October 3, Section 1.2 Scope and Section 6.6 were revised to clarify interior and exterior construction types allowed.

Similar documents
DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PLASTICS REPORT HOLDER: HB&G BUILDING PRODUCTS, INC.

April 2, 2018 PARTIES INTERESTED IN CROSS LAMINATED TIMBER PANELS USED AS COMPONENTS IN FLOOR AND ROOF DECKS

February 1, SUBJECT: Proposed Revisions to the Acceptance Criteria for Staples, Subject AC R1 (EL/JF)

June 7, 2012 PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES

December 3, 2012 PARTIES INTERESTED IN INTUMESCENT FIRE-RESISTANT COATINGS FIELD-APPLIED TO PREFABRICATED WOOD I-JOISTS

December 1, 2014 PARTIES INTERESTED IN STRUCTURAL WOOD-BASED PRODUCTS

February 1, 2018 PARTIES INTERESTED IN DECK BOARD SPAN RATINGS AND GUARDRAIL SYSTEMS (GUARDS AND HANDRAILS)

August 1, Removed reference to the standard edition from Sections and

June 1, 2012 PARTIES INTERESTED IN COLD-FORMED STEEL FRAMING MEMBERS

July 23, 2010 PARTIES INTERESTED IN REFLECTIVE FOIL INSULATION

ACCEPTANCE CRITERIA FOR POLYMER-BASED AND POLYMER-MODIFIED EXTERIOR AND INTERIOR WALL CLADDING

ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) PREFACE

June 1, 2017 PARTIES INTERESTED IN POST-TENSIONING ANCHORAGES AND COUPLERS OF PRESTRESSED CONCRETE

June 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON REFLECTIVE FOIL INSULATION

June 22, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON COMPOSITE COLD-FORMED LIGHT GAGE STEEL AND CONCRETE MASONRY LINTELS

April 18, 2018 PARTIES INTERESTED IN ADHERED PORCELAIN TILE WALL CLADDING SYSTEM

June 1, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON STRUCTURAL WOOD-BASED PRODUCTS USED AS STUDS

The purpose of this memo is to respond to the comments received in response to the May 1, 2007, staff letter and the revised criteria.

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER

ACCEPTANCE CRITERIA FOR THREADED HIGH-STRENGTH STEEL BARS FOR CONCRETE REINFORCEMENT PREFACE

June 9, 2008 PARTIES INTERESTED IN EVALUATION REPORTS ON TERMITE- RESISTANT FOAM PLASTICS

October 12, Yours very truly, Gary G. Nichols, P.E., SECB Vice President. GGN/md Enclosure Evaluation Committee

April 18, 2018 PARTIES INTERESTED IN FIBER REINFORCED PLASTIC (FRP) MODULAR WALL SYSTEMS

PMG LISTING CRITERIA FOR MULTILAYER PIPE AND FITTINGS ASSEMBLY FOR REFRIGERANT APPLICATIONS LC1036

April 18, 2018 PARTIES INTERESTED IN RAISED-DECK SYSTEMS INSTALLED OVER ROOF ASSEMBLIES OR EXTERIOR SUPPORTING STRUCTURES

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER PREFACE

ACCEPTANCE CRITERIA FOR ROOF UNDERLAYMENT FOR USE IN SEVERE CLIMATE AREAS PREFACE

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: FOUR SEASONS BUILDING PRODUCTS, LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

The Rehabilitation of Existing Building Drains and Building Sewers by the

DIVISION: CONCRETE SECTION: MAINTENANCE OF CONCRETE REPORT HOLDER: STRUCTURAL TECHNOLOGIES, LLC

DIVISION: CONCRETE SECTION: INSULATING CONCRETE FORMING REPORT HOLDER: DIVERSIFOAM PRODUCTS EVALUATION SUBJECT:

Trusted ICC ES MILAN ITALY SYSTEMS. Look. Conformity! Evaluation. ICC-ES Evaluation

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: FOUR SEASONS SOLAR PRODUCTS

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 3000 SERIES FASTENERS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: PLASTIC DECKING REPORT HOLDER: SILCA SYSTEM

February 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON ROOF UNDERLAYMENTS FOR USE IN SEVERE CLIMATE AREAS

ACCEPTANCE CRITERIA FOR EXPANSION BOLTS IN STRUCTURAL STEEL CONNECTIONS (BLIND-BOLTS) PREFACE

February 1, 2016 PARTIES INTERESTED IN EXTERIOR ULTRA-HIGH PERFORMANCE CONCRETE THIN WALL CLADDING PANELS

(800) (562) A Subsidiary of the International Code Council

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES

DIVISION: FINISHES SECTION: GYPSUM BOARD REPORT HOLDER: PANEL REY, S.A.

Trusted ICC ES TEK USA, Evaluation. report, or as to any. ICC-ES Evaluation

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: QUALITY WAY PRODUCTS, LLC 407 HADLEY STREET HOLLY, MICHIGAN 48442

April 1, 2015 PARTIES INTERESTED IN FLEXIBLE FLASHING MATERIALS

December 29, 2011 PARTIES INTERESTED IN TRANSLUCENT FIBERGLASS REINFORCED PLASTIC (FRP) FACED PANEL WALL, ROOF AND SKYLIGHT SYSTEMS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: EXTERIOR INSULATION AND FINISH SYSTEMS REPORT HOLDER: PAREX USA, INC.

REPORT HOLDER: R.L. ADAMS PLASTICS, INC CROSSROADS COMMERCE PARKWAY WYOMING, MICHIGAN EVALUATION SUBJECT: POLYCORE BRAND INSULATION

October 1, SUBJECT: Proposed Revisions to the Acceptance Criteria for Walking Decks, Subject AC R1 (WU/CA).

December 1, 2011 PARTIES INTERESTED IN ALTERNATE DOWEL-TYPE THREADED FASTENERS

ESR-2036 Reissued May 1, 2013 This report is subject to renewal June 1, 2015.

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 5000 SERIES FASTENERS

ESR-2894 Reissued April 2014 This report is subject to renewal April 1, 2016.

PMG LISTING CRITERIA FOR STRUCTURAL ADHESIVE JOINING SYSTEMS FOR FITTINGS PREFACE

REPORT HOLDER: FASTENING SPECIALISTS, INC. 726 CENTRAL FLORIDA PARKWAY ORLANDO, FLORIDA EVALUATION SUBJECT:

ICC ES SYSTEM SYSTEM. Trusted DIVISION: 07 SECTION: AND FINISH REPORT HOLDER: ICC-ES Evaluation. Reissued 08/2016.

PMG LISTING CRITERIA FOR PERT-AL-PERT PIPE AND FITTINGS FOR REFRIGERATION APPLICATIONS LC1039. Approved Date: November 2015 PREFACE

DIVISION: SPECIALTIES SECTION: MANUFACTURED FIREPLACES REPORT HOLDER: FIRE ROCK PRODUCTS LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: SIDING REPORT HOLDER: BORAL COMPOSITES, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: EXTERIOR INSULATION AND FINISH SYSTEMS REPORT HOLDER: DRYVIT SYSTEMS, INC.

DIVISION: MASONRY SECTION: CONCRETE UNIT MASONRY REPORT HOLDER: 3B CONSTRUCTION SOLUTIONS, INC.

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS SECTION: PRECAST STRUCTURAL CONCRETE SECTION: SITE CAST CONCRETE

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

ACCEPTANCE CRITERIA FOR METAL COMPOSITE MATERIAL (MCM) PREFACE

ESR-1794* Reissued September 1, 2012 This report is subject to renewal November 1, 2014.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER CEMENT SIDING REPORT HOLDER: RIEDER FASERBETON ELEMENTE GmbH

DIVISION: CONCRETE SECTION: INSULATING CONCRETE FORMING REPORT HOLDER: SUPERFORM PRODUCTS LTD. EVALUATION SUBJECT:

PMG LISTING CRITERIA FOR PRESS-CONNECTION FITTINGS FOR POTABLE WATER TUBE AND RADIANT HEATING SYSTEMS PREFACE

ARCHITECTURAL TESTING, Inc. Code Compliance Research Report #0774 CCRR-0131

REPORT HOLDER: JAACO CORPORATION NE 68 TH STREET, SUITE C 130 REDMOND, WASHINGTON EVALUATION SUBJECT:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: TRESPA NORTH AMERICA, LTD.

REPORT HOLDER: BLUE POINT FASTENING, INC YORBA COURT CHINO, CALIFORNIA EVALUATION SUBJECT:

ACCEPTANCE CRITERIA FOR WATER-RESISTIVE BARRIERS PREFACE

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT:

April 2, 2012 PARTIES INTERESTED IN EXPANSION ANCHORS IN MASONRY ELEMENTS

REPORT HOLDER: THE DOW CHEMICAL COMPANY 1501 LARKIN CENTER DRIVE MIDLAND, MICHIGAN EVALUATION SUBJECT:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: LAMINATED VENEER LUMBER REPORT HOLDER: REDBUILT LLC EVALUATION SUBJECT:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: EVALUATION SUBJECT: STRUCTURAL PANELS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: NAILS REPORT HOLDER: HY-TEK FASTENERS INC. EVALUATION SUBJECT: HY-TEK NAILS

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: AKRON PRODUCTS COMPANY

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

ICC-ES Evaluation Report Reissued March 2014 This report is subject to renewal May 1, 2015

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

ESR-1190 Reissued December 1, 2013 This report is subject to renewal December 1, 2014.

Trusted ICC ES. Conformity! Look. Evaluation. ICC-ES Evaluation

CITY OF LOS ANGELES CALIFORNIA

PMG LISTING CRITERIA FOR PUSH-FIT FITTINGS FOR POTABLE WATER TUBE AND RADIANT HEATING SYSTEMS LC1009

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: FUNDERMAX GMBH

Originally Issued: 11/06/2017 Valid Through: 11/30/2018

REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: HILTI LOW VELOCITY X-U AND X-U 15 UNIVERSAL FASTENERS AND X-P CONCRETE FASTENERS

DIVISION: CONCRETE SECTION: SPECIALTY PLACED CONCRETE REPORT HOLDER: EMMEDUE S.P.A.

ACCEPTANCE CRITERIA FOR FASTENERS POWER-DRIVEN INTO CONCRETE, STEEL AND MASONRY ELEMENTS PREFACE

December 1, 2014 PARTIES INTERESTED IN WATER-RESISTIVE BARRIERS

ATI Evaluation Service A Division of Architectural Testing Certification Services

Gold Bond BRAND Gypsum Sheathing

REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH BRAND FASTENERS

Transcription:

October 3, 2016 TO: PARTIES INTERESTED IN EVALAUTION REPORTS ON FIBER- REINFORCED POLYMER (FRP) COMPOSITE COLUMNS USED AS AXIAL LOAD-BEARING AND NONLOAD-BEARING ARCHITECTURAL AND DECORATIVE COLUMNS SUBJECT: Proposed Revisions to the Acceptance Criteria for Fiber-reinforced Polymer (FRP) Composite Columns Used as Axial Load-bearing and Nonload-bearing Architectural and Decorative Columns, Subject AC265-1016-R1(MO/WM) Dear Colleague: We are seeking your comments on proposed revisions to the subject acceptance criteria, as presented in the enclosed draft. The revisions, which are being posted on the ICC-ES web site for 30 days of public comment, may be summarized as follows: 1. Section 1.2 Scope and Section 6.6 were revised to clarify interior and exterior construction types allowed. 2. Section 3.2 Structural was revised to clarify that this testing is only required for load-bearing columns. 3. Section 3.3 Durability was revised to clarify that this testing is only required for exterior use columns. 4. Section 6.4 was revised to clarify that use of the load-bearing columns for uplift and lateral loads is outside the scope of the evaluation report. While the Evaluation Committee will be voting on the revised criteria during the 30- day comment period, we will seriously consider all comments from the public and will pull the criteria back for reconsideration if public comments raise major issues. In that case, we would seek a new committee vote; further revise the draft and post it for a new round of public comments; or put the revised criteria on the agenda for a future Evaluation Committee hearing. If they are of interest, please review the proposed revisions and send us your comments at the earliest opportunity. At the end of the 30-day comment period, we will post on our web site the correspondence we have received and, in memo form, the responses of our technical staff.

AC265-1016-R1 2 To submit your comments, please use the form on the web site and attach any letters or other materials. If you would like an explanation of the alternate criteria process, under which we are soliciting comments, this too is available on the ICC-ES web site. Please do not try to communicate directly with any Evaluation Committee member about a criteria under consideration, as committee members cannot accept such communications. Thank you for your interest and your contributions. If you have any questions, please contact me at (800) 423-6587, extension 5685, or Woods McRoy, Senior Staff Engineer, at extension 5686. You may also reach us by e-mail at es@icc-es.org. Yours very truly, MO/raf Encl. cc: Evaluation Committee Michael O Reardon, P.E. Regional Engineering Director

www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council PROPOSED REVISIONS TO THE ACCEPTANCE CRITERIA FOR FIBER- REINFORCED POLYMER (FRP) COMPOSITE COLUMNS USED AS AXIAL LOAD-BEARING AND NONLOAD-BEARING ARCHITECTURAL AND DECORATIVE COLUMNS AC265 Proposed October 2016 Previously approved February 2005 (Previously editorially revised December 2015, February 2014, January 2012) PREFACE Evaluation reports issued by ICC Evaluation Service, LLC (ICC-ES), are based upon performance features of the International family of codes. (Some reports may also reference older code families such as the BOCA National Codes, the Standard Codes, and the Uniform Codes.) Section 104.11 of the International Building Code reads as follows: The provisions of this code are not intended to prevent the installation of any materials or to prohibit any design or method of construction not specifically prescribed by this code, provided that any such alternative has been approved. An alternative material, design or method of construction shall be approved where the building official finds that the proposed design is satisfactory and complies with the intent of the provisions of this code, and that the material, method or work offered is, for the purpose intended, at least the equivalent of that prescribed in this code in quality, strength, effectiveness, fire resistance, durability and safety. ICC-ES may consider alternate criteria for report approval, provided the report applicant submits data demonstrating that the alternate criteria are at least equivalent to the criteria set forth in this document, and otherwise demonstrate compliance with the performance features of the codes. ICC-ES retains the right to refuse to issue or renew any evaluation report, if the applicable product, material, or method of construction is such that either unusual care with its installation or use must be exercised for satisfactory performance, or if malfunctioning is apt to cause injury or unreasonable damage. Acceptance criteria are developed for use solely by ICC-ES for purposes of issuing ICC-ES evaluation reports. Copyright 2016 ICC Evaluation Service, LLC. All rights reserved.

PROPOSED REVISIONS TO THE ACCEPTANCE CRITERIA FOR FIBER- REINFORCED POLYMER (FRP) COMPOSITE COLUMNS USED AS AXIAL LOAD-BEARING AND NONLOAD-BEARING ARCHITECTURAL AND DECORATIVE COLUMNS (AC265) 1.0 INTRODUCTION 1.1 Purpose: The purpose of this criteria is to establish requirements for fiber-reinforced polymer (FRP) composite columns used as axial load-bearing and nonload-bearing architectural and decorative columns to be recognized in an ICC Evaluation Service, LLC. (ICC- ES), evaluation report under the 2015, 2012 and 2009 International Building Code (IBC) and the 2015, 2012 and 2009 International Residential Code (IRC). Bases of recognition are IBC Section 104.11 and IRC Section R104.11. Applicable code sections are IBC Sections 602.3 (Construction Classification Type III), 602.4 (Construction Classification Type IV), 602.5 (Construction Classification Type V), 803 (Wall and Ceiling Finishes), Chapter 16 (Structural Design), and Chapter 17 (Structural Tests and Special Inspections); and IRC Sections R301 (Design Criteria) and R302.9, Flame spread index and smoke-developed index for wall and ceiling finishes). The reason for the development of this criteria is to provide guidelines for the evaluation of fiber-reinforced polymer (FRP) composite columns since the codes do not provide test methods and performance requirements for such products. 1.2 Scope: Fiber-reinforced polymer (FRP) composite columns, axial load-bearing and nonload-bearing architectural and decorative columns. Exterior use loadbearing and nonload-bearing columns shall be used on the exterior of buildings of Type V-B construction to resist gravity axial loads only and shall not be used to resist wind or earthquake loads. Interior use load-bearing and nonload-bearing columns shall be used on the interior of buildings of Type III, IV and V construction, non-fire-resistance-rated. The columns shall not be used to resist uplift loads or as a component of a braced frame or lateral load resistance system. 1.3 Codes and Reference Standards: Where standards are referenced in this criteria, these standards shall be applied consistently with the code upon which compliance is based. 1.3.1 Codes: 1.3.1.1 2015, 2012 and 2009 International Building Code (IBC), International Code Council. 1.3.1.2 2015, 2012 and 2009 International Residential Code (IRC), International Code Council. 1.3.2 ASTM International: 1.3.2.1 ASTM B117-11, Standard Practice for Operating Salt Spray (Fog) Apparatus. 1.3.2.2 ASTM C67-13, Standard Test Methods for Sampling and Testing Brick and Structural Clay Tile. 1.3.2.3 ASTM C672/C 672M-12, Standard Test Method for Scaling Resistance of Concrete Surfaces Exposed to Deicing Chemicals. 1.3.2.4 ASTM D790-10, Standard Test Methods for Flexural Properties of Unreinforced and Reinforced Plastics and Electrical Insulating Materials. 1.3.2.5 ASTM E84-2013A, Standard Test Method for Surface Burning Characteristics of Building Materials. 1.3.2.6 ASTM G153-13, Standard Practice for Operating Enclosed Carbon Arc Light Apparatus for Exposure of Nonmetallic Materials. 1.3.2.7 ASTM G154-06, Standard Practice for Operating Fluorescent Light Apparatus for UV Exposure of Nonmetallic Materials. 1.3.2.8 ASTM G155-05a, Standard Practice for Operating Xenon Arc Light Apparatus for Exposure on Non-Metallic Materials. 1.3.3 Underwriters Laboratories Inc.: 1.3.3.1 UL 723-2008, Standard for Test for Surface Burning Characteristics of Building Materials with Rev. through Sept. 2010. 1.4 Definitions: 1.4.1 Fiber-reinforced Polymer (FRP) Composite Columns: Round and square, hollow, spuncast, fiberreinforced polymer (FRP), composite columns with nominal diameters, tapered toward the top with variable wall thickness. The round columns may be produced with plain and fluted surfaces, and non-tapered. Square columns may be either tapered or non-tapered. The columns are supplied with or without caps and bases. The FRP composite material is a proprietary mixture of thermoset resin, chopped fiberglass strands and an inorganic filler substance used to provide fire resistance. 2.0 BASIC INFORMATION 2.1 General: The following information shall be submitted: 2.1.1 Product Description: Complete information concerning material specifications, thickness, size and the manufacturing process. 2.1.2 Installation Instructions: Installation details and limitations, fastener materials, and installation manual. 2.1.3 Packaging and Identification: A description of the method of packaging and field identification of the panel. Identification provisions shall include the evaluation report number. 2.1.4 Field Preparation: A description of the methods of field-cutting, application and finishing. 2.2 Testing Laboratories: Testing laboratories shall comply with Section 2.0 of the ICC-ES Acceptance Criteria for Test Reports (AC85) and Section 4.2 of the ICC-ES Rules of Procedure for Evaluation Reports. 2.3 Test Reports: Test reports shall comply with AC85. 2.4 Product Sampling: Products shall be sampled in accordance with Section 3.1 of AC85. 2

PROPOSED REVISIONS TO THE ACCEPTANCE CRITERIA FOR FIBER-REINFORCED POLYMER (FRP) COMPOSITE COLUMNS USED AS AXIAL LOAD-BEARING AND NONLOAD-BEARING ARCHITECTURAL AND DECORATIVE COLUMNS (AC265) 3.0 TEST AND PERFORMANCE REQUIREMENTS 3.1 Surface-burning Characteristics: The fiberreinforced polymer (FRP) composite columns shall be tested for surface burning characteristics to document flame-spread index and smoke-developed index. The test methods are noted in Section 4.1 of this acceptance criteria. 3.2 Structural: For columns intended to be load bearing, tthe FRP composite columns shall be load tested to determine allowable axial gravity load capacity. The test methods are noted in Section 4.2 of this acceptance criteria. 3.3 Durability: For columns intended to be used for exterior use, tthe column material shall be tested for durability, accelerated weathering, freeze-thaw resistance, salt spray exposure and resistance to deicing chemicals. The test methods are noted in Section 4.3 of this acceptance criteria. 4.0 TEST METHODS 4.1 Surface-burning Characteristics: Surfaceburning characteristics of the FRP composite columns shall be determined by testing in accordance with ASTM E84 or UL 723. Testing shall be performed on sheets of the maximum and minimum wall thickness. Conditions of Acceptance: The flame-spread index (FSI) and smoke-developed index (SDI) shall be listed for the product and the product shall be rated as either a Class A, B or C interior finish material as defined in Section 803.1 of the IBC. When the product is limited to exterior use, the FSI shall be not greater than 200 and the SDI shall not be restricted. 4.2 Structural: 4.2.1 Axial Loadings: Compression load testing of the product shall be performed using the test method described in Annex A of this criteria. The columns may be tested in a horizontal or vertical position. The columns shall be load-tested with no lateral support between the columns top and bottom load-bearing supports. Load testing shall be performed for each column cross-section size, round and square for shortest, middle and longest column length, with a minimum of three specimens for each cross-section size and each length. The maximum length column shall be tested. The allowable load for column lengths not tested shall be based on the next longer column tested. The columns shall be subjected to eccentric load testing using a minimum eccentricity for documenting allowable concentric loadings. The minimum eccentricity shall be 1 / 6 the column diameter and shall be measured from the centerline of the top of the column. The columns shall also be tested for a maximum eccentricity as determined by the applicant, and the maximum allowable load shall be reported in the evaluation report for this eccentricity. Conditions of Acceptance: The columns shall be loaded to failure, with the allowable load established as the lowest failure load divided by a factor of 5.0. A load table shall be developed using the allowable loads, length and size of column. A sample load table is shown at the end of this acceptance criteria. 4.2.2 Load Duration (Creep Effects): Columns shall be load tested to document a load duration of 60 3 days. The load testing shall be performed using three identical samples using the smallest diameter and longest column size tested under Section 4.2.1. Compression load testing of the product shall be performed using the test method described in Annex A of this criteria. The columns shall be loaded to two times the allowable load capacity of the columns and the load shall be maintained for a period of 60 days. The bearing surfaces of the columns shall be inspected prior to load testing. The load shall be removed after the 60-day duration and bearing surfaces of the columns shall be inspected for damage. Deformations shall be recorded to document change in column length. Conditions of Acceptance: The columns shall sustain the test load for the duration of the test without failure. Bearing surfaces shall have no visible damage after load testing. 4.3 Durability: The column material shall be tested under the following procedures: 4.3.1 Accelerated Weathering: A minimum of five samples, using the minimum thickness produced, shall be tested for a minimum of 2000 hours of exposure in accordance with Section 4.3.1.1, 4.3.1.2 or 4.3.1.3. Weathered samples and a minimum of five control samples at minimum thickness shall be subjected to flexural loading in accordance with D 790. 4.3.1.1 Tests shall be in accordance with ASTM G153. The operating schedule shall be Cycle 1 set forth in Table X1.1 of ASTM G153. 4.3.1.2 Tests shall be in accordance with ASTM G154. The operating schedule shall be Cycle 1 set forth in Table X2.1 of ASTM G154. 4.3.1.3 Tests shall be in accordance with ASTM G155. The operating schedule shall be either Cycle 1, 5, or 9 as set forth in Table X3.1 of ASTM G155. Conditions of Acceptance: The average flexural strength of the weathered samples shall be at least 90 percent of the average flexural strength of the control samples tested. 4.3.2 Freeze-thaw Resistance: A minimum of five samples, using the minimum thickness produced, shall be tested in accordance with Section 8 of ASTM C67. Conditions of Acceptance: The samples shall show no breakage and shall not have more than 1 percent loss in dry weight of any sample. 4.3.3 Salt Spray Exposure: A minimum of five samples, 4 inches by 6 inches (102 mm by 142 mm), using the minimum thickness produced, shall be tested in accordance with ASTM B117. The test period is 300 hours. Conditions of Acceptance: The test samples shall have no deleterious effects. 4.3.4 Resistance to Deicing Chemicals: A minimum of five samples, using the minimum thickness produced, shall be tested in accordance with Section 9 of ASTM C672, 50 cycles. A minimum of five control samples at minimum thickness are compared to exposed samples. Conditions of Acceptance: The exposed samples shall be visually rated as either no scaling or very slight

PROPOSED REVISIONS TO THE ACCEPTANCE CRITERIA FOR FIBER-REINFORCED POLYMER (FRP) COMPOSITE COLUMNS USED AS AXIAL LOAD-BEARING AND NONLOAD-BEARING ARCHITECTURAL AND DECORATIVE COLUMNS (AC265) scaling [ 1 / 8 inch (3 mm) depth, maximum] and shall be compared to control samples. 5.0 QUALITY CONTROL 5.1 The products shall be manufactured under an approved quality control program with inspections by ICC- ES or by a properly accredited inspection agency that has a contractual relationship with ICC-ES. 5.2 Quality documentation complying with the ICC-ES Acceptance Criteria for Quality Documentation (AC10) shall be submitted. 5.3 A qualifying inspection shall be conducted at each manufacturing facility when required by the ICC-ES Acceptance Criteria for Inspections and Inspection Agencies (AC304). 6.0 EVALUATION REPORT RECOGNITION The following are conditions of use for fiber-reinforced polymer (FRP) composite columns covered by this acceptance criteria: 6.1 Structural design calculations must be submitted to the code official when a permit is applied for. The calculations must be signed, sealed and dated by a registered design professional when required by the statutes of the jurisdiction in which the project is to be constructed. 6.2 Columns installed on the interior must be listed for use as interior finish and must be labeled with either a Class A, B or C classification by an accredited third-party inspection agency. 6.3 Design loads on the columns must be determined in accordance with Chapter 16 of the code and must not exceed the allowable loads shown in Table(s). [see example of table, below]. 6.4 The use of the columns must not be used to resist uplift or lateral loads resulting from seismic or wind applications is outside the scope of this report. 6.5 Details of top and bottom connections must be provided in the evaluation report. 6.6 The load-bearing and nonload-bearing exterior use columns must only be used on the exterior of buildings of Type V-B construction or any construction under the IRC. Load-bearing and nnonload-bearing interior use columns must only be used on in buildings of Type III, IV and V construction, non-fire-resistance-rated or any construction under the IRC. [EXAMPLE] TABLE [#] ALLOWABLE LOADS COLUMNS COLUMN TYPE AND NOMINAL SIZE (in) WALL THICKNESS MAXIMUM (in) ALLOWABLE LOAD (lbs) ECCENTRIC LOADINGS LENGTH MINIMUM ECCENTRICITY Bottom Top (ft-in) Maximum e (in) Allowable Load (lbs) Table 1 Notes: 1. SI Units conversion: 1 in. = 25.4 mm, 1 ft = 0.3 m, 1 lbf = 4.5 N. 2. Round columns include plain and fluted. 3. Maximum e (in) is eccentricity measured in inches from the center line of the top of the column 4

PROPOSED REVISIONS TO THE ACCEPTANCE CRITERIA FOR FIBER-REINFORCED POLYMER (FRP) COMPOSITE COLUMNS USED AS AXIAL LOAD-BEARING AND NONLOAD-BEARING ARCHITECTURAL AND DECORATIVE COLUMNS (AC265) A1.0 SCOPE ANNEX A COMPRESSION TEST PROCEDURE Eccentric loads are applied to the columns in a specialized steel test frame capable of producing a maximum axial load of 200,000 pounds (900 000 N). The loads shall be applied via a hydraulic pump and hydraulic ram, or equivalent load-producing system. The applied load shall be measured using a calibrated test gauge and/or the combination of a load cell and a digital weight indicator, or equivalent load-measuring system. A2.0 TERMINOLOGY A2.1 Definitions of terms specific to this procedure: A2.1.1 Eccentric Loading: The loading condition upon a structural column such that the base of the column is flush against the end plate of the load frame while the top of the column is loaded to simulate a roof truss resting over the top of the column at some specified offset distance. A2.1.2 Failure: The point at which the column is no longer capable of carrying increased loads or when significant physical damage to the column occurs. Note 1: The highest load maintained for 1 minute shall be recorded as the ultimate load. If the column does not fail before reaching capacity of the load frame, the report will reflect the maximum load achieved. A3.0 SUMMARY OF TEST PROCEDURE This test procedure consists of loading a column into a compression load frame, using a load-producing system, such as a hydraulic pump and hydraulic ram, to apply an axial load at specified load increments, and holding each incremental load for a period of time until failure occurs. A4.0 TEST PROCEDURE GENERAL A4.1 Unwrap the column from any and all packing material. A4.2 Inspect column for damage or any unusual conditions. A4.3 Unless otherwise specified, orient the column on the floor in front of the load frame so that the base of the column is in front of the movable crosshead of the load frame. A4.4 Place a permanent mark to label the top and the base of the column. A4.5 Photograph the top and the base of the column. A4.6 Measure the column length, size, and wall thickness at the top and the base and record the thicknesses on a data sheet. The wall thickness at the top and base shall be determined as the average of three equally spaced measurements around the diameter of round columns, or four measurements for square columns where one measurement is obtained at the center of each face. Note 2: For a round column, three thickness measurements shall be recorded. The measurements shall be taken at equal spaces around the perimeter of the column end. For a square column, four thickness measurements shall be recorded, one on each side. A5.0 TEST PROCEDURE ECCENTRIC LOADING A5.1 Position the column in the load frame and support the column such that the geometric center of the base and the top is in the center of the end plates. Place a spacer of specified size in between the top of the column and the top end plate at a designated offset distance. A5.2 Permanently mark the column identification on the shaft of the column. A5.3 Photograph the column in the load frame, making sure that the column identification is visible. A5.4 Check the connections of all equipment and measuring devices and zero the load-indicating system. A5.5 Unless otherwise specified, load the column to one-half the rated load and hold the load for a period of not less than 1 minute. A5.6 After the first load time period has expired, increase the load in 1000-pound (4500 N) increments until failure occurs. Each increment shall be held for not less than one minute. A5.7 Record the ultimate load [truncated to next lowest 1000-pound (4500 N) increment] and the failure mode on the data sheet. A5.8 Photograph the failure mode of the column. Note 3: In the instance where the rated load of the column is not specified or unknown, the initial load shall be 5000 pounds (22 500 N). The load shall then be increased in 1000-pound (4500 N) increments until failure occurs. Each increment, as described above, shall be maintained for not less than 1-minute. 5