WHITE PAPER. Chiller Plant Optimization - A Practitioner s Perspective. Abstract

Similar documents
WHITE PAPER. Diagnostics and Prognostics of Centrifugal Chillers. Abstract

17/09/2014. Modern buildings. Green building experiences of Infosys. Modern buildings. Modern buildings

Outline Chilled Water T Study AHU Coil Overview Cooling Overview Test Setup Data Analysis Findings Summary

Optimizing Central Chilled Water Systems

Chilled Water Energy Savings Study

ENHANCING BUSINESS EFFICIENCY WITH AI AND ENGINEERING DATA ANALYTICS

RPA VALIDATION PITFALLS AND HOW TO AVOID THEM

WHITE PAPER. Leveraging advanced validation techniques for retail size optimization. - Divya Mohan C, Chitra Sylaja

PREDICTIVE ANALYTICS FOR DATA-DRIVEN DECISIONS

MODERNIZING THE MIDDLEWARE

WHITE PAPER. IoT-enabled Banking Services

AUTOMATING BIG DATA TESTING FOR PERFORMANCE

Reimagining Life Sciences With AI-Enabled Digital Transformation. Abstract

Infosys. Driven by Values

CASE STUDY. Streamlined Operations Through New Business Process Transformation

ENERGY AS SERVICES COMPANY ESCO. Jamal E. Alostaz. Projects Engineer Al-Salem Johnson Controls

FRESH INSIGHTS FROM REAL-TIME DATA, COURTESY AI-DRIVEN ANALYTICS

AVOIDING EQUIPMENT FAILURE WITH ENGINEERING DATA ANALYTICS AND AI

Chilled Water Plant Design American Standard Inc.

Knowledge is Power Belimo Energy Valve CHW DELTA T MITIGATION STUDY AHR Expo Innovation Award Winner in the Category of Building Automation

PERSPECTIVE. Effective Capacity Management with Modeling and Simulation - assisted Performance Testing. Abstract

BANKING WITH THE RIGHT REGULATIONS

Intelligent System Design

September 22, Roy Hubbard HVAC Systems Technology

D DAVID PUBLISHING. Optimizing Thermal Energy Storage Systems in the Hospitality Industry. 1. Introduction

Intelligent. Powerful. Proven. usa.siemens.com/demandflow

Central Chilled Water Plant Sustainable Design. By : George Berbari, CEO DC PRO Engineering

A 7-STEP FRAMEWORK TO IMPLEMENT CICD IN ETL TESTING

ENDLESS POSSIBILITIES WITH DATA FOR RETAIL, CPG AND LOGISTICS

ENABLING SALES TEAMS TO CREATE WINNING QUOTES

District Cooling Sustainable Design. Presented by George Berbari CEO of DC PRO Engineering

KNOWLEDGE-BASED ENGINEERING (KBE) Key product-development technology to enhance competitiveness

RETAIL AND CPG HUMAN AMPLIFICATION IN THE ENTERPRISE

INFOSYS BUSINESS PROCESS MANAGEMENT OFFERINGS

SGM Engineering, Inc.

CASE STUDY THE SPEND ELIXIR

Large University Central Chiller Plant Design Considerations

FINDING AIRCRAFT PARTS BEFORE THEY ARE LOST, WITH PREDICTIVE ANALYTICS

THE INVISIBLE HR PROBLEM

Small Oil-Less Centrifugal Compressors: Bringing Energy Efficiency and Reduced Costs to Chiller Plants

FRIGI-TECH OIL SUPPLEMENT TEST GAMMA BIOLOGICALS, INC MANGUM ROAD HOUSTON, TEXAS. performed by:

PERSPECTIVE. MAKING GPP (Global PAYplus) TESTING PREDICTABLE

TRANSFORMING THE LANDSCAPE FOR INSURANCE CLAIMS

Design Criteria for High Efficiency Centrifugal Chillers in District Cooling Plants

PERSPECTIVE. Accounting General Ledger Challenges in Facets. Vikas Kumar Abstract

GALAXY ENERGY SOLUTIONS LLP THE SAVING ANALYSIS REPORT

NAVIGATE YOUR NEXT TARGET PERFORMANCE WITH DIGITIZE CFO DASHBOARD

WHITE PAPER. Getting started with Continuous Integration in software development. Amruta Kumbhar, Madhavi Shailaja & Ravi Shankar Anupindi

ACCELERATING DIGITIZATION THROUGH NEXT-GENERATION INTEGRATION

Optimizing Chilled Water Systems for Energy Efficiency and Occupant Comfort

To efficiency and beyond

NEXT GENERATION ENERGY EFFICIENT TECHNOLOGIES: A CASE STUDY DEMONSTRATING TOP OPERATIONAL PERFORMANCE. The Aventine Chiller Plant Optimization

WHITE PAPER. Application Grading for Comprehensive Quality Assurance. Abstract

18 th National Award Excellence in Energy Management Zonal Office, New Delhi

WHITE PAPER LEVERAGING 3-C PHILOSOPHY FOR ENHANCED ROI FROM CHANNELS

Application of Steam Turbine Driven Chillers in CHP/DES System

Progressive Organization PERSPECTIVE

DIGITAL OUTLOOK INDUSTRIAL MANUFACTURING INDUSTRY

Optimized System for Your Bottom Line. Trane Training Class 1 Dec, 2017

B. System Design and Performance Requirements

REDUCING TIME TO MARKET WITH DEVOPS

Condenser Water Heat Recovery"

york yvwa variable-speed, water-cooled, screw chillers Infinite chiller configurations to help you achieve your goals

WHITE PAPER. Effective Audit Hosting Strategy: A Perspective. Abstract. Pranav Gadre, Sanjay Martis

Performance Improvement and Efficiency Optimization of an Industry through Energy Audit

IS YOUR WORKPLACE SAFETY A DIFFERENTIATOR? The power of environmental health and safety

BEST STORIES OF INFOSYS SALESFORCE IMPLEMENTATION

Agenda. Understanding the three basic piping systems. Low DeltaT Syndrome causes, effects, and solutions Design & Control Considerations (VPF)

Dresden, Germany 2 Thermodynamics Laboratory, University of Liège, Belgium 3 Vabi Software bv, Delft, The Netherlands ABSTRACT INTRODUCTION

CHANGE IMAGINED. CHANGE DELIVERED

Saving Energy with VFDs

WHITE PAPER. How to optimize close cycle using Hyperion Financial Management. - Navpreet Singh, Principal Consultant

Central Chiller Plants

WHITE PAPER. Master Data Management as a Solution Using SAP MDM and Complementing Technologies

Chilled Water System Optimization

Smardt Water Cooled Chillers

Chiller plant optimization

PERSPECTIVE. Assuring the digital utilities transformation. Gaurav Kalia Client Solution Manager

05/14/2012 THE CRIME OF IMPROPER ENERGY MANAGEMENT AGENDA

Utilities Infrastructure Cooling Distribution. Purpose of Today s Presentation. Agenda. GLHN Architects & Engineers, Inc.

COMPLIANCE AND RISK MANAGEMENT AS A CATALYST FOR CHANGE

BEST STORIES FOR DIGITAL IN COMMUNICATION SERVICES

DIGITAL OUTLOOK CONSUMER PACKAGED GOODS INDUSTRY

Water cooled central plant (vp/vs) Design Envelope application guide

Innovations in Chiller Technology

PRODUCT COMPLAINTS MANAGEMENT. Infosys Handbook For Life Sciences

CII 18 th National Award for Excellence in Energy Management ICICI Bank Ltd, Thane, Mumbai. August 30 & 31, 2017

ORACLE SUPPLY CHAIN MANAGEMENT PRACTICE

WHITE PAPER. Loss Prevention Data Mining Using big data, predictive and prescriptive analytics to enpower loss prevention.

VIEW POINT. The Enterprise QA Transformation Model A solution to enhance an enterprises testing maturity. Abstract. Reghunath Balaraman, Aromal Mohan

THE GREAT CHILLED WATER DEBATE. Michael Dagher

ARMSTRONG DESIGN ENVELOPE FAQ

DIGITAL TRANSFORMATION WITH INTELLIGENT SOLUTIONS FROM INFOSYS AND PEGA

PERSPECTIVE. Operational Risk Management in Banks: The Way Forward

INFOSYS BPM DIGITAL Empowering you to cash on digital opportunities

ACCELERATE YOUR JOURNEY TO BEING DIGITAL

WHITE PAPER. The PLM Domino Effect. - Jagmeet Singh and Jeff Kavanaugh

Water cooled central plant (all-variable) Design Envelope application guide

Xavier University of Louisiana

SMART HVAC & LIGHTING SYSTEMS. Savings From Two Major C&I End Uses

Transcription:

WHITE PAPER Chiller Plant Optimization - A Practitioner s Perspective Sridhar Chidambaram Advanced Engineering Group, Engineering Services, Infosys Limited Bangalore, India Abstract Maintaining optimal energy efficiency in air conditioning systems is a constant challenge one that all heating, ventilation and air conditioning (HVAC) engineers work tirelessly to overcome. However, for many years, the air conditioning industry has struggled to identify and resolve common problems that affect chiller operations and lead to poor performance, high energy consumption and greater operating cost. This paper explores the most common operational challenges in chillers identified by Infosys upon analyzing historical data from chiller plants on its own campuses. It also explains the solutions Infosys used to address these issues in a systematic manner.

1.0 Introduction Infosys has made significant investments in green initiatives across its campuses in India. For instance, all the campus buildings and chiller plants have been outfitted with the latest Internet-of-Things (IoT) technology. These sensors capture real-time operational data that can be monitored through a centralized command centre. Infosys also uses advanced technologies such as the Industrial IoT to continuously improve efficiency and manage energy, water, waste, security, and transportation within its campuses. As a direct result of these initiatives, we have reduced nearly 50% of our per capita energy consumption over a period of 9 years [1]. Air conditioning systems, particularly chillers, consume a large share of the total energy used in buildings. Over the past several years, Infosys has been collecting historical data and maintenance records from more than 130 chillers on its campuses. This data is being used to understand chiller performance, identify common operational problems and design relevant solutions. Chiller data is analyzed using Infosys knowledge-based artificial intelligence (AI) platform NIA to develop diagnostics and prognostics models for chiller energy management systems. the temperature of chilled water entering and leaving the chiller system, is not achieved. Here, even though the building has a maximum heat load, the chiller operates at sub-par capacity in a partial load condition. Low ΔT syndrome arises due to the following reasons: Air handling units (AHUs) temperature set-points are below the designed value The variable frequency drives (VFDs) of AHUs operate in a fixed mode Peripheral system components not designed for the same temperature OFF Chiller # 1 Chiller # 2 range Improper selection of coils and control valves Choked cooling coils Improper water balancing Thus, to meet the maximum building load, the control valve responds by opening the valve to 100%, thereby allowing more chilled water to circulate. This reduces the chilled water flow rate in secondary water pumps. Further, it causes a negative flow of return chilled water though the de-coupler line in order to meet the flow requirement, as shown in Figure 1. Primary chiller water pump 1440 GPM 350 TR of 600 TR 44 0 F 54 0 F De-coupler line Negative flow 960 GPM @ 54 0 F 48 0 F Secondary chiller water pump Fig 1: A chiller plant with low ΔT syndrome 54 0 F Building load at 600 TR 2.0 Common operational issues Chiller operations are complex. In this section, we identify and explain the top 6 challenges in chiller operations along with the solutions deployed by Infosys. 2.1 Low ΔT syndrome A major challenge in several large capacity chiller plants with primary - secondary pumping system is the low temperature difference (ΔT) syndrome. This occurs when the appropriate chilled water temperature range, i.e., the difference in In such a situation, the chiller plant operations are compromised leading to further complications: After mixing with the return water, the temperature of the chilled water supplied to the building increases Control valves remain completely open owing to high temperature of supply chilled water Energy consumption from secondary water pumping systems increases Chiller operations continue in the low ΔT syndrome condition The following steps can address low ΔT syndrome: Adopting a variable primary pumping system This eliminates the de-coupler line, enabling operators to immediately identify and rectify low ΔT syndrome (Refer Table 1) Reducing the temperature range This allows the chiller to increase the flow rate with the same capacity. While it causes wastage of primary pumps, it offers energy savings from secondary pumps.

Conversion of variable primary chiller water flow (VPF) system in GEC-2, Infosys campus, Mysore [2] Facility description Number Capacity of installed chillers 4 x 250 TR Constant primary chiller water pumps 5 Variable secondary chiller water pumps 4 Condenser water pumps 5 Cooling towers 5 Project benefits Equipment details Before After % reduction Number of chillers 4 4 - Number of pumps 14 8 43% Number of valves 74 25 66% Load of chilled water pumps 223 kw 44 kw 80% Load of condenser water pumps 75 kw 44 kw 41% Chiller plant space 3,200 sq.ft. 2,450 sq.ft. 23% Annual energy consumption 2.13 million kwh 1.49 million kwh 30% Table 1: Effect of variable primary chiller water flow system 2.2 Higher small temperature difference of chiller heat exchangers The performance of chiller heat exchangers (including evaporators and condensers) depends on the small temperature difference, also known as the approach [3]. The value of the approach is determined by the difference between the refrigerant saturation temperature and leaving water temperature, as illustrated in Figure 2. Typically, chiller heat exchangers are designed for an approach of 2.2 C. A higher approach value increases the load of the chiller and is caused by the following problems: Formation of fouling in internal tubes Inadequate water flow rate Improper flow of refrigerant inside the tubes Shortage of refrigerant gas In most chillers, the approach values are displayed in the chiller control panel. It can also be estimated from the refrigerant pressure and leaving chilled water temperature for regular monitoring. Usually, the main reason for a high T1-54 0 F T1-85 0 F approach is due to fouling of condenser tubes as these are open loops and they depend on the quality of the condenser water. Saturation condenser temperature (Ts) = 97 o F @ 187 psig for R-22 Condenser Approach Heat of condensation T2 95 0 F Heat of evaporation Saturation evaporator temperature (Ts) = 42 o F @ 71.5 psig for R 22 T2-44 0 F Fig 2: Performance of chiller heat exchangers (evaporator and condenser) Evaporator Approach

o 0 7.0 0.520 6.0 0.515 5.0 0.513 2.2 0.480 IPLV Integrated part load value LCHWT Leaving chilled water temperature kw/tr Kilowatt per ton of refrigeration Table 2: Performance of chiller heat exchangers (evaporator and condenser) To minimize the high approach of condenser tubes, Infosys installed an automatic tube cleaning system for all the chillers. This system helped us get close to the desired chiller operating efficiency (ikw/tr). We also tested next-generation water treatment systems such as nonchemical, ozone and magnetic water treatment systems. 2.3 High temperature of condenser water entering the chiller It is critical to supply condenser water at the right temperature for optimal chiller performance and energy consumption. However, in most chiller plants, the temperature of the condenser water entering the system is higher than normal owing to: Poor maintenance/selection of cooling towers Improper sizing of cooling towers At the right temperature, the entering condenser water will lower the discharge pressure of the refrigerant and provide maximum condenser relief to the chiller. This helps chillers operate in a part-load condition. To lower the temperature of the entering condenser water, one should properly control the cooling tower fans and maintain the designed approach of cooling towers, i.e., maintain the appropriate temperature difference between entering condenser water and ambient wet bulb. After identifying the importance of entry condenser water temperature, Infosys leveraged a logical control-based system to diligently operate and manage the cooling tower, thereby ensuring that the entering condenser temperature is as low as possible. This solution allows the chiller to operate at maximum efficiency. (Refer Fig 3:) 1 Chiller Efficiency (ikw/tr) 0.8 0.6 0.4 0.2 Legend: ECWT ( o F) 86 F 82 F 78 F 74 F 70 F 66 F 0 100% 90% 80% 70% 60% 50% 40% 30% 23% % of Load (TR) Fig 3: Example of Centrifugal Chiller Performance Curve Note: ECWT - Entering Condenser Water Temperature

2.4 Incorrect size of chiller auxiliary water pumps Often, when installing chiller auxiliary pumps such as chilled water pumps and condenser water pumps, the sizes are over-estimated to allow for safety factors. However, this results in a mismatch between chiller design parameters. If the pumps deliver a higher flow rate than expected, then the flow gets throttled in the chiller and the balancing valve is forced to maintain the required flow. This increases the system operating pressure/ head and consumes higher power during operations. Therefore, it is very important to calculate that the required flow rate and head based on the designed ΔT, then selecting Pump Curve the right capacity pump, which helps to operate at its best efficiency point (BEP). BEP is where the system curve crosses the pump curve as shown in Figure 4. Pumps can also be selected based on the flat and steep curve profiles. The steep curve is preferred for open systems such as cooling towers while a flat curve is recommended for systems with control valves. Total Head (ft) Best Efficiency Point System Curve Flow Rate (GPM) Fig 4: A typical performance curve for a centrifugal pump 2.5 Low quality of condenser water While condenser water is not typically considered a parameter for operational efficiency, low-quality condenser water can create problems in the open cooling loop system, such as: Scale formation Scale refers to precipitated solids or calcium carbonate crystals that obstruct heat transfer in the heat exchangers, thereby reducing the performance of the cooling system Metal corrosion Corroding metal reduces the integrity, strength and thickness of the metal structure by creating holes in the material Biological fouling formation This refers to the growth of organisms in protected environments such as internal tubes, which is difficult to remove. It reduces the heat transfer efficiency and results in microbiologically-induced corrosion, which can affect human health. Infosys monitors and controls water quality using various control parameters such as conductivity, oxygen reduction potential, treatment chemical concentration levels, general water analysis, etc. Further, the auto bleed-off valve in the cooling tower ensures that water blow down to maintain the acceptable Total Dissolved Solids (TDS) in condenser.

2.6 Inaccurate sensors Inaccurate sensors have a significant impact on energy conservation initiatives. For every 1 C decrease in chilled water temperature, there is a corresponding 1 % to 3% increase in chiller energy consumption [4]. Thus, inaccurate readings from temperature sensors, pressure sensors and water flow meters as well as inaccurate data due to manual error can severely affect chiller operations. The impact of inaccurate sensor values is illustrated in Table 3. Well-defined and properly calibrated sensors and instruments can deliver high precision measurement, thereby eliminating excess energy usage. To ensure that we obtain accurate values of chiller operations, Infosys conducts regular instrument calibration as a part of chiller maintenance. Parameters Unit Design Chiller panel Leaving chilled water temperature C 6.67 6.50 6.68 Entering chilled water temperature C 10.56 10.20 10.42 Leaving condenser water temperature C 31.44 31.10 31.46 Entering condenser water temperature C 28.89 28.70 29.00 Chilled water flow rate GPM 1812-1854 Condenser water flow rate GPM 3180-3229 Pressure drop across evaporator ftwc 5.00 4.94 Pressure drop across condenser ftwc 13.00 13.49 Cooling capacity (tonnage) TR 528 514 519 Compressor power input kw 269 284 271 Chiller energy efficiency kw/tr 0.51 0.55 0.52 With calibrated instrument Table 3: Validating actual vs. designed chiller operating parameters at 100% load ftwc Feet of water column GPM Gallon per min

3.0 Conclusion Air conditioning systems account for nearly 40% of the total energy consumption of a typical commercial building. Thus, it is essential to ensure proper operations and maintenance of chiller systems to prevent high energy consumption, equipment deterioration and poor quality of circulated air. By using real-time operational and maintenance data collected from over 130 chillers on its campuses, Infosys has identified the leading causes of poor chiller performance. These include improper temperature differences in entering chilled water, leaving chilled water and condenser water as well as incorrect sizing of chiller pumps, inaccurate sensors and low quality of condenser water. Technologies such as the Industrial Internet-of-Things (IIoT) have helped Infosys create unique solutions for each of these challenges, thereby saving nearly 50% of per capita energy consumption. In future, operational data and analytics models can help Infosys explore and solve site-specific issues as well, thereby maximizing gains from their green energy initiatives. 4.0 Acknowledgements I would like to acknowledge the technical support provided by the Green Initiatives team and Advanced Engineering Group. Special thanks to subject matter experts Dr. Ravi Kumar G.V.V., Dr. Ravi Prakash and Guruprakash Sastry for their useful inputs and valuable time spent in reviewing this paper. 5.0 References 1. Sustainability Report 2016-17, Infosys Limited https://www.infosys. com/sustainability/documents/infosyssustainability-report-2016-17.pdf 2. HVAC retrofit saves energy for Infosys, ISHRAE Journal, Apr June 2012 3. Centrifugal chiller fundamentals, Application guide AG 31-002, McQuay International, 2000 4. Energy auditor exam course material of Bureau of Energy Efficiency (BEE), Ministry of Power, Govt. of India

For more information, contact askus@infosys.com 2017 Infosys Limited, Bengaluru, India. All Rights Reserved. Infosys believes the information in this document is accurate as of its publication date; such information is subject to change without notice. Infosys acknowledges the proprietary rights of other companies to the trademarks, product names and such other intellectual property rights mentioned in this document. Except as expressly permitted, neither this documentation nor any part of it may be reproduced, stored in a retrieval system, or transmitted in any form or by any means, electronic, mechanical, printing, photocopying, recording or otherwise, without the prior permission of Infosys Limited and/ or any named intellectual property rights holders under this document. Infosys.com NYSE: INFY Stay Connected