality Assessment September 2016

Indoor Air Quality through Design

Healthy Learning Environment

SPORE TRAP SAMPLING REPORT FOR CENTENNIAL LANE ELEMENTARY SCHOOL 3825 CENTENNIAL LANE ELLICOTT CITY, MARYLAND PREPARED FOR:

How We Obtained LEED Certification pertaining to the Indoor Environmental Quality Category. Ron Fields, CAFS, NCT General Dynamics C4 Systems

Detailed Instrumentation of a Building Bake-Out Procedure

Mold Inspection Report

2/22/2008. Indoor Environmental (Air) Quality. Time Spent in Locations: Indoors & Outdoors. Why Should You Care About Indoor Air Quality?

MEP Engineer's Letter of Assurance

Indoor Air Quality Management Plan

Model Written Indoor Air Quality Program. The Summit Board of Education Administrative Offices 14 Beekman Terrace Summit, NJ

Underf loor For Schools

Air STANDARD. FOR COMMERCIAL INTERIORS v2.0. RESET Air STANDARD for Commercial Interiors v2.0. Copyright 2018 RESET

ASHRAE Standard INTRODUCTION AND OVERVIEW Plus a few other issues: Outdoor Air Quality and the IAQ Procedure

Hollingsworth & Vose

Improve Schools Indoor Environment

Indoor Air Quality Monthly Testing Services, Corcoran Gallery of Art, th Street NW, Washington, DC December 2017

U.S. INDOOR AIR QUALITY MARKET

Transcription:

June 22, 2018 To: Waverly Elementary School From: Christopher Madden, CIH Indoor Environmental Quality Manager Re: Indoor Air Quality Testing During Renovations - May As Waverly Elementary School is currently undergoing renovations, the Howard County Public School System s Office of the Environment is conducting weekly Indoor Air Quality (IAQ) Testing to determine if renovation activities are adversely impacting the IAQ in areas located in close proximity to the renovation. The Office of the Environment visited Waverly Elementary on May 4, 11, 17 and 25, 2018. The Office of the Environment observed if engineering controls were in place to limit construction related constituents from migrating into occupied areas of the school and collected measurements of temperature, relative humidity, carbon dioxide (CO2), carbon monoxide (CO), volatile organic compounds (VOCs), and particulate matter. General Observations May 4, 11, 17, and 25 2018 activities varied during the assessment and included electrical work, duct installation, and finishing work. The construction containments were in place and negative air machines were operational (if work was taking place). Visible emissions were not observed in the school in the vicinity of the construction containment. General Indoor Air Quality Measurements Temperature, Relative Humidity, CO2, CO, and VOC readings were collected as part of the IAQ assessment. The American Society of Heating Refrigeration and Air Conditioning Engineers (ASHRAE) recommends a temperature range of 68.5 to 75 degrees Fahrenheit (F) in the winter and 75 to 80.5 degrees F in the summer (assuming 50% relative humidity) (Indoor Environmental Quality 2015). The recommended temperature ranges vary slightly depending on relative humidity. There are no recommendations for the spring and fall due to the variabilities in outdoor temperatures. To prevent mold growth, The Environmental Protection Agency (EPA) recommends relative humidity should be maintained below 60%, ideally between 30-50%. Humidity readings below 30% are often encountered in buildings where humidity is not introduced through the Heating Ventilation and Air Conditioning (HVAC) system. Carbon Dioxide measurements can provide a general sense of the adequacy of the ventilation system. It is recommended that CO2 readings be less than 700 parts per million plus the outside concentration of CO2.

Carbon Monoxide can be introduced through incomplete combustion (car exhaust, improperly ventilated boilers, etc.) and should not exceed 9 ppm. Low levels of VOCs are ubiquitous in indoor and outdoor air from both natural and man-made sources (The IAQ 2016). VOCs can be introduced by a variety of indoor (paints, perfumes, art products, building materials, carpet, furnisher, etc.) and outdoor sources (vehicles, manufacturing emissions, etc.). A spike is identified when indoor readings are significantly higher than the outdoor readings. Temperature, Relative Humidity, CO2, and CO data was collected using a TSI IAQ Calc (Model #7545). VOC data was collected using a Rae ToxiRae Pro Photoionization Detector (PID) (Model #PGM-1800). Below are the results of the temperature, relative humidity, CO2, and CO measurements collected. Table I - General IAQ Measurements May 4, 2018 CO2 CO Outside 89.8 43.3 470 0.0 0.1 82.6 39.0 507 1.0 0.1 Lobby 84.8 39.7 550 0.3 0.1 Music 82.9 43.4 719 0.0 0.1 Outside of 81.9 45.3 572 0.1 0.1 A123 78.0 50.0 570 0.1 0.0 A125 77.2 50.0 503 0.0 0.0 Health 76.5 44.3 724 0.0 0.1 Media 77.3 45.4 887 0.1 0.1 1 st Floor Addition (Near B135) 73.9 48.4 639 0.0 0.0 Cafeteria 76.0 59.5 971 0.0 0.6 Outside 87.7 54.6 607 0.0 0.0 Note: Bolded values were not within recommended limits. Table II - General IAQ Measurements May 11, 2018 CO2 CO Outside 76.7 51.5 386 0.0 0.0 75.8 44.4 536 0.4 0.0 Music 74.3 47.5 681 0.2 0.0 Cafeteria 73.6 51.9 639 0.0 0.0 Lobby 73.7 51.7 694 0.0 0.0 Outside of 73.9 51.9 607 0.1 0.0 A123 74.0 51.7 572 0.0 0.0 A125 73.4 51.2 504 0.0 0.0

Table II - General IAQ Measurements (Continued) May 11, 2018 CO2 CO Health 73.2 44.9 704 0.0 0.0 Media 73.2 54.0 849 0.0 0.0 1 st Floor Addition (Near B135) 72.5 51.8 591 0.0 0.0 Outside 74.4 49.1 388 0.0 0.0 Table III - General IAQ Measurements May 17, 2018 CO2 CO Outside 73.9 78.7 443 0.5 0.0 72.2 66.6 742 0.2 0.0 Lobby 74.6 65.1 637 0.0 0.0 Music 74.4 64.7 707 0.0 0.0 Outside of 73.4 62.2 606 0.0 0.0 A123 73.4 70.7 623 0.0 0.0 A125 73.7 70.3 482 0.0 0.0 73.7 53.5 915 0.1 0.0 Media 73.1 61.9 687 0.0 0.0 1sr Floor Addition 72.6 61.9 565 0.0 0.0 Cafeteria 72.2 69.6 713 0.0 0.0 Outside 71.2 74.2 446 0.0 0.0 Table IV - General IAQ Measurements May 25, 2018 CO2 CO Outside 88.7 40.0 432 0.0 0.1 84.3 37.8 445 0.5 0.0 Lobby 73.8 50.7 550 0.0 0.0 Music 74.8 48.3 618 0.0 0.0 Outside of 71.8 50.1 540 0.0 0.0 Health A123 71.1 54.3 705 0.0 0.1 A125 72.2 53.9 646 0.0 0.0 72.8 57.5 848 0.0 0.1 Media 72.6 53.4 693 0.0 0.0 1 st Floor Addition 70.4 54.6 480 0.0 0.0 Outside 83.4 51.5 419 0.0 0.0

Particulate Matter Measurements Particulate matter is a complex mixture of extremely small particles and liquid droplets that get into the air (Particulate 2017). The data collected does not distinguish between types of particles in the air which can include pollen, skin cells, soil, human/animal hairs, etc. Particles designated as respirable are less than 10 micrometers (µm) in diameter and typically fall into two categories, coarse and fine particles. Coarse particles are those that are less than 10 um (PM10) and fine particles are those less than 2.5 µm (PM2.5). ANSI/ASHRAE standard 62.1-2016 suggests target indoor concentration for PM2.5 and PM10 of 12 and 50 µg/m3 respectively. Particulate matter data was collected with a TSI AeroTrak Particle Counter (Model #9306-V2). Note that the particle counter is not capable of collecting PM2.5 data. Due to this limitation, PM3.0 data is used. This would provide a more conservative, overestimate of PM2.5. Table V - Particulate Matter Measurements May 4, 2018 PM 0.5 (µ/m 3 ) PM 1.0 (µ/m 3 ) PM 3.0 (µ/m 3 ) PM 5.0 (µ/m 3 ) PM 10.0 (µ/m 3 ) Outside 3 5 10 13 31 6 9 27 88 323 Lobby 2 3 7 20 69 3 4 11 43 197 A123 2 3 5 10 24 A125 2 3 4 5 10 Health 3 5 21 51 145 Media 2 3 5 9 29 1 st Floor Addition (Near B135) 2 3 5 8 17 Cafeteria 2 3 10 42 152 Outside 3 4 10 19 47 Table VI - Particulate Matter Measurements May 11, 2018 PM 0.5 (µ/m 3 ) PM 1.0 (µ/m 3 ) PM 3.0 (µ/m 3 ) PM 5.0 (µ/m 3 ) PM 10.0 (µ/m 3 ) Outside 1 2 4 9 14 2 3 9 21 74 Lobby 1 1 5 21 85 Music 1 1 4 13 55 Cafeteria 1 1 2 5 16 1 1 4 15 38 A123 0 0 1 5 13 A125 1 1 1 2 2 Health 1 1 3 6 20 Media 1 1 5 18 72 1 st Floor Addition (Near B135) 1 1 3 8 17 Outside 1 2 4 7 18

Table VII - Particulate Matter Measurements May 17, 2018 PM 0.5 (µ/m 3 ) PM 1.0 (µ/m 3 ) PM 3.0 (µ/m 3 ) PM 5.0 (µ/m 3 ) PM 10.0 (µ/m 3 ) Outside 1 2 3 6 19 0 0 2 7 30 Lobby 0 0 1 7 31 0 0 1 5 21 A123 0 0 1 5 12 A125 0 0 0 3 0 0 0 1 4 14 Media 0 0 1 3 10 1sr Floor Addition 0 0 1 2 3 Cafeteria 0 0 1 5 23 Outside 1 1 2 6 13 Table VIII - Particulate Matter Measurements May 25, 2018 PM 0.5 (µ/m 3 ) PM 1.0 (µ/m 3 ) PM 3.0 (µ/m 3 ) PM 5.0 (µ/m 3 ) PM 10.0 (µ/m 3 ) Outside 3 5 9 13 29 4 6 16 52 233 Lobby 3 4 6 9 33 Music 2 3 5 13 49 2 3 4 6 14 A123 2 3 4 7 31 A125 2 3 4 7 28 3 4 10 29 71 Media 2 3 4 8 22 1 st Floor Addition 2 3 4 5 9 Outside 3 4 7 12 23 Discussion With the exception of May 17, 2018, no major concerns were identified during the sampling activities. On May 17, elevated humidity was identified. Conversations with building occupants also indicated the building had felt more humid days prior to the sampling. After discussions with the Office of and their Heating Ventilation and Air Conditioning (HVAC) contractor it was determined that the HVAC units discharge set point was improperly configured. This means the outdoor air temperature was not being cooled enough to properly dehumidify the air before being delivered to occupied portions of the building. Elevated particulate (PM10.0) was detected in various locations. Elevated concentrations are expected and would not necessarily be associated with construction activities. Dust levels are expected to vary overtime based on student and staff activities. Slightly elevated dust levels were identified in the Media on May 11. Conversations with the principal indicated that construction trades were improperly entering/leaving the construction area through the media. A barrier was added to direct contractors to the proper entrance/exit doors.

Conclusion The sampling activities conducted in May indicate measures are being taken to prevent construction odors/vocs from entering the occupied areas of the school. A deficiency was identified associated with relative humidity, however the issue has been corrected. Regarding dust, it should be noted that elevated concentrations are expected and may not necessarily be associated with construction activities. Dust levels are expected to vary overtime based on student and staff activities. Additionally, dust levels are far from the enforceable OSHA Occupational Exposure Limit for respirable nuisance dust of 5,000 µg/m 3. Housekeeping practices are also pivotal for dust control. Increased frequency of vacuuming and cleaning could also help reduce dust levels in areas around the construction containment such as the lobby, hallway outside of health, and the health suite. Sticky mats could also be added in areas where trades enter/exit the construction areas through the school. This will likely alleviate the tracking of construction dusts into occupied areas of the school. It should be noted that the sampling is not being conducted for Occupational Safety and Health Administration (OSHA) compliance, in association with the renovation/construction contractors.

References Indoor Environmental Quality, the National Institute for Occupational Safety and Health/Centers for Disease Control and Prevention, September 1, 2015. Retrieved from: https://www.cdc.gov/niosh/topics/indoorenv/temperature.html The IAQ Investigator s Guide, 3 rd Edition, American Industrial Hygiene Association, Edited by Ellen C. Gunderson, CIH, CSP, 2016. Particulate Matter (PM) Pollution, Environmental Protection Agency, Last Updated on August 21, 2017. Retrieved from: https://www.epa.gov/pm-pollution Volatile Organic Compounds (VOC) Criteria for New White Paper, American Industrial Hygiene Association, March 15, 2017.